EVALUATION!-REPORT RIDA BUILDING CODE,6'EDmoN(2017)
Manufacturer. MID-STATES ASPHALT AND CANT S IP,INC. issued October 11,2017
1637 51"Street
Tuscaloosa,AL 35401
(800)489-2391
www.msaroofcom
Manufacturing Location: Tuscaloosa,AL
Quality Assurance: UL LLC(QUA9625)
SCOPE
Category: Roofing
Subcategory: Undedayments
Code Sections: 1504.3.1,1507.1.1
Properties: Physical properties
PRODUCT DESCRIPTION AND LIMITS OF USE
QUIK-Stick lee&Water QUIK-Stick Ice S Water Granular is ASTM D 1970 self-adhesive underlayment
Granular constructed from SBS modified asphalt a fiberglass mat reinforcement and surfaced
with granules. The product is supplied n 2 sq,rads with nominal dimensions of 3-ft x
66.8-ft and has a nominal thickness of 5 mils.
QlliK=Stick ice&Water Granular is pe itted to be used as prescnbed.in FBG Section
1507.1.1 for mechanically attached roofi coverings. Exposure on the roof deck shall
be limited to a maximum 30 days.
QUIK-Stick Ice&Water QUIK-Stick Ice & Water Sand is ASTM D 1970 self-adhesive underlayment
Sand constructed from SBS modified asphalt ith a fiberglass mat reinfumement and surfaced
with sand The product is supplied in 2- q.rolls with nominal dimensions of 3-11 x 66.8-ft
and has a nominal thickness of 50 mils.
QUIK-Stick foe& Water Sand is pTngcoveyings.
to be used as prescribed in FBC Section
1507.1.1 for mechanically attached Exposure on the roof deck shall
be limited to a maximum 30 days.
QUIK-Stick HT QUIK-Stick HT is an ASTM D 1970 s -adhesive undedayment constructed from SBS
(High Temperature) modified asphalt with a fiberglass m reinforcement and poly-fabric surface. The
product is supplied in 2-sq-rolls with no 'nal dimensions of 3-ft x 66.8-ft or 3-ft 34n x 61-
ft and has a nominal thickness of 60 mil .
QUIK-Sfick HT is to be used as prescri in FBC Section 1507.1.1. QUIKStick HT is
permitted to be used with adhered , ay or concrete We roofing using either ICP
Adhesives Polyset AH-160 QCP Adhe es and Sealants, Inc.). Exposure on the roof
deck shall be limited to a maximum 90 ays.
The maximum roof slope shag be 6.12 en used with day or concrete file installations
without battens. Tile shag be stored on battens for roof slopes greater than 6:12. Tiles
shall not be stacked greater 10 tiles per stalk.
MSA17001 FLiT401-R4 Page 1 of
This evaluation report is provided far State of Florida product approval uRule 61G203. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance than es throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty.installation. ended use,or other product attributes that are not
specifically addressed herein.
`. CREEK MID-STATES ASPHALT AND CANT STRIP,INC
Self Adhering Undedayments
A�i TECHNiCAL SERVICES,LLC
QUiK-Stick HT Pro QUIK Stick HT Pro is an ASTM D 1970 f-adhesive undedayment constructed from
(High Temperature) SBS modified asphalt with a fiberglass m It reinforcement and poly-fabric surface. The
product is supplied in 2-sq. rolls with no inal dimensions of 3-ft x&S.8 ft and has a
nominal thickness of 60 mils.
QUIK-Stick HT Pro is permitted to be u as prescribed in FBC Section 1507.1.1 for
mechanically attached roofing coverings. osure on the roof deck shall be limited to a
maximum 30 days.
GUNK-Stick FS QUIK-Stick FS is an ASTM D 1970 self dhesive undedayment constructed from SBS
(Film-Surface) modified asphalt with a fiberglass mat 'nforcement and textured Min surface. The
product is supplied in 2-sq. rolls with no inal dimensions of 3-ft x 66.8-ft and has a
nominal thickness of 45 mils.
QUIK-Stick FS is permitted to be used as prescribed in FBC Section 1507.1.1 for
mechanically attached roofing coverings. osure on the roof deck shall be limited to a
maximum 30 days.
PRODUCT APPLICATfON
Min.Roof Slope: 2:12 or in accordance in with the FBC
Application: All underlayments shall be installed in acc rdance with the FBC.
Deck substrates shall be clean, dry, an free from any irregularities and debris. All
fasteners in"the deck shall be checked for rotrusion and corrected prior to undedayment
application. Prior to beginning instalia n, the undedayment shall be unrolled and
allowed to relax fora minimum of 3-5 min tes.
- The underlayment shalt be installed with a release backer removed.and pressed firmly
into place to ensure complete contact M the deck.The undedayment shall be installed
with the roil length parallel to the eave, Fling at the eaves and with minimum 3-side
laps-and minimum 6"end taps staggered in.6-ftfrom preceding course.
It is permissible to back nall the underka ent 12-inches on-center as needed(nails shall
be installed perpendicular to deck with a trail heads flush to the top surface of the
underlayment).
Min.Application 40°F;Confact the manufacturer when in ting at temperatures below the minimum
i Temperature: application temperature.
WIND RESISTANCE
The Maximum.Design Pressures shown below were calculated using 2:1 margin of safety per FBC Section 1504.9.
Undedayment System mo.1—CUHT niC ty
Roof Deck: Min.15132-inch CDX plywood attached t wood supports spaced a maximum 2,V o.c.
Underlayment QUIK-Stick H3 shall be fully adhered to I ie optionally primed plywood deck.
Maximum Design -52.5 psf
Pressure:
MSA17001 FL17401-R4 Page 2 of 4
This evaluation report is provided for State of Florida product approval under 61 G20-3. The manufacturer shag notify CREEK
Technical Services,LLC of any product changes or quality assurance thong throughout the duration for which this report is valid..
This evaluation.report does not express nor imply warranty,installation,reco nmended use.or other product attributes that are not
specifically addressed herein.
i
� I
MID-STATES ASPHALT AND CANT STRIP,INC
!xp- CREEKSelf-Adhering Undertayments
TECHNICAL SERVICES,LLC
GENERAL Umiu'nONS
1) This evaluation report is not use in the HVHZ.
2) Fire.Classification is not within the scope of this evaluation.
3) Installation of the evaluated product shall comply with this rt,the FBC,and the manufacturer's published
application instructions. Where discrepancies exist betweer these sources,the more restrictive and FBC
compliant installation detail shall.prevail.
4) The roof deck shall be constructed of closely fitted plywood Bathing for new or existing construction.
5) The space under the deck area shall be properly ventilated in 3ccordance with the FBC requirements.
6) All side lap seams shall be installed to shed water from the de k.
7) The underlayment may be used as described in other current BC product approval documents.
8) Design wind load pressures shall be determined for comp nests and cladding in accordance with FBC
1609.
9) The roof deck shall be designed by others in accordance W FBC requirements to resist the design wind
load pressures for componentsand cladding.
10) Maximum Design Pressures for a given undedayment shall meet or exceed the design wind loads
determined for the roof assembly.
11) All products listed in this report shall be manufactured under c i quality assurance program in compliance with
Rule 61020-3.
REFERENCES
Entity Report No. Standard Year
PRI Construction Materials Technologies(TST5878) BWR-514-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies(TST5878) BWR-522-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies(TST5878) BWR-533-02-01 TAS 103 1995
PRI Construction Materials Technologies(TST5878) BWR-534-02-01 ASTUD 1970 2015a
ASTM D 4798 2011(2016)
'PRI Construction Materials Technologies(TST5878) SWR 543-02-01 ASTM D 1970 2015a
PRI ConstmetionMaterials Techndlogtes:(TST5878) WRMI-011-02-01 ASTM D 1970' 2015a
PRI ConstU fiction Materials Technologies(rST6049) -MSA-007-02-01 UL 1897 "" 2012
PRI Construction Materials Technologies(TST6049) MSA-026-02-01 ASTM D 1970 2015a
I
MSA17001 FL17401-R4 Page 3 of 4
This evaluation report is provided for State of Florida product approval under ule 611320-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance change.throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation, runerided use..or other product attributes that are not
specifically addressed herein.
MID-STATES ASPHALT AND CANT STRIP,INC
CREEKSelf-Adhering Underlayments
IL
s
TECHNICAL SERVICES,LLC
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have dem 3nstrated compliance with the Florida Building
Code,6Edition(2017)as evidenced in the referenced documents sul imitted by the named manufacturer.
�r,�u rurrrr
,%01,�.RY.R. 2017.10.11
11 :41:31
�y No 74021 j
� R� •(^yam� WWMMbnMi,Ne -04'00'
�O•,•• STATE OF
•- Q _�� Zachary R.Priest,P.E.
�i��S••� R t.�•• ��%�` Florida Registration No.74021
�% Organization No.ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services,LLC does not have,nor will it acquire,a financial interest in any company manufacturing or distributing
products under.this evaluation.
CREEK Technical Services,LLC is not owned,operated,or controlled by any i ompany manufacturing or distributing products under
this-evaluation.
Zachary
his evaluation-
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R.-Priest,P.E.does-not have,nor will acquire,a financiaUnterest'in ai iy other entity involved,inths approvaLprocess of.the
product.
END OF REPORT
MSA17001 FL17401-R4 Page 4 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20.3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance chang throughout the duration for which this report is valid.
This evaluatiorrreport does not express nor imply warranty,installation,rm mmended use,or other product attributes that are not
specifically addressed herein.