HomeMy WebLinkAboutDrawing Piiieview MHP
3265 South Us Highway 1 Meter to be set at the rear
Fort Pierce._FL 34982 of the lot between 16& 17
200 amp panel with sub-feed
FPUA 400 amp breakers to seperately feed each
Transfomser lot for: 15,16,17,18,18a,18b.
Senzce kill be mounted 200 amp 4/0 Yhhw-2
0upon a rack constructed ® jumper conductors
of 2" IMC conduit and ®p #4 cu.grounding.
lv
gaanized slotted strut. iooa881ooa
The rack will be 200 a88
supported in concrete.
® 1aoaBB1aoa
FPUA
Pole
P 15
v 16
C 117
S is
c 18a 111Hh 18b
8
0 70 amp mobile home panel
i with 50amp/240v.outlet
&20a Gfci receptacle
1-1/4"pec Conduit
#2 Xhhn-2 al.conductors
98 cu.grounding conductor
per NEC 250.66
grounding conductor is
1/0 cu.
Hautmole
Pec Sc
h 40 (not less than 24"below
grade)
18"below grade
600 kcmil Xhhw-2 aL 3" conduitt
NAtiDµOL[ LbCA`reD Zegik1D Lo-r 147
I leo r-r 5• S W of KeTelp_ N hl
RECEIVED
CONTRACTOR COPY JAN 23 18
ST. Lucie County, Permitting
Pineview MHP
3265 South Us Highway I Meter to be set at the rear
Fort Pierce.FL 34982 of the lot between 16&17
FPUA 400 amp
Transtomxr 200 amp panel with sub-feed
0 breakers to seperate1v feed each
200 amp lot for: 15,16,17,18,18a,18b.
® 4/0 X hhw-2
Sen ice Rill be mounted 400P jumper conductors
upon a rack constructed ® BB #4 cu.grounding.
of 2" IMC conduit and 700arnp 2W BB
galvanized slotted stmt. ® BB
The rack will be
pole supported in concrete.
P P
V V
C C
S s Future proposed 200 anip
h
C Installation >
0 0 BB
BB
I.
per NEC 250** 200 amp panel with sub-feed
grounding conductor is breakers to seperatel-feed each v
1/0 ctt. lot for: 9,10,11,12,13,14 C
4/0 X hhw-2
x�aaahLok jumper conductors c
#4 cu.grounding. h
8 1
0 #4 cu.gro ding
Pvc Sch 40 (not less than 18"below grade) Pvc Sch 40 (not less than 18"below grade)
6000 kcmil Xhbw-2 aL 3" conduit 4/0 Xhhw-2 2.5" conduit
MAo,4a46LE L.0CATEl bG41hib Lar y7 ._.....
Y6 OrT. S Sw• bF WETEQ CA PJ
RECEIVED
CONTRACTOR COPY JAN 2 s 2318
ST. Lucie County,Permitt'no