HomeMy WebLinkAboutDiIorio Jim Mitsubishi mini-split eqpmt specs08162018Indoor Unit: MSZ-HMI2NA-Ul
Wireless Remote Controller Outdoor Unit: MUZ-HMI2NA-U1
ACCESSORIES:
Indoor Unit
n Condensate Pump (BlueDiamond X87-711/721; 115/230V)
n Condensate Pump (Sauermann S130-115/230; 115/230V)
r, Anti -Allergy Enzyme Filter (MAC-408FT-E)
o Drain Pan Level Sensor (DPLS2)
Outdoor Unit
❑ Outdoor Mounting Pad (ULTRILITEI)
u Drain Pan Heater (MAC-64OBH-U)
❑ 3-1/4" Mounting Base [Pair] (DSD -400P)
❑ Drain Pan Socket (MAC-860DS)
❑ Air Outlet Guide (MAC-889SG)
❑ Wali Mounting Bracket (QSWB2000M-1)
SPECIFICATIONS:
Compressor DC INVERTER -driven Twin Rotary
Fan Motor (ECM) F.L.A. 0.5
Indoor DRY 170-237-321-399
(Cooling) WET 134-201-286-364
Indoor CFM
(Heating) DRY 170-237-321-406
Outdoor u 1,243 / 1,229
Cooling 22-30-37-45
Indoor
Cooling' BtumHeating /w i 12,000 / 1,210 d6(A) 22-30-37-43
Cooling 49
Heating at 47° Fz Btu/h / W 12,200/990 Outdoor Heating 51
Cooling' Btu/h 3,800 12,200
Heating at 47° Fz Btu/h 4,500 14,500
Heating at 17° F3 Btufh - 9,000
Heating at 5° F4 Btu/h 7,500
' Coding i Indoor: 80° F(27° C)OB / 67° F(190 C)WS; Outdoor: 95° F(35° C)DB / 75° F(24° C)WB'
Heating at 47°F i Indoor: 70° F (21° C)DB / 60° F (16° C)WB; Outdoor: 47° F (8° C)DB /430 F (6° C)WB'
' Heating at 17° F i Indoor: 70° F(21° C)DB / 60° F(16° C)WB; Outdoor: 17° F(-8° C)DB ! 15° F(-9° C)WB'
' Heating at 5° F I Indoor. 70° F (210C)DB/600 F(16° C)WB; Outdoor: 5° F(-15° C) DB / 5° F(-15° C)WB
' Rating Conditions per AHRI Standard:
I
ndoorD) 11-5/8 x 31-7/16 x 9-1/8
(295 x 798 x 232)
In.(mm)
x D) 21-5/8 x 31-1/2 x 11-1/4
(550 x 800 x 285)
Indoor 22 (10)
Lbs.(kg)
Outdoor 1 73 (33)
+. -
Cooling 90° F (32° C) DB / 67° F (19° C) DB
Indoor Munsell 1.OY 9.2 / 0.2
Heating 80° F (27° C) DB / 70° F (21° C) DB
- Outdoor Munsell No. 3Y 7.8 / 1.1
Cooling" 115 F (46° C) DB / 14° F (-10° C) DB R410A; 1 Ib. 12 oz.
I Heating 75° F (24° C) DB / -4° F (-20° C) DB" Refrigerant Piping
Applications should be restricted to comfort coding only; equipment cooling applications are not Liquid (High Pressure)
recommended for low ambient temperature conditions. In.(mm) —
" System cuts out at -9" F (-27" C) to avoid thermistor error and automatically restarts at .4" F (.20o C). Gas (Low Pressure) 3/8 (9.52)
Max. Total Refrigerant 40 (12)
Pipe Length (Height Diff.)
SEER / EER / HSPF 18.0 / 9.9 / 10.0 — , Ft (m)
Max. Total Refrigerant ( )
COP at 47° F / 17° F 3.61 / 2.78 Pipe Length (Length.) 65 20
208 / 230V, 1 -Phase, 60 Hz
MInInium Circuit Ampacity (MCA)
Indoor/ Outdoor A
Specifications are subject to change without notice. 0 2017 Mitsubishi Electric US, Inc.
MSZ-HM12NA-U1
+It �
'l'�a�aaa®u�aaa�■a�
Ill�w�l��ll���■il
Air in
Unit: in. (mm)
M UZ-H M 12NA-U 1
REQUIRED SPACE
'1 4 in. (too mm) or more when
front and sides of the unit are clear(
•2 When any 2 sales of left right
and rear of the unit are dear
FORM# MSZ-HM12NA-U1 ( MUZ-HM12NA-U1 - 201705
Unit: in. (mm)
MITSUBISHI
Alr` ELECTRIC
COOLING & HEATING
1340 Satellite Boulevard. Suwanee, GA 30024
Toll Free: 800-433-4822 www.mehvac.com
c ETV u5
Intertek
Specifications are subject to change without notice. 0 2017 Mitsubishi Electric US, Inc.
Insulation e1 -3/8 0.13
Liquid line at/4 19 - 11/16 (Flared connection e1/4)
CL
Gas line e3/8 16 - 15/16
(Flared connection, o3/8 (HMO9112NA , e1/2 (HM15N
Drain hose Insulation of -118 0.13 Connected W e5/6 O.D
Unit: in. (mm)
MITSUBISHI
Alr` ELECTRIC
COOLING & HEATING
1340 Satellite Boulevard. Suwanee, GA 30024
Toll Free: 800-433-4822 www.mehvac.com
c ETV u5
Intertek
Specifications are subject to change without notice. 0 2017 Mitsubishi Electric US, Inc.
1-2. SELECTING THE INSTALLATION LOCATION
• Where airflow is not blocked.
Where cool (or warm) air spreads over the entire room.
On a rigid wall to reduce the possibility of vibration.
Where it is not exposed to direct sunlight. Do not expose
to direct sunlight also during the period following unpack-
ing to before use.
• Where it can be easily drained.
At a distance 3 ft. (1 m) or more away from a TV and
radio. Operation of the air conditioner may interfere with
radio or TV reception. An amplifier may be required for
the affected device.
• In a place as far away as possible from fluorescent and
incandescent lights. In order to make the infrared remote
control operate the air conditioner normally. The heat
from the lights may cause deformation or the ultraviolet
may cause deterioration,
Where the air filter can be removed and replaced easily.
Where it is away from the other heat or steam source.
Note:
Install the indoor unit high on the wall where air can
distribute over the entire room.
• Where it is convenient to operate and easily visible.
Where children cannot easily touch it.
Select a position about 4 ft. (1.2 m) above the floor.
Check that signals from the remote controller from
that position are received by the indoor unit ('beep'
or'beep beep' receiving tone sounds). Then, attach
remote controller holder to a pillar or wall and install
wireless remote controller.
1-3. SPECIFICATIONS
Note:
In rooms where inverter type fluorescent lamps are used,
the signal from the wireless remote controller may not be
received.
• •+•EIIIIIIIII
Where it is not overly exposed to strong winds. If the
outdoor unit is exposed to a wind during defrosting, the
defrosting time will be longer.
Where airflow is good and dustless.
Where neighbours are not annoyed by operation sound
or hot (or cool) air.
Where rigid wall or support is available to prevent the
increase of operation sound or vibration.
Where there is no risk of combustible gas leakage.
If installing the unit in a location high above the ground,
be sure to secure the unit legs.
Where it is at least 10 ft. (3 m) away from the antenna
of TV set or radio. Operation of the air conditioner may
interfere with radio or TV reception in areas where recep-
tion is weak. An amplifier may be required for the affected
device.
Install the unit horizontally.
Please install it in an area not affected by snowfall or
blowing snow. In areas with heavy snow, please install
a canopy, a pedestal and/or baffle boards.
1.3-1. POWER SUPPLY AND INDOOR/OUTDOOR
WIRE CONNECTION
Power should be taken from an exclusive branched circuit.
Wiring work should be based on applicable technical standards.
Wiring connections should be made following the diagram.
Securely tighten screws.
Connecting wires and the ground wire
Use solid conductor Min. AWG14 or stranded conductor
Min.. AWG14.
Use double insulated copper wire with 600 V insulation.
Use copper conductors only.
Follow local electrical codes.
Power supply cable and ground wire
• Use solid or stranded conductor Min. AWG14.
Use copper conductors only.
Follow local electrical codes.
Note:
When the indoor unit is powered from the outdoor unit, depend-
ing on local code, a disconnect switch needs to be installed to a
power supply circuit.
1-3-2. REFRIGERANT PIPES
To prevent condensation, insulate the two refrigerant pipes.
Refrigerant pipe bending radius must be 4 in. (100 mm) or more.
0 CAUTION
Be sure to use the insulation of specified thickness (table on the
right). Excessive insulation may cause incorrect installation of
the indoor unit, and too little insulation may cause condensate
to form.
• The unit has flared connections on both indoor and outdoor
sides.
Remove the valve cover from the outdoor unit, then connect
the pipe.
• Refrigerant pipes are used to connect the indoor and outdoor
units.
Be careful not to crush or over bend the pipe in pipe bending
• Refrigerant adjustment.., If pipe length exceeds 25 ft. (7.5 m),
additional refrigerant (R410A) charge is required.
(The outdoor unit is charged with refrigerant for pipe length up
to 25 ft. 17.5 mj)
Electrical specifications
Note:
It is advisable to make a piping loop near outdoor unit
so as to reduce vibration.
For increased efficiency, install the outdoor unit in a
location where continuous direct sunlight or excessive
water can be avoided as much as possible.
Note:
When operating the air conditioner in low outside tem-
perature, be sure to follow the instructions described
below.
Never install the outdoor unit in a place where its air
inlet/outlet side may be exposed directly to wind.
To prevent exposure to wind, install the outdoor unit
with its air inlet side facing the wall and a baffle board
on the air outlet side.
Avoid the following places for installation where air
conditioner trouble is liable to occur.
Where flammable gas could leak.
Where there is an excessive amount of machine oil
in the air.
Where oil is splashed or where the area is filled with
oily smoke (such as cooking areas and factories, in
which the properties of plastic could be changed and
damaged).
Salty places such as the seaside.
Where sulfide gas is generated such as hot spring,
sewage, waste water.
• Where there is high -frequency or wireless equipment.
Where there is emission of high levels of VOCs, includ-
ing phthalate compounds, formaldehyde, etc., which
may cause chemical cracking.
MODEL
MSZ-HM09NA
MSZ-HM12NA
MSZ-HM15NA
HV>rtiCM]R UN r
thickness
thickness
Insulation material
Power supply (V, PHASE, Hz)
inch (mm)
208/230, 1, 60
(Refer to the table below.)
Min. Circuit Ampacity iA,
0.0315 (0.8)
1.0
Heat resistant
foam plastic 0.045
Fan motor (F.L.A.) (Ai
1/2(12.7)
0.76
5/16 8
OUT004DA LW11*,1
Power supply (V, PHASE, Hzj
208/230, 1, 60
Max. Fuse size time dela ) 1&
15 1
15 1
15
Min. Circuit A acit jAi
12
12
10
Fan motor (F.L.A.1 tAi
0.50
0.50
0.50
Compressor (R.L.A) (A)MSZ
(L.R.A) (A)
6.6
6.6
7.4
I MSZ 8.2 8.2
9.3
Control voltage
Indoor unit- Remote controller- (Wireless)
Indoor unit - Outdoor unit: DC12-24 V (Polar?
Outside diameter
Minimum wall
Insulation
Pipe length
Pipe
thickness
thickness
Insulation material
inch (mm)
(Refer to the table below.)
For liquid 1/4(6
0.0315 (0.8)
5/16(8)
Heat resistant
foam plastic 0.045
Forges 3/8 (9.52) 0.0315 t0.8) 5/16(8)
1/2(12.7)
0.0315 10.8)
5/16 8
Specific gravity
Limits
Pipe length 65 ft. (20 m) max.
Height difference 40 ft. (12 m) max.
No. of bends 10 max.
Up to 25 ft. (7.5 m)
No additional charge is required.
Pipe length
Exceeding 25 ft. (7.5 m)
Additional charge is required.
(Refer to the table below.)
Refrigerant to be
added
1.08 oz each 5 ft. 20 /m
( 9 )