Loading...
HomeMy WebLinkAboutProduct Approval PILE COPY EXTERIOR RESEARCH&DESIGN, LLC. Certificate of Authorization 119503 UD RINITY I 353 CHRISTIAN STREET, UNIT#13 ERD OXFORD,CT 06478 (203)262-9245 EVALUATION REPORT Owens Corning Evaluation Report 037940.02.12-118 One Owens Corning Parkway FL10674-1113 Toledo,OH 43659 Date of Issuance:02/06/2012 (740)404-7829 Revision 8: 10/09/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Owens Corning Asphalt Roof Shingles LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein and FBC 1507.2.7.1/R905.2.6.1. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinity I ERD;requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity]ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety. INSPECTION: Upon request, a copy of this,entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 8. Prepared by: — s %. Robert J.M.Nieminen,P.E. .,Z,t`o`�"="•" �• The facsimile seal appearing was authorized by Robert Florida Registration No.59166,Florida DCA ANE1983 Nieminen,P.E.on 10/09/2017:This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. Trinity lERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Trinityl ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E. are, in any way, the Designer.of Record for any project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained specifically for that purpose. QNTRINITYIERD ROOFING SYSTEMS EVALUATION: 1. SCOPE: Product Category: Roofing Sub-Category: Asphalt Shingles Compliance Statement: Owens Corning Asphalt Roof Shingles,as produced by Owens Corning, have demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code and Florida Building Code, Residential Volume through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations/Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1507.2.5,R905.2.4 Physical Properties ASTM D3462 2010 1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D3161 2016 1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D7158 2011 3. REFERENCES: Entity Examination Reference Date UL LLC(CER9626) Physicals&Wind Resistance File R2453,Vol.3 02/15/2007 UL LLC(CER9626) Physicals&Wind Resistance 20120516-112453 05/16/2012 UL LLC(TST9628) Physical Properties 06CA20263 04/18/2006 UL LLC(TST9628) Wind Resistance 11CA34308 02/18/2012 UL LLC(TST9628) Physicals&Wind Resistance 4786093137 02/01/2014 UL LLC(TST9628) Wind Resistance 4786126532 02/10/2014 UL LLC(TST9628) Physical Properties Classification letter 02/13/2014 UL LLC(TST9628) Physical Properties Classification letter 10/02/2015 Miami-Dade(CER1592) FBC HVHZ Compliance Various NOAs Various UL LLC (QUA9625) Quality Control Service Confirmation Exp.05/16/2020 4. PRODUCT DESCRIPTION: 4.1 Asphalt Shingles: 4.1.1 Classic and Supreme®are fiberglass reinforced,3-tab asphalt roof shingles. 4.1.2 Berkshire'are fiberglass reinforced,4-tab asphalt roof shingles. 4.1.3 Devonshire''are fiberglass reinforced,5-tab asphalt roof shingles. 4.1.4 Duration, TruDefinition® Duration, Duration' Premium Cool, TruDefinition® Duration' Designer Color Collection, TruDefinition®Oakridge®, Oakridge' and WeatherGuard' HP are fiberglass reinforced, laminated asphalt roof shingles. 4.2 Hip&Ridge Shingles: 4.2.1 Berkshire® Hip & Ridge Shingles, High Ridge, WeatherGuard® HP Hip & Ridge Shingles, ProEdge Hip & Ridge Shingles and Dura Ridge'" Hip&Ridge Shingles are fiberglass reinforced,hip and ridge asphalt roof shingles. 4.3 Accessory Starter Strips: 4.3.1 Starter Strip Shingle,Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. 5.3 Fire Classification is not part of this Evaluation Report;refer to current Approved Roofing Materials Directory for fire ratings of this product. Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8 Certificate of Authorization#9503 6'"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-1113 Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017 Page 2 of 8 UT__R1NrrYjERD 5.4 Wind Classification: 5.4.1 All Owens Corning asphalt shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161,Class F and/or ASTM D7158,Class H, indicating the shingles are acceptable for use in all wind zones up to Vasd = 150 mph (V,,it = 194 mph). Refer to Section 6 for installation requirements to meet this wind rating. 5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the shingles are acceptable for use in all wind zones up to Vasd=150 mph (Veit=194 mph). Refer to Section 6 for installation requirements to meet this wind rating. 5.4.3 Classification by ASTM D7158 applies to exposure category B or C, as defined in FBC 1609.4.3, and a mean roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions outside these limitations. Contact the shingle manufacturer for data specific to each shingle. 5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations. 5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C.Rule 61G20-3. 6. INSTALLATION: 6.1 Underlayment: 6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product Approval,or be Locally Approved per Rule 61G20-3, per FBC 1507.2.3,1507.2.4 or R905.2.3. 6.2 Asphalt Shingles: 6.2.1 Installation of asphalt shingles shall comply with the Owens Corning current published instructions, using minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following exceptions: ➢ Berkshire shingles require minimum five(5)nails per shingle. ➢ WeatherGuardo HP shingles require minimum six(6)nails per shingle. ➢ Devonshire TM shingles require minimum six(6)nails per shingle. ➢ Starter Strip Shingle and Starter Strip Plus require minimum five(5)nails per strip. Refer to Owens Corning published information on wind resistance and installation limitations. 6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC 1507.2.6 or R905.2.5. Staples are not permitted. 6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are required. See figures below for details. 6.2.5 Minimum Nailing—Starter Strip Shingle and Starter Strip Plus: Feltunderlayment Deck Felt underlayment Deck SeH$dhered WeatherLockS Self-adhered undedayment WeatherLoclta underlayment Drip edge Drip Drip edge i Is located Nails located Y-3'from eave 2=3"from eave Install Fust Self-sealing adhesive ung long ere Starter Strip positioned along gave vvitlr 6Install�Rmeved rststarteStripplus positioned along ave shingle with 6"removed \ , Starter Strip flus overhangs eaves and rakes 1/41-3/4" Starter Strip shingle overhangs eaves and rakes/i'--'/." � Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8 Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113 Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017 Page 3 of 8 TRINITY I ERD 6.2.6 Minimum Nailing—Classic®&Supreme: Normal Mansard or Area para Normal Mansard or Area pin Wind Areas. High Wind dasvanes y Wind Areas High Wind desyanes y Area par vientos normates Areas Wentos faertes Ana para.vientos normeles Areas viontos fu�rtes t't, TAI tt,t" rt. Z. i6 �Z' t' '� y [AI tit?', a• 2•- BI �• t' S Exposure li 9117 Exposure Exposie7on Exposiaidn 6.2.7 Minimum Nailing—Berkshire®: Sealant strip, Sealant strip to fha de seRaaloc 18 tha de selladar 01 0 Yf ' 917 } ,8 w 8 W 1• 1"J r r 1 ♦.. Standard Fastening Pattern 6-Nail Fastening Pattern SAlat t strip - 6lira de sdkJar- aE--►ate—�a :a�—i a�— )a gyp 9 Yf 9.W 811T t" t• . 2 Asphalt roolingYatrt%tit Com ala de feels da asta80. Mansard or Steep Slope Fastening Pattern Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8 Certificate of Authorization#9503 6'EDITION(2017)FBC NON-HVH7 EVALUATION FL10674-R13 Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017 Page 4 of 8 TRINITY I ERD 6.2.8 Minimum Nailing—Devonshire'r": 7" 8" on vpn 7n O • g Nal7aw+ ails •••-•_• r r a r 56/8'exposure Sealant location "" Exposidbn de 5 6/8 put Ubicadbn del sellador • Ten V Spots of Asphah Roof Cement Standard 6-Nail Fastening Pattern Mansard or Steep Slope Fastening Pattern 6.2.9 Minimum Nailing — Duration®, TruDefinition® Duration, Duration® Premium Cool & TruDefinition® Duration®Designer Color Collection: 4-Nail Fastening,Pattern 6-Nail Fastening Pattern LSUMM10ftstonlivalwilmsm 9u nttanatdate"area Mme Nan.Typical �9.Typical 12^'I] 1' e tni a se F] F� G-1W a srs^ F]' Standard Fastening Pattern 6-Nail Fastening Pattern Fastening for Slopes Greater Than 21:12 SuMUM fa.bniap u.•wWth N.u.TYWc+i 1" 12^ I 12^ e-in^s-sie^ Pour 1^spat mwvpha t paaeng C.meW Mansard or Steep Slope Fastening Pattern Exterior Research and Design,LLC. Evaluation Report 037940.02.12-118 Certificate ofAuthori2ation#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113 Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017 Page 5 of 8 l-RINITY I ERD 6.2.1 Minimum Nailing—TruDefinition®Oakridge®,Oakridge®: 4,Nail,Paltern 6-Nall Pattern Esquema con 4 clavos. Esguema con 6 clavos p p ft= .12- -Nails 6518"Exposure5618"Exposure Naffs Ficposkidn.de55/8putg clavas p ade55/8pulg. 56/81,Exp.os Clavas 6,6/8"Exposu�e Ezposluon de 6618 ping Expcsicion de 56/8 ping. Standard Fastening Pattern 6-Nail Fastening Pattern Fastening for Slopes Greater Than 21:12 5—HaDW-t-1.9-t-1.9 ores width .�,+YPCm +^ +r +r +^ 6+18^ Fotu+^$"ofAaPMa Ro ftng Cement Mansard or Steep Slope Fastening Pattern 6.2.1 Minimum Nailing—WeatherGuard°HP: 1' 1 1n04.sidr Vlow :s:•; :::1• famunwThgiNilLine �i�w IrYnw i t�die Exterior Research and Design,LLC. Evaluation Report 037940.02.12-118 Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113 Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017 Page 6 of 8 VTRINITYJERD 6.3 Hip&Ridge Shingles: 6.3.1 Installation of Berkshire Hip and Ridge Shingles, High Ridge, WeatherGuard® HP Hip and Ridge Shingles and ProEdge Hip,& Ridge Shingles shall comply with the Owens Corning current published instructions, using four (4) nails per shingle. Installation of DuraRidge"m Hip & Ridge Shingles shall comply with the Owens Corning current published instructions, using two (2) nails per shingle. Refer to Owens Corning published information on wind resistance and installation limitations, including the use of hand-sealing for wind warranties. 6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC 1507.2.6 or R905.2.5. Staples are not permitted. 6.3.3 Minimum Nailing—Berkshire®Hip&Ridge and High Ridge: Flg.1 4, Fig.2 E= Direction A.. top Vim SldeYiew Nails ---� � A Nal. .Nails Top Lamtrlafetl' ,.a I I 6'. Pi- • zNAI I I I I i I 12" 6.3.4 Minimum Nailing—WeatherGuard®HP Hip and Ridge: Fig.'d• q 4 Fig.C Hip'4(R dge'Shingle Fastening TopVlaw PrevallNg Y71ntl �—Dlroetlin' A F Walls~y44 A I I Nal@ Nails I I 7 2 A\ I I I I • EIpoSare W Erposule 17' Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8 Certificate of Authorization 119503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-R13 Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017 Page 7 of 8 TRINITY I ER® 6.3.5 Minimum Nailing-ProEdge Hip&Ridge Shingles: Prevailing Standard t11■_� Wind Direction SealaMStrip Patternng 6'Exposure 12' 1 Sealant Fasten 71h' 7�I=� 6"Exposure Cover Exposed 1 1 Fasteners with _I Roof Cement 6.3.6 Minimum Nailing—DuraRidge'"Hip&Ridge Shingles: Note:The drawings below pertain to minimum,as-tested attachment requirements. Refer to Owens Corning published installation instructions for their minimum requirements. Prarairng Wind Direction Top View �—Diroctiondarnimntadavent r vtue oe p r I' Dim c=do[viaito prodwnironte CNA NCy6�� p I, OvrensComfng SumNeir Cd01O CIm°o I p A i i 16 J k i v ele� fe-t'r;o U I ■fib°,� I�� LIS I F la 12 7. LABELING: 7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. 7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC Table 1507.2.7.1/R905.2.6.1. 8. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 9. MANUFACTURING PLANTS: Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA requirements. 10. QUALITY ASSURANCE ENTITY: UL LLC—QUA9625; (631)546-2458; Kanchi.Agrawala-Dokania@ul.com - END OF EVALUATION REPORT- Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8 Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-1113 Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017 Page 8 of 8 FILE COPY CREEK OWENS CORNING ROOFING AND ASPHALT LLC WeatherLock®Self-Sealing Ice&Water Barriers TECHNICAL SERVICES, LLC GENERAL LIMITATIONS 1) This evaluation report is not use in the HVHZ. 2) Fire Classification is not within the scope of this evaluation. 3) Installation of the evaluated product shall comply with this report,the FBC,and the manufacturer's published application instructions. Where discrepancies exist between these sources, the more restrictive and FBC compliant installation detail shall prevail. 4) The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. 5) The space under the deck area shall be property ventilated in accordance with the FBC requirements. 6) All side lap seams shall be installed to shed water from the deck. 7) The underlayment may be used as described in other current FBC product approval documents. 8) Design wind load pressures shall be determined for components and cladding in accordance with FBC 1609. 9) The roof deck shall be designed by others in accordance with FBC requirements to resist the design wind load pressures for components and cladding. 10) Maximum Design Pressures for a given underlayment shallmeet or exceed the design wind loads determined for the roof assembly. 11 All products listed in this report shall be manufactured under a quality assurance program in complianceliance with Rule 61 G20-3. COMPLIANCE STATEMENT The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building Code 6th Edition (2017)as evidenced in the referenced documents submitted by the named manufacturer. `ttttutlrrrr % %�,,tP'RY %% E��••cN,s"- Fs' 2017.10.11 No 74021 09:06:29 -04'00' STATE OF :14/- ��,�•. ,� Q :��� Zachary R. Priest, P.E. '�,��`• 40 R 10.•'����` Florida Registration No.74021 /ON A1-���`�� Organization No.ANE9641 �rrrr fill itt CERTIFICATION OF INDEPENDENCE CREEK Technical Services, LLC does not have,nor will it acquire,a financial interest in any company manufacturing or distributing products under this evaluation. CREEK Technical Services,LLC is not owned,operated,or controlled by any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products under this evaluation. Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the product. END OF REPORT OCR14002.8a FL9777-R11 Page 4 of 4 This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. OWENS CORNING ROOFING AND ASPHALT LLC' CREEK WeatherLock®Self-Sealing Ice&Water Barriers TECHNICAL SERVICES, LLC PRODUCT APPLICATION Min. Roof Slope: 2:12 in accordance with the FBC Application: All underlayments shall be installed in accordance with the FBC. Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck shall be checked for protrusion and corrected prior to underlayment application. Prior to beginning installation, the underlayment shall be unrolled and allowed to relax for a minimum of 3-5 minutes. The underlayment shall be installed with the release backer removed and pressed firmly into place to ensure complete contact with the deck. The underlayment shall be installed with the roll length parallel to the eave, starting at the eave, and with minimum 3" side laps and minimum 6"end laps staggered min.6-ft.from preceding course. Additionally, if applying WeatherLock® Specialty Tile & Metal, end laps shall be primed with ASTM D 41 primer or sealed with asphalt roof cement a minimum of 3-4 inches across the width of the lap. It is permissible to back nail the underlayment 12-inches on-center as needed(nails shall be installed perpendicular to deck with the nail heads flush to the top surface of the underlayment). Additionally, WeatherLock®Specialty Tile & Metal shall be back nailed when installed on roof slopes greater than 3:12. Min.Application 40°F; Contact the manufacturer when installing at temperatures below the minimum Temperature: application temperature. WIND RESISTANCE The Maximum Design Pressures shown below were calculated using a 2:1 margin of safety per FBC Section 1504.9. Underlayment System No.1 —WeatherLock Specialty Tile&Metal Only Roof Deck: Min. 15/32-inch CDX plywood attached to wood supports spaced a maximum 24"o.c. Underlayment: WeatherLock® Specialty Tile & Metal shall be applied in accordance with manufacturer's installation instructions to the fastened deck and backnailed along the selvage with minimum 12ga., 1-1/4-inch galvanized ring shank roofing nails through optionally primed, 32ga. x 1-5/8-inch 0 tin caps spaced 12" o.c. The applied underlayment shall be rolled with a minimum 751b steel roller immediately following application. Maximum Design -142.5 psf Pressure: OCR14002.8a FL9777-Rl l Page 3 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. I CDEEK OWENS CORNING ROOFING AND ASPHALT LLC j� WeatherLock®Self-Sealing Ice&Water Barriers TECHNICAL SERVICES, LLC PRODUCT DESCRIPTION AND LIMITS OF USE WeatherLock®G WeatherLock®G is an ASTM D 1970 self-adhesive underlayment constructed from SBS (Brentwood, NH) modified asphalt, a fiberglass mat reinforcement and surfaced with granules. The product is supplied in 2-sq.rolls with nominal dimensions of 3-ft x 66.7-ft. WeatherLock® G is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roofing coverings. Exposure on the roof deck shall be limited to a maximum 30 days. WeatherLock®Mat WeatherLock® Mat is an ASTM D 1970 self-adhesive underlayment constructed from (Brentwood, NH or SBS modified asphalt with a fiberglass mat reinforcement. The product is supplied in 1- Houston, TX) sq. rolls with nominal dimensions of 3-ft x 33.3-ft and 2 sq. rolls with nominal dimensions of 3-ft x 66.7-ft. WeatherLock® Mat is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roof coverings. Exposure on the roof deck shall be limited to a maximum 30 days. WeatherLock®Metal WeatherLock® Metal is an ASTM D 1970 self-adhesive underlayment constructed from (Brentwood, NH) SBS modified asphalt with a fiberglass mat reinforcement and plastic film surface. The product is supplied in 2.0 sq.rolls with nominal dimensions of 3-ft x 66.7-ft. WeatherLock® Metal is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roof coverings. Exposure on the roof deck shall be limited to a maximum 90 days. WeatherLock® WeatherLock® Specialty Tile &Metal is an ASTM D 1970 self-adhesive underlayment Specialty Tile&Metal constructed from SBS modified asphalt and surfaced with a non-woven polyester fabric. (Brentwood, NH or The product is supplied in 2.14 sq.rolls with nominal dimensions of 3-ft x 71.3-ft. Houston, TX) WeatherLock® Specialty Tile & Metal is permitted to be used as prescribed in FBC Section 1507.1.1. WeatherLock® Specialty Tile & Metal is permitted to be used with adhered clay or concrete tile roofing using either ICP Adhesives Polyset AH-160 (ICP Adhesives and Sealants, Inc.)or TILE BONDTM Roof Tile Adhesive (The Dow Chemical Company). Exposure on the roof deck shall be limited to a maximum 90 days. The maximum roof slope shall be 6:12 when used with clay or concrete tile installations without battens. Tile shall be stored on battens for roof slopes greater than 6:12. Tiles shall not be stacked greater 10 tiles per stack. WeatherLock®G(High WeatherLock®G(High Tear)is a self-adhered, underlayment used as an alternative to Tear) ASTM D 226,Type I or Type II roofing felt and ASTM D 1970 self-adhering polymer (Houston, TX) modified bitumen underlayment. The underlayment is composed of SBS modified asphalt with a fiberglass mat internal reinforcement and is surfaced with granules. The product is supplied with a nominal thickness of 50 mils in 1.95-sq rolls with nominal dimensions of 3-ft x 65-ft. WeatherLock® G (High Tear) is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roof coverings. Exposure on the roof deck shall be limited to a maximum 30 days. OCR14002.8a FL9777-R11 Page 2 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. ( t Certificate of Authorization bur 29824 CREEK17520 Edinburgh Drive Tampa, FL 33647 TECHNICAL SERVICES, LLC (813)480-3421 EVALUATION REPORT FLORIDA BUILDING CODE,61"EDITION(2017) Manufacturer: OWENS CORNING ROOFING AND ASPHALT LLC Issued October 11, 2017 1 Owens Corning Parkway Toledo, OH 43657 (800)438-7465 www.owenscorning.com Manufacturing Location: Brentwood, NH Houston,TX Quality Assurance: UL LLC(QUA9625) SCOPE Category: Roofing Subcategory: Underlayments Code Sections: 1504.3.1, 1507.1.1 Properties: Physical properties REFERENCES Entity Report No. Standard Year PRI Construction Materials Technologies(TST5878) NEI-039-02-01 ASTM D 1970 2015 PRI Construction Materials Technologies(TST5878) NEI-042-02-01 REV2 ASTM D 1970 2015 PRI Construction Materials Technologies(TST5878) NEI-045-02-01 TAS 103 1995 PRI Construction Materials Technologies(TST5878) NEI-045-02-01 ASTM G 155 2005a PRI Construction Materials Technologies(TST5878) NEI-053-02-01 TAS 103 1995 PRI Construction Materials Technologies(TST5878) NEI-053-02-01 ASTM G 155 2005a PRI Construction Materials Technologies(TST5878) NEI-093-02-02 ASTM D 1970 2015 PRI Construction Materials Technologies(TST5878) OCF-213-02-01 ASTM D 1623 2009 PRI Construction Materials Technologies(TST5878) OCF-237-02-01 UL 1897 2012 PRI Construction Materials Technologies(TST5878) OCF-252-02-01 ASTM D 4798 2001 PRI Construction Materials Technologies(TST5878) OCF-252-02-01 ASTM D 1970 2015 PRI Construction Materials Technologies(TST5878) OCF-253-02-02 ASTM D 1970 2015 PRI Construction Materials Technologies(TST5878) OCF-272-02-01 TAS 103 1995 PRI Construction Materials Technologies(TST5878) OCF-296-02-02 ICC-ES AC 188' 2012 ICC-ES AC 48 2012 PRI Construction Materials Technologies(TST5878) OCF-297-02-01.1 ASTM D 1970 2015 PRI Construction Materials Technologies(TST5878) OCF-318-02-01 ASTM D 1970 2015 PRI Construction Materials Technologies(TST5878) OCF-320-02-01 TAS 103 1995 PRI Construction Materials Technologies(TST5878) OCF-320-02-01 ASTM G 155 2005a PRI Construction Materials Technologies(TST5878) OCF-321-02-01 ASTM D 1623 2009 PRI Construction Materials Technologies(TST5878) OCF-322-02-01 UL 1897 2012 PRI Construction Materials Technologies(TST5878) OCF-355-02-01 UL 1897 2012 'Determined to be equivalent to ASTM D 226-09,Type I and II OCR14002.8a FL9777-R11 Page 1 of 4 This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein.