NOTICE OF PRODUCT CERTIFICATION
CERTIFICATION NO: N1011661.01-RI
DATE: 09106/2013
CERTIFICATION PROGRAM: Structural
COMPANY: JELD-WEN
+ CODE: 1822-1
REVISION DATE: 06/10/2017
Iverify that the"Notice ol'Product Certification"is valid,please visit to assure that(tie
p roduct is active and currently listed.This certification represents product conformity to the applicable specification and
il iat certil ication criteria has been satisfied. A NAM approved certification label must be applied to the product to clain)
c.rtification status. Please review anti advise NAM I if any corrections are required to this document_
COMPANY' NAME AND ADDRESS PRODUCT DESCRIPTION
ELD-WEN "Premium Atlantic Vinyl
Ir737 Lakeport Boulevard Casement Window(Impact)"
Klamath Falls,OR 97601 Vinyl Casement Window
w/Fin or Flange Installation
Configuration: X
Glazing:16-118"Annealed Glas,,Vl-aminatc-118"
Annealed Glass/0.090'DuPom SGP Interlayev,1 18"
Annealed Glass
Frame: W-914niin(36.00") 11-1371mrn(72.00")
Vent: W-876nun(.14-50") H-1301 111m00.500
DLO: W-762mm(30.00") 1`1-1 282nun(66.00")
SPECIFICATION PRODUCT RATING
TAS 201/202/203-94 Design Pressure: 2394 Pa (50 psi)
Negative Design Pressonre:2394 Pa(50 psf)
Large Missile Impact Rated
oduct Tested By: National Certified Testing Laboratories
eport No: NCTL-2.10-3903-01
I
x1piration Date: July 31,202
P dininistrator's Signature:
NATIONAL ACCREDITATION AND
MANAGEMENT INSTITUTE., INC.
4794 George Washington Memorial Highway
Hayes,VA 23072
Tel:(804)684-5124
Fax: (804)684-5122
n'w NAIL FIN INSTALLA`PION
DDRMDORM
T � [RS l l/2'MIN.EMBEbMENT
1
2 2X WOOD FRAME
AtIN DISTANCE uTN
yq�tAN— FOR ECS9 37d'—�`v FOR EDGE-3/4"
,a•ae. 3
nN IM MAX 2X WOOD 7f
SHIM SPACE FRAME .3
22.0 MM
2.0 mm 2 1/4°MAX
3.0 mm 3.0 mm SHIM SPACE
DOW
CORNING 998 11/2•MIN, ��
EMBEDMENT
GLASS BITE:
GLAZING DETAIL 13,0 mm 1
FRAME SECTION(TYP) JAMB SECTION(TYP)
VERTICAL SECTION HORIZONTAL.SECTION
Wjl(iaA 6lww.l{Y4 f�7{W W Opwp
NOTF•tm.tr Wb•u,Naliq ft.q•.A WWtl DN.,'r9
t/4•NIAX
aHTM SPACE
MTN.OISTANCE
�t
FOR EME:3/4' PREMIUM ATLANTIC VINYL CASEMENT
2 2X WOOD FRAME _Max Frame _f DP RATING IMPACT
1+ _ WDDW MDTR(34'WUL) I 1 1112'MIN.EMBMMD-IT 36 x 72 +/-50 1 YES
TYPICAL ELEVATION WITH FASTENER SPACING
Installation Notes: General Notes:
1. Seal flangelframe to substrate. 1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
2. Use#10 PH or greater fastener though the nail fin with sufficient length to penetrate a minimum of i of the adopted Inlemational Building Gode(IBC),the International Residential Cods(IRC),the Florida
1/2'into the wood framing. For 2X wood frame substrate(min.S.G.=0.42). Building Code(FBC)Including HVHZ and the industry requirement for the stated conditions.
3. Host structure(wood buck,masonry,steel)to be designed and anchored to properly transfer all loads 2. All glazing shall conform to ASTM E1300.
to the structure. The host structure is the responsibility of the architect or engineer of record for the 3. At minimum,glazing is 3mm annealed•13mm airspace-3mm annealed-2mm PVB or SGP-3mm
project of installation. Digitally signed by Hermes F.Norero,P.E. annealed,
Reason:I am approving this document 4. Use structural or composite shims where required.
Date:2013.10.2818:42:40-04'00' 5. Installation methods can be interchanged within the same opening.
6. An impact protective system is not required where wind borne debris protection is mandated by local
This schedule addresses only the fasteners required to anchor the ,`t t t I I t rrlr building code.
window to achieve the rated design pressure up to the size limitations <<� �i� 7. Maximum sizes are buck sizes and do not include fin or flange.
noted. It is not intended as a guide to the installation process and does �� z f� PRCI3ECT ENGINEER: DATE:
.•• •• r ._ 3737 Lakeport Blvd
not address he sealing consideration(hat may arise in different wall �� �Q`°••.• t� �` �� 10/2S/2013 EL "�VEN'
conditions. For the complete installation procedure,see the instructions .'` �� �++�+N BY: scalF: T jr Klamath Falls,OR.97601
p p �' C d D.Vezo NT$ y Phone: (541)882-3451
packaged whit the window or go to :, NQ!7:37$.
CHE{KED BY: TnnE:
www.jeid-wen.com/resourcesfinstallation, ]. Kantola
DISCLAIMER: + 0 : STATE QF N'PROVEO BY; Premium Atlantic Vinyl Impact Casement Window
This drawing and its contents are confidential and are not to be % • Pggro�Et7g� Nail Fin Installation(36"x 72")
reproduced or copied in whole or in part or used or disclosed to others fi o4y` UU 9 LG
except as authorized by JELD•WEN Inc. soa ttll0 Sae 10ENTIFIER No. PUNT NAME'AND LOCATION; CAD DWG,Nu.: RN: 51,EET
e NCTL210-3903- A-FBC {)�
a' MIN,DISTANCE THROUGH FRAME
FOR.EDGES 3/4. 3 INSTALLATION
' I 2
_� -N.lpSlAy. _ - t l�/BE2OMMIN.
-MAX THRU
n=1 1/4-MAX t 2/2'MIN.
t SHIM SPACE EMBEDMENT
t/4'MAx
22.0 mm 3
M z. SHIM SPACE
3.0 mm 3.0 mm
0 rtBn
Dow �.
CORNING 995
MIM WSTANCE 2FOR ED6E:3/4' (� r
GLASS OM: u
13.0 mm
GLAZING DETAIL JAMB SECTION(TYP}
FRAME SECTION(TYP) HORIZDNTAL SECTION
VERTICAL SECTION
1/4'MAX
sHrM SPACE
3
2 tf/rMIN. PREMIUM ATLAN71C VINYL.CASEMENT
EMBEDMENT Max Frame I DP RATING IMPACT
TYPICAL ELEVATION WITH FASTENER SPACING MIN.DISTANCE 36 x 72 1 +/-50 YES
FOR ED&Ec 3/4'
Installation Notes: General Notes;
1. Seal flangelframs to substrate. 1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
2. Use#10 PH or greater fastener though the frame with sufficient length to penetrate a minimum of 11/2" of the adopted International Building Code(IBC),the International Residential Code(IRC),the Florida
into the wood framing. For 2X wood frame substrate(min.S.G.=0.42). Building Gode(FBC)including HVHZ and the Industry requirement for the stated conditions.
3. Host structure(wood buck,masonry,steel)to be designed and anchored to properly transfer all loads 2. All glazing shall conform to ASTM Ell 300.
to the structure. The host structure is the responsibility of the architect or engineer of record for the 3. At minimum,glazing is 3mm annealed-13mm airspace-3mm annealed-2mm PVB or SGP-3mm
project of installation. annealed.
4. Use structural or composite shims where required.
5. Installation methods can be interchanged within the same opening.
6. An impact protective system is not required where wind borne debris protection is mandated by local
This schedule addresses only the fasteners required to anchor the `t t 11 t r r building code.
window to achieve the rated design pressure up to the size limitations %%% P AJ_ � 7. Maximum sizes are buck sizes and do not include tin or flange.
noted. It is not intended as a guide to the installation process and does PROJECT ENGINEER: DATE:
,••••r �i 3737 Lakeport Blvd
not address he sealing consideration that may arise in different wall �Q� .• d � -- 10/25/2013
conditions. For the complete installation procedure,see the instructions : .r �}G'+` 1 � : DRAWN BY: $CAGE; JELDVEN Klamath Falls,OR,97601
packaged with the window or go to : / D.Vezo NTS Phone: (541)882-3451
'' 'V A77 .� CHECKED 8Y: TITI.F:
www.jeld-wen,com/resourcesfinstallation. = * 1f $ .t * _ J. KED BY.
� tola
AT,E QF rr APPRowoBY; Premium Atlantic Vinyl Impact Casement Window
DISCLAIMER: W
This drawing and its contents are confidential and are not to be O -'•.'Z( 'pP `� PUL D� Through Frame Installation(36"x 72")
reproduced or copied in whole or in part or used or disclosed to others 46w, . . FOP
except as authorized by JELD-WEN Inc. see � " sse f�It NL21�1-3903 A A9 ANS AND LUUTION: CAD OWL NO.: REV: 00 s+eE� 2 of 4
a,MM FAR DISTANCE MASONRY INSTALLATION
eDit+s FOR to"!z lit'
— z
Ali
mosrAH a t v,MIN
uAx.T=
PaAtrc
Ills•MIN.
t/A'MAX EMYEDMERT
SNDA SDACE
t/4'MAX
•Q SHIM SiACE
mm—
MMAAR DISTANCE2.0 V
s,
lomm 3.O mm Foa tDGC-a Vd -
c I' bow
CORNTN&995
I &LASS aAUSOWY
13.0 mm ROCK
m.
GLAZING DETAIL JAMaSEC7LP
HORIZONTAL SECTION
FRAME SECTION(TYP)
VERTICAL 5 CTION
t 1/A'MAX
stnM PACE
1114,MIN
G �' EAlBEDMENT PREMIUM ATLANTIC VINYL CASEMENT
I vnmww WM 1W WYa I R, oI Max Frame I bP RATINGI IMPACT
TYPICAL ELEVATION WITH FASTENER SPACINb AAN.OLSTANCE 36 x 72 1 +/-50 1 YES
POa EDGE,2 U2'
Installation Notes: General Notes:
1. Seal flangelframo to substrate. 1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
2. Use 311 V Topcon or equivalent fasteners through frame with sufficient length to penetrate a minimum of the adopted International Building Code(IBC),the International Residential Code(IRC),the Florida
of 1114'into concrete or masonry at each location with a 2112'min from edge distance.For concrete Building Code(FBC)Including HVHZ and the industry requirement for the stated conditions.
(min.fc=3000ps1)or masonry substrate(CMU shall adhere to ASTM C90), 2. All glazing shall conform to ASTM E1300.
3. Host structure(wood buck,masonry,steel)to be designed and anchored to property transfer all loads 3. At minimum,glazing is 3mm annealed•13mm airspace-3mm annealed•2mm PVB or SGP-3mm
to the structure. The host structure is the responsibility of the architect or engineer of record for the annealed.
project of installation. 4. Use structural or composite shims where required.
S. Installation methods can be interchanged within the same opening.
6. An impact protective system is not required where wind borne debris protection is mandated by local
This schedule addresses only the fasteners required to anchor the building code.
window to achieve the rated design pressure up to the size limitations `,��1 1 t 1 t t f r�r/7' 7. Maximum sizes are buck sizes and do not include fin or flange.
noted. It is not intended as a guide to the installation process and does �� PROJECT EN6IYEER: DATE:
w �,..•c•.� 3737 Lakeport Blvd
not address he sealing consideration that may arise in different wall �� Q- ,.• ,! �` �� -- 10/25/2013
conditions. For the complete installation procedure,see the instructions ' 'ZZ ��G�f /s '.�0 + DRAW"m•; SCA,z JM"ENKlameth Falls,OR.97601
D. BY
NTS Phone: (541)882-3451
packaged with the window or go to Q;77
►vww:eld-wen.comtresourcestinstallation. _ * .:" �'• $ * f3.Ka t Tme:
ola
-d STATE Q� t APPROVEDa; Premium Atlantic Vinyl Impact Casement Window
DISCLAIMER: 113 ; Masonry Installation(36" x 72")
This drawing and its contents are confidential and are not to be ;, O •.�� � � P�t�P�o,1€CJ
reproduced or copied in whole or in part or used or disclosed to others '� , I
except as authorized b JELD•WEN Inc. 398 998 IDENTiF1ER NO. DIA:YT NA41EAND LOCA'nOM CAD DWG.NO.: REV: SHEET
P Y m NCTL210-3903- -F8C 00 I OF 4
a•aux Min mtWdment STEEL INSTALLATION .
FROM of spree it+-wds
00KH y pas.frmae Is gouge m:n
Z (seal Stud
irt
—YI WlAN
MAX.T�ii�M! _j'�
MAW Cly t/4•MAX 1/4"MAX
t SHIM SPACE SHIM SPACE
Min.embedment
ZZ.0 3.0 ntm 3.0 tam mm of three threads I�
- 1 2mm
.0 DOW post frame D
..
D
CORNING 995 18 gauge min
Steel Stud cc
GLASS BITE:
13.0 mm
GLAZING bETAIL JAMB SECTION(TYP)
FRAME SECTION(TYP) HORIZONTAL.SECTION
VERTICAL SECTION
t I/Vaux
$HI
- SHIM SPAM
U. a PREMIUM ATLANTIC VINYL CASEMENT
�tT�TM tu•riot(1----� Steel Max Frame OP RATING IMPACT
Min.embedment 36 x 72 +/-5L) YES
TYPICAL ELEVATION WITH FASTENER SPACING of three threads
PW{(sane
Installation Notes: General Notes,
1. Seal flange/frame to substrate. 1. The product shown herein is designed,tested and manufactured to comply with the wind load criteria
2. For anchoring into metal framing use#10 TEK Self Tapping screws with sufficient length to achieve a of the adapted International Building Code(IBC),the International Residential Code(IRC),the Florida
minimum embedment of three threads past the frame thickness. Steel substrate min.189a.,fy=33 ksh Building Code(FBC)including HVHZ and the industry requirement for the stated conditions.
3. Host structure(wood buck,masonry,steel)to be designed and anchored to properly transfer all loads 2. All glazing shall conform to ASTM E1300.
to the structure. The host structure is the responsibility of the architect or engineer of record for the 3. At minimum,glazing is 3mm annealed-13mm airspace-3mm annealed-2mm PVB or SGP-3mm
project of installation. annealed.
d. Use structural or composite shims where required.
5. Installation methods can be interchanged within the same opening.
B. An impact protective system is not required where wind home debris protection is mandated by local
This schedule addresses only the fasteners required to anchor the building code.
window to achieve the rated design pressure up to the size limitations 4 7. Maximum sizes are buck sizes and do not include fin or flange.
noted. It is not intended as a guide to the installation process and does `� 4e PA01ECr ENGINEER: DATE:
. o..• /Q 3737 Lakeport Blvd
not address he sealing consideration that may arise in different wall ��� c' .• '• F �1, 10/25/2013 �j ,E�r� �
., �C/ �(, DRnwNB". SCAM; j.,t Klamath Falls,OR.976t}i
conditions. For the complete installation procedure,see the instructions y fir. ',• _t:O D.Vezo NTS Phone: (541)882-3451
packaged with the window or go to "N CHECKED BY: TrnE
www.jeld-wen.com/resourcesfnstallafon. Tk t' f" yt _ J. Kantola
-n TATE QF cr = AMR0408Y: Premium Atlantic Vinyl Impact Casement Window
DISCLAIMER: : 73 ' Ott --
This drawing and its contents are confidential and are not to be O •••'�C ` l�P .� ` PUT�UDy't G Sleet Instalfatlon(36 x 7Z )
reproduced or copied in whole or in part or used or disclosed to others Ii . . o U G
No—
except t as authorized b JELD-WEN Inc. see Boa Io[NnrIEN Na PLANT NAME AtlD LDG57SOHt CAD DWG.Nu.: REY: SHEET
p y e NCTL210-3903- A-PBC 00 I°f'
398 East Dania Beach Blvd.
BUILDING DROPS Suite 338
Dania Beach,FL 33004
A Perfect Solution in Every Drop 954.399.8479 PH
Certificate of Authorization:29579 954.744.4738 FX
contact@buildingdrops.com
Of
JELD-WEN, inc.
Premium Atlantic Vinyl Casement
Window
for
Florida Product Approval
Current Florida Building Code
Method: I —A (Certification)
Category: Windows
Sub—Category: Casement
Product: Casement Window(linpact)
Material: PVC
Product Dimensions: 36"'x 72 (X)
Prepared For:
Prepared by:
F
Florida Professional Engineer tt 73779 -7
0
Date:08/11/2014 4.1
0
No. 767.70('
Contcnt.�;: 7Ar77
Evaluation Rcporl Pages 1 4 't3tr
W, T41t
*- -* 144
%
Digitally signed by Hermes F.Norero,
Reason:I am approving this document"O,
Date:2014.09.2213:51:22-0400'
Hermes F.Norero,P.E.
Florida No.73778
1
BUILDING DROPS
Date: 12014
A Perfect Solution in Every Drop 0 : 3
Report No: 31flfl
Certificate of Authorization.29578
Man cturer: JELD-WEN,Inc.
Produci Category: Windows
Produ _ Sub-Category: Casement
Compli nce Method: State Product Approval Method(1)(a)
Produ Name: Casement Window
36 x 72"(X)
Scope: This is a Product Evaluation Report issued by Hermes F.Norero,P.E.(FL#73778)for JELD-WEN,int.
based on Method la of the State of Florida Product Approval,Department of Business and
Professional Regulation-Florida Building Commission.
Hermes F,Norero, P.E.does not have nor will acquire financial interest in the company
manufacturing or distributing the product or in any other entity involved in the approval process of
the product named herein.
This product has been evaluated for use in locations adhering to the current Florida Building Code.
See Installation.Instructions NCTL210-3903-1A-FOC,signed and sealed by Hermes F.Norero,P.E.(FL#
73778)for specific use parameters.
Limits c f Use:
1. This product has been evaluated and is in compliance with the current Florida Building Code,
including the"High Velocity Hurricane Zone"(HVHZ).
2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment into
substrate material shall be beyond wall dressing or stucco.
3. When used in areas requiring wind borne debris protection this product complies with
Section 1609.1.2 of the current Florida Building Code and does not require an impact
resistant covering.
5. Site conditions that deviate from the details of drawing NCTL210-3903-lA-FBC require
further engineering analysis by a licensed engineer or registered architect.
6.' See Installation Instructions NCTL220-3903-1A-FBC for size and design pressure limitations.
Hermes F.Norero,P.E.
Florida No.73778
Page 2 of 4
BUILDING DROPS
A Perfect Solution in Every Drop Date: 08/11/2014
Certificate of Authorization:29578 Report No: 3100
Certific 3tion Agency: The manufacturer has demonstrated compliance of products in accordance with the
Florida Building Code for manufacturing under a Certification Agency through
National Accreditation&Management Institute(FBC Organization#CER1773).
Perfory iance Standards: The product described herein has been tested per:
• TAS 201-94
• TAS 202-94
jTAS 203-94
Refere�ted Data:
1 1. Product Testing performed by National Certified Testing Laboratories
(FBC Organization#TST1589)
Report#: NCTL-210-3903-01, Report Date:07/29/2013
2. Certification Agency
National Accreditation&Management Institute
(FBC Organization#CER1773)
3. Material Certification
Miami Dade RER—Product Control Section NOA
E.I.DuPont De Nemours&Co.,Inc.:SentryGlas Plus Interlayer
4. Material Certification
Miami Dade RER—Product Control Section NOA
E.I.DuPont De Nemours&Co.,Inc.:PVB Interlayer
5. Material Certification
Miami Dade RER—Product Control Section NOA
Quanex Building Products:PVC Extrusions
1
1
Hermes F.Norero,P.E.
Florida No.73778
Page 3 of 4
I
/r/.N\.
BUILDING DROPS
A Perfect Solution in Every Drop Date: 0 oiVo:: 31 014
Report 3100
h. Certificate of Authorization:29578
Install 'on: 1. Approved anchor types and substrates are as follows:
Nailing Fin Installation:
A. For two by(2X)wood frame substrate(Min.S.G.=0.42),use#10 Wood Screw type wood
frame anchors of sufficient length to achieve minimum embedment of 1.50"into wood
framing.
Through Frame Installation:
A. For two by(2X)wood buck substrate(Min.S.G.=0.42),use#10 Wood Screw type
installation anchors of sufficient length to achieve a minimum embedment of 1.50"into
3 the wood substrate.
B. For concrete(Min.f'c=3000 psi)or masonry(Conforms to ASTM C90)substrate where
one by(1X),non-structural,wood bucking is employed,use 3/16"diameter ITW Tapcon
type concrete screw anchors of sufficient length to achieve minimum embedment of
1.25"into concrete or masonry.
C. For concrete(Min.f'c=3000 psi)or masonry(Conforms to ASTM C90)substrate where
wood bucking is NOT employed,use 3/16"diameter ITW Tapcon type concrete screw
anchors of sufficient length to achieve minimum embedment of 1.25"into concrete or
masonry.
D. For steel stud substrate(Min 18 Ga., Fy=33 ksi),use#10 ITW TEK Screw type steel stud
anchors of sufficient length to achieve minimum 3 threads penetration beyond steel
structure.
Refer to Installation Instructions(NCTI210-3903-1A-FBC)for anchor spacing and more details of the
installation requirements.
Design ressure:
Design Pressure Rating
Positive 50 PSF
Negative 50 PSF
Hermes F.Norero,P.E.
Florida No.73778
Page 4 of 4
398 East Dania Beach Blvd.
BUILDING DROPS Suite 338
Dania Beach,FL 33004
A Perfect Solution in Every Drop 954.399.9478 PH
Certificate of Authorization:29578 954.744.4738 FX
contact@buildingdrops.com
Of
JELD-WEN, inc.
Premium Atlantic Vinyl Casement
Window
for
Florida Product Approval
"r 4,1
Current Florida Building Code
Method: I —A (Certification)
Category: Windows
Sub—Category: Casement
Product: Casement Window(Impact)
Material: PVC
Product Dimensions: 36"x 72"{X)
Prepared For:
Prepared by:
Florida Proressional Engineer#73778
.Z. 40��- C)
Date:08/)112014
0
Evaluation Report Pages 1 4 `o'T�T't OF
0 % 9ZdFZfb?-----
Digitally signed by Hermes F.Noreror
Reason:I am approving this document ss/ON Al,V�Z- %
Date:2014.09.2213:51:22-04'00'
Hermes F.Norero,P.E.
Florida No.73778
BUILDING DROPS
A Perfect Solution in Every Drop Date: 08/11/2014Report No: 3100
Certificate of Authorization:29578
I
Manufacturer: 1ELD-WEN,Inc.
Produ I Category: Windows
Produ Sub-Category: Casement
Compli nce Method: State Product Approval Method(1)(a)
Product Name: Casement Window
36 x 72"(X)
i
Scope: This is a Product Evaluation Report issued by Hermes F.Norero,P.E,(FL#73778)for 1ELD-WEN,inc.
based on Method 1a of the State of Florida Product Approval,Department of Business and
Professional Regulation-Florida Building Commission.
Hermes F. Norero,P.E.does not have nor will acquire financial interest in the company
manufacturing or distributing the product or in any other entity involved in the approval process of
the product named herein.
This product has been evaluated for use in locations adhering to the current Florida Building Code.
See Installation Instructions NCTL210-3903-1A-FBC,signed and sealed by Hermes F.Norero,P.E.(FL#
73778)for specific use parameters.
Limits Use:
1. This product has been evaluated and is in compliance with the current Florida Building Code,
including the"High Velocity Hurricane Zone"(HVHZ).
2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment into
substrate material shall be beyond wall dressing or stucco.
3. When used in areas requiring wind borne debris protection this product complies with
Section 1609.1.2 of the current Florida Building Code and does not require an impact
resistant covering.
S. Site conditions that deviate from the details of drawing NCTL210-3903-IA-FBC require
further engineering analysis by a licensed engineer or registered architect.
' 6. See Installation Instructions NCTL210-3903-IA-FBC for size and design pressure limitations.
Hermes F.Norero,P.E.
Florida No.73778
Page 2 of 4
BUILDING DROPS
A Perfect Solution in Every Drop Date: 08/11/2014
31 014
Certificate of Authorization_29578 Report No: 3144
Certifi tion Agency: The manufacturer has demonstrated compliance of products in accordance with the
Florida Building Code for manufacturing under a Certification Agency through
National Accreditation&Management Institute(FBC Organization#CER1773).
Perforn iance Standards: The product described herein has been tested per:
• TAS 241-94
• TAS 202-94
• TAS 203-94
Referenced Data:
1. Product Testing performed by National Certified Testing Laboratories
(F8C Organization# TST1589)
Report#:NCTL-210-3903-01, Report Date:07/29/2013
2. Certification Agency
National Accreditation&Management Institute
(FBC Organization#CER1773)
3. Material Certification
Miami Dade RER—Product Control Section NOA
E.I.DuPont De Nemours&Co.,Inc.:SentryGlas Pius Interlayer
j 4. Material Certification
Miami Dade RER—Product Control Section NOA
E.I.DuPont De Nemours&Co.,Inc.:PVB Interlayer
5. Material Certification
Miami Dade RER—Product Control Section NOA
Quanex Building Products: PVC Extrusions
i
Hermes F.Norero,P.E.
Florida No.73778
Page 3 of 4
BUILDING DROPS
Report No: 3100
Certificate of Authorization-29578
A Perfect Solution in Every Drop Date: 0811112014
Install tion: 1. Approved anchor types and substrates areas follows:
Nailing Fin Installation:
A. For two by(2X)wood frame substrate(Min.S.G.=0.42),use#10 Wood Screw type wood
frame anchors of sufficient length to achieve minimum embedment of 1.5W into wood
framing.
Through Frame Installation:
A. For two by(2X)wood buck substrate(Min.S.G.=0A2),use 410 Wood Screw type
installation anchors of sufficient length to achieve a minimum embedment of 1.50"into
the wood substrate.
S. For concrete(Min.f c=3000 psi)or masonry(Conforms to ASTM C90)substrate where
one by(IX),non-structural,wood bucking is employed,use 3/16"diameter ITW Tapcon
type concrete screw anchors of sufficient length to achieve minimum embedment of
1.25'into concrete or masonry.
C. For concrete(Min.I'c=3000 psi)or masonry(Conforms to ASTM C90)substrate where
wood bucking is NOT employed,use 3/16"diameter ITW Tapcon type concrete screw
anchors of sufficient length to achieve minimum embedment of 1.25"into concrete or
masonry.
M For steel stud substrate(Min 18 Ga.,Fy=33 ksi),use#10 ITW TEK Screw type steel stud
anchors of sufficient length to achieve minimum 3 threads penetration beyond steel
structure.
Refer to Installation Instructions(NCTL210-3903-1A-F8C)for anchor spacing and more details of the
installation requirements.
Design ressure:
Design Pressure Rating
Positive so PS
Negative 50 PSF
Hermes F.Norero,P.E.
Florida No.73778
Page 4 of 4