HomeMy WebLinkAboutProduct Approval ECEIVED EXTERIOR RESEARCH&DESIGN, LLC.
Certificate of Authorization#9503
MAY 0 2 2018 353 CHRISTIAN STREET, UNIT#13
QOTRINITY ERD OXFORD,CT 06478
(203)262-9245
EVALUATION REPORT
ST. Lucie County, Permitting
Owens Corning Evaluation Report 037940.02.12-R8
One Owens Corning Parkway FL10674-1113
Toledo,OH 43659 Date of Issuance:02/06/2012
(740)404-7829 Revision 8: 10/09/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: Owens Corning Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein and FBC 1507.2.7.1/R905.2.6.1.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. TrinityJERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity IERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by: —
o?.r
CF
���FSS.'_ . The facsimile seal appearing was authorized by Robert
Florida Registration No.59166,Florida DCA ANE1983 ' +•��" Nieminen,P.E.on 10/09/2017. This does not serve as an
electronically signed document.
UJ CERTIFICATION 01 INDEPENDENCE:
1. Trinity IERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
LL 4. Robert Nieminen, P.E. does not have,nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
TRINITY;ERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles,as produced by Owens Corning, have demonstrated
compliance with the following sections of the 6th Edition (2017) Florida Building Code and Florida Building Code,
Residential Volume through testing in accordance with the following Standards. Compliance is subject to the
Installation Requirements and Limitations/Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1507.2.5,R905.2.4 Physical Properties ASTM D3462 2010
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D3161 2016
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D7158 2011
3. REFERENCES:
Entity Examination Reference Date
UL LLC(CER9626) Physicals&Wind Resistance File R2453,Vol.3 02/15/2007
UL LLC(CER9626) Physicals&Wind Resistance 20120516-112453 05/16/2012
UL LLC(TST9628) Physical Properties 06CA20263 04/18/2006
UL LLC(TST9628) Wind Resistance 11CA34308 02/18/2012
UL LLC(TST9628) Physicals&Wind Resistance 4786093137 02/01/2014
UL LLC(TST9628) Wind Resistance 4786126532 02/10/2014
UL LLC(TST9628) Physical Properties Classification letter 02/13/2014
UL LLC(TST9628) Physical Properties Classification letter 10/02/2015
Miami-Dade(CER1592) FBC HVHZ Compliance Various NOAs Various
UL LLC (QUA9625) Quality Control Service Confirmation Exp.05/16/2020
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Classic'and Supreme are fiberglass reinforced,3-tab asphalt roof shingles.
4.1.2 Berkshire'are fiberglass reinforced,4-tab asphalt roof shingles.
4.1.3 Devonshire'"are fiberglass reinforced,5-tab asphalt roof shingles.
4.1.4 Duration', TruDefinition' Duration', Duration" Premium Cool, Tru Definition' Duration' Designer Color
Collection, Tru Definition'Oakridge, Oakridge' and WeatherGuard' HP are fiberglass reinforced, laminated
asphalt roof shingles.
4.2 Hip&Ridge Shingles:
4.2.1 Berkshire" Hip & Ridge Shingles, High Ridge, WeatherGuard' HP Hip & Ridge Shingles, ProEdge Hip & Ridge
Shingles and Dura Ridge'"" Hip&Ridge Shingles are fiberglass reinforced, hip and ridge asphalt roof shingles.
4.3 Accessory Starter Strips:
4.3.1 Starter Strip Shingle,Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report,or previous versions thereof,is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report;refer to current Approved Roofing Materials Directory
for fire ratings of this product.
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8
Certificate ofAuthori:ation#9503 6'"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 2 of 8
TRINITY I ERD
5.4 Wind Classification:
5.4.1 All Owens Corning asphalt shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161,Class F and/or ASTM D7158,Class H, indicating the shingles are acceptable
for use in all wind zones up to V,,d = 150 mph (V„it = 194 mph). Refer to Section 6 for installation
requirements to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are
Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the
shingles are acceptable for use in all wind zones up to Vasd=150 mph (V,,,= 194 mph). Refer to Section 6 for
installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C, as defined in FBC 1609.4.3, and a mean
roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions
outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C.Rule 611320-3.
6. INSTALLATION:
6.1 Underlayment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product
Approval,or be Locally Approved per Rule 61G20-3, per FBC 1507.2.3,1507.2.4 or R905.2.3.
6.2 Asphalt Shingles:
6.2.1 Installation of asphalt shingles shall comply with the Owens Corning current published instructions, using
minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following
exceptions:
Berkshires shingles require minimum five(5)nails per shingle.
WeatherGuard�HP shingles require minimum six(6)nails per shingle.
i Devonshire•"shingles require minimum six(6) nails per shingle.
Starter Strip Shingle and Starter Strip Plus require minimum five(5)nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing—Starter Strip Shingle and Starter Strip Plus:
Felt underlayment Deck Felt underlayment Dade
wathoto"
Setl•adhered urWad Y go
Weatherl ocke
underlayment
Drip_ Drip edge Drip
edge
Naik from bcatad Male
r 1.1rom ave
-
2"3"from eave
Install first Self-sealing adhesivblad first e �deg+ eeAe
Starter Strip positioned along eave With 6,rarnaved r V, 11, abna a'"'s
shingle with \ ,
6"removed Starter Pks ovwM aves and rata 7/P-]14•
Starter Strip shingle overhangs saves and rakes,lr.-3'r" ^�
Exterior Research and Design,U.C. Evaluation Report 037940.02.12-R8
Certificate of Authorization 119503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 3 of 8
",,,�
TRINITY ERD
6.2.6 Minimum Nailing—Classic'&Supreme:
Normal Mansard or Area para Normal Mansard or Area pars
Wind Areas High Wind desvanes y Wind Areas High Wind desvenes y
Area pars vientos normales Areas vientos fuertes Area pars vientos normales Are" vientos fuertes
t lAl r t z (BI_ v2- r r (A) T t z, IBI z
tt� tr tz u I
1 _! t •�1�,
5"Exposure 5 5/13'Exposure
Exposicidn Exposicidn
6.2.7 Minimum Nailing—Berkshire':
Seahm,lrip Sealant strip
La lira de spdador La lira de sOador
A OM
Yz' A Vf 9 Vt' 8 V: 8 8 S z e' 1
r t..
r
r
r
Standard Fastening Pattern 6-Nail Fastening Pattern
&.ahnl strip
La lira de selledor
8 tlf 8 Vf' 4112P
8 bt'
r
1 •R
2" Asphalt rooting cement
Convolo&Who do whho
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8
Certificate of Authorization#9503 6'"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-R13
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 4 of 8
TRINITY I ERD
6.2.8 Minimum Nailing–Devonshire'":
1. 7" 8" 8" 8- 7" �•
17ftw _
Naas
53/8"exposure sesunt locatbn
Exposlcidn de 5 3/8 pulp Ubiad6n del sdador S.• 6�
Ten 1"SpotsolAsphah Roof Cemlart
Standard 6-Nail Fastening Pattern Mansard or Steep Slope Fastening Pattern
6.2.9 Minimum Nailing – Duration®, TruDefinition® Duration, Duration® Premium Cool & TruDefinition"
Duration*Designer Color Collection:
4-Mil Fastsnhg Pattern 64UN FasaNrg Pattern
susaa•o wrwq er a wwn surothm Wrer a a•a.kan
wq ryp" a+.rypka
1 �r it
s-w saA^
F1 F�
F I F� ILJ
Standard Fastening Pattern 6-Nail Fastening Pattern
Fesaning for Slopes Greats Than 21:12
saw"r"uft Mkv—wim
ww,rypor
�• �: +r
MM Sd!
pa. •spa.a Ap"re x..rro o.m.a
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 5 of 8
QOTRINITYIERD'
6.2.1 Minimum Nailing—Tru Definition'Oakridge®,Oakridge®:
4 Nail Pattern 6 Nail Pattern
Esquema con 4 clavos Esquema colt 6 clavos
Imo—
12' �I >z
---moi H--- 12-
5 518"Exposure
2.5518"Expaure Nals 66f9"Exposunt Plad.
Expmvon de 6 5,/8pulg. CIA vas Expa4aim&5518pulg. 5 6/8"Exposure clavos 55'8'Expo>uie
Egmsicfon de 5618 pufg. Exposicion de 55/8 putg
Standard Fastening Pattern 6-Nail Fastening Pattern
Fastening for Slops Greater Than 21:12
t..urw a.v.�wp r...wan
r 1r 1r
s.vr ssn^
�r
rar 1•syob aAryYn A 0 C.
Mansard or Steep Slope Fastening Pattern
6.2.1 Minimum Nailing—WeatherGuard®HP:
1• /� Simple
i berral
Fustmm Thrw+*Mall lira
chem w L Ki di fon"m
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8
Certificate ofAuthorizotion#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 6 of 8
\J\TRINITY ERD
6.3 Hip&Ridge Shingles:
6.3.1 Installation of Berkshire' Hip and Ridge Shingles, High Ridge, WeatherGuarde HP Hip and Ridge Shingles
and ProEdge Hip & Ridge Shingles shall comply with the Owens Corning current published instructions,
using four (4) nails per shingle. Installation of DuraRidge'" Hip & Ridge Shingles shall comply with the
Owens Corning current published instructions, using two (2) nails per shingle. Refer to Owens Corning
published information on wind resistance and installation limitations, including the use of hand-sealing for
wind warranties.
6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing—Berkshire®Hip&Ridge and High Ridge:
Fig.1 v Fig.2
PMWNMvrnn
DaachosA TopMsr SbleVlw
Nets"'--�� A � N.M. Nrk
LanlYlslas r T
A i i /' Plau
Q I I I
I I j j I
E>poeuxa I
I
1
I
1
I
1
6.3.4 Minimum Nailing—WeatherGuard®HP Hip and Ridge:
Fig.C Hip&Ridge Shingle Fastening
Fig.A Y v TopV*w
plsnlsg wwa
f.-practbn A
A
A i I NOIY Nails
A I I I I
1 I I I
�ElpOatlR
V. Exposure
'I
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8
Certificote of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 7 of 8
Q0TRINTY
6.3.5 Minimum Nailing-ProEdge Hip&Ridge Shingles:
Prevailing Standard -11'-
Wind Direction Fastening
Sealant Strip Pattern
6'Exposure 2' r ~rj r
• 12' ieelnst
Fasten 71h' 7'k' d•�gsp°re
Cover Exposed
Fasteners with J
Roof Cement
6.3.6 Minimum Nailing—DuraRidgeT" Hip& Ridge Shingles:
Note:The drawings below pertain to minimum,as-tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
r trre•eifne Wind Dineian �h Top
View
e
Direction damrunte du•e•t
Direao,on del•itntr predniieet• I vim 1
I
• OearCarxiq iunNae' • �"
N.k
cclow
:,rr
I I •I
r I
�-100V
• I1
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1/R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625; (631)546-2458;Kanchi.Agrawala-Dokania@ul.com
- END OF EVALUATION REPORT-
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 8 of 8