EXTERIOR RESEARCH&DESIGN,LLC.
�y Certificate of Authorization#9503
TRINI 1 1 33 CHRISTIAN STREET, UNIT
Q0ERD OXFORD,CT 065478478
(203)262-9245
EVALUATION REPORT
TRI-BUILT Materials Group,LLC Evaluation Report A42960.10.12-R5
PO Box 70 !; FL16048-115
Rutherford, NJ 07070 Date of Issuance:10/25/2012
(800)516-1485 Revision 5: 06/12/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rulesand regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been 'reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance-with the 5th Edition (2014) Florida Building Code
sections noted herein.
DESCRIPTION: TRI-BUILT Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate.to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify,lRobert 'Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity)ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity IERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done,in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by: ,r
Robert J.M.Nieminen P.E. ��i fl�A Et Yo The facsimile seal appearing was authorized by Robert Nieminen,
Nieminen, t4SS!.. •L. c�.
- 'r'l%sy.,,,trttssI P.E.on 06/12/2017.This does not serve as an electronically signed
Florida Registration No.59166,Florida DCA ANE1983 ��'' document.Signed,sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. Trinity IERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any,company manufacturing or
distributing products it evaluates.
2. Trinity ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued. I
4. Robert Nieminen, P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity I ERD nor Robert Nieminen, P.E. are, in any way,the,Designer of Record for any
project on which this Evaluation Report,or previous versions thereof, is/was used for permitting'or design guidance unless retained
specifically for that purpose.
, I
�TRINITYJERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Underlayment
Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have
demonstrated compliance with the following sections of the Florida Building Code through testing in accordance
with the following Standards. Compliance is subject to the Installation Requirements and Limitations/Conditions of
Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1504.3.1 Wind Resistance FM 4474 2004
1504.3.1 Wind Uplift UL 1897 2004
1507.2.4,1507.2.8,1507.2.9.2, Physical Properties ASTM D1970 2009
1507.4.5.1,1507.5.3,1507.7.3
1504.6 Accelerated Weathering ASTM G155 2005
1507.3.3 Installation Practice FRSA/TRI April 2012(04-12) 2012
1523.6.5.2.1 Physical Properties TAS 103 1995
3. REFERENCES:
Entity Examination Reference Date
ERD(TST6049) Physical Properties S40540.02.13-1 02/19/2013
ERD(TST6049) Physical Properties 540540.11.13 11/19/2013
ERD(TST6049) Physical Properties 540540.03.14 03/26/2014
ERD(TST6049) Physical Properties 544870.04.14-2 04/02/2014
ERD(TST6049) Physical Properties 544870.04.14-3 04/02/2014
ERD(TST6049) Physical Properties 544870.04.14-1 04/10/2014
ERD(TST6049) Physical Properties S44870.04.14-4 04/10/2014
ERD(TST6049) Physical Properties 543530.02.14-1-R1 05/14/2014
ERD(TST6049) Physical Properties S43530.05.14 05/28/2014
ERD(TST6049) Physical Properties 540540.10.14 10/31/2014
ERD(TST6049) Physical Properties SC7645.02.15 02/13/2015
ERD(TST6049) Accelerated Weathering SC8520.04.15 05/27/2015
ERD(TST6049) Wind Resistance SC14045.05.17-R1 06/07/2017
UL,LLC.(QUA9625) Quality Control Multiple-Listing R16814 09/04/2015
UL,LLC.(QUA9625) Quality Control Service Confirmation Exp.10/16/2017
4. PRODUCT DESCRIPTION:
4.1 Tri-Built Sand-R SA Shingle Underlayment is a self-adhering, glass-mat reinforced, sand-surfaced, SBS
modified bitumen roof underlayment,with a 36-inch sheet width.
4.2 Tri-Built S/A HT TU Underlayment is a self-adhering, non-woven polyester fabric surfaced, SBS modified
bitumen roof underlayment
4.3 Tri-Built Smooth HT S/A Underlayment is a self-adhering, glass-mat reinforced, film-surfaced, SBS
modified bitumen roof underlayment.
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
Exterior Research and Design,LLC. Evaluation Report A42960.10.12-R5
Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION FL16048-RS
Tri-Built Materials Group,I.I.C. Revision 5:06/12/2017
Page 2 of 6
i
Q 0
TRIIeIITY ERD
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof' cover, where the product is
specifically referenced within FBC approval documents. If not listed, a ,reque'st may be made to the
Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the
prepared roof covering.
I
5.5 Allowable roof covers applied atop the underlayments are as follows:
TABLE 1: ROOF COVER OPTIONS
Asphalt Wood Shakes
Underlayment Shingles Nail-On Tile Foam-On Tile Metal &Shingles Slate
Tri-Built Sand-R SA Shingle
Underlayment Yes No No No Yes Yes
Tri-Built S/A HT TU Yes
Yes Yes � Yes Yes Yes
Underlayment See 5.5.1
Tri-Built Smooth HT S/A Yes No No Yes Yes Yes
Underlayment
5.5.1 "Foam-On Tile" is limited to use of the following Approved tile adhesives unless tensile adhesion / long
term aging data from an accredited testing laboratory is provided)
➢ Tri-Built S/A HT TU Underlayment with ICP Adhesives "Polyset AH-160" (FL6332) or Dow Chemical
"TileBond•"Roof Tile Adhesive"(FL717)
5.6 Allowable substrates are noted below:
5.6.1 Direct-Bond to Deck:
Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment on Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Plywood;ASTM D41 primed plywood; OSB;ASTM D41 primed OSB; Southern Yellow Pine;ASTM D41
primed Southern Yellow Pine;ASTM D41 primed structural concrete.
While not required over plywood,OSB or Southern Yellow Pine substrates,TRI-BUILT Materials Group,LLC
recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note:
TRI-BUILT Materials Group, LLC requires tongue-and-groove board decking be covered with plywood or
OSB prior to installation of the self-adhering underlayment.
i
5.6.2 Bond-to-Insulation:
Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment o Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Dens Deck Prime;SECUROCK Gypsum-Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam-on tile systems (Tri-Built S/A HT TU Underlayment only), ;insulation attachment shall be
designed by a qualified design professional and installed based on testing'of the insulation/underlayment
system in accordance with FM 4474,Appendix D or TAS 114,Appendix J.
I '
i
Exterior Research and Design,LLC. Evaluation Report A42960.10.12-RS
Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION FL16048-R5
Tri-Built Materials Group,LLC. Revision 5:06/12/2017
Page 3 of 6
Y
F)o
TRII rry I ERD
5.6.3 Bond to Mechanically Attached Base Laver:
Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ ASTM D226,Type I or II felt.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam-on tile systems (Tri-Built S/A HT TU
Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-
12).
5.6.4 Wind Resistance for Underlayment Systems in Foam-On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam-on tile systems, where
the underlayment forms part of the load-path. The following wind uplift limitations apply to direct-deck
underlayment systems that are not addressed in FRSA/TRI April 2012(04-12)and are used in foam-on tile
applications. Maximum Design Pressure is the result of testing for wind load resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12) or FBC 1609 for
determination of design wind pressures.
5.6.4.1 Maximum Design Pressure=-45.0 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: (Optional)ASTM D41 or RESISTO EXTERIOR PRIMER
Underlayment: Tri-Built S/A HT TU Underlayment,self-adhered.
5.6.4.2 Maximum Design Pressure=-67.5 psf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: Soprema Elastocol 600c
Underlayment: Tri-Built S/A HT TU Underlayment,self-adhered.
5.6.4.3 Maximum Design Pressure=-150.0 psf:
Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit
adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp
splinters and wood projections shall be removed/sanded.
Primer: (Optional) RESISTO EXTERIOR PRIMER
Underlayment: Tri-Built S/A HT TU Underlayment, self-adhered, shall be thoroughly roll using hand
roller and/or weighted roller to ensure there are no voids, and ensure there are no
voids/bridging at side and end-laps.
5.6.4.4 Maximum Design Pressure=-60.0 psf:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1)
and tin caps(FBC 1517.5.2)spaced 6-inch o.c. at the 4-inch laps and 6-inch o.c. in three,
equally spaced rows in the center of the sheet.
Underlayment: Tri-Built S/A HT TU Underlayment,self-adhered.
5.7 Exposure Limitations:
5.7.1 Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left
exposed for longer than 30-days after installation
5.7.2 Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installation.
Exterior Research and Design,LLC. Evaluation Report A42960.10.12-R5
Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION FL16048-R5
Tri-Built Materials Group,I.I.C. Revision 5:06/12/2017
Page 4 of 6
QIOTRINITYIERD
6. INSTALLATION:
6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC
published installation requirements subject to the Limitations set forth in Section 5 herein and the
specifics noted below.
6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application,and prime the substrate(if applicable).
6.3 Tri-Built Sand-R SA Shingle Underlavment Tri-Built S/A HT TU Underlavment or'Tri-Built Smooth HT S/A
Underlavment:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Sections
1507 for the type of prepared roof covering to be installed.
6.3.2 Non-Tile applications:
While priming is optional,TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof
cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel-off the release film diagonally while holding the
membrane tight. Firmly roll, broom or hand-press the membranelinto place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below,sealed in accordance with
TRI-BUILT Materials Group,LLC requirements.
When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back-nailing in the
overlap area at the top of the sheet at 12-inch o.c.
j For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center, of the valley or ridge in
each direction. For valleys,apply the sheet starting at the lowest point and work'upward.
6.3.3 Tile Applications(Tri-Built S/A HT TU Underlavment only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above as a guideline.
For foam-on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that
fall outside the scope of FRSA/TRI April 2012(04-12). 1 1
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment.
Tri-Built S/A HT TU Underlayment has met the tile slippage test requirements specified in FRSA/TRI April
2012 (04-12) up to a 10-tile stack to a maximum roof pitch of 6:12 for flat tiles and 5:12 for lugged tiles.
Lugged tiles staged at pitch>5:12 may use alternate staging method (bottom 2-tile stack shall be inverted,
followed by 8 tiles high on slope,as shown below).
,I
Exterior Research and Design,U.C. Evaluation Report A42960.10.12-115
Certificate of Authorization 1!9503 FBC NON-HVHZ EVALUATION FL16048-RS
Tri-Built Materials Group,U.C. Revision 5:06/12/2017
Page 5 of 6
1
TRII ITY I ERD
"= ILI
r
f
Figure 1: Alternate Staging Method
Alternatively, at roof slopes greater than these limitations, all tiles shall be loaded onto a nominal 1"x 2"
horizontal batten to prevent slippage or damage to the underlayment.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered for F.A.C. Rule 9N-3 QA requirements.
9. QUALITY ASSURANCE ENTITY:
UL,LLC—QUA9625;(314)578-3406;k.chancellor@us.ul.com
-END OF EVALUATION REPORT-
Exterior Research and Design,LLC. Evaluation Report A42960.10.12-RS
Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION FL16048-RS
Tri-Built Materials Group,I.I.C. Revision 5:06/12/2017
Page 6 of 6
11/2/2017 Florida Building Code Online ?
BusinessW7 0
1po0 S,9
BCIS Home I Log In I User Registration I Hot Topics I Submit Surcharge .I Stats&Facts I Publications I FBC Staff I BCIS Site Map'I Links I Search I
i
I
i Product Approval
USER:Public User
I
8
Product Approval Menu>Product or Aoolication Search>Application List>Application Detail
• FL# FL18355-R3
Application Type Revision i
Code Version 2014
Application Status Approved
I I
' I
Comments
Archived �]
Product Manufacturer TAMKO Building Products,Inc.
Address/Phone/Email PO Box 1404
Joplin, MO 64802
(417) 624-6644 Ext 2305
kerri eden@tamko.com
Authorized Signature Kerri Eden
kerri_eden @tam ko.co m'
Technical Representative
Address/Phone/Email
i
I
Quality Assurance Representative
Address/Phone/Email
I N
Category Roofing
Subcategory Asphalt Shingles
I
I
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
C? Evaluation Report-Hardcopy Received
Florida Engineer or Architect Name who developed the Zachary R. Priest
Evaluation Report
.Florida License PES 4021
Quality Assurance Entity UL ELC {
Quality Assurance Contract Expiration Date 01/07/2019
Validated By Locke Bowden
f , Validation Checklist=Hardcopy Received
I
Certificate of Independence FL18355 R3 COI TBP15001.3 FBC 2014 Product Evaluation Report
Shinoles.Ddf 4 i
Referenced Standard and Year(of Standard) Standard Year
ASTM D 3161 2009
ASTM D 3462 2009
ASTMD D 7158 2008
TAS 100 1995'
Equivalence of Product Standards
Certified By
Sections from the Code
. I
https://floridabuilding.org/pr/pr app_dtl.aspx?param=wGEVXQwtDquvosrHazGXQW83MPT3uofKl2FSvRVj3yllYNvoJiP6ggp/pad°/p3d 1/2
11/2/2017 Florida Building Code Online
Product Approval Method Method 1 Option D
Date Submitted 05/09/2017
Date Validated 05/10/2017
Date Pending FBC Approval 05/15/2017
Date Approved 08/08/2017
Date Revised 09/25/2017
Summary of Products
FL# Model,Number or Name Description
18355.1 Glass-Seal, Elite Glass-Seal, ASTM D 3462 asphalt shingles and hip and ridge shingles
Heritage, Heritage Premium,
Heritage Woodgate, Heritage
Vintage, Hip and Ridge, and Vintage
Hip and Ridge Shingles
Limits of Use Installation Instructions
Approved for use in HVHZ:Yes FL18355 R3 II TBP15001.3 FBC 2014 Product Evaluation
Approved for use outside HVHZ:Yes Report Shingles.Ddf
Impact Resistant: N/A Verified By: Zachary R. Priest PE-74021
Design Pressure: N/A Created by Independent Third Party: Yes
Other:See evaluation report for limits of use. Evaluation Reports
FL18355 R3 AE TBP15001.3 FBC 2014 Product Evaluation
Report Shingles.Ddf
Created by Independent Third Party: Yes
Back. Next
Contact Us::2601 Blair Stone Road.Tallahassee FL 32399 Phone:850-487-1824
' The State of Florida is an WEED employer.Copyright 2007-2013 State of Florida.::Privacy Statement::Accessibility Statement::Refund Statement
Under Florida law,email addresses are public records.If you do not want your e-mail address released In response to a public-records request,do not send electronic
mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.-Pursuant to Section
455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if they have
one.The emails provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to supply a personal
address,please provide the Department with an email address which can be made available to the public.To determine if you are a licensee under Chapter 455,F.S.,
please click here.
Product Approval Accepts:
® ® ®� ®
Credit Card
Safe
https://floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDquvosrHazGXQW83MPT3uofKl2FSvRVj3yllYNVOJiP6gg%3d%3d 2/2
No.
CREEK Certificate of Authorization inb rgh Dr
17520 Edinburgh Dr
Tampa,FL 33647
TECHNICAL SERVICES, LLC (813)480-3421
EVALUATION REPORT FLORIDA BUILDING,CODE 5T"EDITION(2014)
Manufacturer: TAMKO BUILDING PRODUCTS Issued May 9, 2017
220 West 4" Street
Joplin,MO 64801
(417)624-6644
Manufacturing Plants: Joplin, MO
Phillipsburg,KS
Frederick,MD
Dallas,TX
Tuscaloosa,AL
Quality Assurance: UL LLC(QUA9625)
SCOPE
Category: Roofing
Subcategory: Asphalt Shingles
Code Sections: 1507.2.5, 1507.2.7.1, 1523.6.5.1
Properties: Physical properties,Wind Resistance,Wind Driven Rain
REFERENCES
Enti Report No. Standard Year
PRI Construction Materials Technologies(TST5878) TAP-043-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-051-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-054-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-114-02-01 TAS 100 91995
PRI Construction Materials Technologies(TST5878) TAP-117-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-130-02-01 TAS 100 1995
PRI Construction.Materials Technologies(TST5878) TAP-131-02-01 TAS 100 ,1995
PRI Construction Materials Technologies(TST5878) TAP-165-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-280-02-01 TAS 100 11995
PRI Construction Materials Technologies(TST5878) TAP-303-02-01 TAS 100 :1995
PRI Construction Materials Technologies(TST5878) TAP-307-02-01 TAS 100 ;1995
PRI Construction Materials Technologies(TST5878) TAP-314-02-01 Rev 2 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-315-02-01 ASTM D 6381 12008(2013)e1
PRI Construction Materials Technologies(TST5878) TAP-317-02-01 TAS 100 0995
UL LLC(TST9628) 02NK9507 ASTM D 3161 X2009
UL LLC(TST9628) 04NK24366 ASTM D 3462 ;2009
UL LLC(TST9628) 05NK28006 UL ASTM
D 6381 �2008(2013)e1
ASTM D 7158 12008d
UL LLC(TST9628) 06NK03898 ASTM D 3161 2009
ASTM D 3462 -2009
UL LLC(TST9628) 08CA59132 ASTM D 3161 82009
UL LLC(TST9628) 09NK07896 ASTM D 3161 2009
ASTM D 3462 2009
UL LLC(TST9628) 1 OCA50498 ASTM D 3462 2009
UL LLC(TST9628) 1OCA64882 ASTM D 3161 '2009
UL LLC(TST9628) 11NK14014 ASTM D 3161 2009
ASTM D 3462 ;2009
UL LLC(TST9628) 12CA24551 ASTM D 3161 2009
UL LLC(TST9628) 4786110543 ASTM D 6381 2008(2013)el
UL LLC(TST9628) 4787043752 ASTM D 3161 2009
UL LLC(TST9628) 4787148748 ASTM D 7158 2008d
ASTM D 3161 :2009
ASTM D 3462 '2009
CREEK Technical Services LLC(ANE11669) TBP15001.3 Calculations; '2017
TBP15001.3, FL18355-R3 ; Page 1 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other'product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
PRODUCT DESCRIPTION
Elite Glass-Seal® 12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
(Frederick,Joplin& asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
Tuscaloosa) ceramic granules complying with ASTM D 3462.
Glass-Seal 12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
(Frederick& asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
Tuscaloosa) ceramic granules complying with ASTM D 3462.
Glass-Seal 12-1/4"x 36",ASTM D 7158, Class H self-sealing, 34ab asphalt shingle with fiberglass
(Joplin) mat coated on both sides with asphalt and surfaced with ceramic granules complying
with ASTM D 3462. Shingles shall be used in the non-HVHZ only.
Heritage® 13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas,Frederick, reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Joplin,Phillipsburg& complying with ASTM D 3462.
Tuscaloosa)
Heritage®Premium 13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas,Frederick, reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Phillipsburg& complying with ASTM D 3462.
Tuscaloosa)
Heritage®Premium 12" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Frederick) laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage®Vintage® 17-1/2"x 40",ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Phillipsburg) laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage®Woodgate 13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas&Frederick) reinforced, laminated architectural asphalt shingle surfaced with mineral granules
complying with ASTM D 3462.
Heritage®Woodgate 12" x 36-3/8", ASTM D 3161, Class F fiberglass reinforced, laminated architectural
(Frederick) asphalt shingle surfaced with mineral granules complying with ASTM D 3462. Shingles
shall be used in the non-HVHZ only.
Hip and Ridge Shingles 12-1/4" x 12", ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt
(Frederick&Joplin) shingle surfaced with mineral granules complying with ASTM D 3462.
Vintage®Hip and Ridge 12" x 12", ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt shingle
(Phillipsburg) surfaced with mineral granules complying with ASTM D 3462.
TBP15001.3 FL18355-R3 Page 2 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
Cp TAMKO BUILDING PRODUCTS
jt K Asphalt Shingles
TECHNICAL SERVICES, LLC
INSTALLATION
Elite Glass-Seal@ Basic Wind Speed(V„it): Max. 194 mph
(Frederick,Joplin& Basic Wind Speed(Vasd): Max. 150 mph
Tuscaloosa) Deck(HVHZ): In accordance with FBC requirements;
& Solidly sheathed min. 19/32 in. plywood or wood plank for
Glass-Seal new construction; Min. 15/32 in. plywood existing
(Frederick,Joplin(Non- construction.
HVHZ)&Tuscaloosa) Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction;Min.7/16 in.OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements.' Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation(HVHZ): Installed with 5-1/8 inch exposure in accordance with RAS
115 and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ): Installed with 5-1/8-inch exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
NAILS
.4
i
Nailing _-- _----- . - : . -- _ -- - - 6-7ff
Area -...._..............--=---___�._...___-.----._______.------•----_.__.___ ..
5-118"
Mete
Figure 1. Elite Glass-Seal&Glass-Seal
4 Nail Pattern(Non-HVHZ only)
NAILS
\.....---------........-----I
Nallin
� n
9 p! ................ .................
-_----
- = =_=-- = ____ =__ __ _ —
5-118"
Area
I �
Butt Edge
Figure 2. Elite Glass-Seal&Glass-Seal
6 Nail Pattern
TBP15001.3- FL18355-R3 Page 3 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical.Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or otherproductiattributes that are not
specifically addressed herein.
CREEK
n TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Heritage® Basic Wind Speed (Vit): Max. 194 mph
(Dallas, Frederick,Joplin, Basic Wind Speed(Vasa): Max. 150 mph
Phillipsburg&Tuscaloosa) Deck(HVHZ): In accordance with FBC requirements;
& Solidly sheathed min. 19/32 in. plywood or wood plank for
Heritage®Premium new construction; Min. 15/32 in. plywood existing
(Dallas, Frederick construction.
Phillipsburg&Tuscaloosa) Deck(Non-HVHZ): In accordance with FBC requirements;
& Solidly sheathed min. 15/32 in. plywood or wood plank for
Heritage®Woodgate new construction; Min.7/16 in.OSB existing construction.
(Dallas&Frederick) Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation(HVHZ): Installed with 5-5/8 in. exposure in accordance with RAS
115 and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ): Installed with 5-5/8 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
FASTENERS NAIL ZON E
COMMON
BOND
6-118" EXPOSURE 5=5/8"
11 12-112" 12-318" - - 12-1/2`
Figure 3. Heritage®, Heritage®Premium, and Heritage®Woodgate(Dallas)
4 Nail Pattern (non-HVHZ only)
FASTENERS NAIL ZONE
COMMON
BOND
61 EXPOSURE 5-518"
1' �7-112' -7-112"-�h- 7 8"-►�7-112" ►N-7-112"-►� �— "
Figure 4. Heritage®&Heritage®Premium .
6 Nail Pattern
TBP15001.3 FL18355-R3 Page 4 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation, recommended use,or other product attributes that are not
specifically addressed herein.
CRK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
NAIL,
_ ZDNEI
ASTENES' Cb1td0N BQJvD
r
Figure 5. Heritage®Woodgate
6 Nail Pattern
r
1,2-1J2"—►j It-12=Ur—
l
' FASTENERS I ® Common Bond
----------------
t
+ 1
39-31W
I I
Figure 6. Heritage®, Heritage®Premium,&Heritage®Woodgate
Alternate 6 Nail Pattern
I ,
I I l
PAINT'
AIL ZONE:
69-0 .2 ..
COMON ,:
BOND
I I
E�CPO,�IJRE
ACOEPTAE3L'E . :. � '�
fASTENER LOCATION!,
D.O.NOT FASTEN:
Tk 4b Ei5:&:OF.
- GOMMONSOND;:
RE ERRED
FAST -WR
L4.CATION
Figure 7. Heritage®(Tuscaloosa) ;I
Expanded Nail Zone
Nail patterns from Figures 3,4, and 6 may be placed in the nail lone as described above
I
TBP15001.3 FI-18355-R3 ! Page 5 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express not imply warranty, installation, recommended use,or other product,,atiributes that are not
specifically addressed herein.
I
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Heritage®Premium Basic Wind Speed(V„i,): Max. 194 mph
(Frederick) Basic Wind Speed(Vasd): Max. 150 mph
Deck(HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min.7/16 in.OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12. .
Installation(HVHZ): Installed with 5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ): Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
NAIL ZONE/
FASTENERS //COMMON BOND
51/211 F1 EKPOSURE 5"F]
li I
1"-- -- 1111--►R�-- 12 —�► -11"—� {4-1
11
Figure 8. Heritage@ Premium(Frederick)
4 Nail Pattern (non-HVHZ only)
NAIL ZONE/
FASTENERS COMMON BOND
T V .
5x.1/211 EXPOSURE 5"
���! ��1hn 9°—►��" 91/2"
�I f Figure 9. Heritage@ Premium(Frederick)
6 Nail Pattern
TBP15001.3 FL18355-R3 Page 6 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
G iJ TAMKO BUILDING PRODUCTS
[1 Asphalt Shingles
TECHNICAL SERVICES, LLC
Heritage®Woodgate Basic Wind Speed (V„it): Max. 194 mph
(Frederick) Basic Wind Speed(Vasd): Max. 150 mph
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed"min. 15/32 in. plywood or wood plank for
new construction;Min.7/16 in.OSB existing construction.
Underlayment: In accordance with FBC requirements. '
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation (Non-HVHZ): Installed with 5 in. exposure. in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached,!using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
I
NAIL ZONE/
FASTENERS COMMON BOND
T
5-112" EXPOSURE 5"
' 1"� �- 11" •..►�--.12-318"—�t– 11" � �-1" ',
Figure 10. Heritage®Woodgate(Frederick)
4 Nail Pattern (non-HVHZ only)
NAIL ZONE/
FASTENERS'
COMMON BOND
5'112" EXPOSURE 5"
Figure 11. Heritage®Woodgate(Frederick)
6 Nail Pattern
i
TBP15001.3 FL18355-R3 Page 7 of 11
This evaluation report is provided for State of Florida'product approval under Rule 61G20-3: The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality'assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other productlattributes that are not
specifically addressed herein.
CREEKT i�K TAMKO BUILDING PRODUCTS
j't Asphalt Shingles
TECHNICAL SERVICES, LLC
Heritage®Vintage® Basic Wind Speed (Wit): Max. 194 mph
(Phillipsburg) Basic Wind Speed (Vasd): Max. 150 mph
Deck(HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min.7/16 in.OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation(HVHZ): Installed with 5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ): Installed with 5 in. exposure in accordance with FBC
requirements and manufacturers published installation
instructions. Shingles shall be attached using either"5 Nail
Pattern"or"6 Nail Pattern"detailed below.
4T
u mne # rkposure
r�anm z No>rh
S, Fagenas .6'
- - - - - - - - - - - -
one
n-112"
S.
Upposure
�1�-�--47Af` 9.1/4`—►�41/S` * .
-1l
Figure 12. Heritage®Vintage®
5 Nail Pattern (non-HVHZ only)
s ml
v-ur
s
Figure 13. Heritage®Vintage®
6 Nail Pattern
TBP15001.3 FI-18355-R3 Page 8 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Hip&Ridge Basic Wind Speed(Wit): Max. 194 mph
(Frederick&Joplin) Basic Wind Speed(V.sd): Max. 150 mph
Deck(HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. i plywood existing
construction.
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction;Min.7/16 in.OSB existing construction.
Undedayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements.
Installation: Installed with 5-1/8 inch exposure in accordance with the
FBC and manufacturer's published installation instructions.
The direction of the exposed end shall be away from the
prevailing wind.
I
Direction prevailing wind
Start �1/8" exposure
erer-
'a
-I II
Start
Figure 1 here 5-1%8"exposure
11
6
S"
-
Fastener Fastener
IS
Figure 2 9Iv Figure 3
Figure 14. Hip&Ridge(Frederick&Joplin)
i�
TBP 15001.3 FL18355-R3 Page 9 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout;the duration for which this report•is valid.
This evaluation report does not express nor imply warranty,installation, recommended use,or other product'attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Vintage®Hip&Ridge Basic Wind Speed(V.1,): Max. 194 mph
(Phillipsburg) Basic Wind Speed(Vasa): Max. 150 mph
Deck(HVHZ): In accordance with FBC requirements;
Solidly sheathed min: 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction;Min.7/16 in.OSB existing construction.
Undedayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements.
Installation: Installed with 5 inch exposure in accordance with the FBC
and manufacturer's published installation instructions. The
direction of the exposed end shall be away from the
prevailing wind.
Direction prevailing wind
caret 5i" exposure
Start
here 5" exposure
Figure 1
Fastener 1/ ,+I Fastener
5-1/2"
Figure 2 1/4 Figure 3
Figure 15. Vintage®Hip& Ridge(Phillipsburg)
TBP15001.3 FL18355-R3 Page 10 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation, recommended use,or other product attributes that are not
specifically addressed herein.
��'��..
� X
i • �
4
t'
`� ,1
1,
�'
,�
fl.
�� �
� �S
., ' 1
� �1
d �i
`� '�
.l
1
� �,1
1
t { 1
1
1M
1,
i
,� 1
,1
3
\�
t
' ��
i
i
Z
4,
t�
� ,,, ��
��
�� �;'�.
�� , .
ti
'
������@��� �m�a0
���8�������8�� ~~^—~''^^'~~'S
Asphalt Shingles
lFEcHrozCAL��cRwnCES' LL��
L|mITATn»mm
.
1) Fire Classification|onot within the scope cfthis evaluation.
2) The roof deck and the roof deck attachment shall be designed by others to meet the minimum design loads
established for components and cladding and in accordance with FBC requirements.
3 The mean roof height shallberestricted toamaximum 33hinthe HVHZ.
4> Classification to ASTM D 7158 applies to exposure B&C with a building mean roof height of 60-ft or less.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners inthe deck
shall be checked for protrusion and corrected prior to underlayment application.
0) Shingles shall be installed starting at the aavm in horizontal layers such that the laps shed water from the
deck.
7) Installation of the evaluated products ahuU comply with this report, the FBC, and the manufacturer's
published application instructions. Where discrepancies exist between these sources, the more restrictive
and code compliant detail shall prevail.
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule G182O'3.
COMPLIANCE STATEMENT '
The products evaluated herein by Zachary R. Phont. P.E. have demonstrated compliance with the Florida Building
Code 5th Edition(2014)as evidenced in the referenced documents submitted by the named manufacturer.
x»ononax«x
No 74021
2017J05.09
15:06]0
. — — ' -04'00
Zachary R. Priest, P.E.
Florida Registration No.74021
."r1. Organization No.xmEnouo
'—vxxmu»"^'
CERTIFICATION opINDEPENDENCE
CREEK Technical Services, LLC does not have,nor will uacquire,qfinancial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services,LuCwnot owned,operated,mcontrolled uyany company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
`
Zachary n.Priest,P.s.does not have,nor will acquire,mfinancial interest Nany other entity involved/nthe approval process mthe
product.
END OF REPORT