HomeMy WebLinkAboutUntitled (2) Architectonic Inc
May 8,2018
Saint Lucie County Building Department
Attn: Roof Permit Plan Review
2300 Virginia Avenue
Ft. Pierce, FL 34982
Re: Roofing specification prepared for the St. Lucie County Building Dept.for the structure
located at 2453 Johnston Road,St. Lucie County
Manufacturer: Tri-Built Roofing Products 1
Profiles: Tri—Built Modified, FL#16027.1
Code: FBC 2017;Section R 905.10
Wind Speed: 160 MPH; Ultimate Design Wind Speeds
Exposure: C
Mean Roof Height: 30' Maximum
Pitch: 1/4/12
Required Design Pressure: Zone1:-31.46 Zone 2:-49.61 Zone3:-68.97
Maximum Uplift Pressure: -90
Base: SBS-SA
Cap: SBS-SA,APP-SA,SBS-TA OR APP-TA
Roof Decking: Existing 5/8" plywood sheathing to be nailed w 8d x 2" ring shank nails
@ 6" O.C.thru out Zone 1,4" O.C. perimeter&6" O.C.field Zone 2,
and 4" O.C.thru out Zone 3.
The above approved, as per Florida Building Code Compliance acceptances, 2017 Florida Building Code,
and the Manufacturer's recommendations.
r
,Respectful y.S.ub t
44 cgil,,.._,,,,,p.,:_l_.J,..,_:z., 41
4k
1Micha I Seal ..
11,
` hit ctonic Inc..•°,1
' EDN 9
1
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg#AA26003348 1 of 1
EXTERIOR RESEARCH&DESIGN,LLC.
Certificate of Authorization#9503
ClCTRINITY353 Christian Street
ERD Oxford,CT 06478
(203)262-9245
EVALUATION REPORT
TRI-BUILT Materials Group,LLC Evaluation Report A42970.10.12-R2
PO Box 70 FL16027-R2
•
Rutherford, NJ 07070 Date of Issuance:10/23/2012
(800)516-1485 Revision 2:09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition(2017)Florida Building Code sections noted herein.
DESCRIPTION: TRI-BUILT Modified Bitumen Roof Systems
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity!ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT:The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 4, plus a 26-page Appendix.
Prepared by:
Robert J.M. Nieminen,P.E. '•,b-; ;Q by
,;•� .� ` The facsimile seal appearing was authorized Robert Nieminen,
Florida Registration No.59166,Florida DCAANE1983
(J ..h�"+'J\>4%,� P.E.on 09/25/2017.This does not serve as an electronically signed
+.JJ,rrr.'t..ris document.
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research&Design,LLC.d/b/a Trinity I ERD does not have,nor does it intend to acquire or will it acquire,a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity'ERD nor Robert Nieminen, P.E. are, in any way,the Designer of Record fo'r any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
t
•
•
cl(
TRINITY ERD
I..APP.ENDIX'1,ATTACHMENT REQUIREMENTS'FOR VIIIND,UPLIF,T RESISTANCE'
Table Deck Application Type Description Page
lA-1 Wood New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 4
1A-2 Wood New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 5
1B Wood New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 5
1C Wood New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 6
10 Wood New,Reroof(Tear-Off)or Recover D Prelim.Attached Insulation,Mech.Attached Base Sheet,Bonded Roof Cover 6
1E-1 Wood New or Reroof(Tear-Off) E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 7
1E-2 Wood New,Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 8
1F Wood New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 8
2A Steel or Structural concrete New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 9
2B Steel or Structural concrete New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 9
2C Steel or Structural concrete New,Reroof(Tear-Off)or Recover D Prelim.Attached Insulation,Mech.Attached Base Sheet,Bonded Roof Cover10
3A Structural concrete New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 11-14
3B Structural concrete New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 14
4A LWIC New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 15-16
4B LWIC New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 16
4C LWIC New or Reroof(Tear-Off) E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 17-19
5A CWF New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover • 20
5B CWF New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 21
5C CWF New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 22
SD CWF' New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 22
5E CWF New,Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover •
22
6A Gypsum New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 23
68 Gypsum New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 24
6C Gypsum New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 24
6D Gypsum New,Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 24
7A Various Recover A-1 Bonded Insulation,Bonded Roof Cover 25-26
7B Various Recover F Non-Insulated,Bonded Base Sheet,Bonded Roof Cover 26
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Insulation/base sheet fasteners shall be of sufficient length for the following deck engagement:
>Wood: Minimum 0.75-inch penetration.
>Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck.
Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions.
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, gypsum-based roof board or mineral-wool roof board that meets the CIA
requirements of F.A.C.Rule 61G20-3 and is documented as meeting FBC 1505.1 and,for foam plastic,FBC Chapter 26,when installed with the roof cover.
Exterior Research and Design,LLC.d/b/a Trinity)ERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Certificate of Authorization#9503 6TH EDITION(2017)FBC NON-HVHZ EVALUATION Revision 2:09/25/2017
Prepared by: Robert Nieminen,PE-59166 TRI-BUILT Modified Bitumen Roof Systems;(800)516-1485 Appendix 1,Page 1 of 26 ,
i
TRINITY I ERD
15. Unless otherwise noted,refer to the following references for bonded base,ply or cap sheet applications.
TAaLE l TRI`•BUILTRooF Covelu
Reference Layer Material Application
BP-AA Base Ply FBC Approved ASTM D4601,Type II HA at 20-40 lbs/square
(Base and Ply sheets,Asphalt-Applied) Ply FBC Approved ASTM D2178,Type IV or VI
SBS-AA Cap Ply TriBuilt SBS Granular HA at 20-40 lbs/square
(SBS,Asphalt-Applied)
SBS-TA
(SBS,Torch-Applied) Cap Ply TriBuilt SB5 Granular Torch-Applied
SBS-SA Base Ply TriBuilt SA SBS Base Self-Adhering
(SBS,Self-Adhering) Cap Ply TriBuilt SA SBS Cap
APP-TA Base Ply or Ply TriBuilt APP Smooth Torch-Applied
(APP,Torch-Applied) Cap Ply TriBuilt APP Smooth,TriBuilt APP Granular
APP-SA
(APP,Self-Adhering) Cap Ply TriBuilt SA APP Cap Self-Adhering
16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure(MDP)limitations. The lesser of the MDP listings below vs.those in Table 3A
applies:
VAPORBARRIEROPTIONS STRUCTURALCONCRETEDECK%ADHERED.INSULATION"PERTABLE3A_;_
Vapor Barrier
Option# Primer Insulation Adhesive MDP(psf)
Type Attach
VB-1. ASTM D41 TriBuilt SA 5BS Base Self-Adhering Inta-Stik or CR-20,12-inch o.c. -60.0
VB-2. ASTM D41 TriBuilt SA SBS Cap Self-Adhering Insta-Stik,12-inch o.c. -75.0
VB-3. ASTM D41 TriBuilt SA SB5 Cap Self-Adhering Millennium One Step Foamable Adhesive,12-inch o.c. -157.5
VB-4. ASTM 041 TriBuilt SA SBS Cap Self-Adhering CR-20,12-inch o.c. -270.0
VB-5. ASTM D41 TriBuilt SA 5BS Base Self-Adhering Millennium One Step Foamable Adhesive,Millennium PG-1 Pump Grade -290.0
Adhesive,OlyBond 500 or CR-20,12-inch o.c.
' 17. Dens Deck shall be field-primed with PG100 prior to self-adhering membrane application. Refer to tables herein for other priming requirements.
18. "MDP"=Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads.Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design,LLC.d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Certificate of Authorization#9503 6TH EDITION(2017)FBC NON-HVHZ EVALUATION Revision 2:09/25/2017
Prepared by: Robert Nieminen,PE-59166 TRI-BUILT Modified Bitumen Roof Systems;(800)516-1485 Appendix 1,Page 3 of 26
•
C)(
. TRINITY ERD
_ -.TABLE lE 2 WOOD DECKS NEW CONSTRUCTION,"REROOF(TEAR-OFF)oR RecovER
SYSTEM TYPE Er.;;NON,INSULATED,MECHANICALLY ATTACHED BASE SHEET;BONDED.:ROOF 000ER
System Base Sheet Roof Cover'(Note 15) MDP
Deck(Note 1)
No. Base Fasteners Attach Base Ply Cap Ply (psf)
Polyglass Elastobase,Polyglass Elastobase
Min.19/32-inch OMG Flat Bottom Plates(square)with 12-inch o.c.in 4-inch lap and 12-inch (Optional)One or
Poly,Polyglass G2 Base,CertainTeed SBS-AA,SBS-
W-1 plywood at max. Glasbase,Firestone MB Base,.IM Perma- Roofgrip#14,Dekfast Hex with Dekfast#14 o.c.in two,equally spaced,staggered more BP-AA or
TA,APP-TA -52.5
24-inch spans Ply 28,Tamko Glass Base or GAFGLAS#75 or TruFast MP-3 with TruFast HD center rows APP-TA
Min.19/32-inch 12-inch o.c.in 4-inch lap and 12-inch SBS-SA,APP-
Polyglass Elastobase or Polyglass Dekfast Hex with Dekfast#14 or TruFast MP- o.c.in two,equally spaced,staggered One or more SBS-
W-2 gg SA,SBS-TA or 52.5*
plywood at max. Elastobase Poly with poly top surface 3 with Tru Fast HD SA
24-inch spans center rows APP-TA
Min.19/32-inch Polyglass Elastobase or Polyglass OMG Flat Bottom Plates(square)with 12-inch o.c.in 4-inch lap and 12-inch (Optional)One or SBS-AA,SBS-
W-3 plywood at max. Elastobase Poly Roofgrip#12 o.c.in two,equally spaced,staggered more BP-AA or TA,APP-TA -60.0
24-inch spans center rows APP-TA
Min.19/32-inch 12-inch o.c.in 4-inch lap and 12-inch SBS-SA,APP-
Polyglass Elastobase or Polyglass OMG Flat Bottom Plates(square)with One or more SBS-
W-4 plywood at max. Elastobase Poly with poly top surface Roofgrip#12 o.c.in two,equally spaced,staggered SA SA,SBS-TA or -60.0*
24-inch spans center rows APP-TA
TABLE iF -WOOD<.DECKS NEW CONSTRUCTION oR REROOF(TEAR OFF)
SYSTEM TYPE F NON-INSULATED,:BONDED ROOF COVER
System Roof Cover(Note 15) I MDP .
No. Deck Primer Joint Treatment Base Ply PlyCap Ply (psf)
Min.15/32-inch plywood (Optional)SBS-SA or SBS-SA,APP-SA,SBS-TA
W-5 at max.24-inch spans (Optional)ASTM D41 None SBS-SA
APP-TA or APP-TA 90.0
Min.15/32-inch plywood Plywood joints are covered with 4-inch wide strips of TriBuilt SA (Optional)SBS-SA or SBS-SA,APP-SA,SBS-TA
W-6 at max.24-inch spans (Optional)ASTM D41 SBS Base,rolled into place to create continuous bond. TriBuilt SA SBS Base APP-TA or APP-TA 97.5
•
•
•
Exterior Research and Design,LLC.d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Certificate of Authorization#9503 6TH EDITION(2017)FBC NON-HVHZ EVALUATION Revision 2:09/25/2017
Prepared by: Robert Nieminen,PE-59166 TRI-BUILT Modified Bitumen Roof Systems;(800)516-1485 Appendix 1,Page 8 of 26 —