HomeMy WebLinkAboutProduct Approval - skylight PTLD COPY
N T
QQ C C
W N a O
MIAMI-D�ADE eo o"�, MIAMI-DADS COUNTY
i ''" c 3 PRODUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES(RER)� X
BOARD AND CODE ADMINISTRATION DMSION v� 11805 SW 26 Street,Room 208
Miami,Florida 33175-2474
NOTICE OF ACCEPTANCE (NOA) T(786)315-2590 F(786)315-2599
Sun-Tek Manufacturing,Inc.
10303 General Drive.
Orlando,FL 32824
i
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. j
The documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control
Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction
(AHJ)•
i
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control
Section(In Miami Dade County)and/or the AHJ(in areas other than Miami Dade County)reserve the right to have i
this product or material tested for quality assurance purposes. If this product or material fails to perform in the
accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke,
modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke
this acceptance, if it is determined by Miami-Dade County Product Control Section that this product or material !
fails to meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the High Velocity Hurricane
Zone of the Florida Building Code.
DESCRIPTION: ICMG Skylight System
APPROVAL DOCUMENT: Drawing No. STI-00000290,titled"ICMG", sheet 1 &2 of 2,prepared by Sun-Tek
Manufacturing, Inc., dated August 07,2007,with last revision"A",signed and sealed by James D. Wells, Jr.,P.E.,
on October 06, 2017, bearing the Miami-Dade County Product Control Revision stamp with the Notice of
Acceptance number and the expiration date by the Miami-Dade County Product Control Section.
MISSILE IMPACT RATING: Large and Small Missile Impact Resistant
LABELING:Each unit shall bear a permanent label with the manufacturer's name or logo,city,state,model/series
and the following statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no
change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use,and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any
section of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by
the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall
be done in its entirety.
INSPECTION:A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA#15-0513.09 and consists of this page 1,evidence submitted pages E-1,E-2,E-3 &E-4 as
well as approval document mentioned above.
The submitted documentation was reviewed by H Imy A.Makar,P.E.,M.S.
MIAMWADE COUNTY NOA No. 17-1023.21
E� f c �•
Expiration Date: 10/10/2018
rovv//ZI22 l Z Approval Date: 02/22/2018
0
8 Page 1
Sun-Tek Manufacturing,Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
1. EVIDENCE SUBMITTED UNDER PREVIOUS APPROVAL# 07-0425.05
A. DRAWINGS
1. Drawing No. STT 00000290-SHTIISHT2, titled "ICMG", sheet I & 2 of 2, prepared by Sun-
Tek Manufacturing, Inc, dated 06104107, with last revision dated 08107107, signed and sealed
by James D. Wells,Jr., P.E.
B. TESTS (submitted under NOA#02-0729.07)
1. Test Report on Large Missile Impact Test per PA 201, Cyclic Wind Pressure Test per
PA 203 and Uniform Static Air Pressure Test per PA 202 of "Model ICMG 4949
Insulated Glass Skylight with Polycarbonate Inner Liner" prepared by National
Certified Testing Laboratories, Report No. 210-2789-1, 2 & 3, dated 03/18/02, signed
and sealed by B. Portnoy, PE.
C. CALCULATIONS
1. Anchor Calculations for attachment of skylight to cubing and curbing to decking, dated
08113107, signed and sealed by James D. Wells, Jr., P.E.
D. MATERIAL CERTIFICATIONS (submitted under NOA # 02-0729.07)
1. Die drawings No. STI-214 of Deco Ring, prepared by Sun-Tek Manufacturing, Inc. on
6119195.
2. Die drawing No. STI-205 of Curb Frame prepared by Sun-Tek Manufacturing, Inc. on
12126196.
E. STATEMENTS (submitted under NOA#02-0729.07)
1. Code compliance and No-Interest letter issued by Product Technology Corporation on
08/27102, signed and sealed by R. J. Quiroga PE
F. OTHER
1. NOA renewal request letter issued by Sun-Tek Manufacturing, Inc., dated 08/16/07,
signed by James Feudner.
2. EVIDENCE SUBMITTED UNDER PREVIOUS APPROVAL # 11-0601.03
A. DRAWINGS
1. Drawing No. STI-00000290-SH7-I/SHT2, titled "ICMG", sheet 1 & 2 of 2, prepared by
Sun-Tek Manufacturing, Inc., dated August 07, 2007, with last revision "A" dated
October 14, 2011, signed and sealed by James D. Wells, Jr., P.E.
elmy A.Makar,P.E.,M.S.
Product Control Section Supervisor
NOA No. 17-1023.21
Expiration Date: 10/10/2018
Approval Date: 02/22/2018
E- 1
Sun-Tek Manufacturing,Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
B. TESTS
1. Test Addendum for Test Report NCTL 210-2760-1, prepared by national Certified
Testing Laboratories, dated October 17, 2011, certifying the interlayer thickness,
signed by Mark Bennett, Manager of Testing Services (see NOA#11-0601.02).
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. By Miami-Dade County Department of Permitting, Environment, and Regulatory
Affairs (PERA).
E. MATERIAL CERTIFICATIONS
1. None.
3. EVIDENCE SUBMITTED UNDER PREVIOUS APPROVAL# 12-1011.16
A. DRAWINGS
1. Drawing No. STI-00000290, titled "ICMG", sheet 1 & 2 of 2, prepared by Sun-Tek
Manufacturing, Inc., dated August 07, 2007, with last revision "A" dated May 03,
2012, signed and sealed by James D. Wells, Jr., P.E.
B. TESTS
1. None.
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. By Miami-Dade County Department of Regulatory and Economic Resources.
E. MATERIAL CERTIFICATIONS
1. None.
F. OTHERS
1. A compliance letter, prepared by J & L Wells Consulting LLC, dated April 25, 2012,
certifying compliance with FBC 2010 edition, sign and sealed by James D. Wells, Jr.,
P.E.
2. Verification testing to be performed per letter from National Certified Testing
Laboratories, dated September 18, 2012, signed by Christopher Bennett.
I
elmy A.Makar,P.E.,M.S.
Product Control Section Supervisor
NOA No. 17-1023.21
Expiration Date: 10/10/2018
Approval Date: 02/22/2018
E-2
t
r
I
Sun-Tek Manufacturing,Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
4. EVIDENCE SUBMITTED UNDER PREVIOUS APPROVAL # 13-1010.09
A. DRAWINGS
1. Drawing No. STI-00000290, titled "ICMG", sheet I & 2 of 2, prepared by Sun-Tek
Manufacturing, Inc., dated August 07, 2007, with last revision "A" dated May 03,
2012, signed and sealed by James D. Wells, Jr., P.E.
B. TESTS
1. Test Report on Large Missile Impact Test per PA 201, Cyclic Wind Pressure Test per
PA 203 and Uniform Static Air Pressure Test per PA 202 of "Model 1CMG 4949
Insulated Glass Skylight with Polycarbonate Inner Liner" prepared by National
Certified Testing Laboratories, Report No. 210-3915-02, dated 09113113, signed and
sealed by Gerard J. Ferrara, P.E., on 09124113.
2. Revised Test Report on Large Missile Impact Test per PA 201, Cyclic Wind Pressure
Test per PA 203 and Uniform Static Air Pressure Test per PA 202 of "Model ICMG
4949 Insulated Glass Skylight with Polycarbonate Inner Liner"prepared by National
Certified Testing Laboratories, Report No. 210-3915-02, dated 09113113, revised on
02126114, signed and sealed by Gerard J. Ferrara, P.E., on 02128114.
C. CALCULATIONS
1. Anchor Calculations for attachment of skylight to cubing and curbing to decking, dated
10103113, signed and sealed by James D. Wells, Jr., P.E., on 10103113.
D. QUALITY ASSURANCE
1. By Miami-Dade County Department of Regulatory and Economic Resources.
E. MATERIAL CERTIFICATIONS
1. None.
5. EVIDENCE SUBMITTED UNDER PREVIOUS APPROVAL# 15-0513.09
A. DRAWINGS
1. Drawing No. STI-00000290, titled "ICMG", sheet I & 2 of 2, prepared by Sun-Tek
Manufacturing, Inc., dated August 07, 2007, with last revision "A" dated May 04,
2015, signed and sealed by James D. Wells, Jr., P.E., on May 04, 2015.
B. TESTS
1. None.
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. By Miami-Dade County Department of Regulatory and Economic Resources.
E. MATERIAL CERTIFICATIONS
1. None.
Hehny A.MaKir,P.E.,M.S.
Product Control Section Supervisor
NOA No. 17-1023.21
Expiration Date: 10/10/2018
Approval Date: 02/22/2018
E-3
Sun-Tek Manufacturing,Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
6. NEW EVIDENCE SUBMITTED
A. DRAWINGS
1. Drawing No. STI-00000290, titled "ICMG", sheet 1 & 2 of 2, prepared by Sun-Tek
Manufacturing, Inc., dated August 07, 2007, with last revision "A", signed and sealed
by James D. Wells, Jr., P.E., on October 06, 2017.
B. TESTS
1. None.
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. By Miami-Dade County Department of Regulatory and Economic Resources.
E. MATERIAL CERTIFICATIONS
1. None.
F. OTHERS
1. A compliance letter,prepared by J&L Wells Consulting LLC dated October 06 2017,
3
certifying compliance with FBC 2017 edition, sign and sealed by James D. Wells Jr.,
P.E.
i
i
i
f
I
t
i
R
3
1
i
3
Helmy A.Makar,P.E.,M.S.
Product Control Section Supervisor
NOA No. 17-1023.21
Expiration Date: 10/10/2018
Approval Date: 02/22/2018
E-4
?&C1DUCT ftEVFSE.13
ar camr,13 ing•=ith the.Florida
U,.=.:Idiag Code
Accc Itawre NO f -—le-4-3.Z/
Y',\'a iF 1:JT I�3lC
PART NAME:ICMG SKYLIGHT PLAN VIEW I FILE E: lD G %A D 20 D AVIANGSIDADE COUNTY ICMG STI-00000290-SHT2 SHEET 2 OF 2 DWG.NO.STI-00000290-SHT2
13y_
51.375 r DESIGN PRESSURE RATING±80 PSF. DECO RING 0.050 00M T-SAClRMX1M
Max SILICONE BEDDING MITERED AND WRAPAROUND
LARGE MISSILE IMPACT RESISTANCE DECOCUP0.076
POLYCARBONATE RBONAT OM OUTBOARD GLASS
SILICONE
(CONE TOP AND
BOTTOM DBD TEMPERED(IW)
B')
(CONTINUOS)
10.84375--
4.00— 1084375— 48-32 x i boll»i nut
Engineer of Record o)P.rdd. A;�,Irr• '
1084375—r 10.84375— 4°�4.00 James D.Wells,Jr.,P.E.
.25 X r ALUMMUM FIAT BAR
— — — — Professional Engineer No.53616 BOB7T.03UTT—SOCORNERS INBOARDom
STHIGlA55 TEMPEREO(1r8y
STI-2050.OWtUrTERED
T AND%WLDEDLDRNERS
J&L Wells Consulting LLC HOOD LINER
ICMG 4949 I
723 1453 Arbitus Circle 012 x r PHILLIPS PAN
Oviedo, FI.32765 HEAD SCREW A.rnu L.4ir
Mit X2PHIlLIPSP FO SCREW I :'D'�reLc r+.•`-�n�•
7 z3 (407496-5469
FASTENED SKYLIGHT TO CURB n.lA FLASHING BY OTHER'N lax 1 91 daea Gee PVC
(5)PERSDE I �,f► �AUthorlZatlOn ACCORDANCEIMTHM(CA (adBl.pe
( '��/ 21DX2•NrDECKSCREW
le8-32%314 BOLT WI NUT ATTACHES 7 2 \ `� �'S LIGHT TUNNEL MATERIAL
\ ,`'f.k g ,••✓,p�� 4'..n 181 PER SIDE BY OTHERS(APPROVED
51.375 FRAME TO ALLMBNUM BAR f �' 1�C roof surface 10 hp BY DADE COUNTY)
` ROOFING FELT
(7)PER SIDE � } *i
No. 53616 ! r
7.23: �P' w�y/� SHINGLESO)
_ i Bi.^ 2X CURB HEIGHTTO BE SIFFOENT TO
DAYLIGHT OPENING I ,Of b aFl,Y rW�. BETWEEN ROOF SUUMAINTAIN W RFACE ANCLEAD
45.5"(MAX)X 45 5"(MAX) f = LOWEST LIP OF FRAME CURB
A STATE QF SUPPLIED BY OTTERS(APPROVED BY
3 +•�\ DADE COUNTY)
CURB TO DECK FASTENERS •���.�+'�••, �l ? 1
e1 D X 2 5" ��S/�i6f d(a f^ ID : b��� ROOF DECK SB MLMNXIM SFJ4ANT � 3"m n
} \ protrusion
1 I f7
(23 CHEDULE
,,7F�II X 102X7 PHNAL kl��ER ILLIPSPANGEAD CURB FAST®RODECEDULECURB FASTENER SUB-FRA ETOFRAME
—1! SCREWS N10 X 2-1/7'DECK SCREWS 111832 BOLT w/NUT
TIP TO MODEL PER PER PER PER PER
— TIP LONG SIDE SHORT SIDE LONG SIDE SHORT SIDE LONG SIDE SHORT SIDE
5 93 d 1.375_X5 1375 4949 5 5 8 8 7 7
48--3f5 x 48.375 4645 5 5 8 8 7 7
a.o035 375 z 51375 3349 5 4 6 6 7 5___
NOTE:
q.00.—` 35.375 x 35.375 33 4 6 5
(1)ALL ROOFING DETAILS SHALL COMPLY NTH 32.375 x 48.375 3046 5 4 8 5 7 5
CHAPTER 15 OF THE 2017 FLORIDA BUILDING CODE 32.375 x 32.375 303D 4 4 5 5 5 5
(2)4"MINIMUM DISTANCE FROM ANGLE LIP TO ROOF 27 375 X _ 3 e �—
SURFACE IS FOR SHINGLE OR B.U.R.WITHOUT 27.375 x 35.375 2533 4 3 6 5 5 4
INSULATION.FOR INSULATION AND TILE ROOF ADD 27.375 x 27.375 2525 3 3 5 4 — 4
24.375 x 48 375 2246 5 3 B 3 7 4
TILE HEIGHT AND INSULATION THICKNESS TO 4".
ANCHORS TO BE MADE FROM NON-CORROSIVE MATERIAL 24.375 x 32.375 2230 4 3 5 3 5 4
(3) 24.375 x 24.375 2222 3 3 1 3 3 4 4
COMPATIBLE WITH ALUMINUM. 19 375,51 7 1749 53 B 3 7 3
(4)NO ONE-THIRD INCREASE IN THE DESIGN PRESSURE WAS USED. 19.375 x 35.375 1733 4 3 6 _ 3 5 3
16.375 x 48 375 1446 5 2 8 3 3
16.375 x 32,375. 1430 4_____j 2 tp 3 5 3
REv1sLON, Rl:VlsloN: PRODUCT NAME:
(CMG I SUN-TEK MANUFACTURING, INC.
BY: PANE BY: JDATE DRAWN BY: JWF I DATE: 08/05/20111 DWG W. STI-00000290-SHT2 REV. A 10303 GENERAL DRIVE ORLANDO,FL 32824
I