EVALUATION REPORT R E C E I VE__D SEP 212017 FLORIDA BUILDING CODE 5T"EDITION(2014)
Manufacturer: UNITED ROOFING MANUFACTURING CO., INC. Issued June 26,2015
P.O.BOX 30
Eutaw,AL 35462
(205)372-3394
hftp://www.unitedroofinci.com/
Distribution: Eutaw,AL
Quality Assurance: UL LLC(QUA9625)
FELE COPY
SCOPE
Category: Roofing
Subcategory: U n de rl ayme nts
Code Sections: 1507.2.3, 1507.2.8, 1507.4.5.1, 1507.4.5.2, 1507.5.3, 1507.5.3.2, 1507.7.3, 1507.7.3.2,
1507.8.3, 1507.8.3.2,T1507.8, 1507.9.3, 1507.9.3.2, 1507.9.5, 1518.4
Properties: Physical properties
REFERENCES
En!Lty Report No. Standard Year
PRI Construction Materials Technologies(TST5878) GGI-132-02-01 ASTM D 226 2006
ASTM D-4869 2005el
PRODUCT DESCRIPTION
Gator Skin A mechanically attached,woven polypropylene underlayment used as an alternative to
ASTM D 226,Type I and Type II and ASTM D 4869 Type II or Type IV, roofing
underlayments
APPLICATION INSTRUCTIONS
Deck Type: The roof deck shall be constructed of closely fitted, solid sheathing for new or existing
construction. Sheathing shall be installed in accordance with FBC requirements. Roof
decks shall have no more than '/s" gap at abutting joints. Minimum 19/32" plywood for
new construction or minimum 15/32"plywood for existing construction in the HVHZ only.
Min.slope: Min. 2:12 and in accordance with the FBC; For slopes less than 4:12, the underlayment
must be half-lapped over the underlying course.
Attachment(Non-HVHZ): Underlayment shall be attached in accordance with the FBC requirements and in
accordance with the manufacturer's installation instructions. The underlayment is
installed starting at the eave, with the length of the roll parallel to the eave with the
printed side facing up. All head laps shall be installed to shed water from the deck and
side laps shall be staggered between successive courses.
Attachment(HVHZ): Underlayment shall be attached in accordance with RAS 115, RAS 130,or RAS 133 and
in, accordance with the manufacturer's installation instructions. The underlayment is
installed starting at the eave, with the length of the roll parallel to the eave with the
printed side facing up. All head laps shall be installed to shed water from the deck and
side laps shall be staggered between successive courses.
Allowable roof coverings: Asphalt shingles, metal roof panels and shingles, slate shingles, wood shakes and
shingles
GG115001 FL17824 Page 1 of 2
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein..
CREEKCIZ �I1 UNITED ROOFING MANUFACTURING CO., INC.
Gator Skin
TECHNICAL SERVICES, LLC
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Wind uplift resistance is not within the scope of this evaluation.
3) Installation of the evaluated product shall comply with this report,the FBC,and the manufacturer's published
application instructions. Where discrepancies exist.between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
5) The underlayment may be used as described in other current FBC product approval documents.
6) Roof coverings shall not be adhered directly to the underlayment. Roof coverings shall be mechanically
fastened through the underlayment to the roof deck.
7) The underlayment shall be exposed on the roof deck for a maximum 30 days unless otherwise stated.
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
COMPLIANCE STATEMENT
The,productsevaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code 5t'Edition(2014)as evidenced in the referenced documents submitted by the named manufacturer.
i
%% G�:P RAF''•
No 74021
2015.06.26
07:52:30-04'00'
:?3' STATE OFAl
��'��'• < O R t O P'N Zachary R. Priest, P.E.
Cl`, Florida
Organization No.on No. 021
ANE96 1
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services,LLC does not have,nor will it acquire,a financial interest in any company manufacturing or distributing products under this
evaluation.
CREEK Technical Services,LLC is not owned,operated,or controlled by any company manufacturing or distributing products under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any company manufacturing or distributing products under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the product.
END OF REPORT
GG115001 FL17824 Page 2 of 2
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.