BASE SHEET ATTACHMENT CALCULATIONS
Project Name St. Lucie County Courthouse Building Report No.: CIS-BS-18.001
Project Address 218 South 2nd Street
Ft. Pierce, FL -34950
Deck Substrate Lightweight Concrete Mean Roof Height 45.0 Feet
Configuration Low Slope Roof Area (Approx.) 22419 Sq.Ft.
Category IV Max. Roof Width 130.0 Feet
Exposure Condition C Perimeter Width 13.0 Feet
Building Type Enclosed Parapet Height 4.0 Feet
Base Wind Speed 180 mph
Slope V 0.0 Slope H 12.0 Slope Angle° 0.00
Uplift Pressures qZ = 0.00256 KZ Kit Kd V2 P = qZ (GCP-GCP;)
qZ KZ KZt Kd V GCP GCP;
75.799 1.070 1.005 0.85 180 -1.00 0.18 Field
-1.80 0.18 Perimeter
-1.80 0.18 Corner
Field P1 ult. -89.44 psf P1 asd -53.67 psf
Perimeter P2 un -150.08 psf P2 asd -90.05 psf
Corner P3 un. -150.08 psf P3 asd -90.05 psf
Proposed System Johns Manville SBS Modified Bitumen Roof System
Product Approval No. FL 2948-R12 (Page 36 of 50) System No.: LWC-55
System Design Pressure -60 psf
Fasteners 1.7" JM LWC CR Base Sheet Fasteners
Base Sheet Width 39 inches Side Lap 4 inches Net Width 35 inches
Fastener Spacing in Lap of Base Sheet 7 inches #Rows 1
Fastener Spacing in Field of Base Sheet 7 inches # Rows 3
Min. Characteristic Resistance Force -25.52 Ibf -42.56 Ibf(MCRF from TAS-105 Tests)
Fastener Spacing {(MCRF/P;) x 1441/Row Spacing
No. of Rows of Fasteners 4 5 6 7
Field Fastener Spacing 7.83 9.78 11.74 13.70
Perimeter Fastener Spacing 4.66 5.83 7.00 8.16
Corner Fastener Spacing 4.66 5.83 7.00 8.16
RECOMMENDED BASE SHEET ATTACHMENT PATTERN
Field 1 row in the laps at 7 inches o.c. 3 rows in the center of the sheet at 7" o.c.
Perimeter 1 row in the laps at 5 inches o.c. 4 rows in the center of the sheet at 5" o.c.
Corner 1 row in the laps at 5 inches o.c. 4 rows in the center of the sheet at 5" o.c.
These calculations have been done in accordance with ASCE 7-10, based on the information provided by the
contractor. The roof system must be installed in accordance with the FBC & manufacturer's recommendations.
Sincerely RECEIVED
FoV Engin Bring Consultants. InLE CO P)
rf
� FEB 2 6 2018
R. N. Sailappan, P.E. ZIs ST. Lucre County, PQrmitting
Principal Engineer
Florida Registration No. 46696
Forensic Engineering Consultants, Inc. (CA#8265), P.O.Box 970034, Boca Raton, FL-33497 Ph(561)901 8490 Fax(561)218 3830
TESTING APPLICATION STANDARD (TAS)No. 105-11
APPENDIX TAS 105-A
FIELD WITHDRAWAL RESISTANCE TEST RESULTS
GENERAL INFORMATION:
Job Name: St. Lucie Coppty Courthouseild
Job Address: 218 South 2nd Street
Ft. Pierce, FL 34950
Job Site Contact: Therms Seal Roof Systems,LLC (561)223-2096
TESTING AGENCY/EQUIPMENT INFORMATION:
Note: The undersigned acknowledges that all testing has been conducted and
results have been reported in compliance with TAS 105 Appendix T105-A
Testing Agency: Cleary Inspection Services, Inc. RECEIVED
Address: 1017 North"H" Street
Lake Worth, FL 33460 FEB 66 2018
Telephone: (561) 722 - 9881 ST. i_ucie County, Permitting
Fax: (561) 582 - 8039
Email: clearyinspections@kcwand.com
Representative Name: Katherine I. Cleary
Title: Inspector
Test Apparatus: COMTEN MODEL#DFG2W2000, SERIAL#20606019
BUILDING/ROOF SYSTEM INFORMATION: Approx.
Roof Area Height: Height: = 45 ft.
Roof Area Dimensions: Length: = 222 ft.
Second largest dim.: = 130 ft.
Total roof area: = 22419 ft.2
Perimeter width: = 13 ft.
Perimeter area: = 8827 ft.2
Corner area: = N/A ft.2
Parapet Height: = 4 ft.
FASTENER INSTALLATION INFORMATION:
Is the fastener a self driller? No
Tool: Pogo-Stick
Fastener type: 1.7
Fastener Manufacturer: OMG
TEST INFORMATION: MAIN ROOF
Test Date: 2/17/2018
Number of Test Conducted 24
*Note the Location of all tests on'Building Information',attached.
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:* See TAS 105-11 to determine number of tests Lightweight
St. Lucie County Courthouse Building Cleary Inspection Service,Inc.
218 South 2nd Street Tel.(561)722-9881,Fax(561)582-8039
Ft. Pierce,FL 34950 Email: clearyinspections@kcwand.com
INITIAL FAILURE
SAMPLE NO. PLAN IDENTIFIER LOAD FIELD PERIMETER CORNER
1 T1 45 X
2 T2 35 X
3 T3 40 X
4 T4 40 X
5 T5 40 X
6 T6 85 X
7 T7 60 X
8 T8 30 X
9 T9 80 X
10 T10 75 X
11 T11 40 X
12 T12 50 X
13 T13 80 X
14 T14 50 X
15 T15 60 X
16 T16 30 X
17 T17 35 X
18 T18 45 X
19 T19 55 X
20 T20 65 X
21 T21 45 X
22 T22 40 X
23 T23 30 X
24 T24 35 X
STATISTICAL ANALYSIS:
No. of Tests n= 24
't'Estimator t'= 2.08
Mean Failure Load: F= 49.58 lbf
Sample Standard Deviation: SF= 16.52 lbf
Minimum-Characteristic Resistance Force: F'= 42.56 lbf
Sincerely,
Cleary Inspections Service,Inc.
e4��j
atherine I. eary R.N. Sailappan,P.E.
Miami-Dade ab Certification No. 16.0211.02 Florida Registration No. 46696
2
Cleary Inspection Service, Inc.
Telephone (561) 722-9881
Fax (561) 582-8039
Email: kc@kcwand.com
Notes:
1. Use of the results herein to determine the required number of
fasteners for insulation attachment or an acceptable anchor or base
sheet fastener spacing, as outlined in TAS 117, shall utilize the
minimum characteristic resistance for(F') determined in compliance
with Section 9 of TAS 105. No margin of safety shall be applied to
field withdrawal resistance test results determined in compliance with
TAS 105.
2. A safety factor of 2 to 1 shall be applied to all results of laboratory
testing.
3. The following pages shall be completed for each roof area and
included with all Field Withdrawal Resistance Test Recording Sheets.
St. Lucie County Courthouse
218 South 2nd Street
Fort Pierce, FL 34950
Test Date: 2/17/2018
Roof Area Buildinq and Parapet Heights.
(If no parapet exists, "N/A")
4'
45'
Ground
Level
Page 3
Cleary Inspection Service, Inc.
Tel. (561) 722-988, Fax(561) 582-8039
Email: clearyinspections@kcwand.com
'Building Information Sheet'
St. Lucie County Courthouse Building
218 South 2nd Street
Fort Pierce, FL 34950
Test Dates: 2/17/2018
N 40'
T1
37' T2 37' 17'
T3 11' 13'
83' 41' 24 T8 17'
T4 T7
T5 T6 T9
T10
T11
T12 T14
93' T13
93'
T15 T16 T20
T19
T17 T18
T21 T22 T23 T24
222'
NOT DRAWN TO SCALE
Drawings & measurements are approximate representation of field layout
Page 4
CERTIFICATE OF CALIBRATION
TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AND PERFORMED IN ACCORDANCE WITH IS010012-2003
THIS DEVICE IS CERTIFIED TO BE WITHIN +/-0.5% OF FULL SCALE READING AT EACH TEST POINT AT
THE TIME OF SHIPMENT
CERTIFICATE NUMBER: 24859 CALIBRATION DATE: 1/23/2018
PART AND CUSTOMER INFORMATION
MODEL#: DFG2W2000 SERIAL#: 20606019
CUSTOMER: CLEARY INSPECTION SERVICE INC. CUSTOMER#: CLE33460
I
CALIBRATION DATA
APPLIED EXPECTED FULL
VALUE VALUE RUN1 AVERAGE SCALE I
i
(LB) (LB) (LB) (LB) ERROR
0.00 0.00 0.000 0.000 0.000%
100.00
400.00 400.00 402.000 402.000 0.100%
600.00
800.00 800.00 804.000 804.000 0.200%
I
1000.00
1200.00 1200.00 1197.000 1197.000 -0.150%
1400.00
1600.00 1600.00 1599.000 1599.000 -0.050% i
1800.00
2000.00 2000.00 2004.000 2004.000 0.200%
CALIBRATION EQUIPMENT USED
SERIAL#1: 11706016 SERIAL#2:
CAL EQUIP: COMTEN INDUSTRIES load cell CNR EA,S/N
I
CNR EA 11706016 was calibrated at ComTen Industries
fj i following to ASTM E-74.The uncertainty is 2
CAL DATE: Lbf.Report No:20300
I 6/12/2017
' i
r THIS EQUIPMENT IS CERTIFIED TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY.
r
j CONDITIONS VALIDATION
TEMPERATURE 70°F
RELATIVE HUMIDITY: 31% CALIBRATION F f.; j
PERFORMED .k s�' �;
v...�:R"�'
AS FOUND NOTES:(`Indicates that the part was out of tolerance) BY: CC ? /
�s �
Calibration not valid without CERTIFIED stamp and initials
6405-49th Street North, Pinellas Park, FL 33781-5724 " 727-520-1200 . FAX 727-520-0299
E-Mail: sales@com-ten.com * Web: www.com-ten.com