EVALUATION REPORT
TRI-BUILT Materials Group,LLC Evaluation Report A42960.10.12-R6
PO Box 70 FL16048-R6
Rutherford,NJ 07070 Date of Issuance:10/25/2012
(800)516-1485 Revision 6: 09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: TRI-BUILT Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes;the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity)ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT:The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request,a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
•0 L
1
Robert J.M.Nieminen,P.E. ''•.;sad;,;;,a?;�
�����+ssrs '- The facsimile seal appearing was authorized by Robert Nieminen,
Florida Registration No.59166,Florida DCA ANE1983 P.E.on 09/25/2017.This does not serve as an electronically signed
document
CERTIFICATION OF INDEPENDENCE:
1. Trinity IERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen,P.E.does not have,nor will acquire,a financial'interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E.are,in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
QOTRINITYIERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Underlayment
Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have
demonstrated compliance with the following sections of the 6u'Edition(2017)Florida Building Code through testing
in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations
Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1504.3.1 Wind Resistance FM 4474 2011
1504.3.1 Wind Uplift UL 1897 2012
1504.6 Accelerated Weathering ASTM G155 2005
1507.2.4/1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015
1507.3.3 Physical Properties FRSA/TRI April 2012(04-12) 2012
3. REFERENCES:
Enti Examination Reference Date
ERD(TST6049) Physical Properties 540540.02.13-1 02/19/2013
ERD(TST6049) Physical Properties 540540.11.13 11/19/2013
ERD(TST6049) Physical Properties S40540.03.14 03/26/2014
ERD(TST6049) Physical Properties S44870.04.14-2 04/02/2014
ERD(TST6049) Physical Properties S44870.04.14-3 04/02/2014
ERD(TST6049) Physical Properties 544870.04.14-1 04/10/2014
ERD(TST6049) Physical Properties S44870:04.14-4 04/10/2014
ERD(TST6049) Physical Properties S43530.02.14-1-R1 05/14/2014
ERD(TST6049) Physical Properties 543530.05.14 05/28/2014
ERD(TST6049) Physical Properties 540540.10.14 10/31/2014
ERD(TST6049) Physical Properties SC7645.02.15 02/13/2015
ERD(TST6049) Accelerated Weathering SC8520.04.15 05/27/2015
ERD(TST6049) Wind Resistance SC14045.05.17-R1 06/07/2017
UL,LLC.(QUA9625) Quality Control Multiple-Listing R16814 12/10/2015
UL,LLC.(QUA9625) Quality Control Service Confirmation Exp.07/18/2020
4. PRODUCT DESCRIPTION:
4.1 Tri-Built Sand-R SA Shingle Underlayment is a self-adhering, glass-mat reinforced, sand-surfaced, SBS
modified bitumen roof underlayment,with a 36-inch sheet width;meets ASTM D1970.
4.2 Tri-Built S/A HT TU Underlayment is a self-adhering, non-woven polyester fabric surfaced, SBS modified
bitumen roof underlayment;meets ASTM D1970 and FRSA/TRI April 2012.
4.3 Tri-Built Smooth HT S/A Underlayment is a self-adhering, glass-mat reinforced, film-surfaced, SBS
modified bitumen roof underlayment;meets ASTM D1970.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity I ERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
Exterior Research and Design,I.I.C. Evaluation Report A42960.10.12-116
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6
TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6:09/25/2017
Page 2 of 6
TRINITY I ERD
5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is
specifically referenced within FBC approval documents. If not listed, a request may be made to the
Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the
prepared roof covering.
5.5 Allowable Roof Covers:
og
Underlayment^ Asphalt Nail-On Tile Foam-On Tile Metal Wood Shakes Slate
Shingles &Shingles
Tri-Built Sand-11 SA Shingle Yes No No No Yes Yes
Underlayment
Tri-Built S/A HT TU Yes Yes Yes Yes Yes Yes
Underlayment See 5.5.1
Tri-Built Smooth HT S/A YesNo No Yes Yes Yes
Underlayment
5.5.1 "Foam-On Tile"is limited to use of the following Approved tile adhesives/underlayment combinations.
a � TABLE IA ALLQWABLETILEAQHESIVE UNOERU1yMENT:COMBINATtONS3xa y
Adhesive Florida Product Approval Underlayments
ICP Adhesives Polyset®AH-160 FL6332 Tri-Built S/A HT TU Underlayment
Dow TileBondl FL22525 Tri-Built S/A HT TU Underlayment
5.6 Allowable Substrates:
5.6.1 Direct-Bond to Deck:
Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Plywood;ASTM D41 primed plywood; OSB;ASTM D41 primed OSB; Southern Yellow Pine;ASTM D41
primed Southern Yellow Pine;ASTM D41 primed structural concrete.
While not required over plywood,OSB or Southern Yellow Pine substrates,TRI-BUILT Materials Group,LLC
recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note:
TRI-BUILT Materials Group, LLC requires tongue-and-groove board decking be covered with plywood or
OSB prior to installation of the self-adhering underlayment.
5.6.2 Bond-to-Insulation:
Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
- ➢ Dens Deck Prime;SECUROCK Gypsum-Fiber Roof Board. .
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam-on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be
designed by a qualified design professional and installed based on testing of the insulation/underlayment
system in accordance with FM 4474,Appendix D or TAS 114,Appendix J.
'Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
Exterior Research and Design,I.I.C. Evaluation Report A42960.10.12-R6
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6
TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6:09/25/2017
Page 3 of 6
QOTRINI-rYIERD
5.6.3 Bond to Mechanically Attached Base Laver:
Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ ASTM D226,Type I or II felt.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam-on tile systems (Tri-Built S/A HT TU
Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012(04-
12).
5.6.4 Wind Resistance for Underlayment Systems in Foam-On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam-on tile systems,where
the underlayment forms part of the load-path. The following wind uplift limitations apply to direct-deck
underlayment systems that are not addressed in FRSA/TRI April 2012(04-12)and are used in foam-on tile
applications. Maximum Design Pressure is the result of testing for wind load resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012(04-12),Appendix A,Table 1A or
FBC 1609 for determination of design wind pressures.
#1 Maximum Design Pressure=-45.0 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: (Optional)ASTM D4.1 or RESISTO EXTERIOR PRIMER
Underlayment: Tri-Built S/A HT TU Underlayment,self-adhered.
#2 Maximum Design Pressure=-67.5 psf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: Soprema Elastoco1600c
Underlayment: Tri-Built S/A HT TU Underlayment,self-adhered.
#3 Maximum Design Pressure=-150.0 psf:
Deck:- Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation: Plywood shall be thoroughly.cleaned to remove dust and debris that may inhibit
adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp
splinters and wood projections shall be removed/sanded.
Primer: (Optional) RESISTO EXTERIOR PRIMER
Underlayment: Tri-Built S/A HT TU Underlayment, self-adhered, shall be thoroughly roll using hand
roller and/or weighted roller to ensure there are no voids, and ensure there are no
voids/bridging at side and end-laps.
#4 Maximum Design Pressure=-60.0 psf:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1)
and tin caps(FBC 1517.5.2)spaced 6-inch o.c.at the 4-inch laps and 6-inch o.c. in three,
equally spaced rows in the center of the sheet.
Underlayment: Tri-Built S/A HT TU Underlayment,self-adhered.
Exterior Research and Design,LLC. Evaluation Report A42960.10.12-R6
Certificate of Authorization#9503 6'"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6
TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6:09/25/2017
Page 4 of 6
s
TRINITY I ERD
5.6.4.1 For mechanically attached Base Sheet,the maximum design pressure for the selected assembly shall meet
or exceed that required under FRSA/TRI April 2012(04-12),Appendix A,Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1
design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an
attachment density designed by a qualified design professional to resist the elevated pressure criteria.
Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing
Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in
Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29(January 2016)for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left
exposed for longer than 30-days after installation
Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installation.
5.8 Tile Slippage Limitations(TAS 103 per FRSA/TRI April 2012(04-12))•
When loading roof tiles on the underlayment in direct-deck tile assemblies,the maximum roof slope shall
be as follows. These slope limitations can only be exceeded by using battens during loading of the roof
tiles.
� � a TA$CER2 TILE"SLIPPAGE LIMITATIONS FOR DIRECT DECKTlLE INSTgUJ1T�ONS
Underlayment Tile Profile Staging Method Maximum
Slope
Flat Max.10-tile stack 6:12
Lugged Max.10-tile stack 5:12
Max.10-tile stack(bottom 2-tile stack
shall be inverted,followed by 8 tiles high 6:12
on slope,as shown below)
Tri-Built S/A HT TU {
Underlayment Lugged
:y
Exterior Research and Design,I.I.C. Evaluation Report A42960.10.12-R6
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6
TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6-.09/ZS/2017
Page 5 of 6
TRINITY ERD
6. INSTALLATION:
6.1 TRI-BUILT Roof. Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC
published installation requirements subject to the Limitations set forth in Section 5 herein and the
specifics noted below.
6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application,and prime the substrate(if applicable).
6.3 Tri-Built Sand-R SA Shinsle Underlayment,Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.3.2 Non-Tile applications:
While priming is optional,TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof
cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel-off the release film diagonally while holding the
membrane tight. Firmly roll,broom or hand-press the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches; configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below,sealed in accordance with
TRI-BUILT Materials Group,LLC requirements.
When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back-nailing in the
overlap area at the top of the sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or.ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys,apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications(Tri-Built S/A HT TU Underlayment only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above as a guideline.
For foam-on.tile applications,reference is made to Section 5.6.4 herein for wind resistance limitations that
fall outside the scope of FRSA/TRI April 2012(04-12).
Tile shall be loaded and staged in a manner that. prevents tile slippage and/or damage to the
underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile
staging.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Gulfport,MS
9. QUALITY ASSURANCE ENTITY:
UL,LLC—QUA9625;(314)578-3406;k.chancellor@us.ul.com
-END OF EVALUATION REPORT-
Exterior Research and Design,I.I.C. Evaluation Report A42960.30.12-116
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-116
TRI-BUILT Roof Underlayments;(80D)516-1485 Revision 6:09/25/2017
Page 6 of 6
4
EXTERIOR RESEARCH&DESIGN, LLC.
p ��/ Certificate of Authorization#9503
STREETUNIT#13
TRIM 1 1 ERD 353 CHRISTIAN
OXFORD,�CT 6478
(203)262-9245
EVALUATION REPORT
Owens Corning Evaluation Report 037940.02.12-R8
One Owens Corning Parkway FL10674-1133
Toledo,OH 43659 Date of Issuance:02/06/2012
(740)404-7829 Revision 8: 10/09/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: Owens Corning Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein and FBC 1507.2.7.1/R905.2.6.1.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, .the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. Trinity IERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by: .•�`'i���;�t'!iri'••. . :
��i;:�o=-s?axs •:tea
.. :z�+:°f
Robert J.M.Nieminen,P.E. ti:yrSg�����`-Yp`4t,, The facsimile seal appearing was authorized by Robert
Florida Registration No.59166,Florida DCAANE1983 � �¢nm��t�" Nieminen,P.E.on 10/09/2017.This does not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. Trinity IERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E.are,in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
TRINITY I ERD
ROOFING SYSTEMS EVALUATION:
I. SCOPE:
Product Category: Roofing
Sub-Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles,as produced by Owens Corning, have demonstrated
compliance with the following sections of the 6th Edition (2017) Florida Building Code and Florida Building Code,
Residential Volume through testing in accordance with the following Standards. Compliance is subject to the
Installation Requirements and Limitations/Conditions of Use set forth herein.
2. STANDARDS:
Section Prope Standard Year
1507.2.5,R905.2.4 Physical Properties ASTM D3462 2010
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D3161 2016
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D7158 2011
3. REFERENCES:
Entity Examination Reference Date
UL LLC(CER9626) Physicals&Wind Resistance File R2453,Vol.3 02/15/2007
UL LLC(CER9626) Physicals&Wind Resistance 20120516-112453 05/16/2012
UL LLC(TST9628). Physical Properties 06CA20263 04/18/2006
UL LLC(TST9628) Wind Resistance 11CA34308 02/18/2012
UL LLC(TST9628) Physicals&Wind Resistance 4786093137 02/01/2014
UL LLC(TST9628) Wind Resistance 4786126532 02/10/2014
UL LLC(TST9628) Physical Properties Classification letter 02/13/2014
UL LLC(TST9628) Physical Properties Classification letter 10/02/2015
Miami-Dade(CER1592) FBC HVHZ Compliance Various NOAs Various
UL LLC (QUA9625) Quality Control Service Confirmation. Exp.05/16/2020
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Classic and Supreme*are fiberglass reinforced,3-tab asphalt roof shingles.
4.1.2 Berkshire*are fiberglass reinforced,4-tab asphalt roof shingles.
4.1.3 Devonshire'"are fiberglass reinforced,5-tab asphalt roof shingles.
4.1.4 Duration*, TruDefinition* Duration*, Duration* Premium Cool, TruDefinition* Duration* Designer Color
Collection, TruDefinition*Oakridge*, Oakridge* and WeatherGuard* HP are fiberglass reinforced, laminated
asphalt roof shingles.
4.2 Hip&Ridge Shingles:
4.2.1 Berkshire Hip & Ridge Shingles, High Ridge, WeatherGuard* HP Hip & Ridge Shingles, ProEdge Hip & Ridge
Shingles and DuraRidgel Hip&Ridge Shingles are fiberglass reinforced,hip and ridge asphalt roof shingles.
4.3 Accessory Starter Strips:
4.3.1 Starter Strip Shingle,Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof,is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory
for fire ratings of this product.
Exterior Research and Design,U.C. Evaluation Report 037940.02.12-R8
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 2 of 8
TRINITY I ERD
5.4 Wind Classification:
5.4.1 All Owens Corning asphalt shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161,Class F and/or ASTM D7158,Class H, indicating the shingles are acceptable
for use in all wind zones up to Va,d = 150 mph (V„It = 194 mph). Refer to Section 6 for installation
requirements to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are
Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161,Class F, indicating the
shingles are acceptable for use in all wind zones up to Va,d=150 mph(V„It=194 mph). Refer to Section 6 for
installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C,as defined in FBC 1609.4.3, and a mean
roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions
outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C.Rule 611320-3.
6. INSTALLATION:
6.1 Underlayment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product
Approval,or be Locally Approved per Rule 611320-3,per FBC 1507.2.3,1507.2.4 or R905.2.3.
6.2 Asphalt Shingles:
6.2.1 Installation of asphalt shingles shall comply with the Owens Corning current published instructions, using
minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following
exceptions:
➢ Berkshire shingles require minimum five(5)nails per shingle.
➢ WeatherGuard*HP shingles require minimum six(6)nails per shingle.
➢ Devonshireym shingles require minimum six(6)nails per shingle.
➢ Starter Strip Shingle and Starter Strip Plus require minimum five(5)nails per strip.
- Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing—Starter Strip Shingle and Starter Strip Plus:
Feltunderlayment Deck rdtuidwYyment beck
Sdkdhercd
Self-adhered uodar4ymerd
WeatherLocka
underlayment 00 edge
edg Dnp edge DrDrip ge
A
Nails located Nai I mted
T•3'fmn nve
2=3"from gave
Installrirst SeN•sealingadhesive knglfintSmtarstrip PIn
Starter trip positioned along eave withr roved positloneddangeave
shingle with
ti removed Starter Strip shingle overhangs eaves and rakes'/s='/P stater Stilp Ms wuhmgs eaves and rams 1141-3/4•
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-118
Certificate of Authorization#'9503 6t"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 3 of 8
S
TRiNIIY I ERD
6.2.6 Minimum Nailing—Classic®&Supreme:
Nomul Mansard orAna pars Norm l Mansard or Ana pan
Wind Areas Hipp YYind dssvanss y Wind Anes High Wind dssvanss y
Ana pati Wontoo normals Areas vistas fraras Area para whWas norma!" Ara" viarrtos fuartos
8'pov rr* E 5W Exposure
ExpoaJaMn
6.2.7 Minimum Nailing—Berkshire®:
Sexlanl sWp Sealant strip
Latiiadasd7xtn Lathdeseliadw
In— e SY. 9 Yf 9 Yf 8 Yf t �,81!' 8 Yt" awl
T 1'J t �•J
s
s
s
Standard Fastening Pattern 6-Nail Fastening Pattern
Sealantsfip
LaW*sdixW
of 1-0
t'
r
r -!lphak roiittigaeiirent
conento de astab
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8
Certificate ofAuthoriration#9503 6T"EDITION(2017)FBC NON-HVH2 EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 4 of 8
��TRINITYIERD
6.2.8 Minimum Nailing—DevonshireTm:
1" 7° 8" 8" 8" 7" 7"
A• dura Nails
Exposidbpn de 5518 ping Sea�nt Iac E "' 4
Ubitsd6n del s�ladgr s a�
Ten t°Spots of Asphalt Roof Cement
Standard 6-Nail Fastening Pattern Mansard or Steep Slope Fastening Pattern
6.2.9 Minimum Nailing — Duration®, TruDefinition® Duration, Duration® Premium Cool & TruDefinitionm
Durationo Designer Color Collection:
"all Fastening Pattani &Nail Fastening Pattern
"4uMia11®raMtny ar.a frldfn - Ln11aiH_feYntrq atm iAM
NaB,Typed tfy4'gN�
it +^ +r +r
.YPm.Ort+.� •"-��i0 �+qQ':a�=.ax 3:-mm fwWltr.Ti+'�3 CI.�. .2!%:�3- ➢.�O _ _�c :O�e -'��;
.. i '.
8•+la•ass• f� (.
K � _
Standard Fastening Pattern 6-Nail Fastening Pattern
Fastening for Slopes Greater Than 21:12
sf..winiamm�am..wm
a,o.rrpeo
r +r +r
I.
avrnt!i x �-
- Iwr9•fpri+MA+vAel RaotYq e�mad .
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-118
Certificate ofAuthoriration#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-R13
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 5 of 8
TRINITY I ERD
6.2.1 Minimum Nailing—TruDefinition®Oakridge®,Oakridge®: .
4 Nail Pattom 6'Nail Pattim
EsqugW eon 4 davos Esqua» 'ear b chvos
`,r t•
FrA
y _
65/rw.aww_ Nails. !i 6/8"Faposule _ Nails 6 618 E:posun
Expasiclgndeb6/8pr6s EiipoRefidade6blBpulg 66f8"Fxpasuw Cbros
Exposlol6n.de b6/BP+rlg Eriposraicr+d,66/80rdg.
Standard Fastening Pattern 6-Nail Fastening Pattern
Fastening for Mon Gmahr Than 21:12
' 9VNWISbehMna ani wtEN
Ntl1,lyPkll _
it
-n9E
i3: 3 r
raV 1•lpela alJUpIW11No9ap GVW
Mansard or Steep Slope Fastening Pattern
6.2.1 Minimum Nailing—WeatherGuard®HP:
4W1kW
'••';%` .1 ;.;:5 Fi��e71�w�Ni lin
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-118
Certiftate of Authorization 119503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-R13
Owens Coming Asphalt Roof Shingles Revision 8:10/09/2017
Page 6 of 8
rTRINITYIERD
6_3 Hip&Ridge Shingles:
6.3.1 Installation of Berkshire Hip and Ridge Shingles, High Ridge, Weat6erGuard® HP Hip and Ridge Shingles
and ProEdge Hip & Ridge Shingles shall comply with the Owens Corning current published instructions,
using four (4) nails per shingle. Installation of DuraRidgeTm Hip & Ridge Shingles shall comply with the
Owens Corning current published instructions, using two (2) nail's per shingle. Refer to Owens Corning
published information on wind resistance and installation limitations, including the use of hand-sealing for
wind warranties.
6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing—Berkshire®Hip&Ridge and High Ridge:
Fig.1 4 Fig.2
F PMYNLkpVWnd
DUedion p 'A iopVler SldWev
. A. Nags ..Nabs
Nais—��4
t•:r TopLttYoafal r �
44 Plece
4 I
_ I
jr NI
laq .
I
I
6.3.4 Minimum Nailing—WeatherGuard®HP Hip and Ridge:
Fig.C Hipt Ridge`Shingle Fastening
Fig.A v Topvlaw
Dimabn
PrevanlgY(k1C
A
Ihlls
I
A I Wtm Nabs
A
T 2..
P 1`
awa
V. FYposuro
Exterior Research and Design,U.C. Evaluation Report 037940.02.12-R8
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL30674-1113
Owens Coming Asphalt Roof Shingles Revision 8:10/09/2017
Page 7 of 8
TRINITY I ERD
6.3.5 Minimum Nailing-ProEdge Hip&Ridge Shingles:
PnvdtSng Standard
Wind Direction Stunts* marng
12� s.dat:
Fastm 7%1 7,h■ g• uiti
cora Elgased
Root
6.3.6 Minimum Nailing—DuraRidge""Hip&Ridge Shingles:.
Note:The drawings below pertain to minimum,as-tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
yFm�i4�or 1'
ilincatr+dd ri.x■f..domeaan
2%* Qou
I
u
7. LABELING:
7.1 . Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1/R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625;(631)546-2458;Kanchi.Agrawala-Dokania@ul.com
END OF EVALUATION REPORT-