HomeMy WebLinkAboutProduct approvalEAGLEVIEW 0
LENGTH DIAGRAM
Total Line Lengths:
Ridges = 67 ft
Hips =Oft
Valleys = 0 ft
Rakes = 92 ft
Eaves = 175 ft
Premium Report
6/19/2018
Flashing = 43 ft
Step flashing = 0 ft
Parapets = 0 ft
w � E
Note: This diagram contains segment lengths rounded to the nearest whole number over 5.0 Feet. to some cases segment labels
have been removed for readability. Plus signs preface some numbers to avoid confusion when rotated e.. +6 and +9).
ZOOB-2018 Eagle Vie. Technologies, Inc and Plctomerry Intemanonal Corp. — All Rights Reserved — ProbBr%d by European Patent Application No. 10152199.3 — Covered by one or more of U.S. Patent Nos. 8,878,936; 8,145,578; 8,170,898;
8,209,152; 8,515,125; 8,825,454; 9,135,737; 8,678,961; 9,514,568; 8,818,778; 8,52,880; 9,244,589; 9,329,749; 9,599,485. Other Patents Pending.
PAGE 4
EAGLES IEWO Premium Report
V 6/19/2018
PITCH DIAGRAM
Pitch values are shown in inches per foot, and arrows indicate slope direction. The predominant pitch an this roof is 4/12
1— 4
4 —r
Note: This diagram contains labeled pitches for facet areas larger than 20 .0 square feet In some cases pitch labels have been
removed for readability. Blue shading indicates a pitch of 3/12 and greater. Gray shading indicates flat, 1/12 or 2/12 pitches. If
present, a value of "F" indicates a flat facet (no pitch),
0512008-2018 Eagle View Technologies, Inc. and RdOrnetry International Corp. —All Rights Reserved — Protected by European Patent Application No. 10162199.3 — Covered by orie or mom of U.S. Patent Nos. 8,[778,436; 8,145,578; 8,170,840;
8,2{19,152; BS15,125; 8,825,454; 9,135,737; 8,b70,901; 9,514,568; 8,818,770; 8,592,880; 9,244,589; 9,329,749; 9,599,466. Other Pate.ts Pending.
PAGE 5
�EAGLEVIEW Q)
AREA DIAGRAM
Total Area = 2,844 sq ft, with 3 facets.
427
1189
1189
Premium Report
6/19/2018
Note: This diagram shows the square feet of each roof facet rounded to the nearest Foot . The total area in square feet at the to
of this page, is based on the non -rounded values of each roof facet rounded to the nearest s uare foot after being totaled).
C% 2008-2618 Eagle View Technalogies, Inc. and Plctometry international rup. — All Rights Reserved — P* tested by European Patent Appticacian No. 10152199.3 — Covered by one or mere of u.s. Patent hos. 8,078,936; 8,145,576; 8,170,890;
8,209,152; 8,515,125; 8,825,454; 9,135,737; 8,670,961; 9,514,558; 8,818,770; 8,542,989; 9,244,589; 9,329,749,; 9,599,466. Other Patents Pending.
PAGE 6
6/612018 Florida Building Code f?nline
6CiS Nto ne Log rn { User Registration i Hot Topics Submit Surcharge I Stats & Facts Publications
b'Product Approval
USER: Public User
Product Approval menu > Product ar Appiicat'son Sezrch. > Application List > Application Detail
FL *
FL17322-R4
Application Type
Revision
Code Version
2017
Application Status
Approved
Comments
Archived
Product Manufacturer Atlas Roofing Corporation
Address/Phone/Email 2000 RiverEdge Parkway
Suite 800
Atlanta, CA 30328
(770) 946-4571
mcoilins@atlasroofng.com
Authorized Signature Meldrin Collins
mcollins c@atlasroofing.com
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Underlayments
E
2015
ASTM D 226
ig 'aa
ASTM D 2626
2004
ASTM D 4869
2016
ASTM D 6380
2003
FBC Staff. _ BCIS Site Map
Links - Search
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report - Hardcupy Received
Florida Engineer or Architect Name who developed Zachary R. Priest
the Evaluation Report
Florida License PE -74021
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 12/31/2020
Validated By Locke Bowden P.E.
Validation Checklist - Hardcopy Received
Certificate of Independence FL17322 R4 COI ATL14QO1,4A 2017 FBC Eva[ Refgort Atlas
Underlayments final.pdf
Referenced Standard and Year (of Standard) Standard Year
ASTM D 1970
2015
ASTM D 226
2009
ASTM D 2626
2004
ASTM D 4869
2016
ASTM D 6380
2003
TAS 103
1995
TAS 110
2000
UL 1897
2012
Equivalence of Product Standards
hops://www. ooridabuilding.org/pr/pr4app_dtl.aspx?param=wGEVXQwtDgsRyNwiNWDrY8PHC4TwsBEc8KxLSaJJG7DPQ]kaGxFKuQ°/a3d'/o3d 1/2
61612018
Certified By
Sections from the Code
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
of Products
Florida Building Code Online
Method 1 Option D
09/30/2017
10/03/2017
10/04/2017
12/12/2017
I FL # Model, Number or Name
; Description
l�
17322.1 Atlas Underlayments
For use in steep slope roofing
Limits of Use
6 Installation Instructions
j Approved for use in HVHZ: Yes
F1_17322 R4 11 ATL140GI.4A 2017 FBC Eva] Report Atlas
Approved for use outside HVHZ: Yes
Underiayments final.pcl
Impact Resistant: N/A
I Verified By: Zachary R. Priest 74021
Design Pressure: N/A
i Created by Independent Third Party: Yes
i Other. See evaluation report for limits of use.
I Evaluation Reports
i
FI -17322 R4 AE ATL14001,48 2017 FBC F.val ReportAtlas
Fabral Underlayment final. pclI
Underlayments final.pdf
1 Created by Independent Third Party: Yes j
7322.2 _ j Fabral All Purpose High Temp i
ASTM D 1970, SBS modified, self -adhering underlayment with j
f Underlayment
fiberglass mat reinforcement and a poly -fabric surface.
L Ys of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL17322 R4 II ATL14001.4B 2017 FBC Eval Report Atlas
Fabral Underlayment finai.pdf
I Approved for use outside HVHZ: Yes
Impact Resistant: N/A i
Verified By: Zachary R. Priest PE -74021
Design Pressure: N/A
Created by Independent Third Party: Yes
Other: See evaluation report for limits of use.
Evaluation Reports
1
FL17322 R4 AE ATL14001,4B 2017 FBC Eval Report Atlas
Fabral Underlayment final. pclI
Created by Independent Third Party: Yes ;
Contact Us :: 2601 Bia}r Stone Road, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida Is an AA/EEO employer. Cop_yright 2007-2013 Stade of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic
maii to this entity. Instead, contact the office by phone or by traditional mail. IF you have any questions, please contact 850.487.1395. *Pursuant to Section
455.275(1), Florida Statutes, effective October 1, 2012, licensees licersed under Chapter 455, FS- must provide the Department with an email address if they have
one. The emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personal
address, please provide the Department with an email address which can be made available to the public. To determine it you are a licensee under Chapter 455, F.S.,
please dick here .
Product Approval Accepts:
Credit Card
Safe
ht,ps:flwww.floddabuilding.org/prlpr_app_dtl.aspx?param=wGEVXQwtDq,gRyNwiNWDrY8PHC4TwsBEc8KxLSaJJG7DPQ[kaGxFKuQ%3d%3d 2/i
0 71
EVALUATION REPORT
Manufacturer: ATLAS ROOFING CORPORATION
2000 Riveredge Parkway, Suite 800
Atlanta, GA 30328
(770)612-6267
www.atlasroofing.com
Quality Assurance
SCOPE
UL LLC (QUA9625)
Certificate of Authorization No. 23824
17520 Edinburgh Dr
Tampa, FL 33647
(813)480-3421
FLORIDA BUILDING CODE, 6T" EDITION (2017)
Category:
Roofing
Subcategory:
Underlayments
Code Sections:
1507.1.1, 1518.4,1523.1.1,1523.6.5.2-1
Properties:
Physical properties
REFERENCES
Issued September 30, 2017
Entity
Report No.
Standard
Year
PRI Construction
Materials Technologies (TST6049)
ATL -033-02-01
ASTM D 226
2009
PRI Construction
Materials Technologies (TST6049)
ATL -068-02-01
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST6049)
ATL -068-02-01
ASTM D 4798
2011(2016)
PRI Construction
Materials Technologies (TST6049)
ATL -068-02-01
TAS 110
2000
PRI Construction
Materials Technologies (TST6049)
ATL -069-02-D1
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST6049)
ATL -090-02-01
TAS 103
1985
PRI Construction
Materials Technologies (TST6049)
ATL -149-02-01
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST6049)
ATL -164-02-01
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST6049)
BWR-533-02-01
TAS 103
1995
PRI Construction
Materials Technologies (TST6049)
BWR-543-02-01
ASTM 0 1970
2015a
PRI Construction
Materials Technologies (TST6049)
MSA -004-02-01
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST6049)
MSA -007-02-01
UL 1897
2012
PRI Construction
Materials Technologies (TST6049)
MSA -026-02-01
ASTM D 1970
20158
PRI Construction
Materiels Technologies (TST6049)
WRMI-011-02-01
ASTM 1970
2015a
PRI Construction
Materials Technologies (TST6049)
MSA -D07-02-01
UL 1897
2012
PRI Construction
Materials Technologies (TST6049)
MSA -034-02-01
ASTM D 1970
2015a
UL LLC (TST1740)
02-NK40952
ASTM D 1970
2015a
UL LLC (TST1740)
02-NK40952
ASTM D 226
2009
UL LLC (TST1740)
02-NK40952
ASTM D 2626
2004(2012)E1
UL LLC (TST1740)
02-NK40952
ASTM D 4869
2016
UL LLC (TST1740)
02-NK40952
ASTM D 6380
2003 (2013)
ATL14001.4A FL17322-R4 Page 1 of 4
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK ATLAS ROOFING CORPORATION
Roofing Underlayments
TECHNICAL SERVICES. LLC
PRODUCT DESCRIPTION
#15 Specification Felt ASTM D 226, Type I asphalt saturated organic felt underlayment for use in the
HVHZ and non-HVHZ,
#30 Organic Saturated Felt
ASTM D 4869, Type 11 asphalt saturated organic felt underlayment for use in the
non-HVHZ only.
#30 Specification Felt
ASTM D 226, Type 11 asphalt saturated organic felt underlayment for use in the
HVHZ and non-HVHZ,
#43 Base Sheet
ASTM D 2626 asphalt saturated and coated, non -perforated, organic felt
underlayment for use in the HVHZ and non-HVHZ,
#90 Mineral Surface Roll
ASTM D 6380, Class M asphalt -saturated organic roll roofing sheet for use in the
Roofing
HVHZ and non-HVHZ.
Gorilla Guard@ EVERFELT 30
Asphalt -saturated organic felt underlayment reinforced with glass fiber that meets
the performance requirements of ASTM D 226, Type I for use in the HVHZ and
non-HVHZ.
Slate/Tile Underlayment
ASTM D 6380, Class M asphalt -saturated organic roll roofing sheet for in
use the
HVHZ and non-HVHZ.
WeatherMaster@ Ice and
Water 100
ASTM D 1970 SBS modified, self -adhering underlayment reinforced with a
fiberglass mat and a granular surface for use in the HVHZ and non-HVHZ. The
self-adhesive side is covered with a release film, which is removed during
installation.
WeatherMaster@ Ice and
Water 200
ASTM D 1970 SBS modified, self -adhering underlayment reinforced with a
fiberglass mat and a granular surface for use in the HVHZ and non-HVHZ. The
self-adhesive
side is covered with a split -release film, which is removed during
installation.
WeatherMaster@ Ice and
Water 216
ASTM D 1970 SBS modified, self -adhering underlayment reinforced with a
fiberglass mat and a granular surface for use in the HVHZ and non-HVHZ. The
self-adhesive side is covered with a split -release film, which is removed during
installation.
WeatherMaster@ Flexible Ice ASTM D 1970 SBS modified, self -adhering underlayment with plastic film surface
and Water for use in the HVHZ and non-HVHZ. The self-adhesive side is covered with a
split -release film, which is removed during installation.
WeatherMaster@) Pro -Grade ASTM D 1970 SBS modified, self -adhering underlayment with a fiberglass mat
Ice and Water reinforcement and a poly -fabric surface for use in the HVHZ and non-HVHZ. The
self-adhesive side is covered with a release film, which is removed during
installation.
WeatherMaster@ Tile TAS 103 SBS modified, self -adhering underlayment with a fiberglass mat
reinforcement and a poly -fabric surface for use in the HVHZ and non-HVHZ. The
self-adhesive side is covered with a release film, which is removed during
installation.
ATL14001.4A FL17322-R4 Page 2 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL, SERVICES, LLC
ATLAS ROOFING CORPORATION
Roofing Underlayments
APPLICATION METHOD
Installation shall be in accordance with the published manufacturer's installation instructions, the FBC, and the
requirements below.
Deck substrates shall be clean, dry, and free from any irregularities and debris_ All fasteners in the deck shall be
checked for protrusion and corrected prior to underlayment application.
The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. Plywood deck
shall be installed in accordance with FBC requirements. Roof decks shall have no more than 1/8" gap at abutting
joints.
Exposure of the underlayments shall be limited to a maximum 30 days except as follows:
a) #15 Specification Felt, #30 Specification Felt, and #40 Base Sheet — exposure for than 24 hours may
adversely affect product performance
b) WeatherMaster@ lce and Water 100, WeatherMaster@ Ice and Water 200, and WeatherMaster® Ice
and Water 216 — maximum 30 days
c) WeatherMaster@ Pro -Grade Ice and Water and WeatherMaster@ Flexible Ice and Water — maximum
30 days
d) WeatherMaster@ Tile — maximum 90 days
Self -adhering underlayments may be adhered to primed or unprimed plywood substrates in the non-HVHZ.
Roof coverings shall be mechanically fastened through the underlayment to the roof deck except as follows (or as
indicated in other current FBG product approval documents):
a) WeatherMastera Pro -Grade Ice and Water or WeatherMaster@ Tile — ICP Adhesives Polyset AH -160
b) Slate/Tile Underlayment or #90 Mineral Surface Roll Roofing — Convenience Products Touch n' Seal
StormBond Roof Tile Adhesive, Dow TileBond, or ICP Adhesives Polyset AH -160
Allowable Roof Coverings:
Underlayment
Asphalt
Shingles
Metal Roof Composite or
Panels and Photovoltaic
Shingles Shingles
Wood
Shingles and
Shakes
Slate Clay and
Shingles Concrete Tile
#15 Specification Felt
Y
Y Y
Y
Y N
#30 Organic Saturated Felt
Y
Y Y
Y
Y N
#30 Specification Felt
Y
Y Y
Y
Y Y
#43 Base Sheet
Y
Y Y
N
Y Y
#90 Mineral Surface Roll Roofing
Y`
N N
N
N Y
Gorilla GuardC EVERFELT 30
Y
Y Y
y'
Y N
SlatelTile Underlayment
Y'
N N
N
N Y
WeatherMasterO Ice and Water
100
Y
Y Y
N
Y N
WeatherMastero Ice and Water
200
Y
Y Y
N
Y N
WeatherMaster@ ice and Water
216
Y
Y Y
N
Y N
WeatherMasterg7 Flexible Ice and
Water
Y
Y Y
N
Y N
WeatherMaster@ Pro -Grade Ice
and Water
Y
Y Y
N
Y N
WeatherMaster@ Tile
N
Y
Y Y
N
Y Y
otes: 1? Open valley appucatlons per 1507,2.9.2
2) Wood shingles only
ATL14001.4A FL17322-R4 Page 3 of 4
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3_ The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid_
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
iffim
CREEK
ATLAS ROOFING CORPORATION
Roofing Underlayments
TECHNICAL SERVICES. LLC
WIND RESISTANCE (NON-HVHZ ONLY)
The Maximum Design Pressures shown below were calculated using a 2:1 margin of safety per FBC Section 1504.9.
Underla ment S stem No.1 — WeatherMastero Tile Qnl
Roof Deck: Min, 15132 -inch CDX plywood attached to wood supports spaced a maximum 24" o.c,
Underlayment: WeatherMaster@ Tile shall be fully adhered to the optionally primed plywood deck.
Maximum Design -52.5 psf
Pressure:
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Roof slope limitations shall be in accordance with FBC requirements.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Products described within this report may be used as described in other current FBC product approval
documents.
5) Roof coverings shall not be adhered directly to the underlayment unless otherwise approved in this or other
current FBC product approval documents.
6) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest P.E. have demonstrated compliance with the Florida Building
Code, 6'h Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
E-''' 2017-09.30
4 No 74021 12:44:22 ^ja2
�- STATE OF
-04'00'
p R O Zachary R. Priest, P.E.
Florida sSI101igistration No.
0NA` � �i Organization No. ANE9641021
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
ATL14001.4A FL17322-R4 Page 4 of 4
This evaluat€on report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
blolzu`18
Flodda Building Code Online.
SOMm t Surcharge Stats & Paas Puhlieations F8C Staff Sc is Site map Links Search
{-..-. '—'_ —�--_> �•'JGEa C: CF FI-7aliC�'<3� sca lii�
�
7
,.��
_ . - u- > Applicatlon Detail
FL T
Application Type
FL16305-R6
Code Version
Revision
Application Status
2017
Approved
Comments
Archlved
Product Manufacturer
Address/Phone/Email
Atlas Roofing Corporation
2000 RiverEdge Parkway
Suite 800
Atlanta, GA 30328
(770) 945-4571
mcollins@atlasroofing.com
Authorized Signature
Meldrn Collins
ncoliins@atlasroofinQ.com
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category
Subcategory Roofing
Asphalt Shingles
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed Zachary R. Priest
the Evaluation Repot
Florida License
Quality Assurance Entity PE -74021
UL LLC
Quality Assurance Contract Expiration Date 12/31/2020
Validated By
Locke Bowden PE.
Validation Checklist - Hardcopy Received
Certificate of Independence - -_ r
_� nau� ^c` CC3-
ai
Referenced Standard and Year (of Standard)
Standard
ASTM D3161
Year
ASTM D 3462 2016
ASTM D 7158 2010
TAS 100 2011
TAS 107 1995
1995
Equivalence of Product Standards
Certified By
Sections from the Code
s:i"W'-h,',;c,idahuilding.orglor/pr app_dtl.aspx?param=WGEVKQwDgtjja ljgUfj3NITGPID8aJCJnk�io2hsJZMHcThL8V13,i-/5,;,o,,,,.,,,,,.,,
W61201 8
Florida Building Code Online
ProduLt Approval Method
Date Submitted
Date Valid2ted
Date Pend�no FBC Approval
Date Approved
Summ oducts
FL Model, Number or Name
!6305.1 ; —At,,, Shingle
Limits of Use
APPrOved for use in HVHZ: yes
Approved for use Outside HVHZ� yes
!MP--Ic:t Resistant: N/A
Design Pressure: N/A
Other: See evaluation rePort for limits of use
Method 1 OpVon D
09/30/2017
10/03/2017
10/04/2017
12112/2017
Description
f Flberg]ESS neInforred larnfriated asphalt shingles
Installation instructions
FL26305 P,6 TT ATLI3002 6 201—, 1 Fz �LK7 _5!_1'Mj(7iC�c
Verified By: Zachary R. Priest 74021
Created by Independent Third Party: Yes
Evaluation Reports
FL16305 P,5 AE ATL!3�002�5
Created by Independent Third Party: Yes
Contact Us *: 25g I Blair StOne goad� Pho��. JiS0_487_1824
State Of Floride is arl AAIE�::O employer- 2�_L'9LL,2_M7-2Dj3 State of porida.
zrivacy�� � :: RtLazim_�
tatnment :.
Under i'larida law, ernail addresses are Public records. If you do no, w2ntYOure-n1aH address released in resp=se to a Public -records request, Ono., rn
mail to this entity. instead ' contact the office tl,� phone or by zraditiona I rneil d erld e ect 0 it
455.2 75(j), Florida Statutes, Ou hava any questions, Please contact 650.487.1395, �Pursuant to Section
aPter 455, Fs� must Pravide the Department with an email address if they have
xcl May be used j or offcial �c'omrnun�catil)n Wth the lfccrisee. However email addresses are Public record. If you do not wish to SUPPly a per onal
One. The emaiTs Provide effective October 1 2012, Itersees licensed under Chy
addFass, Please Provide the DePartment with Bn CMEJ] address which can be made available to the public. To determine if You are a licensee underChapter 455, 5F.S.,
niezise click t-e—re .
Product APProval Accepts.,
lr=1 R� E
Credit GP -rd
Safe
2�. J
:s:!'."'�",'v�,lar'idabuilciirig.oralpriP�—aPP—dtl-aSpx?param=WGEVXQMDquJBMjgUlj3NI7'GPID8aJC,'.I,kDl-'.)�,� �' .1 1—, — —
Certificate of Authorization No. 29824
R E E K17520 Edinburgh Dr
Tampa, FL 33647
FCHNICAL SERVICES, LL (813) 480-3421
EVALUATION REPORT FLORIDA BUILDING CODE 6TH EDITION (2017)
Manufacturer:
ATLAS ROOFING CORPORATION Issued September 30, 2047
Pinnacle® Pristine
2000 Riveredge Parkway, Suite 800
GlassMaster& 30
Atlanta, GA 30328
(Ardmore & Hampton)
(770) 612-6267
Manufacturing Plants:
Hampton, GA
(Ardmore & Hampton)
Meridian, MS
Pro -Cut® Hip & Ridge
Dangerfield, TX
(Ardmore & Hampton)
Ardmore, OK
Franklin, OH
Quality Assurance:
UL LLC (QUA9625)
SCOPE
Category: Roofing
Subcategory: Asphalt Shingles
Code Sections: 1504.1.1, 1507.2.5, 1507.2.7.1, 1523.6.5.1
Properties: Physical properties, Wind Resistance, Wind Driven Rain
PRODUCT DESCRIPTION
Legend (Ardmore)
ASTM D 3161, Class F fiberglass reinforced, 3 -tab asphalt shingle with a dashed,
Pinnacle® Pristine
thermally -activated, self-sealing sealant stripe that complies with ASTM D 3462.
GlassMaster& 30
ASTM ❑ 3161, Class F fiberglass reinforced, 3 -tab asphalt shingle with a dashed,
(Ardmore & Hampton)
thermally -activated, self-sealing sealant stripe that complies with ASTM D 3462.
Tough-Master&20
ASTM D 3161, Class F fiberglass reinforced, 3 -tab asphalt shingle with a dashed,
(Ardmore & Hampton)
thermally -activated, self-sealing sealant stripe that complies with ASTM D 3462.
Pro -Cut® Hip & Ridge
ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt shingle with a
(Ardmore & Hampton)
dashed, thermally -activated, self-sealing sealant stripe that complies with ASTM D
3462.
Pro -Cut& Starter Strip ASTM D 3161, Class F fiberglass reinforced, starter asphalt shingle with a dashed,
(Hampton) thermally -activated, self-sealing sealant stripe that complies with ASTM D 3462.
ProLAMTm Architectural ASTM D 3161, Class F & ASTM D 7158, Class H fiberglass reinforced, laminated
(Hampton, Franklin & architectural asphalt shingle with a dashed, thermally -activated, self-sealing sealant
Meridian) stripe that complies with ASTM D 3462
Pinnacle® Pristine,
ASTM D 3161, Class F & ASTM D 7158, Class H fiberglass reinforced, laminated
Pinnacle® Pristine
architectural asphalt shingle with two, dashed, thermally -activated, self-sealing sealant
Lifetime w/Scotchgard
stripes that complies with ASTM D 3462.
(Dangerfield, Hampton,
Franklin & Meridian)
StormMaster® Shake
ASTM D 3161, Class F & ASTM D 7158, Class H fiberglass reinforced, laminated
(Dangerfield)
architectural modified asphalt shingle with two, dashed, thermally -activated, self-sealing
sealant stripe that complies with ASTM D 3462.
ATL13002.6 FL 16305-R6 Page 1 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEKATLAS ROOFING CORPORATION
Asphalt Shingles
Wa TECHMICAL SERVICES. LLC
StormMaster@ Slate ASTM D 3161, Class F & ASTM D 7158, Class M fiberglass reinforced, laminated
(Ardmore) architectural modified asphalt shingle with two, dashed, thermally -activated, self-sealing
sealant stripe that complies with ASTM D 3462.
REFERENCES
Entity
Report No.
Standard
Year
PRI Construction Materials Technologies (TST5878)
ATL -079-02-01
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -083-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -086-02-01 Rev 1
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -104-02-01
ASTM D 3462
2010A
PRC Construction Materials Technologies (TST5878)
ATL -106-02-01
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -106-02-01 Rev 1
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -107-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -107-02-01.1
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -109-02-01
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -116-02-D1
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -118-02-01
ASTM D 3462
2010A
PRi Construction Materials Technologies (TST5878)
ATL -119-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -123-02-01
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATLA 25-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -127-02-01 Rev 1
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -132-02-01
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -133-02-01
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -135-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -136-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -137-02-D1 Rev 1
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -138-02-01 Rev 1
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -143-02-01
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -144-02-01
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -151-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -162-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATLA 67-02-01
ASTM D 3161
2016
PRI Construction Materials Technologies (TST5878)
ATL -168-02-01
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -169-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -170-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATLA 71-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -172-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -174-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -179-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -184-02-01
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -185-02-01
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -186-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -187-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -220-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -220-02-02
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -220-02-03
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -220-02-04
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -221-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -22.1-02-02
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -221-02-03
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -221-02-04
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -222-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -222-02-02
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -222-02-03
ASTM 1) 3161
2016
ATL13002.6 FL 16305-R6 Page 2 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL LAICAL SERVICES, LLC
ATLAS ROOFING CORPORATION
Asphalt Shingles
ATL13002.6 FL 16305-136 'Page 3 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3_ The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein..
Report No,
Standard
Year
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -222-02-04
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -223-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -223-02-02
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -223-02-03
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -223-02-04
ASTM D 7158
2011
PRI Construction Materials Technologies (TST5878)
ATL -224-02-01
ASTM D 3462
2010A
PRI Construction Materials Technologies (TST5878)
ATL -225-02-01
ASTM D 3462
2010A
PRI Construction Materiels Technologies (TST5878)
ATL -225-02-02
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
ATL -225-02-03
ASTM D 3161
2016
TAS 107
1995
PRI Construction Materials Technologies (TST5878)
ATL -225-02-04
ASTM D 7158
2011
ATL13002.6 FL 16305-136 'Page 3 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3_ The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein..
CREEK
TECi-If',1 CAL SERVICE s, LLC
INSTALLATION
Legend Basic Wind Speed (Vu,r):
Basic Wind Speed (Vag):
Deck (HVHZ):
Deck (Non-HVHZ):
Underlayment:
Min. slope:
Installation (HVHZ):
Installation (Nan-HVHZ):
�I
ATLAS ROOFING CORPORATION
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed mics. 19/32 in, plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
In accordance with FBG requirements;
Solidly sheathed min. 15132 in. plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FISC requirements. Contact
the Atlas Roofing Corporation when installing at slope
greater than 21:12.
Installed with 5 -inch exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 5 -inch exposure in accordance with FBC
requirements and manufacturer's published installation
instructions- Shingles shall be attached using either 'A Nail
Pattern" or "6 Nail Pattern" detailed below.
Figure 1. Legend 4 Mail Pattern (Non-HVHZ only)
+_
�13� �{��� P%IGFL ,LL �s.•II
s.-----�!
Figure 2. Legend 6 Nail Pattern
ATL13002.6 FL 16305-R6 Page 4 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technicai Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does riot express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHN11CAL SERVICES. LLC
GlassMaster@ 30 &
Tough -Master® 20
Basic Wind Speed (Vint):
Basic Wind Speed (Vam):
Deck (HVHZ):
Deck (Non-HVHZ):
Underlayment:
Min. slope:
Installation (HVHZ)
Installation (Non-HVHZ):
ATLAS ROOFING CORPORATION
Asphalt Shingles
Max. 194 mph
Max. 1501 mph
In accordance with FBC requirements;
Solidly sheathed min. 19132 in. plywood or wood plank for
new construction; Min, 15132 in, plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15132 in, plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FSC requirements. Contact
the Atlas Roofing Corporation when installing at slope
greater than 21:12.
Installed with 5 -inch exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 5 -inch exposure in accordance with FBC
requirements and manufacturer's published installation
instructions- Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern" detailed below.
Nark
rrw "M am 1r NM a W= +rte owe rwrr arra
14 --_ -- 12+_ 1 __ I
Figure 3. GlassMaster@ 30 & Tough -Master@ 20 4 Nail Pattern (Non-HVHZ only)
Evils
Figure 4. GlassMaster@ 30 & Tough -Master@ 20 B Nail Pattern
ATL13002.6 FL 16305-R6 Page 5 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
ECREEK
TECHNICAL SERVICES, LLC
ProLAMT"" Architectural Basic Wind Speed (V,,it):
Basic Wind Speed (Vard):
Deck (HVHZ):
Deck (Non-HVHZ)
Underlayment:
Min. slope:
Installation (HVHZ):
Installation (Non-HVHZ):
ATLAS ROOFING CORPORATION
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;.
Solidly sheathed min. 19132 in. plywood or wood plank for
new construction; Min. 15132 in- plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15132 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Contact
the Atlas Roofing Corporation when installing at slope
greater than 21:12.
Installed with 6 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 6 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern" detailed below.
GI4irL� Y•" SL4L=Ji7 %F PATTER':
LEHCTLi GN'_ I' OF
% ' 3
t
117-
-
1F
.....---------
-._..
Lr qc;utrcarsEA
� sly
Figure 5. ProLAMTl* Architectural Shingle 4 Nail Pattern (non-HVHZ only)
Figure 6. Pro-LAMTm Architectural Shingle 6 Nail Pattern
ATL13002.6 FL 16305-R6 Page 6 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECF{NINCAL SERVICES. LLC
Pinnacle® Pristine & Basic Wind Speed (Vuf1):
StormMaster(R) Shake Basic Wind Speed (Vard):
Deck (HVHZ):
Deck (Non-HVHZ):
Underlayment:
Min. slope:
Installation (HVHZ):
Installation (Non-HVHZ):
ATLAS ROOFING CORPORATION
Asphalt Shingles
Max. 194 mph
Max. 156 mph
In accordance with FBC requirements;
Solidly sheathed min. 19132 in. plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15132 in. plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Contact
the Atlas Roofing Corporation when installing at slope
greater than 21:12.
Installed with 6 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 6 in, exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either 'A Nail
Pattern" or "6 Nail Pattern" detailed below.
2"
I DOUBLE r' SEALANT UNE PA-FF—RN 1
IcO-TOIM: 1" LENGTH ON', 1" OrF I
1313'
14"- lYF
i"
— r--------------�i –---------...-.. - --------------------- --------- --- _..--- ----- ----
4111111111— 411111111IL—
74` b$ ,
i v.
I
Figure 7. Pinnacle@ Pristine and StormMasterC) Shake 4 Nail Pattern (Non-HVHZ only)
SEALANT LINE =<
LENGTH ©W 1" OFF
----------------r
- 1' - r- - -
--•--------- f ---------------
- ------ - ---- --- ---- -- --------------------- ....... ..-- -
�-
La�• �1F.�; 71G PREF
11111111111W_ – son_
Figure 8. Pinnacle@ Pristine and StormMastert] Shake 6 Nail Pattern
ATL13002.6 FL 16305-R6 Page 7 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
14"
CREEK
TECHNICAL SERVICES. LLC
StormMaster0 Slate Basic Wind Speed (V,,it):
Basic Wind Speed (V,�):
Deck (HVHZ):
Deck (Non-HVHZ)
Underlayment:
Min. slope:
Installation (HVHZ)
Installation (Non-HVHZ):
ATLAS ROOFING CORPORATION
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19{32 in. plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15132 in. plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction_
In accordance with FBG requirements.
2:12 and in accordance with FBC requirements. Contact
the Atlas Roofing Corporation when installing at slope
greater than 21:12.
Installed with 8.5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 8.5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern" detailed below..
Figure 9, StormMaster0 Slate 4 Nail Pattern
T
1
Figure 10. StormMaster@ Slate 6 Nail Pattern
ATL13002.6 FL 16305-R6 Page 8 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERV€CES, LLC
Pro -Cut® Starter Strip Basic Wind Speed (Vuir):
Basic Wind Speed (Vasa)
Deck (HVHZ):
Deck (Non-HVHZ)
Underlayment:
Min- slope:
Installation (HVHZ)
Installation (Non-HVHZ)
ATLAS ROOFING CORPORATION
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19132 in. plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7116 in. 038 existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBG requirements. Contact
the Atlas Roofing Corporation when installing at slope
greater than 21:12.
Installed in accordance with RAS 115 and manufacturer's
published installation instructions. Shingles shall be
attached as shown below.
Installed in accordance with FBC requirements and
manufacturer's published installation instructions. Shingles
shall be attached as shown below.
------------------------------------ -------------
u-
H3 PtOn
! 2 ga. 1-1l2' .fag shar.& nail
1
Figure 91. Pro -Cut@ Starter Strip
ATL13002.6 FL 16305-R6 Page 9 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
i EEK
PCO -Cuter Hip & Ridge Basic Wind Speed (V„ 1t):
Basic Wind Speed (V,,):
Deck (HVHZ):
Deck (Non-HVHZ):
Undertayment:
Min. slope:
Installation (HVHZ and
non-HVHZ):
ATLAS ROOFING CORPORATION
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19132 in_ plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15132 in, plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements.
Installed with 5-518 inch exposure in accordance with RAS
115 (HVHZ only) and manufacturer's published installation
instructions. The direction of the exposed end shall be
away from the prevailing wind.
T
12 ga. 1-1/2" ring
i shank nail
1,
_12" 2"
6"
it
t
i
Figure 12. Pro -Cut@ Hip & Ridge
ATL13002.6 FL 16305-R6 Page 10 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEKATLAS ROOFING CORPORATION
Asphalt Shingles
TECHNICAL SERVICES, LLC
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) The roof deck and the roof deck attachment shall be designed by others to meet the minimum design loads
established for components and cladding and in accordance with FBC requirements.
3) The mean roof height shall be restricted to a maximum 33 ft in the HVHZ.
4) Classification to ASTM D 7158 applies to exposure B & C with a building mean roof height of 33 -ft or less.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) Shingles shall be installed starting at the eave in horizontal layers such that the laps shed water from the
deck.
7) Installation of the evaluated products shall comply with this report, the FBC, and the manufacturer's
published application instructions. Where discrepancies exist between these sources, the more restrictive
and code compliant detail shall prevail.
8) All products listed in this report shall bo manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6th Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
E�N s��'�!
No 74021
m
` 13 STATE OF .� 4iJ d
CERTIFICATION OF INDEPENDENCE
2017-©9.3
lZ��'- 0 12:3724
—04400'
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
ATL13002.6 FL 16305-R6 rage 11 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.