HomeMy WebLinkAboutProduct Approval URNER 1239 Jabara Ave. North Port, FL 34288 ENGINEERING& Ph. 941-380-1574 TCONSULTING, INC. FBPE C.O.A. #29779 Evaluation Report 1069B December 1, 2015 Product Description: Series 6500 PVC Double Hung, Large Missile Impact Wind Zone 3, 53 1/8"x 76"max:unit size+/-45 psf,or 48"x 72"max. unit size+/-50 psf Manufacturer: Custom Window Systems, Inc. 1900 SW 44h Ave, Ocala, FL 34474 Statement of Compliance: This report evaluates the above-listed product per the requirements of FAC Product Approval Rule Chapter 61 G20-3.005 (4). This product complies with the requirements of the 5`h Edition(2014)Florida Building Code,not including the High Velocity Hurricane Zone or Wind-Zone 4. The product testing standards performed are outlined below. Technical Documentation: 1) This report,prepared by Lucas A. Turner,P.E., at 1239 Jabara Ave.,North Port, FL - 2) Approval drawing CWS-1069B; signed and sealed by Lucas A. Turner, P.E. 3) Test Reports NCTL-210-3964-03/04/09/10, by National Certified Testing Laboratories, Orlando,FL,with testing performed: ASTM E 1886 `05,ASTM E 1996 `05/09 (large missile impacts in accordance with Wind Zone 3), and AAMA/WDMA/CSA 10l/I.S.2/A440 '08 4) Supplemental Calculations to support CWS-1069B, signed and sealed by Lucas A. Turner,P.E. Installation: Units.must be installed according to approval document CWS-1069B. Limitations of Use: This product: • May be used up to the sizes and daylight openings with glazing as indicated in CWS- 1069B • Achieves design pressures of+/-45 psf in the 53-1/87'x76"unit size for flange and fin • Achieves design pressures of+/-50 psf in the 48"x72"unit size for flange and fin • Is Large Missile impact resistant and does not require the use of shutters • May not be used in the High Velocity Hurricane Zone or Wind Zone 4 areas • Requires Kuraray(Dupont)Butacite PVB Interlayer • Requires ATN PVC frames with current listing as AAMA 303 Certified Profile Licensee Certification of Independence: I do not have, nor do I intend to acquire,nor will I acquire, a financial.interest in.Custom Window Systems or in any company manufacturing or distributing products for which this report.is being issued. I do not have,nor do I intend to acquire, nor will I acquire; a financial interest in any other entity involved in the testing or approval process of this product. p tittti��t is o rrrt,�'�,r rr; No 58201 Lucas A.Turner . . • f 2015-12-01 = = _ 16:54-05:00 u 12/1/2015 733 8 TAT EOP 4a 4a Lucas A. Turner,P.E. �� �'�0'� •;; � .•�N��.�~ FL PE#58201 GENERAL NOTES: DOUBLE HUNG - LARGE MISSILE IMPACT 1.THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED TO COMPLY WITH THE FLORIDA BUILDING CODE(FBC),CURRENT WINDaW SVSTEPIS EDITION AND IS RATED FOR MISSILE LEVEL D IMPACT USE IN WIND 1900 SW 44TH AVE. ZONE 3 AREAS AS DEFINED IN ASTM E 1996 PER THE FBC. OCALA,FLORIDA 34474 WWW.CWS.CC PRO THIS DUCT MAY NOT BE USED IN THE HIGH VELOCITY HURRICANE ZONE(HVHZ)OR IN ASTM E 1996 WIND ZONE 4 AREAS. 543/8' 49114' 6500 PVC FLANGE WIDTH FLANGE WIDTH 2.GLAZING OPTIONS:(SEE SHEET 2) 531!8" MAX.UNIT WIDTH 3.CONFIGURATIONS:"X/X'. DOUBLE HUNG MAX UNIT WIDTH IMPACT 4815116" 4313116_ 4.DESIGN PRESSURE RATING: MAX.UPPER SASH WIDTH MAX.UPPER.SASH WIDTH TT -NEGATIVE DESIGN LOADS BASED ON,TESTED PRESSURE AND 46 114• 41116" GLASS TABLES ASTM E-1300-04. GLASS DLO GLASS DLO -POSITIVE DESIGN LOADS BASED ON,TESTED PRESSURE,WATER o o F A INFILTRATION TEST PRESSURE AND GLASS TABLES o o O ASTM E-1300-04. ---- Y Y ----- 5.ANCHORAGE:THE 33 1!3/STRESS INCREASE HAS NOT BEEN USED w w m -- -- -I- ! IN THE DESIGN OF THIS PRODUCT.SEE SHEET 5 FOR ANCHOR rn DETAILS. WINDLOAD DURATION FACTOR Cd=1.6 WAS USED FOR WOOD ANCHOR CALCULATIONS. -N- O 3515116' o ¢ UJ MAX 33 !8" -6" 6.PRODUCT APPROVED FOR IMPACT RESISTANCE. SHUTTERS ARE a o Z > 77 1lq. UPPER '` GLASS DLO M X 31318" NOT REQUIRED. ❑ m Ofr FLANGE HEIGHT B I B SASHR GLASS DLO n ? a HEIGHT 73 1/4' I HEIGHT 7.ALL FRAMES AND VENTS FULLY WELDED.SMALL JOINT SEAM x LL FLANGE SEALANT USED AT FIXED MEETING RAIL JAMB. < z v HEIGHT ❑ ¢ w S.SERIES!MODEL DESIGNATION DH-6500. p MA 72' ............... MAX - .... ........... .................... .... UNIT R MAX 9.THE DESIGNATION X AND O STAND FOR THE FOLLOWING: m ¢ z HEIGHT I 5 HEIGHT UNIT X=OPERABLE SASH I C �#' 5 10.SECTION CALLOUTS APPLY TO ALL ELEVATIONS IN A SIMILAR ,���� PNDREW 'fle 3615116 X D 3415116 X 313/8 LOCATION. o�Q`.�iGENgF.,:Qtiy� MAX. - 5 MAX GLASS DLO .�.J, to LOWER LOWER, 11.EXTERNAL WEEP SLOT-V2 x 2-1/2'LOCATED 5•FROM BOTH v• No 5$201 5 SASH I G�33 318.O SASH ENDS. HEIGHT HEIGHT Lucas A.Turner :Q' STATE OF: 4u A 2015-12-01 ''. Fs�(O R ID.,Gz A '�• 5 16:54 05:00 '�ihS+ONA�EC��`� 46114' 411/8' GLASS DLO GLASS DLO z . 4915/16* 44 13/i6' 12/1/2015 MAX LOWER SASH WIDTH MAX.LOWER SASH WIDTH LUCAS A.TURNER,P.E. FL PE#58201 1239 JABARA AVE. NORTH PORT,FL 34288 PH.941-380-1574 SHEET DESCRIPTION: GENERAL NOTES AND ELEVATIONS TABLE OF CONTENTS MAX. UNIT DESIGN PRESSURE IMPACT RATING DRAWN BY: DATE: SIZE RATING EMK 05/26/15 GENERAL NOTES&ELEVATIONS.....1 DWG#: REV.: SECTION VIEWS&GLAZING..............2 53-1/8"x 76" +/-45 PSF LARGE MISSILE IMPACT CWS-1069 B EXTRUSIONS&B.O.M.........................3 SCALE: ANCHOR SCHEDULE&NOTES..........4 48"X 72" +/-50 PSF SHEET INSTALLATION DETAILS.....................5 1:20 1 OF 5 WIi�9DOYV SYsrr�ls 2 4 8 8 19 8 1900 SW 44TH AVE. OCALA,FLORIDA 34474 www.cws.cc 0 a � b ❑ 6500 PVC DOUBLE HUNG 1 IMPACT [�� to to �4.-_.- --� c o F 0o o D 33 El D t 1 34 2 18 3 6 3819 24 w W m SECTION VIEW 8-13 Z 7 cn O tu o tx Cf) 1 11 n o n 0 W Er ❑ 16 x z a �J < Z U 6 i t mu, LLI X11 9 m d Z 12 11 4ElT/8'OVERALL 36 `rwillA1171ts", 118'ANNEALED ♦-%, I,L4ORLD41r r;'!" 7116'AIRSPACE ,jGPr' NSF{"�1t^, No 58201 5/16'LAMINATED *„ �* 1/8'ANNEALED r.-0 .131. STATE OF . '4 .090"DUPONT PVB INTERLAYER i.0'. tt/w ❑ 7 11W ANNEALED 4�S R ♦� --- 4 36 SIKAFLEX 2 OR P RFECT GLAZE'H" 1 1 14 12/l/2015 LUCAS A.TURNER,P.E. ❑ a 5/8"GLASS BITE FL PE#58201 3 1239 JABARA AVE. 13 NORTH PORT,FL 34288 prim n -- -- � PH.941-380-1574 a 0 SHEET DESCRIPTION: SECTION VIEWS AND SECTION VIEW A-A GLAZING DETAIL ALTERNATE FIN FRAME DRAWN BY: DAZE: EQa—s--2, EMK 1 05/26/15 DWG d; REV.: GLASS TYPE A CWS-1069 B 1.1 SCAT SHEET 1:2 2OF5 I PARTS LIST ITEM PART#DESCRIPTION MATERIAL VENDOR 4 1M* FRAME CORNER 1 H-6721 HEAD,OUTERFRAME PVC ATN CONSTRUCTION 2 -fi:6122 JAMBS,OUTERFRAME PVC ATN WINDOW SYSTEMS 3 H-6123 SILL,OUTERFRAME PVC ATN 1900 SW 44TH AVE. 4 H-61 Yo TOP RAIL,UPPERSASH PVC ATN OCALA,FLORIDA 34474 5 H-6m BoTrom RAIL,IFP-PER SASH PVC ATN 2 WwW.Cws.CC 6 H-6132 SASH SIDE RAIL,UPPER SASH PVC ATN LL -11 E-1 7 H-6133 BOTTOM RAIL,LOWER SASH PVC ATN 4 IIIS' 4116' 8 H-6i-34 SASH SIDE RAIL,—LOWER SASH PVC 6500 PVC - ATN CORNER WELD 9- H-6135 TOP RAIL,LOWER SASH PVC ATN 0 (ALL SIDES) DOUBLE HUNG 10 P-3028 SETTING BLOCK RUBBER FRANK LOWE u 1.6 IMPACT 11 P,3515 #8 x 518 PHIL EMT WHITE SMS STEEL FASTENAL 12 P-4146 #8 X 34 PHIL FLAT TEK. STEEL FASTENAL 14 P-5085 WSTP,.355 X 333SULB VINYL AMESBURY PVC FRAME HEAD PVCFRAMEJAMB ill C> I- AME H-6121 (o 15 P-5086 WSTP,.300 X 187BULB VINYL H-6122 13 P-5420 WEEP COVER NYLON M&M 16 P-378_3 LOCKS SBURY INTERLOCK 17 P-3784 KEEPERS INTERLOCK 43/16'= tu w m 18 P-5424 WS—TP.-500 X 1:5"ADHESIVE BACK STRIP ULTRAFAB ------ 19 17-5392 ISASH TILT LATCH NYLON CALDWELL - !2 z rj) 21 P-5396 PIVOTBAR SS CALDWELL < LD 22 P-5412 JAMB JACK STEEL MERCHANTS m (n 24 P-3305.WSTP., 2-70XI87 w -- 5; ULTRAFAB I Z I 7/16" L j - F V5 0 25 S-2001 INTERLOCK RAIL ALUM ASCEND 1116" 4 z tt 27 S-2003 REINF,BOT RAIL,UPPER SASH ALUM ASCEND =x REINF;SIDE RAIL,LOWER SASH ALUM ASCEND. 37/8 0 1 7116* 1116" 1 112' 28 S-2004 , ru a U) w 29 S-2005 REINF,TOP RAIL,LOWER SASH,&SIDE RAIL LOWER SAS ALUM ASCEND L 30 S-2006, REINF,SASH TOP AND.SIDE RAIL,UPPER SASH ALUM ASCEND 31 S-2010 REINF,BOTTOM RAIL,LOWER SASH ALUM ASCENDm 0 z 32 S-2027 REINF,SIDE RAIL,UPPER SASH, PVC TOP RAIL UPPER PVC BOT RAIL UPPER 'I ALUM ASCEND H-6130 H-6131 33 S-6141 GLAZING BEAD PVC ATN %-'��,eREW Al, 34 S-6142 SASH-STOP PVC FRAME SILL ....... ',.�p 35 TAgN—CERS-CONSTANT FORCE FIT CALDWELL H-6123 E N$6 36 HOTMELTSILICONE TRUSEAL No 58201 'P 37 GLASS SEESHEET2 9 P-5425 WSTP; 0 XIS X5/8"DUST PLUG ULTRAFAS —2118* 111/16'- Z-0. -jrz P-3218!�SMRE �FRAWE_" ALUM FLA SC ULTRAFAS STATE OF %t� 40 P 754 SCREEN CORNER KEY NYLON FLA SCREEN • 7 0 R IV.," 41 P-3 228 SCREEN SPLINE— DADA J-1 'ff;l 1-0 N A 142 P-3029 ISCREEN LIFTS SUMMIT 7116" 115116, T- 7 43 P-3033 ISCREEN SPRINGS 1 1 ISMS* -1116, 1 FLA SCREEN L fns CT'11161 L —ills" PVC SSR UPPER 121112015 H-6132 PVC BTM RAIL LOWER PVC SSR LOWER PVC TOP RAIL LOWER LUCAS A.TURNER,P.E. H-6133 H-6134 H-6135 FL PE#58201 1239 JABARA AVE. 314' NORTH PORT,FL 34288 �-13116'-j 9116. rl 3fl6' g1jr. 15116" PH.941-380-1574 1/16' 9 3t 30 13/16`1 SHEET—DESCRIPTIOM 6 6 . F .052. L-093' -.062* 1/16' BOM AND EXTRUSIONS INTERLOCK 193" -.062" ?o ,4c to L-F—L q REINFORCEMENT REINFORCEMENT .393, S-2001 S-2003 S-2004 REINFORCEMENT REINFORCEMENT REINFORCEMENT REINFORCEMENT DRAWN BY: DA E: S-2005 S-2006 S-2027 S-2010 EMK 05/26/15 DWG_# WE—V.- CWS-1 069 B :LINE!TENS NOTE; EX�TRUSIONS.ARE AL�UM_6063­T6�UNLESS UNLESS OTHERWISE WA_LE:_ SHEET CIEL(MEMtS16"MAX.(TYP.) 4'MAX(1YP.) 8'MAX(TYPd MIDPOINT 1900 SW 44TH AVE. 6"MAX(TYP.) SEE NOTE 2 4"MAX'(TVP') SEE NOTE 2 OCALA,FLORIDA 34474 W W W.CW S.CC 6500 PVC X 8"MAX(TYP:) X DOUBLE HUNG IMPACT 141/2' MAX O.C. J_]] (TYP.) I �D t ZZ i —q�MiG RAIL —gMTG RAIL ! ^o F' o o 4"(TYP.) 4'THRUFRAMEr �,} X , X INSTALLATION W (TYPW [D ANCHORS(TYP.) U) z J p 65 4 INSTALLATION `� ANCHORS 9 0 9 Z W N N O x ? a ANCHOR LAYOUT-(FLANGE) ANCHOR LAYOUT-(FIN) m z ¢ [NO SILL ANCHORS REQUIRED] [NOTE THRU FRAME ANCHORS] p ¢ W J UU DO Q Z ti��tn��rgr� ``. PNOREW .G E NS tRq��i No 58201 NOTES: 9:, STATE OF /dt� 1.INSTALL ONE ANCHOR AT EACH INSTALLATION LOCATION. •,�f���S�`� R•� G\�+ 2.SHIM AS REQ AT EACH INSTALLATION ANCHOR USING LOAD BEARING SHIMS. MAX ALLOWABLE SHIM STACK TO BE 1/4". USE SHIMS WHERE SPACE GREATER THAN 1/16'IS PRESENT. LOAD BEARING SHIMS SHALL BE IOjjl CONSTRUCTED OF HIGH DENSITY PLASTIC OR BETTER.WOOD SHIMS ARE NOT ALLOWED. 3.ANCHOR TYPE,SIZE,SPACING AND EMBEDMENT SHALL BE AS SPECIFIED IN THESE DRAWINGS,SEE TABLE 1,SHEET 5. 12/1/2015 4.ALL INSTALLATION ANCHORS MUST BE MADE OF OR PROTECTED WITH A CORROSION RESISTANT MATERIAL OR COATING. DISSIMILAR.METALS OR MATERIALS IN CONTACT WITH PRESSURE TREATED WOOD MUST LUCAS A.TURNER,P.E. BE PROTECTED TO PREVENT REACTION. FL PE#58201 1239 JABARA AVE. 5.INSTALLATION.ANCHORS SHALL BE IN ACCORDANCE WITH ANCHOR MANUFACTURER'S INSTALLATION INSTRUCTIONS,AND ANCHORS SHALL NOT BE USED IN.SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM NORTH PORT,FL 34288 SPECIFIED IN TABLE 1,SHEET 5. PH.941-380-1574 6.ANCHOR EMBEDMENT TO SUBSTRATE SHALL BE BEYOND WALL DRESSING OR STUCCO. FOR CONCRETE/CMU OPENINGS,EMBEDMENT SHALL BE BEYOND WOOD BUCKS,IF USED,INTO SUBSTRATE SHEET DESCRIPTION: INSTALLATIONS INTO SOLID CONCRETE OR GROUT FILLED CMU MAY INCLUDE BUT DO NOT REQUIRE 1X WOOD BUCKS BETWEEN THE PRODUCT AND THE SUBSTRATE. ANCHOR SCHEDULE AND INSTALLATIONS INTO HOLLOW CMU REQURE THE USE OF 1X WOOD BUCKS BETWEEN THE PRODUCT AND SUBSTRATE. NOTES 7.A MINIMUM CENTER-TO-CENTER SPACING SHALL BE MAINTAINED BETWEEN ALL FASTENERS:3-9/16"FOR MASONRY,1"FOR WOOD AND METAL. DRAWN BY: DATE: 8.WOOD OR MASONRY OPENINGS,BUCKS AND BUCK FASTENERS SHALL BE PROPERLY DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD AND INSTALLED TO TRANSFER WIND LOADS TO THE STRUCTURE. EMK 05/26/15 SUBSTRATES SHALL MEET THE MINIMUM STRENGTH REQUIREMENTS AS SHOWN IN TABLET,SHEET 5. CONCRETE AND MASONRY SUBSTRATES MAY NOT BE CRACKED. DWG 0: REV.: CWS-1069 B AN 9.SEALING AND FLASHING STRATEGIES FOR OVERALL WATER RESISTANCE OF INSTALLATION SHALL BE DONE BY OTHERS FOLLOWING THE CURRENT VERSION OF THE REFERENCE DOCUMENTS: sc w FMA/AAMA 100(FIN WINDOWS),FKWAAMA 200(FLANGE WINDOWS), FMADMA 250(BOX WINDOWS),FMA/AAMAMDMA 300(EXTERIOR DOORS) SHEET 1:25 4OF5 MIN.EMBEDMENT SUBSTRATE TYPICAL HEAD ANCHORAGE SEE TABLE 1 BY OTHERS WINDOW SYSTEMS MAX.SHIM SEE TABLE 1 MIN.EDGE DIST. SUBSTRATE MIN.EDGE DIST. OCA A, LTH AVE. SEE TABLE 1 SEE TABLE 1 BY OTHERS FSEE TABLE t OCALA,FLORIDA 34474 1/4'MAX.SHIM WWW.CWS.CC SUBSTRATE BY OTHERS MIN.EDGE DIST. SEE TABLE 1 SEE TABLE 1 MIN.EMBEDMENT O PERIMETER SEALANT SEE TABLE 1 6500 PVC INSTALLATION ANCHOR BYINSTALLER SEE TABLE I B DOUBLE HUNG INSIDE ANDOUTp MIN..EMBEDMENT SEALANT BEHIND L7 !]❑ SEE TABLE I. IMPACT FLANGE BYINSTALLER L-3�. ...._...:...- - - - -- .........._ Dom- r Qoe PERIMETER SEALANT o o ~ Q PERIMETER SEALANT Qeao BY INSTALLER o o ❑ BY INSTALLER INSIDE AND OUT [� INSIDE AND OUT INSTALLATION ANCHOR Y O SEE TABLE 1 W W m INSTALLATION ANCHOR SEALANT BEHIND FLANGE BY INSTALLERco SEE TABLE 1 FIN BYNT BEHIND z FIN BY INSTALLER J O 8 HORIZONTAL SECTION C HORIZONTAL SECTION 5 5 TYPICAL JAMB ANCHORAGE TYPICAL FIN ANCHORAGE a w. j HEAD AND SILL SIMILAR FOR FIN INSTALLATION o o. Z W rn O � ABP INUOUS DBL 114"BEAD OF SEALANT NOTE:ADDITIONAL THRU-FRAME ANCHORS ^ a ND PERIMETER Ca ALL INDICATED ;` u.AROUND POINTS BETWEEN FRAME AND SUBSTRATE (AS SHOWN IN DET.B/5)REO'D AT MTG RAIL. cr OINT TALLER SEE SHEET 4 ANCHOR LAYOUT. po ¢ w 0 1/4"MAX.SHIMSEAm a OFLANGE BY 14STALLE +0%T BEIHIND 10RE41r�PERIMETER SEALANThlo 58201SYINSTALLER INSIDE AND OUTSUBSTRATE BY OTHER SEE TABLE 1 z 9; STATE OF :'4& A VERTICAL SECTION :O� 5 TYPICAL SILL ANCHORAGE �i�'�'•'c� pP,:�c�+++ NO SILL ANCHORS REQUIRED O❑ �i�S O R« G+++ D z� 1211/2016 TABLE 1:APPROVED INSTALLATION FASTENERS LUCAS A.TURNER,P.E- FRAME TYPE SUBSTRATE TYPE ANCHOR TYPE MIN.EMBEDMENT MIN.EDGE DIST. FL PE#58201 FLANGE CONCRETE(2Q KSI MIN.) 3/16"ITW TAPGON 1-1/2" 1-1/8" PERIMETER SEALANT 1239 JABARA AVE. FLANGE HOLLOW OR GROUT-FILLED CMU(117 PCF MIN.) 3/16"ITW TAPCON i" 2' BY INSTALLER NORTH PORT,-1 34286 FLANGE CONCRETE 285 KSI MIN.) 3/16"ELCO ULTRACON 1" 1• INSIDE AND OUT PH.941-380-1574 1574 ( D HORIZONTAL SECTION SHEET DESCRIPTION: FLANGE GROUT-FILLED CMU(ASTM 0-90) 3/16"ELCO ULTRACON 1-3/4" 2-1/2 5 BOX FRAME INSTALLATION FLANGE 2X MIN.SOUTHERN PINE(G=0:55) 3/16"ITW TAPCON 13/8" 7/8" SIMILAR FOR HEAD AND SILL FOR BOX INSTALLATION INSTALLATION DETAILS OR ELCO ULTRACON FLANGE 2X MIN.SOUTHERN PINE(G=0.55) #10 WOOD SCREW 1-318" 7/8" FLANGE REMOVAL NOTE:PARTIALLY OR FULLY REMOVING THE FLANGE, DRAWN BY: DATE: 16 GAUGE(0.060")MIN.STEEL STUD #1016 HILTI KWIK-FLEXOR ITW FULL THREAD 7/16 UP TO AND INCLUDING A BOX-FRAME APPLICATION IS ACCEPTABLE PROVIDED: EMK 05/26/15 FLANGE (33 KSI YIELD MIN) TENS SELF-DRILLING SCREW THRU 0:060" DWG a: REv.: -MIN.1/4°FILLET OF CONSTRUCTION-GRADE ADHESIVE CAULK IS APPLIED FLANGE 1/8'ALUM.(6063-T5 MIN.)OR #10 GRADE 5 SELF-TAPPING/ FULL THREAD 7116" INSIDE AND OUT,FULL PERIMETER,BY INSTALLER. CWS-1069 B 1/8"STEEL(33 KSI MIN.) DRILLING SCREW THRU 0.125" PRODUCT ANCHORAGE IS IN ACCORDANCE WITH REQUIREMENTS AS -§GALE: SHEET FIN 2X MIN.SOUTHERN PINE(G=0.55) #10 WOOD SCREW 1-1/2"' 1/2" SHOWN FOR FLANGE WINDOWS. 1:2 5 OF 5 RW R W Building Consultants, Inc. B Consulting and Engineering Services for the Building Industry C P.O.Box 230 yalrico,FL 33595 Phone 813.659.9197 Florida Board of Professional Engineers.Certificate of Authorization No.9913 Product Evaluation Report '/ I Septeniber 26, Product Category Sub Category Manufacturer Product Name Plastpro Inc. Glazed Fiberglass Single Door Swinging Exterior 5200 W.Century Blvd. w/orwlout Sidelites :Doors Exterior Door Assemblies Los Angeles,CA 90045 Inswing i Outswing (440)969-9773 "Impact' Scope: This is a Product Evaluation report issued by.R W Building Consultants,Inc.and Lyndon F.Schmidt, P.E.(System ID.# 1998)for Plastpro:Inc.based on Rule Chapter No.61 G20-3,Method 1 D of the State of Florida Product Approval, Department of Business&Professional`Regulation. RW Building Consultants and Lyndon P.Schmidt, P.E.do not have nor will acquire financial interest in:the company manufacturing or distributing the product or in any other entity involved in the approval process of the product named herein. Limitations: 1. This product has been evaluated and is in compliance with the 6th Edition(2017)Florida Building Code(FBC)structural requirements excluding the"High Velocity Hurricane Zone". 2.•Product anchors shall be as listed and spaced as shown on details.Anchor embedment to base material shall be beyond wall dressing orstucco.. 3.When used in areas requiring wind borne debrisprotection.this product'complies with FB.C:Sections1609.1.2&R,301.2.12 and does not require an impact resistant covering.This.product meets missile level"13"and includes Wind Zone 4 as defined'rn.ASTM E1996 and FBC Sections 1609.1:2.2&R301.2.1:2.1 4—For stud framing construction,anchoring of these units shall be the sante as that shown for 2x buck masonry construction. 5 Site. conditions that deviate from the details of drawing FL-17184.9 require further engineering analysis by a licensed engineer or registered architect. 6: See-drawing FL-17184:9 for size and design pressure limitations. Supporting Docu/nenfs: 1. Test Report No: TestStandard Testing Laboratory Signed by TEL 01 3W243 TAS 201,202 and 203-94 Testing Evaluation Lab.,lnc. Wendell W.Haney,P.E. TEL 01390365 TAS 201,202 and 203-94 Testing.Evaluation Lab.,lnc. Lyndon F.Schmidt,P.E. 2. Miami Dade NOA Materials Testing 11-0112.04 Saflex®PVB Interlayers(Eastman Chemical Company) 3. Drawinn.No. Prepared by Signed&Sealed bV No.FL-17184.9 RW Building Consultants,Inc.(CA#9813) aenaelir Lyndon F.Schmidt,P.E. 4. Calculations Prepared by ®� a g(�•., l ego Signed&Sealed by a1 Anchoring RW Building Consultants, Inc.(CA#9813) e®� �;>�\G E S °° --�yndon F.Schmidt,P.E. ® a 'e 5. Quality Assurance � No 43409a Certificate of Participation issued by National Accreditation and m Management institute,certifying that Plastpro Inc.is man ufacturing.product 0 0 0 Within a quality assurance program that complies with ISO/IEC 17020 and STAT OF v� Guide 53. ®{ a% k Lyndon F.Schmidt,P.E. L p R tm°°{yti � FL PE No.43409 10/10/2017 Sheet 1 of 1 p°° `�S'a &tI ��`0 t c' plastpro z . :O` � o a 5200 W. CENTURY BLVD'. �,�>•... 'S`' o LOS ANGELES, CA 90045 �''������ P �`�' o n.z S UN•- � a o eZg n C z A a co 9 cw GLAZED FIBERGLASS SINGLE DOOR Na m a a 115.p"MAX.OVERALL FRAME WIDTH x W/ or W/ovt SIDELITES 37-TMAX. 37.25"MAX. OVERALL ' v°au " INSWING/OUTSWING FRAME WIDTH FRAME WIDTH oa o "IMPACT" x �Z Zoo z� GENERAL NOTES 0 1. This product has been evaluated and is in compliance with the 6th Edition J NEn (2017)Florida Building Code(FBC)structural requirements excluding the z p e X am "High Velocity Hurricane Zone"(HVHZ). >_ > o �I o a 0 !E LL13 2. Product anchors shall be as listed and spaced as shown on details.Anchor ~ g embedment to base material shall be beyond wall_dressing or stucco. 1 1 OX � 3. When used in areas requiring wind borne debris protection this product compries with FBC Sections 1609.1.2&R301.2.1.2 and does not require an o impact resistant covering.This product meets missile level"D"and includes OXO Wind Zone 4 as defined in ASTM E1996 and FBC Sections 1609.1.22& x o a R301.21.2.1. R R N a z 4. For 2x stud framing construction;anchoring of these units shall be the same w o as that shown for 2x buck masonry construction. N � 5. Site conditions that deviate from the details of this drawing require further XO o 0 engineering analysis by a licensed engineer or registered architect. W DESIGN PRESSURE(PSI) DESIGN PRESSURE(PSF) TABLE OF CONTENTS MAX. MAX.SIDELITE a SNEEip DESCRIPTION INSWING OUTSWING CONFIGURATION FRAME D.L.O. "r a 1 Typical elevations,design pressures&general notes DIMENSION DIMENSION POSITIVE NEGATIVE POSITIVE NEGATIVE "<o z 2 Door panel details +50.0 -50.0. E 3 Sidefte panel details and glazing detail X 37 5"X 82.0" N/A +50.0 -50.0' "—z oa :02/29/12 z z 4 Elevations , sr� N.T.S. E 5 Horizontal cross sections OX/XO 76.25"X 82.0" 20:5"X 62.75' +50.0 -50.0 +50.0 -50.0 6 Vertical cross sections Mr.W. JK m' 7 Vertical cross sections CHK er: LFS 3 g Buck anchoring OXO 115.0"X 82.0" 20.5'X 62.75" +50.0 -50.0 +50.0 -50.0 S 9 Frame anchoring nawwc Ho.: N 10 Bal of materials and components FL-17184.9 ° J - Sr{FET OF 10 N .40" G1 • ',,�� }--1.00 EXTERIOR T0(1 � A7. a ! r m 7�: 00 >•'• may.` >>m to INTERIOR (OM} r`1.58 ,''4��ttt*tttl `` o n m z° HINGE STILE LOCK BLOCK(WOOD) Cellular PVC STILEREINFORCEMENT v o i q (LVL) STILE REINFORCEMENT(LVL) Ec W 9 m w cs ; o::::: i4 gyg 5oz° A .,,..,;ARL;;j;3;;;;;�i�:ri;;ii;;;>:;;?;:??';;;f: Ch NAR W kEGH. LATCH STILE a m a a 120 1 HORIZONTAL CROSS SECTION Cellular PVC a ^ 2 * vZ T FOAM COREt ::: t• (POLYURETHANE- c311.LOCK. SIGNAIURESERIBDEADBOLT: SIGNATURE SERIFS(760) STRUCTURAL SILICINE(DOW 995) 1.9 PCF MIN.) LOCK YHCOLLECTION 5/8"GLASS BRE DEADBOLT: YHCOLLECTION(80SERM) En NON STRUCTURAL SEALANT pR,KNOB: 'FSERIES(FLO) T"OVERALL GLASS THK, d00DEADBOLT' B'SERIB(B60/62) . 1/8'ANNEALED GLASSo� W 35.7S'DOOR z 24.27MAX. 0.090'SAFLE0PVB m 4� o" WIDTHINTERLAYERWIDTH INTERLAYERwm cs 2 20.5'MAX_ 1/8"ANNEALED GLASS EL co a m Z D,LO.WIDTH AIR SPACE ) 0 y 1/8"TEMPERED GLASS GI Y a a #7-19 X 1-3/4"PIH ALUMINUM SPACER fl�I SELF DRILLING SMS 3A INT. INTERIOR EXTERIOR m NON STRUCTURAL SEALANT $ / w t=9 G1 GLAZING DETAIL m x w nv g4 w = 00 d t3 z C7 •S 1 X �O N e � C4n 0.063" TiBERGLASSSKIN n F F (0.07S'THICK) NN¢ J BOTTOM RAIL nod = SEEHARDWARETABLE (COMP.) z n a (TYP-) 6+�02121112 z_° w ODL LITE FRAME 3A (ONOLntLTE FRAA6E seauE M.T.S. 5 sD awe.BY: JK m e CHK.er. LFS 3 s d0 DOOR PANEL 21�VER-TICAL CROSS SECTION mwm �. FT--17184.9 0 d - SHM 2 OF 10 N R:\Ctlents\Plastow Inc PERMANE -Florida Pmduct A rovals FL•17184 Flber lass Door-Ins ln-outswln OHI\C-Drawln s -17189 6TH ED 7A37 FL-17184.9.10,dw 1-3 79Z'OA HEIGHT z rno = c z W�+ �� nm 1.75' � a 1.58° w cn - o N-1 0 - wta o Q v� 66.35 MAX.O.A.FRAME HEIGHT� O y 62.63"MAX.D.L.O.HEIGHT I x 0 m 1 [ 5.7S' rn �EIpj T1.0 MAX z n O.C. z c 279" c � Z a O c —1.76"—� z cn in z O m 0 0i z` a z o ty yea _L v O wz 3 v N � o � A z Yzfazz nn m m 3 m m ZY iv b m O GI 0 ZZ m ,"rt 4 wIa z T 0 ' r Z m m 0 m 1 _L 1.20" � 3.20" .�� �!'`Vie@'••�` '�. j y No.43409 /O•la.rl r Y $ `E 4 PRODUCT; Occumanta Pmp.md By1, r " PLASTPRO INC. tynaon F. Sehmtdt '�� ••'• �I?1, �• IW N FIBERGLASS DOOR P.E. No. 43408 'fi`,S�S/p�AL �� v z N -772-4/1-7— hrtrrlf►ttt�N y T UPDATE TO 8TH ED. 2617 FBC JK PART OR ASSEMBLY: BUILDING CONSULTANTS, INC. ( .mp ;,z 0 _ f 04 22 15 UPDATE TO STH ED. 2014 FVC JK P.O. Box 230, Vatrlco. FL 33595 I� M NO DATE BY SIDELITE PANEL DETAILS phone No.: e13.859.9197 R 1510 S AND GLAZING DETAIL FSPE C.A. No. 9813 02012 R.W.BUILDma ODNsULTANTe IND. R:\Clients\Plastpro,Inc PERMANENT\A-Florida Product Approvals\FL-17184 Fiberglass Door-Inswing-Cutswing(BHI)\C-Drawings\FL-17184 6TH ED(2017)\FL-17184.9.10.dwg,14 N� � D P W Z X P A P N d P th N N P P to A d V� m V W O V N V A N 0 Z V N Q4 t1 0 P A Q P N P N lA w P P N A Q V� V A N D- -4 N Oaf m rr� OP W P r Z P A P N 0 Q P N 4Ca) P P O N0.43409 . /aro., ylr fr' $ - PRODUCT: Dooumente Propared By:�� PLASTPRO INC. Lyndon F. Sehmlot ��i\• FlOR19� FlBERGLASS DOOR P.E. No. 43409 'rissYpfyAl. ��`� V o Z N ��//1111111` —i---772-471-7—UPDATE TO 6TH ED. 2017 FBC JK PART OR ASSEMBLY: BUILDING CONSULTANTS, INC. l � E,~is\ 1 04/22/15 UPDATE TO 5TH ED. (2014) FBC JK tJ li'I/1/ P.O. Box 230, VDlrioo, FL 33595 a U ro NO DATE BY ELEVATIONS YYYVVV Phone No.: 813.659.9197 REVISIONS FBPE C.A. No. 9813 ®201D R.W.BUILDING CDN3UI-NTS INC. 1-1/4"MIN. ..* � ) EMB. P. E 60 9 11 K ` EXTERIOR a ty EXTERIOR 27 s�;7 z Co 00M U IF)••Z e v e ' o °Za sora K SEE NOTE 1 a m a a 9 o F INTERIOR INTERIOR 8 o 3 a40 (� 7 1 21 20 "3 8 0.15' L m C D 1 1 4"MIN. C SINK o / A z e e15' 21 20 EMB.(TYP.) 21 20 (TYP.) C ?o a� -C-SINK 1-1/4"MIN. on zw L (TYP.) EMB.(TYP.) a 3 m o c' a E B C 4 HORIZONTAL CROSS SECTION rS1 HORIZONTAL CROSS SECTION (n N Q: 5 Outswing shown-inswing also approved 5 Outswing shown-inswing also approved Shownw/1X sub-buck 4 0 1 HORIZONTAL CROSS SECTION 5 Outswing shown-inswing also approved o a a a O Y Yc- 3 NOTE: ''m 1.Spacing for item K:6"from ends t 1 88 and 6 more equally spaced along EXTERIOR 88 M 27 EXTERIOR 9 K SEE NOTE 1 m o sidelite(8 total). 10 K SEE NOTE 1 K 1 Z _N 4 i iO o Z 0 U a a zg° �� 5 '0 40 7 LL ^ 2 INTERIOR 7 INTERIOR 8 8 onre 02/21/12 s z 21 ZO L 21 20 scAm, N. S. L owc.BY. JK m 2 HORIZONTAL CROSS SECTION 3 HORIZONTAL CROSS SECTION CHK.N1 Fs 3 a 5 Outswinq shown-inswing also approved �5J Outswing shown-inswing also approved cwwNG No: N Shown with 2X reinforcement Shown with 2X reinforcement FL-17184.9 0 SHEET 5 cF 10 n 17 a R:\Ur lents\Plastpro,Inc PERMANENT\A-Rodda Product Approvals\FL-17184 Fiberglass Door-Inming-Outswing(BHI)\C-Drawings\FL-17184 6TH ED(2017)\FL-17189.9-10.dwg,1.6 m A m ° e T iZO7 � n ga O Q 0 n ° .°� O m .N A y 7 ZD m OD V OQ a 02 O , '0 70 ° P 0.15' ° C'INK °p 1-114"MIN. (TYP.) EMB.(TYP.) m m 1-1/4"MIN. EMB.(TYP.) m a ° Z m Z as a. aN m IA �•G O SO ° T O 7 ►� °p 0r- y 6 A n > o Z rn o . A a �+ m O 1-1/4"MIN. a EMB.(TYP.) ° 1-1 EMB.(TYP.) 1-114"MIN. EMB.(TYP.) ^r m ° 0 D p. W 70 � A N �G �0T d. 0 m � a o X�r v0 g � a �n ter" 10� 0C) ° uyi 0 Z m 0 y ° 22 • `tt111111177 Cmj < A a ���� SCHCD M�� i N No,43409 ' r'r o � 1-114" EMB.(TYP.) .� Q PRODUCT: Documents PrcPored 9y: ' �DRID��•:` ``� ' PLASTPRO INC. Lyndon F. Schmidt I N FIBERGLASS DOOR P.E. No. 43409 IO1 v$ Z m ��111111f11t�� o r- L y -N.• --Y-71-2-4 17 UPDATE.70 BTH ED. 2017 FBC JK PART OR ASSEMBLY: J V BUILDING CONSULTANTS. INC. I -N y 7 04 22 15 UPDATE i0 5TH ED. 2014 FBC JK VERTICAL CROSS SECTIONS VV P.O. Box 230, Valrico, FL 33595 O io N NO DATE BY Phone No.: 813.859.9197 REVISIONS FBPE C.A. No. 9813 ®201 2 R.W.13Ul—IQ32C[1123BLMAI.mel:.....N6.—.To I... R:\dlents\Plastpro,Inc PERMANENT\A-Florida Product Approvals\FL-17184 Fiberglass Door-Inswing•Outswing(BHP\C-Drawings\FL-17164 6TH ED(2017AFL-17184.9-10.dwg,1-7 m •o -i Fn • o 70 m z0 0. m 0 VW �c"a V� m rn 0-1 A 7t ° ° m ° . 0 Qr O n 0 N N 'a m p T m O < O z 0 oQ m < z 0 v° z O o °4 a o a . a � a n 0,15' a. . C'SINK 1-1/4"MIN. (TYp•) c ° . EMB.(TYP.) n 1-1/44'MIN. ° EMB.(TYP.) 1-1/4"MIN. EMB.(TYP.) • 'fi D ° C4 • 0 N Z O V A m O Z 0(0 O 7 O a 0 �n2hCD3 0 W�` �n o ' 01 CA 3 o N p ry77 .� 0 S a (p Q a rn z • n rn N m o a 0a FA 0 m 70 V 70 oo a T p 0 T v r o p O a < 6�O V w C O� � o v :3 v Z o < •,v O N y o m N m A Q o 0 0 A 1-1/4"MIN. z EMB."P.) 1-1/4'"MIN. L No.43409 ' EMB.(TYP.) Aeoy T z F Q PRODUCT: Document.Praperad By— PLASTPRO INC. Lyndon F. Schmidt ��j�•' �ORID��.•' O P.E. No. 43409 Ii ss••" �� IV I o \ FIBERGLASS DOOR Z ry �7� !11111 o ` y 2 7 24 17 UPDATE TO 6TH ED. (2017) FBC JK PART OR ASSEMBLY: �/[ BUILDING CONSULTANTS, INC. 1 07124117 4 22 15 UPDATE 70 5TH ED. (2014 FBC JK VERTICAL d l�1/j/ P•O. Box 230, Wrlco, FL 33595 to to ro N0. DATE I REVISIONS BY CROSS SECTIONS FBPE C.APhone : 81 95539197 ®2012 R.W.8UILDI4''D20O9SRL%KN!r8ILGWG DONBULTANT9 INC. Q.. z Fc`fp dm UN•• G 4" 4" l� > o ° z'sZa }- A" 8" (IYP} a �w 00,a m'n a 1 -- It II ti w a II � II II if D QQ MASONRY 7 TYP.HEAD TYP-HERD II II 31 &JAMBS I I 31 TYP.HEAD cio z OPENING &JAMBS MASONRY III MASONRY I I I I &JAMBS zo OPENING 2X REINFORCEMENT-1"1: OPENING (� A( a� SHOWN FOR REF. I I 2X REINFORCEMENT- o SHOWN FOR REF. w 2X BUCK ONLY I I ONLY a " cxi 2X BUCK---\ t 2X BUCK !2m '4r I —ci v, � II II �' ao m II II II 1i ° 11 13 o a o ��•.: I I t�. I I I I fP N N BUCK ANCHORINGBUCK ANCHORING BUCKANCHORING d o $ x OX/x0 Oxo �t? R CONCRETEANCHOR NOTES: 0 0 T.Concrete anchorlocations at the comers may be a4usted to maintain the min. a edge distance to mortar joints. Z 8 2.Concrete onchorlocollons noted as MAX.ON CENTER"must be adjusted to 'F maintain the min.edge distance to mortar MX joints,additional concrete anchors w Z may be required to ensure the AON CENTER"dimension are not exceeded. N o 3.Cancreteanchortab(& 0 4NGHOR ANCHOR j4TfAF M!N CLEARANCE,1p11N CLA!#ANC N o O ,,, TON1ASt7NRY 1'OA4IACEttT', z a TYPE S1zE J nA6EDMf tf EDC+E ANCHbR; t IMM'02/21/12ITW ° z TAPCON® 1/4" 1.1/4" 4" 4" smE* N.T.S. ° JK S ELCO •UY: m ULTRACON 1/4" 1-1/4" 1" 4" cwc BY.. LFS 3 WOOD SCREW INSTALLATION NOIES: utuwnc wo.: -Maintain a min mum 518"edge distance,1"end dktonce,&I"o.c.spacing of FL-17184.9 N wood screws to prevent the spGMing of wood. a P SHEEt 8 OF� stA 3 z �j.• q�:z a ro a� 6„ } 3"(TYP.) 3"(TYP.) �'i� fi�� } 7 {iYP) tit"t * tt�' z a..o �' Fri ",flits 1\ 0 N ti — 6"(iYP.) I —4 6�-) v n 4 £ Z m Z U �.. m4 ii Eta o °c w - �a y g M a. " � v m a.a c - L 2X BUCK - e2XBUUaCK ; v MASONRY--7. i4 0 re OPENING I IX BUCK MASONRY -O `' `a MASONRY-7 2X BUCK n �a a TYP.HEAD OPENING Tt'P @ OPENING J 1XBUCK L TYP. `4 FRAME - &JAMBS FRAME HEAD FRAME TYP.0 HEAD ANDJAM - _ JAMBS n cio z �� O 2X BUCK or r x —TYP.N SILL — TYP.C�SRL L V TYP.@SILL TYP.@ SILL 2X BUCK rLL O 2XBUCK FF P. N �o D D F a ffi s — _ o� ~ S FRAME ANCHORING l FRAME ANCHORING FRAME ANCHORING X XX OXO 0 F F z a Q to o�N CONCAElEANCHOR LADIES: 1.Concrete anchor locations at the comers may be adjusted to maintain the min. o q edge distance to mortarjoints. 2.Concrete anchor locotions noted as"MAX.ON CEMER"must be adjusted to Z maintainlhemtn.edgedistancetomortarjoints,additionalconcreteanchors G 1XBUCK 1XBUCK H ^^ F „ may be required to ensure the AJAX ON CENTER"dimension ore not exceeded. *- 9 3 Concrete anchor table 28 M 2X BUCK 2X BUCK K AWCHOR ANCHOR M111N MtH CtEA.... MIN ctEARAN�E ( n v m TYPESIZE J:htl}E`OMEtJT MASOt�'RY 7O ADJACENT- 1 O O >:Dc>::... aAlvtttOA 27 11 M DAM 02/21/12 i Itue 713" tats• r s n TAPCON N.T S. SCJ¢E: ELCO ® t/4" 1-114° 1" 4" eWG.BY: .£ir. m S utTlwcoN HINGE DEWE ITw ® 3116" 73/4• 3' 1-71r LATCH&DEADSOLTDEWL 2X Buck CHV.sr: LFS 3 TAPCON aRAYANc tr0.: ¢ WOOD SCREW INSTAUAIION NOTES: N yt I.Malntdnamintmum5te•edgadatance.l,enddtstance,&I-accspadagof STRIKE JAMB HINGE FL-17184.9 woad straws to prevent fhosplitting of wood. sHEHr 9 of i 0 N 4.56" BILL OF MATERIALS .o REM 4 DESCRIPTION MATERIALEoa�, A 1X BUCK(SG>=0.42) WOOD ;7 i B 2X BUCK(SG>=0.42) WOOD I V"• 'ti C 1/4"MAX.SHIMSPACE _ I--2.36" 27'A ��ii� '•• :45��� >mm D 1/4"X 2-3/4"ELCO OR ITW CONCRETE SCREW STEEL i���i''' * ��``�` o 0 m z° HEAD&SIDE Lltll ��� U N-: E MASONRY-3,000 PSI MIN.CONCRETE CONFORMING TO ACI CONCRETE 20 .Iamb �a o =z 4 301 OR HOLLOW BLOCK CONFORMING TO ASTM C90 F1114'X2-114'PFH ELCO OR ffW CONCRETE SCREW STEEL $ a E m 9 m o° F»------4.56" n a ` a N°a j p t a G 3/16"X 3.1/4"PFH ITW CONCRETE SCREW STEEL ! I o (-- "} m d a L o I H 114'x 3-1/4"PFH ELCO OR ITW CONCRETE SCREW STEEL I �` ' S .. -}— � . J 1/4"X 3-3/4"PFH ELCO OR ITW CONCRETE SCREW STEEL ry L Z K #9 X 2-1/7'PFH WOOD SCREW STEEL - 0 a L #10 X 2-1/7'PFH WOOD SCREW(1.15'MIN.EMBEDMENT) STEEL II Ell M #8 X 7'PFH WOOD SCREW STEEL h--2.44" - -h--213" w N 1/4"X 1-3/4"PFH ELCO OR ITW CONCRETE SCREW STEEL SIDEL1IE SPACER 7 FORCE 5 WEATHERSTRIP(ENDURA) FOAM 21 HEAD d SIDE 29 BSIB �o QE 8 COMPRESSION WEATHERSTRIP QLON 650(SCHLEGEL) FOAM Paly fiberjamb 30 m STEEL Wz 9 4'X 4"BUTT HINGE 10 #9 X 1"PFH WOOD SCREW STEEL w o� 11 #9 X 3/4"PFH WOOD SCREW STEEL 20 FINGER JOINTED PINE FRAME,HEAD&HINGE JAMBS WOOD4.56" 4.56" i5 am COMP./VINYL -{ l o m s 21 POLY FIBER JAMB I 27 LATCH STRIKE PLATE STEEL a 28 DEADBOLT STRIKE PLATE STEEL a a 29 SIDELITE SPACER(ISSLB) PVC 'sMoA!ff:1 m 30 DOOR SWEEP PVC A 31 OUTSWING THRESHOLD BY DLP(QOSH) ALUM./WOOD 00 a 32 ADA THRESHOLD BY DLP(ISHC) ALUM. �In 33 INSWING THRESHOLD BY DLP(ISCS) ALUM./WOOD 31 Q�HwtNG THRESHOLD INSWING THRESHOLD n o BCS 34 SIDELffE THRESHOLD BY DLP(ISH/EIS) ALUM./WOOD z 35 TRIM WOOD W g 36 OUTSWING ADA BUMP THRESHOLD ALUM. fn 40 DOOR PANEL-SEE DOOR PANEL DETAIL SHEET FOR CONSTRUCTION DETAIIS Ej 60 SIDELITE PANEL-SEE SIDELITE PANEL DETAIL SHEET FOR CONSTRUCTION DETAILS - (-- 4.6T { " Q o 88 2X REINFORCEMENT(CLEAR PINE:SG>=0.49) WOOD I I a z 32 ADA SILL uj $ BHC N N 9SIDELIIE THRESHOLD ^ _ r` o r BHI BS '-z v o DAM 02121112 i SCALE N.T.S. ° owc.BY. X m' S a+K.BY. LFS 3 OUISW'NG ADA BUMP THRESHOLD Dtaw xG NO.: a �J OSHC FL-17184.9 " a n mimr LO of10 w uL URNER 1239 Jabara Ave. North Port,FL 34288 ENGINEERING & Ph. 941-380-1574 TCONSULTING, INC. FBPE C.O.A. #29779 Evaluation Report 491C September 7, 2017 Product Description: Series 8100 PVC Single Hung Window, Large Missile Impact, Continuous Head and Sill, twin configuration with integral mullion, 74 1/8" x 72" unit size (36 3/8" max. single unit width), 75 3/8" x 73 1/4"flange size, with 1/8 (Ann or Temp)—Air— 1/8-.090PVB-1/8 glass Manufacturer: Custom Window Systems, Inc. 1900 SW 44th Ave, Ocala, FL 34474 Statement of Compliance: This report evaluates the above-listed product per the requirements of FAC Product Approval Rule Chapter 61 G20-3.005 (4). This product complies with the requirements of the 6th Edition (2017) Florida Building Code including the High Velocity Hurricane Zone. The product testing standards performed are outlined below. Technical Documentation: 1) This report,prepared by Lucas A. Turner, P.E., at 1239 Jabara Ave.,North Port, FL 2) Approval drawing CWS-491C, signed and sealed by Lucas A. Turner, P.E. 3) Test Report NCTL-210-3621-1, -lA, -2, -2A,National Certified Testing Laboratories, Orlando, FL, signed and sealed by Gerard J. Ferrara, P.E. a. Testing Performed: TAS 201/202/203 1994, including impact at midspan of integral mullion. AAMA/WDMA/CSA 101/I.S.2/A440-05. ASTM E1886/1996- 05, including impact at midspan of integral mullion 4) Supplemental Calculations to support CWS-491 C, signed and sealed by Lucas A. Turner, P.E. Installation: Units must be installed according to approval document CWS-491C. Limitations of Use: This product: • May be used in twin unit configuration O/X— integral mullion—O/X with continuous head and sill in sizes up to 74 1/8" x 72" unit size (36 3/8" max. single unit width), 75 3/8"x 73 1/4" flange size, with max. glass daylight heights of 31 15/16" on the fixed panel and 32" on the sash • Achieves a max. design pressure of+67.5/-67.5 psf • Is impact resistant and does not require the use of shutters • May be used in the High Velocity Hurricane Zone • Requires 1/8 outboard(Annealed or Tempered, Tempered required above 30 ft in HVHZ) —Air— 1/8Ann-.090PVB-1/8Ann glass minimum RE Lucas Page 1 of 2 * * 9/07/2017 Turner : Lucas A. Turner P.E. 2017-09-16 ' STATE OF ,:W; ' �, , ;•,, � �,•.• +,� FL PE#58201 09:27+20:00 '�•,, • ..o .. ►'C'."N Limitations of Use, cont'd: • Requires Kuraray(Dupont) PVB Interlayer per Miami-Dade NOA 16-1117.021 • Requires Quanex(Mikron)white rigid PVC framing per Miami-Dade NOA 17-0206.101 1 I have evaluated the interlayer and framing materials in these Kuraray(Dupont) and Quanex(Mikron)NOAs and find that they comply with the requirements of the 6t'Ed. (2017) Florida Building Code for use in this product. Certification of Independence: I do not have, nor do I intend to acquire, nor will I acquire, a financial interest in Custom Window Systems or in any company manufacturing or distributing products for which this report is being issued. I do not have, nor do I intend to acquire, nor will I acquire, a financial interest in any other entity involved in the testing or approval process of this product. Page 2 of 2 9/07/2017 Lucas A. Turner, P.E. FL PE#58201 r ' SINGLE HUNG - LARGE MISSILE IMPACT GENERAL NOTES- 1. OTES 1.THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED YINDOY SY5T@@RS TO COMPLY WITH THE FLORIDA BUILDING CODE(FBC),CURRENT 1g00 SW 44TH AVE. 75 3/8" MAX FLANGE WIDTH EDITION INCLUDING THE HIGH VELOCITY HURRICANE ZONE(HVHZ)AND OCALA,FLORIDA 34474 IS RATED FOR WIND ZONE 4 MISSILE LEVEL D IMPACT USE AS DEFINED VvjW.CWS.CC 741/8"MAX UNIT WIDTH IN ASTM E 1996 PER THE FBC. 36318.MAX SINGLE UNIT WIDTH 2.GLAZING OPTIONS:(SEE SHEET 2) m0 PVC 32 3/m- --- /16"--- GLASS DLO -- - -A-- -- 3.CONFIGURATIONS:"O/X-O/X'. SINGLE HUNG 4.DESIGN PRESSURE RATING: IMPACT 731/41, -NEGATIVE DESIGN LOADS BASED ON,TESTED PRESSURE AND MAX -- __ _ I f GLASS TABLES ASTM E-1300-04e01/09. z FLANGE f `` I - -POSITIVE DESIGN LOADS BASED ON,TESTED PRESSURE,WATER ¢ '� W O p HEIGHT f f INFILTRATION TEST PRESSURE AND GLASS TABLES Z W W 0 'Q 2 F f ASTM E-1300-04e01/09. w z 0 z -- m 3115/16" B f r] ,=N-7-0a�^o 5 + f 5.ANCHORAGE:THE 331/3%STRESS INCREASE HAS NOT BEEN USED E P w Z`F'3 O GLASS DLO f f B IN THE DESIGN OF THIS PRODUCT.SEE SHEET 6 FOR ANCHOR O O I=-O d<T O a i DETAILS. WINDLOAD DURATION FACTOR Cd=1.6 WAS USED FOR WOOD 0 U cn N z Z t_(� f I f ANCHOR CALCULATIONS. Z p Z V Uj z-_30- 72" f 4 '- '� OwZ UNITMAX f 6.PRODUCT APPROVED FOR IMPACT RESISTANCE. SHUTTERS ARE ¢',O w-r O- HEIGHT f f NOT REQUIRED, THE IMPACT ROTARY LOCKS ARE INTENDED TO BE 4 " N 0`��0 f LEFT UNLATCHED DURING NORMAL OPERATION OF THIS PRODUCT, j j O o M y o w-rw f BUT MUST BE ENGAGED PRIOR TO EXPOSURE TO HURRICANE WINDS w O-�_cn t 0 uj CL W AND FLYING DEBRIS. 0 t I I 7.ALL FRAMES AND VENTS FULLY WELDED,SMALL JOINT SEAM SEALANT a r a a f USED AT FIXED MEETING RAIL,INTERNAL MULL ENDS AND JAMBS. �'0141*1110 t f 6 8.SERIES 1 MODEL DESIGNATION SH-8100 CONTINUOUS FRAME. +`sllPN�R ..;•Tfi� GLASS DLO ! /\ 1/ g 9.THE DESIGNATION XAND O STAND FOR THE FOLLOWING: :`.J�,•'• Na, rs$2p9 `""r, D 355/16 X18 X=OPERABLE SASH,O=FIXED SASH # SASH 10,SECTION CALLOUTS APPLY TO ALL ELEVATIONS IN A SIMILAR f t HEIGHT LOCATION. ; I, STATE OF •"ta 4 C j 11.EXTERNAL WEEP SLOT=1/4"x 1-114"LOCATED 4"FROM BOTH ENDS. it %�`*'` C A- _ A �— LucasTurne GLASS DLO 12_15/16" r 9/22(2017 MAX SASH WIDTH 2017-09-22 12:52-04:00 LUCAS PE TURNER, P 1239 JA13ARA A%f% NORTH H. 9411380-1574 SHEET DESCRIPTION: A TABLE OF CONTENTS GENERAL NOTESELEVATIONS NERAL NOTES&ELEVATIONS LOCATION MAX. UNIT SIZE DESIGN PRESSURE D'�""'"�` AYE, ��-- 4ZING DETAIL.................................2 ADE 101'✓Q j0 'TIONVIEWS.................................3 RATING IMPACT RATING �: � 'RUSIONS&B.O.M........................4 NON-HVHZ Dw� .HDR SCHEDULE&NOTES.........5 74-118"x 72" �-65 PSF CWS-491 sN�>� TALLATIONDETAlLS....................6 HVHZ LARGE MISSILE IMPACT +t-67.5 PSF SCALE: O ______.—----------. i i SINGLE HUNG - LARGE MISSILE IMPACT GENERAL NOTES: Com ' 1.THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED WINDOW SYSTEMS TO COMPLY WITH THE FLORIDA BUILDING CODE(FBC),CURRENT 1800 SW 44TH AVE. EDITION INCLUDING THE HIGH VELOCITY HURRICANE ZONE(HVHZ)AND 1900 S FLORIDA E. 75 318"MAX FLANGE WIDTH IS RATED FOR WIND ZONE 4 MISSILE LEVEL D IMPACT USE AS DEFINED OCAWWW CFLORI 34474 IN ASTM E 1996 PER THE FBC. 741/8"MAX UNIT WIDTH 2.GLAZING OPTIONS:(SEE SHEET 2) 36 318"MAX SINGLE UNIT WIDTH 8100 PVC 323116. 3.CONFIGURATIONS:"O/X-ODC. SINGLE HUNG A GLASS DLO 4.DESIGN PRESSURE RATING: IMPACT —————————— ——— ———— ——— -NEGATIVE DESIGN LOADS BASED ON,TESTED PRESSURE AND GLASS TABLES ASTM E-1300-04e01/09. -POSITIVE DESIGN LOADS BASED ON,TESTED PRESSURE,WATER Q z ¢Z MAX I ASTM INFILTRATION3 0-04e0�pgRESSURE AND GLASS TABLES Z w w 0 ¢ Z w FLANGE w Z O z D_——1= HEIGHT O aco�}OD=�m B 5.ANCHORAGE:THE 331/3%STRESS INCREASE HAS NOT BEEN USED LL F-w z��2_ 31 15116" O O B IN THE DESIGN OF THIS PRODUCT.SEE SHEET 6 FOR ANCHOR O O X. O¢<:r w O O DETAILS. WINDLOAD DURATION FACTOR Cd=1.6 WAS USED FOR WOOD O U O 0 ci D. �a GLASS DLO I ANCHOR CALCULATIONS. Z O O O?z j U U) 6.PRODUCT APPROVED FOR IMPACT RESISTANCE. SHUTTERS ARE ¢ I z LL�O O LL z 72^ NOT REQUIRED. THE IMPACT ROTARY LOCKS ARE INTENDED TO BE O I.-F-!Z Z MAX I LEFT UNLATCHED DURING NORMAL OPERATION OF THIS PRODUCT, F It Y �O UNIT BUT MUST BE ENGAGED PRIOR TO EXPOSURE TO HURRICANE WINDS w OLL o�U)o w(D w HEIGHT AND FLYING DEBRIS. as z 2 a �p ai K =~ w 3 w I � 7.ALL FRAMES AND VENTS FULLY WELDED.SMALL JOINT SEAM SEALANT o_ F a. � D. USED AT FIXED MEETING RAIL,INTERNAL MULL ENDS AND JAMBS. B llllauungr 6 8.SERIES/MODEL DESIGNATION SH-0100 CONTINUOUS FRAME. 1,11 PtjOREW TCi�y� C .� �'•''GfN 9.THE DESIGNATION XAND 0 STAND FOR THE FOLLOWING: ��Jtg �t `SF"'�L� 6 X=OPERABLE SASH,0=FIXED SASH Z,:. No 58201 3 GLASS DLO I i 6 SO� 10 .SECTION CALLOUTS APPLY TO ALL ELEVATIONS IN A SIMILAR ASH HEIGHT LOCATION. tv STATE OF A %O"" I I 11.EXTERNAL WEEP SLOT=1/4"x 1-1/4"LOCATED 4"FROM BOTH ENDS. LI C I lJ , � 00L c �rrS`�dNA A LucasTurne 29V8" 32 15116" GLASS DLO _ MAXSASH WIDTH 2017-09-22 9/22/2017 12:52-04:00 LUCAS A.TURNER,P.E. FL PE#58201 1239 JABARA AVE. NORTH PORT,FL 34288 PH.941-380-1574 SHEET DESCRIPTION: GENERAL NOTES AND ELEVATIONS TABLE OF CONTENTS DESIGN PRESSURE DRAwNSY: DATE: GENERAL NOTES&ELEVATIONS.....1 LOCATION MAX. UNIT SIZE RATING IMPACT RATING ADE 10/30/09 GLAZING DETAIL.................................2DWG#- REV.: -SECTION VIEWS.................................3 NON-HVHZ +/-65 PSF CWS-491 C EXTRUSIONS&B.O.M........................4 74-1/8"x 72" LARGE MISSILE IMPACT ANCHOR SCHEDULE&NOTES.........5 HVHZ +/-67.5 PSF SOS' SHEET INSTALLATION DETAILS....................6 1 1 1 OF 6 WiNCiOYV SYSTEMS 1900 SW 44TH AVE. OCALA,FLORIDA 34474 WWW.CWS.CC 8100 PVC SINGLE HUNG IMPACT 7/8"OVERALL INSULATED GLASS 7/8"OVERALL INSULATED GLASS 1/8"ANNEALED OR TEMPERED 1/8"ANNEALED OR TEMPERED Z W J 0 ¢W o w W ZOZ O_=z= 7/16"AIRSPACE 7/16"AIRSPACE O C to�}O��m 5/16"LAMINATED GLASS 5116"LAMINATED GLASS Z Z 2 Z�W O= O O 0F-0ci<M. w 1/8"ANNEALED 1/8^ANNEALED U U N F-Z D-F to D_ O Z— -?I-7tn .090 PVB INTERLAYER BY DUPONT .090 PVB INTERLAYER BY DUPONT Z 000 U U Z O U— LL 1/8"ANNEALED 1/8"ANNEALED � Q O W O O Z Z QUANEX DURASEAL IGSSEX RURASEAL F- O Q }_ O IG SPACER w z U W U O_j u H 33 PURFECT GLAZE"H"OR SIKAFLEX 552 33 PURFECT GLAZE"H"OR SIKAFLEX 552 d Z=O_ 0_O-O CL _~CL D. I 'D- x D 14 1/2"GLASS BITE 14 112"GLASS BITE 9 9 ,e���`" CREW�f i��� .-to E IV S�,UyQ��� t No 58201 ,�p 7 10 O Z-A% STATE OF 'VJ O A,� li SASH LITE $oil FIXED LITE 9/22/2017 LUCAS A.TURNER,P.E. FL PE#58201 1239 JABARA AVE. NORTH PORT,FL 34288 PH.941-38G-1574 SHEET DESCRIPTION: GLAZING DETAIL DRAWN BY: DATE: ADE 10/30/09 DWG IF: REV.: SETTING BLOCKS PER FBC 2411.3.3.1 CWS-491 C SCALE: SHEET 1:1 2 OF 6 t WiB+1f301N SYSTEMS 3 1 1 13 40 1 431 41 30 3 1900 SW 44TH AVE. OCALA,FLORIDA 34474 o� www.cws.cc 3 a 8100 PVC p SINGLE HUNG IMPACT 39 ¢ Zy O ,nI F ❑WO wOd 14 a O II 14 0 30 9 1 w0 F 1Z LLZ�}Z 10~Kwm .0 2 Z ZX2<WWOO 0 33 SECTION VIEW B-B O U In—�z UF) D.H cw LL O zz~�Ln Q OZUUz�UU —u �00LL <3:O OZ— 7 33 3 W 0 0>-5 co LD W Zcnw O—j Cf)H s 0- WHO Q..Oafaf r w H Of W wIn 38 36 D s �.•�5. .......... sr •..Up•., so �.v � F•.,� 44 8 No 58201 ,O r 33 X90; STATE OF OR1p. ta••� CT NA�Ey a`�• 10 14 54 � q 9 z� O 9/22/2017 UQ O LUCAS A.TURNER,P.E. FL PE#58201 1239 JABARA AVE. 16 5 s NORTH PORT,FL 34288 p 53 p PH.941-380-1574 2 p 39 SHEET DESCRIPTION: B SECTION VIEWS SECTION VIEW A-A SECTION VIEW C-C DRAWN BY: DATE: ALTERNATE FIN FRAME ADE 10/30/09 DWG REV.: CWS-491 C ITEMS NOT SHOWN FOR CLARITY: SCALE: 6,15,18,25,32 42,45,48 SHEET 1.2 3 0F 6 i PARTS LIST 31/8" FRAME CORNER �Cy(f�(yli//UULla ' ITEM PART# DESCRIPTION VENDOR MATERIAL �3 1/8- CONSTRUCTION 1 H-6031 Frame Head,Fig, Mikron Vinyt s WINDOW SYSTEMS 2 H-6031 Frame Sill,Fig, Mikron Vinyl D O1900 SW 44TH C:-3 3 H-6031 Frame Jamb,Fig, Mikron Vinyl 2 a W ALA,FLORIDAFLFLORIRI DA34474 4 H-6031 Internal Fr.,Jb. Mikron Vinyl o C7 3 5 H-6026 Frame,Fin Mikron Vinyl 4 1116" 6 S-6025 Sash Stop/Filler Mikron Vinyl 2„/1s^ 3 9/16" 08100 PVC 7 H-1836 Alum.Fixed Meet Rail Keymark Alum o fns" HID I CO LL SIDES SINGLE HUNG 8 H-6027 Sash Top Rail Mikron Vinyl 1:8 9 H-1497 ReirdorcementforSTR Keymark Alum L IMPACT 10 H-6028 Sash Bottom Rail Mikron Vinyl PVC FRAME FLANGE-6031 11 H 1699 ReirdorcementforSBR Keymark Alum PVC FRAME FIN-6026 Q ? wZo 12 H-6004 Sash Side Rail Mikron Vinyl Z w o a Z w 1 15/16"�{ 2 3/16" 0 Z u Z O it—~ 13 S-1498 Reinforcementfor SSR Keymark Vinyl I LL W Z F- 14 S-6064 Glazing Bead Mikron Vin z z= Z t WOO 15 P-3059 Sash Cam M&M Plastic ,2 0 0( Z 0-F a 16 P-4479 Weep Housing&Flap Assm. M&M Plastic 1 5/8" q 1Frf 1 5/8" FIXED MEETING RAIL p Z— Z Z F.�U) SCREWED TOGETHER WITH Z O U O 00- 17 Block&Tackle Balance Caldwell Steel I q I 1/1 ^ OUTERFRAME ¢ F LL2p O rL Z]— 1/16" ^ J 1:8 > a�O W—m O— 18 P-3295 Take Out Clip Summit Steel of 2 qQ �F-!=z 19 Sash SEE SHEET 2 CARDINAL GLASS PVC SASH SIDE RAIL-6004 PVC SASH BTM.RAIL-6028 PVC SASH MTG.RAIL-6027 I j O O W p W w 20 Fixed SEE SHEET 2 CARDINAL GLASS a ZiLL a.a. 0 p�r~n 21 P-3429 Wstp.,0.270 x 0.187 back FinSeal UltraFAB Nylon 0 _~K a- 'Cn 22 P4638 98 x 2-1/2 PH Mod.Truss,Type A, Fastenal Steel 215/16" -{ 7 1,/z" a- I- D. D_ n 23 #10 x 1 1/2"Panhead SMS Fastenal Steel 13/8' 9/16^ `t�pauar4ry��I 24 Flat Washer Fastenal Steel 41 . ` PrtOREN' 25 S-6014 Screen Support Mikron Vinyl 1314' 21/8" 1/16^ 13/16 6 1 5/16" 41 gS.��GEtJs 26 S-6013 Screen Catch Mikron Vinyl 3/16" }_ oas v s No 58201 +:�9 27 S-6063 Fixed Rail Cover Mikron Vinyl 1/1fi =*e * # 28 P-3113 Screw Support,PVC Team Plastics Rubber PVC SASH STOP-6025 PVC FXD RAIL COVER-6063 INTERNAL MULL BAR-1736 MTGRAIL-1636 STATE OF itu 29 P-3352 Set Elk.85 Dur.1/8"x5/8"x 2" Frank Lowe Rubber �0�.• N:�4u 30 S-6018 Mullbar Cover Mikron Vinyl %i5'.%0RtQ. 31 P-3767 #10x1Hex Head M-550 Fastenal Steel 314--1 33 ,/a' ��iSjONA'; 32 P-3342 Seam Sealer,SM-5504 Schnee 3116• I s� 33 SikaFlex552orPurfectGlaze"H" Sika/Henkel ,3 9 ,a 34 P-3541 #8 x 1/2 Flat Tek Fastenal Steel 1" ,s/,s ITZ116' 7/6 vs" LO: 1116" lL 35 P-4051 #8 x 1 1/4"PH Flat Tek Fastenal Steel z✓� 36 P-3783 Lock Interlock Steel REINF.S.S.R.-1498 REINF.S.T.R.-1497 REINF.S.B.R.-1699 PVC GLAZEBEAD-6064 37 P4069 Keeper Interlock Steel 9/27/2017 38 P4264 #8 x3/4"PH Flat w/#6 Head Fastenal I Steel 11/8• 1/2 LUCAS A.TURNER,P.E. Sns^ /6' 39 P-3752 Hole Plug M&M Plastic 1/2" 11 ns'i f~—3" FL PE#58201•1 1239 JABARA AVE. 40 P-3559 #8 x 3/8"PH Pan Tek Fastenal Steel , —,— {2s� 1l� 6 NORTH PORT,FL 34288 41 H-1736 Internal Mullbar Keymark Alum 1/16 ` 1/16 T PH.941-380-1574 44 P-3218 Screen frame ALL Metal Alum SCREW SUPPORT-3113 SHEET DESCRIPTION: 45 P-3321 Screen Comer Key ALL Metal Plastic PVC SCREEN SUPPORT-6014 PVC SCREEN CATCH-6013 46 P-3228 Screen Spline DAPA Rubber BOM AND EXTRUSIONS 47 P-3033 Screen Spring FLA Screen Steel DRAWN BY: DATE: 48 P-3029 Screen Pull tab Summit Alum ADE 10/30/09 49 Screen Material NY Wire Fiberglass OWG M REV.: 50 P-4959 Wstp.,0.420 x 0.187 back UltraFAB Nylon LINE ITEMS NOT USED: CWS 491 C 51 P-3541 #8 x 1/2,Pan Head,Tek Fastenal Steel 4243 NOTE:ALL EXTRUSIONS ARE ALUMINUM 6063-T6 UNLESS OTHERWISE NOTED. sc SHEET 4ii52 P 4632 Sweep Lock Sullivan 1:2 4 OF 6 53 -P- 3 and Screw Sullivan 54 P-3118 Keeper Sullivan 10 1/4"MAX O.C.(TYP.) 6"MAX(TYP.) MAX O.C.(rYPJ8"MAX O.C.(TYP.) W)NiDOW SYSYE@MS 6"MAX(TYP) 3"MAX O.C.(fYP.) 4"THRU FRAME ANCHOR(TYP.) t4" W MAX O.C.(TYP.) 4"MAX(TYP.) Z 1900 SW 44TH AVE. 4"MAX(TYP.) DETAIL A OCALA,FLORIDA 34474 - WWW.CWS.CC --------------- ------- ------- I I SEE NOTE 2 I 1 I I R 8100 PVC 1 , SINGLE HUNG 12 I O O I MAX D.C. O O I 2"(TYP.� IMPACT MAX D.C. I cryp•) I ` (TYP.) I I I I < ? a z o � owo ")woo ANCHOR AT MTG I I INSTALLATION I I DETAIL B O Q(O�}O Of Z IFF.. ANCHOR REQUIRED THRU FIN WITHIN L. h w Z I-�2_ �P)ENTERUNE I I ANCHOR(fYP.) I 1"OF MULLBAR CENTERLINE.(TYP.) O O F=-O Q Q w o o I I ci XF-X U UCH D Ff- I I I o z—w—zi_-ocn 8"(TYP.)_ I 1 I I 43 ¢ F�UgZOL.0 I X X I I X X I , <�ow_moz F I I I Q 4 1 af I e a z`nLau 0_1 i- 1 4 4 1 ---- e p w~o a W� = a ----- ---- — of (L t ANCHOR LAYOUT-(FLANGE) DETAIL B I I �� �PKORF... ANCHOR LAYOUT-(FIN) �CEtJSF,{Py�i�l J No 58201 ,,' 3 STATE OF j4i ,�rsOR "ONA ���'•��• NOTES: DETAIL A 1.INSTALL ONE ANCHOR AT EACH INSTALLATION LOCATION.SILL ANCHOR SPACING SAME AS HEAD. INTERNAL MULL ATTACHMENT 1:2 2,SHIM AS REQ AT EACH INSTALLATION ANCHOR USING LOAD BEARING SHIMS. MAX ALLOWABLE SHIM STACK TO BE 1/4". USE SHIMS WHERE SPACE GREATER THAN 1/16"IS PRESENT. LOAD BEARING SHIMS SHALL BE -? CONSTRUCTED OF HIGH DENSITY PLASTIC OR BETTER.WOOD SHIMS ARE NOT ALLOWED. (- 9/22/2017 3.ANCHOR TYPE,SIZE,SPACING AND EMBEDMENT SHALL BE AS SPECIFIED IN THESE DRAWINGS,SEE TABLE 1,SHEET 6. LUCAS A.TURNER,P.E. 4.ALL INSTALLATION ANCHORS MUST BE MADE OF OR PROTECTED WITH A CORROSION RESISTANT MATERIAL OR COATING. DISSIMILAR METALS OR MATERIALS IN CONTACT WITH PRESSURE TREATED WOOD MUST FL PE#58201 BE PROTECTED TO PREVENT REACTION. 1239 JABARA AVE. 5.INSTALLATION ANCHORS SHALL BE IN ACCORDANCE WITH ANCHOR MANUFACTURER'S INSTALLATION INSTRUCTIONS,AND ANCHORS SHALL NOT BE USED IN SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM NORTH PORT, 34288 SPECIFIED IN TABLE 1,SHEET 6. PH.9411 574 SHEET DESCRIPTION: - 6.ANCHOR EMBEDMENT TO SUBSTRATE SHALL BE BEYOND WALL DRESSING OR STUCCO. FOR CONCRETE/CMU OPENINGS,EMBEDMENT SHALL BE BEYOND WOOD BUCKS,IF USED,INTO SUBSTRATE. ANCHOR SCHEDULE AND INSTALLATIONS TO SOLID CONCRETE OR GROUT-FILLED CMU MAY INCLUDE BUT DO NOT REQUIRE 1X WOOD BUCKS BETWEEN THE PRODUCT AND THE SUBSTRATE. NOTES INSTALLATIONS TO HOLLOW CMU REQUIRE THE USE OF 1X BUCKS BETWEEN THE PRODUCT AND SUBSTRATE. . DRAWN BY: DATE: 7,A MINIMUM CENTER-TO-CENTER SPACING SHALL BE MAINTAINED BETWEEN ALL FASTENERS:3"FOR MASONRY,1"FOR WOOD AND METAL. ADE 10/30/09 &WOOD OR MASONRY OPENINGS,BUCKS AND BUCK FASTENERS SHALL BE PROPERLY DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD AND INSTALLED TO TRANSFER WIND LOADS TO THE STRUCTURE. DWG a: REV.: SUBSTRATES SHALL MEET THE MINIMUM STRENGTH REQUIREMENTS AS SHOWN IN TABLET,SHEET 6. CONCRETE AND MASONRY SUBSTRATES MAY NOT BE CRACKED. CWS-491 C 9.SEALING AND FLASHING STRATEGIES FOR OVERALL WATER RESISTANCE OF INSTALLATION SHALL BE DONE BY OTHERS FOLLOWING THE CURRENT VERSION OF THE REFERENCE DOCUMENTS: SCALE: SHEET FMA/AAMA 100(FIN WINDOWS),FMA/AAMA 200(FLANGE WINDOWS), FMA/WDMA 250(BOX WINDOWS),FMA/AAMAIWDMA 300(EXTERIOR DOORS) 1.20 5 OF 6 MIN.EMBEDMENT TYPICAL HEAD ANCHORAGE SEE TABLE 1 SUBSTRATE f�\/,y✓I/I BY OTHERS WINDOW SYSTEMS MIN.EDGE DIST. 114"MAX SHIM SEE TABLE 1 MIN.EDGE DIST. SUBSTRATE 1900 SW 44TH AVE. SEE TABLE 1 SEE TABLE 1 BY OTHERS 1/4"MAX SHIM SEE TABLE 1 OWE CWS.CC FLORIDA 34474 SUBSTRATE BY OTHERS SEE TABLE 1 MIN.EDGE DIST. MIN.EMBEDMENT SEE TABLE 1 PERIMETER SEALANT SEE TABLE 1 8100 PVC BYINSTALLER INSTALLATION ANCHOR IDE AND OUT SEE TALLA SINGLE HUNG IN SEALANT BEHIND 0 SEE TABLEDMENT IMPACT FLANGE BY INSTALLER 114"MAX SHIM fl �° ( a u ¢Z0 O n° PERIMETER SEALANT BY Z W J p Q W O W HIND PERIMETER SEALANT �""'""' NSIDE AND UT NSTALLER O 2 U) }O w Ei IN INSTALLER z Z=`z a w W Q O INSIDE AND OUT INSTALLATION ANCHOR Z SEE TABLE 1 O OF-O(jQ=Fw SEALANT INSTALLATION ANCHOR FLANGE BYINSTALLER l �SEALANT BEHIND 00 Z-U))Z Z F~-7 cn SEE TABLE 1 FIN BY INSTALLER Z O Z to Z O O- B HORIZONTAL SECTION C HORIZONTAL SECTION Q --O W O O LFLL� Z 8 TYPICAL FIN ANCHORAGE 2 g O H F F O- 6 TYPICAL JAMB ANCHORAGE HEAD AND SILL SIMILAR FOR FIN INSTALLATION F O' Y� O W 00 >_ WfAW NOTE:ADDITIONAL THRU-FRAME ANCHORS a z=a 0 O co P Q o (AS SHOWN IN DET.B/6)REQ'D AT THE MULL, O w I-O a 114"MAX SHIM SEE SHEET 5 ANCHOR LAYOUT. a F a w a SEALANT EHIND FLANGE BY INSTALLER O ppiORE4y 4 •''G£td PERIMETER SEALANT MIN.EMBEDMENT �w; No 58201 ••.x'73 BY INSTALLER SEE TABLE 1 INSI DEANDOUT *� * '*Z =roe :az` 9�. STATE OF PU SUBSTRATE BY OTHERS �: (.'.0 p R 14A'\��� SEE TABLE 1 MIN.EDGE DIST. ,,i��sS� NAG�N �, SEALANT UNDER SCREW SEE TABLE 1 �� �i HEAD BY INSTALLER � q VERTICAL SECTION 8 TYPICAL SILL ANCHORAGE 9/2212017 TABLE I:APPROVED INSTALLATION FASTENERS FRAME TYPE SUBSTRATE TYPE ANCHOR TYPE MIN.EMBEDMENT MIN.EDGE DIST. LUCAS A.TURNER,P.E. FL PE#58201 FLANGE CONCRETE(2.0 KSI MIN.) 3/16"TTW TAP CON 1" 1-118" PERIMETER SEALANT 1239 JABARA AVE. FLANGE HOLLOW OR GROUT-FILLED CMU(117 PCF MIN.) 3115'ITW TAPCON 1" 2" BY INSTALLER NORTH PORT,FL 34288 FLANGE CONCRETE(2.85 KSI MIN.) 3116"ELCO ULTRACON 1" 1" INSIDE AND OUT PH.94TION: 1574 D HORIZONTAL SECTION SHEET DESCRIPTION: FLANGE GROUT-FILLED CMU(ASTM C-90) 3/16"ELCO ULTRACON 1-114" 2-1/2" 6 BOX FRAME INSTALLATION FLANGE 2XMIN.SPRUCE-PINE FIR(G=0.42) 3116"TIWTAPCON 13/8„ 7/8" HEAD AND SILL SIMILAR FOR BOX INSTALLATION INSTALLATION DETAILS OR ELCO ULTRACON FLANGE 2X MIN.SPRUCE-PINE-FIR(G=0.42) #10 WOOD SCREW 1-3/8" 7/8" FLANGE REMOVAL NOTE:PARTIALLY OR FULLY REMOVING THE FLANGE, T, UP TO AND INCLUDING A BOX-FRAME APPLICATION IS ACCEPTABLE PROVIDED: "eY: DATE: FLANGE 16 GAUGE(0.069')MIN.STEEL STUD #10-16 HILTI KWIK-FLEXOR ffW FULL THREAD 7/16„ ADE 10/30/09 (33 KSI YIELD MIN) TEKS SELF-DRILLING SCREW THRU 0.060" MIN.1/4"FILLET OF CONSTRUCTION-GRADE ADHESIVE CAULK IS APPLIED DWG 0: REV.: FJ�4NGE 1/8"ALUM.(6063-T5 MIN.)OR #10 GRADE 5 SELF TAPPING/ FULL THREAD 7/15, INSIDE AND OUT,FULL PERIMETER,BY INSTALLER. CWS-491 C 1/8"STEEL(33 KSI MIN.) DRILLING SCREW THRU 0.126' PRODUCT ANCHORAGE IS IN ACCORDANCE WITH REQUIREMENTS AS FIN 2XMIN.SPRUCE-PINE-FIR(G=0.42) #8 WOOD SCREW 1-1/2" 7/16" SHOWN FOR FLANGE WINDOWS. SCALE-- SHEET 1.2 6 OF 6 UR1239 NER Jabara Ave. North Port,FL 34288 ENGINEERING & Ph. 941-380-1574 TCONSULTING, INC. FBPE C.O.A. #29779 Evaluation Report 812C August 29, 2017 Product Description: Series 8100 PVC Single Hung,Large Missile Impact, 517/8"x 613/4"unit size, +/-70 PSF,no anchors in sill Manufacturer: Custom Window Systems, Inc. 1900 SW 44`h Ave, Ocala,FL 34474 Statement of Compliance: This report evaluates the above-listed product per the requirements of FAC Product Approval Rule Chapter 61G20-3.005 (4). This product complies with the requirements of the 6`h Edition(2017)Florida Building Code including the High Velocity Hurricane Zone. The product testing standards performed are outlined below. Technical Documentation: 1) This report, prepared by Lucas A. Turner,P.E.,at 1239 Jabara Ave.,North Port,FL `2) Approval drawing CWS-812C, signed and sealed by Lucas A. Turner,P.E. 3) Test Report NCTL-210-3815-1A, -2, and-2A,by National Certified Testing Laboratories, Orlando, FL, signed and sealed by Gerard J.Ferrara,with testing performed: TAS 201/202/203- 94,ASTM E 1886-02/04/05, 1996-02/04/06/09,and AAMA/WDMA/CSA 101/I.S.2/A440-08 4) Supplemental Calculations to support CWS-812C, signed and sealed by Lucas A.Turner, P.E. Installation: Units must be installed according to approval document CWS-812C. Limitations of Use: This product: • May be used in O/X configuration in sizes and with max. glass DLO heights as shown in CWS- 812C • Is impact resistant and does not require the use of shutters • May be used in the High Velocity Hurricane Zone • Requires 7/8"Insulating Glass consisting of 1/8 Annealed or Tempered outboard lite(Tempered required above 30 ft in HVHZ) —Air—5/16 Laminated(1/8Ann-.090PVB-1/8Ann)inboard lite • Requires Kuraray(Dupont)PVB Interlayer per Miami-Dade N.O.A. 16-1117.02, • Requires Quanex(Mikron) white rigid PVC framing per Miami-Dade N.O.A. 17-0206.10, ,I have evaluated the materials in these NOAs and find that they comply with the requirements of the 6`h Ed. (2017)Florida Building Code for use in this product. Certification of Independence: I do not have,nor do I intend to acquire,nor will I acquire, a financial interest in Custom Window Systems or in any company manufacturing or distributing products for which this report is being issued. I do not have, nor do I intend to acquire, nor will I acquire, a financial interest in any other entity involved in the testing or approval process of this product. o t7itlilro',/ ��tt �10 RE W ��r�i a.• ° � •' �` • o* Lucas No SS201 +' Turner 2017-08-30 S.13 16:11+20:00 .. Q STATE OF1 8/29/2017 `'•,�`, ''•.. N. 0 n k ••�N,`` Lucas A. Turner, P.E. X004'#/ONAy 01``�`� FL PE#58201 GENERAL NOTES: SINGLE HUNG - LARGE MISSILE IMPACT 1.THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED WINDOW SYSTEMS TO COMPLY WITH THE FLORIDA BUILDING CODE(FBC),CURRENT EDITION INCLUDING THE HIGH VELOCITY HURRICANE ZONE(HVHZ)AND 1900 SW 44TH AVE. IS RATED FOR WIND ZONE 4 MISSILE LEVEL D IMPACT USE AS DEFINED OCALA,FLORIDA 34474 IN ASTM E 1996 PER THE FBC. WWW.CWS.CC 2.GLAZING OPTIONS:(SEE SHEET 2) O 53 1/8"MAX OVERALL FLANGE WIDTH 3.CONFIGURATIONS:"O/X". 8100 PVC 517/8"MAX UNIT WIDTH SINGLE HUNG 4.DESIGN PRESSURE RATING: IMPACT 4711/16"GLASS DLO -NEGATIVE DESIGN LOADS BASED ON,TESTED PRESSURE AND GLASS TABLES ASTM E-1300-04e01/09. A -POSITIVE DESIGN LOADS BASED ON,TESTED PRESSURE,WATER z ¢ ?� INFILTRATION TEST PRESSURE AND GLASS TABLES F z U)I o w 0 il o p z w�❑ ¢ O w w zOz D=-Z� 63" _ __ __ I _ 5.ANCHORAGE:THE 331/3%STRESS INCREASE HAS NOT BEEN USED o F W Z O m m MAX IN THE DESIGN OF THIS PRODUCT.SEE SHEET 6 FOR ANCHOR Z z=2¢D_w oO p OVERALL I I DETAILS. WINDLOAD DURATION FACTOR Cd=1.6 WAS USED FOR WOOD O O 1-0 6¢_I-w FLANGE ANCHOR CALCULATIONS. o U c z a F y D- HEIGHT O Z ZO D--50— B i B 2G61�6" 6.PRODUCT APPROVED FOR IMPACT RESISTANCE. SHUTTERS ARE } 1-- '20 w p O z DLO NOT REQUIRED. F _ Z I I I 22 7.ALL FRAMES AND VENTS FULLY WELDED.SMALL JOINT SEAM SEALANT w 00of} 66131314" I I USED AT FIXED MEETING RAIL AND JAMB. a Z 2 a m 0 JO(n 1-- a- HEIGHT LINT 8.SERIES/MODEL DESIGNATION SH-8100. _~OfLu w m o a 9.THE DESIGNATION X AND O STAND FOR THE FOLLOWING: aaaatnarri� X=OPERABLE SASH,0=FIXED SASH a�aa�P IOREW y� I I iia 5 .......... 316" I I 26 7/8" 10.SECTION CALLOUTS APPLY TO ALL ELEVATIONS IN A SIMILAR y�JG�;•"�} SF'•;py�:� SA H GLASS LOCATION. No 58201 '.-P r HEIGHT X j DLO 11.EXTERNAL WEEP SLOT=1/4"x 1-1/4"LOCATED 4"FROM BOTH ENDS. *: * '* CV. STATE OF :A,+� 4 I �•�SS�ONq;E�O�� 77-- LucasTurne 67 A r 451/16 201 7-09-22 �Z GLASS DLO 48 3/8" 13:36-04:00 9/22/2017 MAX SASH WIDTH LUCAS A.TURNER,P.E. FL PE#58201 1239 JABARA AVE. NORTH PORT,FL 34288 PH.941-380-1574 SHEET DESCRIPTION: GENERAL NOTES AND ELEVATIONS TABLE OF CONTENTS DRAWN BY: DATE: GENERAL NOTES&ELEVATIONS.....1 DESIGN PRESSURE BAT 06/18/12 GLAZING DETAIL.................................2 MAX. UNIT SIZE IMPACT RATING DWG#: SECTION VIEWS.................................3 RATING EXTRUSIONS&B.O.M........................4 CWS-812 c ANCHOR SCHEDULE&NOTES.........5 51-7/8"x 61-3/4" +/-70 PSF LARGE MISSILE IMPACT SCALE: INSTALLATION DETAILS....................6 SHEET 1:15 1 OF 6 wlNcrOw sysTeMs 1900 SW 44TH AVE. OCALA,FLORIDA 34474 W W W.CWS.CC 8100 PVC SINGLE HUNG IMPACT z 3: ¢z� F- OWO ¢Wow Z W J D W ZOZ of I-- O Q(n;Y>-0 O] LL I-W ZF?i�= 7/8"OVERALL INSULATED GLASS 7/8"OVERALL INSULATED GLASS Z Z=2 Q 0_W O O O OF-06<XI..Q: 1/8"ANNEALED OR TEMPERED 1/8"ANNEALED OR TEMPERED 00 Z-U)Z Z n N 7116"AIRSPACE 7/16"AIRSPACE Q O WZ U 2'0 p u Z >- Q?: W-20— 5/16"LAMINATED GLASS 5/16"LAMINATED GLASS 2§ O F-F-F Z 1/8"ANNEALED 1/8"ANNEALED W 0 0 w W(n W iE zea 0-1tnF- .090"PVB INTERLAYER BY DUPONT .090"PVB INTERLAYER BY DUPONT a F- 0-0Ts } ~ _ W S w cn 1/8"ANNEALED 1/8"ANNEALED D. F- o_ a QUANEX DURASEAL zQUANEXDURASEAL IG SPACER IG SPACER 4 PURFECT GLAZE"H"OR SIKAFLEX 552 4 URFECT GLAZE"H"OR SIKAFLEX 552 ,,���yOP.ZIORE.Eris : No 58201 14 1/2"GLASS BITE 14 1/2"GLASS BITE 48 -at 13'. STATE OF ;4utut 3P,%T O R 10. ��a��, 1 1 IONA L Sipe O SASH LITE 9/22/2017 FIXED LITE LUCAS A.TURNER,P.E. FL PE#58201 1239 JABARA AVE. NORTH PORT,FL 34288 PH.941-380-1574 SHEET DESCRIPTION: GLAZING DETAILS DRAWN BY: DATE: BAT 06/18/12 DING ft: REV.: CWS-812 C SETTING BLOCKS PER FBG 2411.3.3.1 S� SHEET 1:1 2 OF 6 C�r���T• INTERIOR WINDOW SYSTEMS i 1900 SW 44TH AVE. OCALA,FLORIDA 34474 WwW.CWS.CC - 45 3 53 1 38 13 3 3 4 ' 8100 PVC D ® SINGLE HUNG 0 IMPACT a O o� �Qoo a zQ Z F owo U)w0p Q 1 w zoz w O ¢cn�yO��m 14 3 Z Z2�a�WpO 3 14 54 14 65 66 63 19 4 O -z* Q=F � SECTIONS-B o Z�uu)i—ZFDco 54 Z 000Dj OU— NOTE:LEFT SIDE SHOWS FIXED SECTION VIEW, Q O O LL z RIGHT SIDE SHOWS SASH SECTION VIEW. >- �,99�OFF 1 Z— W 009 Owu)w LL(nw OJ(nH 1439 _~Of W�w a0 0 D- m o e �0 gOR✓W 1 3 INTERIOR ����5�:.......... 9 ���GP••y� SF`•,�� .� No 58201 �,p$ , c:,� '9; STATE OF 14 65 10 6 3 f—f- 3 9/22/2017 19 Q o s LUCAS A.TURNER,P.E. 2 4 FL PE#58201 3 1239 JABARA AVE. 30 o NORTH PORT,FL 34288 PH.941-380-1574 0 SHEET DESCRIPTION: SECTION A-A SECTION VIEWS DRAWN BY: DATE: BAT 06/18/12 DWG 0: REV.: NOTE: ITEMS NOT SHOWN FOR CLARITY: CWS-812 C 20,25-26,36-37,44,51-52,55-56,64,67-68 SCALE: SHEET 1.2 3 OF 6 PARTS LIST FRAME CORNER ITEM PART# DESCRIPTION VENDOR MATERIAL 3 1/8"--� CONSTRUCTION { 1 H-6031 Main Fr.,SH,w/Flg.,PVC,Head Mikron Vinyl I WINDOW SYSTEMS 2 H-6031 Main Fr.,SH,w/Flg.,PVC,Sill Mikron Vinyl 1 15/,6^--I 3 H-6031 Main Fr.,SH,w/Fig.,PVC,L.Jb. Mikron Vinyl 1 I �--2 3116" OCALA,1900 LTH AVE. OCAFLORIDA 34474 4 H-6031 Main Fr.,SH,w/Flg.,PVC,R.A. Mikron Vinyl Q p JA 3 � e WWW.CWS.CC 6 S-1577 Impact Hook Keymark Alum 4 8 H-6027 Sash Meet.Rail,PVC Mikron Vinyl 211/16" 1Ew1 5/8" 9 H-1497 Reinf.Sash Meet.Rail Keymark Alum 1/16" ,,16„ 8100 PVC 10 H-6028 Sash Bottom Rail,PVC Mikron Vin I O CORNER WELD 12 H-6004 Sash Side/Top/Bot.Rail Mikron Vinyl La (ALLSIB ES) SINGLE HUNG 13 S-1498 Reinf.S.B.R./S.S.R IMPACT 14 S-6064 Glz.Bd.,7/8" Mikron Vinyl PVC FRAME FLANGE-6031 PVC SASH BTM.RAIL-6028 PVC SASH TOP RAIL-6027 18 S-6013 Scm.Adapt.,w/Nib,PVC,Hodz. Mikron Vinyl ¢ z 3: ¢Z 3� 19 S-6014 Scm.Adapt.,PVC,Vert. Mikron Vinyl 1 112,. F- C w O U)w o p 20 S-6029 Sash Stop/Filler,PVC,Vert. Mikron Vinyl 3 w Z O z w k z r 13/16" O U-}O w- m 23 H-1699 Reinforcement,SBR Keymark Alum 9718'116" 1 , LL H w Z I-��2 24 P-2190 Balance BSI 9/16" Z Z= a D_w 0 0 O OF-0Cja=�� 25 P-3059 Sash Cam,PVC BSI Plastic 3 U U U I- t-U a 1 5/8" 21/8° 1/16" FIXED MEETING RAIL U)Z- 26 P-3046 Take Out Clip BSI SS z z- z Z)�U 1116" SCREWED TOGETHER WITH Z 00 U O U- 27 P-3783 Lock,Impact,PVC Interlock 1/16^ OUTERFRAME Q F-LL 2 0 O LL Z 28 P-4069 Keeper,Impact,PVC Interlock Zamac 1:8 r ¢3:p w-=O- 30 P-3215 Weep CO1Rr w/Flap Gaer Plastic REINF.,IMPACT HOOK-1112 Q W2§y}j§O uj F 32 P-3429 Wstp.,0.270 x.187 back FinSeal,Gray Ultrafab PVC SASH SIDE RAIL-6004 FIXED RAIL-1836 w LL U) U w U O w(n w 37 P�638 #8 x 2-1/2 PH Mod.Truss,Type A,TEK 2 Fastenal Steel a YP a z= Of (n 38 P-3768 #8 x 0.625 Ph PH SMS Hub City Steel 15/16" 9116" 0 =~� w D_(}n 1 118" a F a tY Wa 39 P-4051 W#8 x 1.250 Ph FH TEK,Wht. Hub City Steel 112"�/8" y16„ 40 P4264W#8 x 3/4 FH PH w/#6 Head,TEK,VOL Hub City Steel 0 1 t�ti'aRE1Vd� 44 P3342 Seam Sealer,SM-5504 Schnee 7/8" 18 1 5116" 19 •���PtSOR@bV 45 P-3752 Cap Plug,112"Hole M&M Nylon 1/16" 045' 1/16 .•q`?"•tOEI(�'• 1/16"F1 0, 'n' 47 P-3438 Sikaflex 552 or Purfect Glaze"H" Sika/Henkel 48 P-3352 Set.Blk.,85 Dur.,118"x 5/8"x 2"Lg. F.Lowe Rubber PVC SASH STOP-6025 PVC SCREEN CATCH-6013 PVC FIXED RAIL COVER-6063 PVC SCREEN SUPPORT-6014 :ter- No 58201 ;7) 51 P-3881 Temporary Lbl.(NFRC/DP) *" 52 P-3613 CWS Lbl.(logo) Pro Label y4" Z9 STATE OF .•w� 53 Sash SEE SHEET GLASS �4" I 54 Fixed SEE SHEET GLASS 3116" ,Oq�a4' ��(`56 P3281 Spacer Duraseal 1315t16" WX/w i 7/+.1 ',,S/ONAi-S il%`` 62 P3218 Screen Frame,Horiz. Allmetal Alum T 1/16 �— J- 63 P3218 Screen Frame,Vert. Allmetal Alum REINF.S.B.R./S.S.R.-1498 REINF. BTM RAIL-1699 REINF.TOP RAIL-1497 PVC GLAZING BEAD-6064 64 P-3321 Screen Frame Comer Key Allmetal Plastic 65 P-3581 Screen Goth,18 x 16 Fiberglass Betterwe Fiberglass 7 66 P-3228 Screen Spline,.155 Dia.,Blk. Dapa Vinyl 67 P-3029 Screen Pull Tab Summit Alum 9/22/2017 68 P-3033 Screen Spring,SS FI.Screen SS 70 P3113 Screw Support for PVC I T.Plastics Nylon LUCAS A.TURNER,P.E. 71 H-1836 Alum.Fixed Rail Keymark Alum 0 3116„ FL PE#58201 72 S-6063 Coyer,Fixed Rail Mikron Vinyl O 1239 JABARA AVE. 73 5-1112 Reinforcement,Impact Hook Keymark Alum NO PH.941-380-1574 RTH PORT,FL 288 74 P-3541 #8 x 1/2",Pan Head,TEK Fasten, Steel 7 1 J1116" 1/2^ SHEET DESCRIPTION: LINEITEMS NOT USED: 63/16 3"—� BOM AND EXTRUSIONS 5,7,11,15-17,21-22,29,31,33-36,41-43,46,49-50,55,57-61,69 /8" -�— I SCREW SUPPORT-3113 DRAWN BY: DATE: IMPACT HOOK BAT 06/18/12 S-1577 DWG#: REV.: CWS-812 C NOTE:ALL EXTRUSIONS ARE ALUMINUM 6063-T6 UNLESS OTHERWISE NOTED. SCALE' SHEET 1:2 4 OF 6 WINDOW svMrss 6"MAX(TYP.) 1T'MAX O.C.(TYP.) 1900 SW 44TH AVE. 6"MAX(T(P.) OCALA,FLORIDA 34474 WWW.CWS.CC SEE NOTE 2 8100 PVC 101/2" ' I SINGLE HUNG Max.O.C. CnL O INSTALLATION IMPACT ANCHOR(TYP.) H Ow0 QwpW ' w z O Z W--F- w FQ-w�Z132= --- rnrc rsna Z Z S m Q w w U U O OU)OdaPcoa 4"(TYP') I I Z 0 0 U vj z:) Q Z Z U X w� Opi0 �oYU ���waOl- MAX O.C. Z (TYP.) O w r 0 mOf = d W w 4"(TYP.) ytc E.....F 4"(TYP.) NO ANCHORS REQUIRED IN SILL j No 5$201 ••,�15 ANCHORLAYOUT-(FLANGE) F NOTES: 1.INSTALL ONE ANCHOR AT EACH INSTALLATION LOCATION.NO ANCHORS REQUIRED IN SILL 2.SHIM AS REQ AT EACH INSTALLATION ANCHOR USING LOAD BEARING SHIMS. MAX ALLOWABLE SHIM STACK TO BE 1/4". USE SHIMS WHERE SPACE GREATER THAN 1/16"IS PRESENT. LOAD BEARING SHIMS SHALL BE �� CONSTRUCTED OF HIGH DENSITY PLASTIC OR BETTER.WOOD SHIMS ARE NOT ALLOWED. 3.ANCHOR TYPE,SIZE,SPACING AND EMBEDMENT SHALL BE AS SPECIFIED IN THESE DRAWINGS,SEE TABLE 1,SHEET 6. 9/22/2017 4.ALL INSTALLATION ANCHORS MUST BE MADE OF OR PROTECTED WITH A CORROSION RESISTANT MATERIAL OR COATING. DISSIMILAR METALS OR MATERIALS IN CONTACT WITH PRESSURE TREATED WOOD MUST LUCAS A.TUR#5NER1 P.E. FL BE PROTECTED TO PREVENT REACTION. 1239 JABARA AVE. 5.INSTALLATION ANCHORS SHALL BE IN ACCORDANCE WITH ANCHOR MANUFACTURER'S INSTALLATION INSTRUCTIONS,AND ANCHORS SHALL NOT BE USED IN SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM NORTH PORT,FL 34288 PH.941-380-1574 SPECIFIED IN TABLE 1,SHEET 6. SHEET DESCRIPTION: 6.ANCHOR EMBEDMENT TO SUBSTRATE SHALL BE BEYOND WALL DRESSING OR STUCCO. FOR CONCRETE/CMU OPENINGS,EMBEDMENT SHALL BE BEYOND WOOD BUCKS,IF USED,INTO SUBSTRATE. INSTALLATIONS TO SOLID CONCRETE OR GROUT-FILLED CMU MAY INCLUDE BUT DO NOT REQUIRE 1X WOOD BUCKS BETWEEN THE PRODUCT AND THE SUBSTRATE. ANCHOR SCHEDULE AND INSTALLATIONS TO HOLLOW CMU REQUIRE THE USE OF 1X BUCKS BETWEEN THE PRODUCT AND SUBSTRATE. NOTES 7.A MINIMUM CENTER-TO-CENTER SPACING SHALL BE MAINTAINED BETWEEN ALL FASTENERS:3"FOR MASONRY,1"FOR WOOD AND METAL. DRAWN BY: DATE: BAT 06/18/12 B.WOOD OR MASONRY OPENINGS,BUCKS AND BUCK FASTENERS SHALL BE PROPERLY DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD AND INSTALLED TO TRANSFER WIND LOADS TO THE STRUCTURE. DWG tt: REV.: SUBSTRATES SHALL MEET THE MINIMUM STRENGTH REQUIREMENTS AS SHOWN IN TABLEI,SHEET 6. CONCRETE AND MASONRY SUBSTRATES MAY NOT BE CRACKED. CWS 812 C 9.SEALING AND FLASHING STRATEGIES FOR OVERALL WATER RESISTANCE OF INSTALLATION SHALL BE DONE BY OTHERS FOLLOWING THE CURRENT VERSION OF THE REFERENCE DOCUMENTS: SCALE: SHEET FMA/AAMA 100(FIN WINDOWS),FMA/AAMA 200(FLANGE WINDOWS), FMAANDMA 250(BOX WINDOWS),FMA/AAMA/WDMA 300(EXTERIOR DOORS) 1:15 5 OF 6 TYPICAL HEAD ANCHORAGE ����+'�' • MIN.EMBEDMENT WINDOW SYSTEMS�1 SEE TABLE I SUBSTRATE MIN.EDGE DIST. BY OTHERS 1900 SW 44TH AVE. SEE TABLE 1 114"MAX SHIM SEE TABLE 1 OCALA,FLORIDA 34474 SUBSTRATE BY OTHERS WWW.CWS.CC SEE TABLE 1 MIN.EMBEDMENT SEE TABLE 1MIN.EDGE DIST. $�OO PVC PERIMETER SEALANT �� SEE TABLE 1 BYINSTALLER INSIDEANDOUT SINGLE HUNG INSTALLATION SEALANT BEHIND � :� SEE TABLE ANCHOR IMPACT FLANGE BY INSTALLER � 1/4"MAX SHIM Ow0aZ� Q~wop w Z O Z w~Z r O Q(n3:}OD 3:m PERIMETER SEALANT LL F-w Z 1-3i 2 2 BYINSTALLER Z Zx2QXWp0 O 0 1-0 a x F-0= INSTALLATION ANCHOR INSIDE AND OUT 0 O N C3 z F-Z a P 0 a SEE TABLE 1 SEANT BEHIND FLAGE BY INSTALLER Z 0 Z 0 N Z O Q�OwOxOZ CONTINUOUS DOUBLE 3/16"BEADS OF B HORIZONTAL SECTION Q w y U)j�Z'6 TREMGLAZE U1600 SEALANT AROUND 6 TYPICAL JAMB ANCHORAGE w 0 0 0_tp p w to W PERIMETER AT ALL INDICATED POINTS - Z U)a 0�cn� BETWEEN FRAME AND BUCK BY INSTALLER. a 2 O 2 to w~af W� wco x 1/4"MAX SHIM a ~ a of a SEALANT BEHIND �7 t"% rf� pw rr FLANGE BY INSTALLER %% ,. CREW 11.. PERIMETER SEALANTMIN.EMBEDMENT t No 58201 0 BY INSTALLER SEE TABLE 1 INSIDE AND OUT 9; STATE OF � �O. e SUBSTRATE BY OTHERS �y'c�:•.,(pA1pP'ot�� SEE TABLE 1 SMIN.EDGE EE TABLE 1ST. jOfYA i�N `! q VERTICALSECTION 6 TYPICAL SILL ANCHORAGE 9/22/2017 TABLE TABLE 1:APPROVED INSTALLATION FASTENERS LUCAS A.TURNER,P.E. SUBSTRATE JA TYPE ANCHOR TYPE MIN.EMBEDMENT MIN.EDGE DIST. FL # PERIMETER SEALANT 1239 JABARA RA AVE.A CONCRETE(2.0 KSI MIN.) 3116"ITW TAPCON 1-1/2" 1-1/8" BY INSTALLER NORTH PORT,FL 34288 HOLLOW OR GROUT-FILLED CMU(117 PCF MIN.) 3/16"fIW TAPCON 1" 2" INSIDE AND OUT PH.941-380-1574 C HORIZONTAL SECTION CONCRETE(2.85 KSI MIN.) 3/16"ELCO ULTRACON 1" 1" 6 BOX FRAME INSTALLATION SHEET DESCRIPTION: GROUT-FILLED CMU(ASTM C-90) 3116"ELCO ULTRACON 1-1/4" 2-1/2" HEADAND SILL SIMILAR FOR BOX INSTALLATION INSTALLATION DETAILS 2XMIN.SOUTHERN PINE(G=0.55) 3116"ITW TAPCON 1-3/8„ 7/8" OR ELCO ULTRACON FLANGE REMOVAL NOTE:PARTIALLY OR FULLY REMOVING THE FLANGE, 2XMIN.SOUTHERN PINE(G=0.55) #10 WOOD SCREW 1-3/8" 7/8" UP TO AND INCLUDING A BOX-FRAME APPLICATION IS ACCEPTABLE PROVIDED: DRAWN BY: DATE: BAT 06/18/12 16 GAUGE(0.060")MIN.STEEL STUD #10-16 HILTI KWIK-FLEXOR ITW FULL THREAD 7/16, MIN.1/4"FILLET OF CONSTRUCTION-GRADE ADHESIVE CAULK IS APPLIED DWG#: REV.: (33 KSI YIELD MIN) TEKS SELF-DRILLING SCREW 'THRU 0.060" INSIDE AND OUT,FULL PERIMETER,BY INSTALLER. CWS-812 C 1/8"ALUM.(6063-T5 MIN.)OR #10 GRADE 5 SELF-TAPPING/ FULL THREAD PRODUCT ANCHORAGE IS IN ACCORDANCE WITH REQUIREMENTS AS 1/8"STEEL(33 KSI MIN.) DRILLING SCREW THRU 0.125" 7/16 SHOWN FOR FLANGE WINDOWS. scALE: SHEET 1:2 6 OF 6 �