HomeMy WebLinkAboutDrawing (2) FI-LE COP- -��l RECEIVED AUG 0 6 2018 sT, Lucie County, Permitting INTRODUCTION INTERLOCK KIT K-5011 1WERLOOCKIT This manual provides instructions for safe installation of the InterLock Kit onto a Square-D panel. The back plate sits securely on the face of the panel cover while allowing the front plate to slide between the main and generator breaker positions.The InterLock Kit will only allow one of these breakers to be in the"ON"position meeting the requirements of Article 702 of the National Electric Code ANSI/NFPA 70. The installation of the breaker retaining strap meets Article 408.36 (NEC 2008). SAFETY PRECAUTIONS—IMPORTANT SAFETY INSTRUCTIONS WARNING: HAZARD OF ELECTRIC SHOCK OR EXPLOSION - This kit must be installed and serviced only by qualified electrical personnel - Turn off all power supplying the equipment where,this kit will be installed before working on or inside the equipment - Always use a properly rated voltage sensing device to confirm that all power is off - Replace all devices, doors,and covers after installing this kit before turning on power to the equipment - Always wear safety eyewear while drilling or working around electrical , equipment FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS INJURY OR DEATH SAFE THESE INSTRUCTIONS INSTALLATION INSTRUCTIONS 1) Disconnect power to the panel 2) Separate plates.Remove backing from double stick tape.Align back plate(P- 5011)with the top of the first and second breaker slot(1,2 slot) on front of panel cover and under opening for main breaker. See Figure I(Do not drill holes at this time) 3) Remove panel cover 4) Relocate breakers from slots 2 and 4 (top 2 spaces of the right breaker column) utilizing piggyback breakers as necessary to create the needed spaces 5) Install generator breaker in the 2,4 slot. 6) Temporarily remove breakers from the 5,6 slots. Loop the breaker retaining strap (S-1004) around breakers 1,2,3,4 - 1/2" from the front face of the breakers. Align the head of the retaining strap at the top right of the number 2 breaker and tighten the strap. See Figure 113. Cut the tail of the retaining strap approximately 2 inches long and install Notice Label(S-1005)around tail. Reinstall the breakers in the 5,6 slots. Verify that the retaining strap keeps the 2,4 breaker in place by attempting to remove the breaker. 7) On suitable surface use included 11/64 drill bit(H-5015)to drill out holes in the panel cover through the predrilled holes in the back plate (P-5011) 8) Use file to smooth surface around holes and remove the burrs on back of panel cover. On the back of the panel cover file away paint to aIIow entire screw head to sit with metal to metal contact. The binder screws (H-5014)must sit flush with the back of the panel cover 9) Insert binder screws(H-5014)through the back of the panel cover, back plate(P- 5011),and front plate(P-5012). Use the binder post(H-5013)to attach to front of binder screws(H-5014).Handhold binder post(H-5013)while using screwdriver to tighten the binder screws(H-5014). The front plate should slide easily and the back plate should sit firmly.Be careful not to over-tighten. 10)Set generator and main breakers in the"OFF"position and reattach panel cover Figure I Figure IB °.7tsX 4 S �p k 11)With the panel cover firmly in place test the InterLock to make sure that it transfers easily between positions. BOTH BREAKERS SHOULD NOT BE ABLE TO BE IN THE"ON"POSITION AT THE SAME TIME.Even with moderate pressure you should not be able to engage both breakers at once. 12)Apply thread lock(H-5016)to all four binder post(H-5013) as per instructions included with the thread lock 13)Attach labels as shown in Figure II 14)Reconnect power to the panel Figure II %auk t��n,,��a.sd.lctLan"e,oi^•�mx`,�.��•� "1,111 AA w�5.�..� a��s reean a3*y��rccexafi �� ;' F r G•TEm.gUrewntui<ceUa, ^at..r'• -• P�SVlUaeoj iRi+tF4rfs�ldim AI}„ g#s (# + tbar�a%taaeigr(stte(ysfAli wr. y �'� ��Xl�v�rsra+r�scua.�iy+rasa:,�#wH++ KIT CONTENTS TOOLS NEEDED TO INSTALL Description Quantity Part# - Drill or cordless drill Back plate 1 P-5011 - Flathead screwdriver Front plate 1 P-5012 - Metal file Binder post 4 H-5013 - Accurate voltage sensor Binder screw 4 H-5014 Drill bit 11/64 1. H-5015 CONTACTING US Thread lock pipette 1 H-5016 Instruction booklet I W-5017 You can contact us by phone at(804) 726- Main label I W-5018 2448 or by fax at(804) 231-1984 DANGER label 1 W-5019 Questions or comments: Generator label 1 W-5020 questions@interlockkit.com Instructions label i W-5021 Retaining Strap 1 5-1004 Retaining Strap Label 5-1005 OPERATION INSTRUCTIONS STATEMENT OF LIABILITY TO SWITCH OPERATION FROM MAIN Electrical equipment should be installed, TO GENERATOR operated, serviced, and maintained by qualified personnel.No responsibility is 1) Turn main breaker to the"OFF" assumed by Generator InterLock position Technologies,LLC for any consequences 2) Turn all branch circuits to the arising out of the misuse of this material. "OFF"position 3) Slide InterLock plate up 4) Connect and start generator 5) Turn generator breaker to the Tested for use with "ON"position UL 67 Listed Panelboards 6) Turn on essential circuits one at Ref.Wyle Laboratories a time WARNING: Allow Test Report T52431-01 appliances to start before engaging next circuit TO RETURN TO MAIN POWER REVERSE PROCEDURE Transfer Equipment Specifications Page 10 (81904TE) Price List Pate 8 a ! Q Power Inlet Bo ee 2.6 The Breaker Iflb, 60, PBlo 45 I All Models I Yeai96Aw26V19.15 No 9.875 t5lbe :PB90 20 All 250V Models YesI20A@260%1420 No 6 P830 30 All 30A,260V Models Yesl30A@260VIL1440 No 7:6 P831 30 All 30A Models Yes130AC126VO-30 No 3.76 P833 30 T1&'T2 PenegUnle Ye9130A,30 I208V No 10.8 L121-30 P850 50 PanstlLink Yea180A@280VIC98866 No 12,6 P851 60 Fane(lLlnk Yes/50AW26V1C86360 No 6,25 PR20 20 AU 260V Models Yes/20AQ260VIL%20 Yes a PR30 30 All 30A,250V Models Yeel30A0260VA.14-30 Yes 7.6 s' { PR80 60 PeneVEnk YGLI50AQ260V/CS6368 Yes 12,6 ti LAn-a 2wWass e O L1420C Connector 20A(q�260 20216A, R20216B 6 L1a-too &Ps20 L1420P Plug 20At$260V ,4 5 L1420F LLUS P L1420R Receptacle 2LI oR .2 6 114300 Connector L14-300 303 8A,R30310B, .4 7.6 &Paso L1430P Plug 30A@250L140 .3P ,4 7.5 L1430R Receptacle 3D Li 02DR50V •2 7.6 W 20R&L143QR LL8640 Connector S 08@6364V Panell/Unle .3 12.6 LL650P Plug 60 S@s 6V Panel/Linke ,9 12.6 P,W-0iC,,,ads @@ @ P02010 10 L14-20 3,6 5 _..t PC202020 L9420 5 6 PC2040 40 04-20 7,6 8 PC3010 10 L14-30 5 7.6 PC-3020 20 L14.30 8.5 7,6 PC3040 40 L14.30 12 7,5 RELIANCE CONTROL6 CORPORATION 12001 YOUNG COURT f RACINE,WI 634041 Phone,(500)634.61651 Fax:(962)634.6436