INTRODUCTION INTERLOCK KIT K-5011 1WERLOOCKIT
This manual provides instructions for safe installation of the InterLock Kit onto a
Square-D panel. The back plate sits securely on the face of the panel cover while
allowing the front plate to slide between the main and generator breaker positions.The
InterLock Kit will only allow one of these breakers to be in the"ON"position meeting
the requirements of Article 702 of the National Electric Code ANSI/NFPA 70. The
installation of the breaker retaining strap meets Article 408.36 (NEC 2008).
SAFETY PRECAUTIONS—IMPORTANT SAFETY INSTRUCTIONS
WARNING: HAZARD OF ELECTRIC SHOCK OR EXPLOSION
- This kit must be installed and serviced only by qualified electrical personnel
- Turn off all power supplying the equipment where,this kit will be installed before
working on or inside the equipment
- Always use a properly rated voltage sensing device to confirm that all power is
off
- Replace all devices, doors,and covers after installing this kit before turning on
power to the equipment
- Always wear safety eyewear while drilling or working around electrical ,
equipment
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS
INJURY OR DEATH
SAFE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
1) Disconnect power to the panel
2) Separate plates.Remove backing from double stick tape.Align back plate(P-
5011)with the top of the first and second breaker slot(1,2 slot) on front of panel
cover and under opening for main breaker. See Figure I(Do not drill holes at this
time)
3) Remove panel cover
4) Relocate breakers from slots 2 and 4 (top 2 spaces of the right breaker column)
utilizing piggyback breakers as necessary to create the needed spaces
5) Install generator breaker in the 2,4 slot.
6) Temporarily remove breakers from the 5,6 slots. Loop the breaker retaining strap
(S-1004) around breakers 1,2,3,4 - 1/2" from the front face of the breakers. Align
the head of the retaining strap at the top right of the number 2 breaker and tighten
the strap. See Figure 113. Cut the tail of the retaining strap approximately 2
inches long and install Notice Label(S-1005)around tail. Reinstall the breakers
in the 5,6 slots. Verify that the retaining strap keeps the 2,4 breaker in place by
attempting to remove the breaker.
7) On suitable surface use included 11/64 drill bit(H-5015)to drill out holes in the
panel cover through the predrilled holes in the back plate (P-5011)
8) Use file to smooth surface around holes and remove the burrs on back of panel
cover. On the back of the panel cover file away paint to aIIow entire screw
head to sit with metal to metal contact. The binder screws (H-5014)must sit
flush with the back of the panel cover
9) Insert binder screws(H-5014)through the back of the panel cover, back plate(P-
5011),and front plate(P-5012). Use the binder post(H-5013)to attach to front of
binder screws(H-5014).Handhold binder post(H-5013)while using screwdriver
to tighten the binder screws(H-5014). The front plate should slide easily and the
back plate should sit firmly.Be careful not to over-tighten.
10)Set generator and main breakers in the"OFF"position and reattach panel cover
Figure I Figure IB
°.7tsX 4
S
�p
k
11)With the panel cover firmly in place test the InterLock to make sure that it
transfers easily between positions. BOTH BREAKERS SHOULD NOT BE
ABLE TO BE IN THE"ON"POSITION AT THE SAME TIME.Even with
moderate pressure you should not be able to engage both breakers at once.
12)Apply thread lock(H-5016)to all four binder post(H-5013) as per instructions
included with the thread lock
13)Attach labels as shown in Figure II
14)Reconnect power to the panel
Figure II
%auk t��n,,��a.sd.lctLan"e,oi^•�mx`,�.��•�
"1,111 AA
w�5.�..�
a��s reean a3*y��rccexafi �� ;'
F r G•TEm.gUrewntui<ceUa, ^at..r'• -•
P�SVlUaeoj iRi+tF4rfs�ldim AI}„ g#s
(# + tbar�a%taaeigr(stte(ysfAli wr.
y �'� ��Xl�v�rsra+r�scua.�iy+rasa:,�#wH++
KIT CONTENTS TOOLS NEEDED TO INSTALL
Description Quantity Part# - Drill or cordless drill
Back plate 1 P-5011 - Flathead screwdriver
Front plate 1 P-5012 - Metal file
Binder post 4 H-5013 - Accurate voltage sensor
Binder screw 4 H-5014
Drill bit 11/64 1. H-5015 CONTACTING US
Thread lock pipette 1 H-5016
Instruction booklet I W-5017 You can contact us by phone at(804) 726-
Main label I W-5018 2448 or by fax at(804) 231-1984
DANGER label 1 W-5019 Questions or comments:
Generator label 1 W-5020 questions@interlockkit.com
Instructions label i W-5021
Retaining Strap 1 5-1004
Retaining Strap Label 5-1005
OPERATION INSTRUCTIONS STATEMENT OF LIABILITY
TO SWITCH OPERATION FROM MAIN Electrical equipment should be installed,
TO GENERATOR operated, serviced, and maintained by
qualified personnel.No responsibility is
1) Turn main breaker to the"OFF" assumed by Generator InterLock
position Technologies,LLC for any consequences
2) Turn all branch circuits to the arising out of the misuse of this material.
"OFF"position
3) Slide InterLock plate up
4) Connect and start generator
5) Turn generator breaker to the Tested for use with
"ON"position UL 67 Listed Panelboards
6) Turn on essential circuits one at Ref.Wyle Laboratories
a time WARNING: Allow Test Report T52431-01
appliances to start before
engaging next circuit
TO RETURN TO MAIN POWER
REVERSE PROCEDURE
Transfer Equipment Specifications Page 10
(81904TE) Price List Pate 8
a ! Q
Power Inlet Bo ee
2.6 The
Breaker
Iflb, 60,
PBlo 45 I All Models I Yeai96Aw26V19.15 No 9.875
t5lbe :PB90 20 All 250V Models YesI20A@260%1420 No 6
P830 30 All 30A,260V Models Yesl30A@260VIL1440 No 7:6
P831 30 All 30A Models Yes130AC126VO-30 No 3.76
P833 30 T1&'T2 PenegUnle Ye9130A,30 I208V No 10.8
L121-30
P850 50 PanstlLink Yea180A@280VIC98866 No 12,6
P851 60 Fane(lLlnk Yes/50AW26V1C86360 No 6,25
PR20 20 AU 260V Models Yes/20AQ260VIL%20 Yes a
PR30 30 All 30A,250V Models Yeel30A0260VA.14-30 Yes 7.6
s' { PR80 60 PeneVEnk YGLI50AQ260V/CS6368 Yes 12,6
ti LAn-a 2wWass
e O
L1420C Connector 20A(q�260 20216A, R20216B 6
L1a-too &Ps20
L1420P Plug 20At$260V ,4 5
L1420F
LLUS P L1420R Receptacle 2LI oR .2 6
114300 Connector L14-300 303 8A,R30310B,
.4 7.6
&Paso
L1430P Plug 30A@250L140
.3P ,4 7.5
L1430R Receptacle 3D
Li 02DR50V
•2 7.6
W 20R&L143QR LL8640 Connector S 08@6364V Panell/Unle .3 12.6
LL650P Plug 60 S@s 6V Panel/Linke ,9 12.6
P,W-0iC,,,ads
@@ @
P02010 10 L14-20 3,6 5
_..t PC202020 L9420 5 6
PC2040 40 04-20 7,6 8
PC3010 10 L14-30 5 7.6
PC-3020 20 L14.30 8.5 7,6
PC3040 40 L14.30 12 7,5
RELIANCE CONTROL6 CORPORATION 12001 YOUNG COURT f RACINE,WI 634041 Phone,(500)634.61651 Fax:(962)634.6436