HomeMy WebLinkAboutProduct Approval Architectonic Inc
October 26, 2018 ERECEIVED
018
Saint Lucie County Building Department
Attn: Roof Permit Plan Review Permitting
2300 Virginia Avenue
Ft. Pierce, FL 34982
Re: Roofing specification prepared for the St. Lucie County Building Dept.for the structure
located at 1103 Osceala Drive,St. Lucie County
Manufacturer: Tri-Built Roofing Products
Profiles: Tri—Built Modified, FL#16027.1,System W-16
Code: FBC 2017;Section R 905.10
Wind Speed: 160 MPIi; Ultimate Design Wind Speeds
Exposure: B
Mean Roof Height: 30' Maximum
Pitch: %/12
Required Design Pressure: Zone1: -26 Zone 2:-41 Zone3:-57
Maximum Uplift Pressure: -60
Base: Polyglass Elastobase Ply, Certain Teed Glasbase
Base Attachment: 32 ga. 1-5/8" diameter tin caps with 11 ga.Annular ring shank nails @
8"o.c. in 4" lap and 8" o.c. in three,equally spaced,staggered center
rows.
Cap: Tri-built APP-TA(torch) Modified Bitumen
Roof Decking: Existing 5/8" plywood sheathing to be nailed w 8d x 2" ring shank nails
@ 6"O.C.thru out Zone 1,4"O.C. perimeter&6" O.C.field Zone 2,
and 4" O.C.thru out Zone 3.
The above approved,as per Florida Building Code Compliance acceptances,2017 Florida Building Code,
and the Manufacturer's recommendations.
®F FLO
Reec°tfully subM d�
moo° ,,N10-J SLgZ °° s
� V °
® ° o
°ich el Seal -
�chit ctoraic°ln°�K�� ( �,
iERED
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg#AA26003348 1 of 1
RECEIVED EXTERIOR RESEARCH&DESIGN,•LLC.
:. Certificate of Authorization#9503
''�`' "' p OCT �, 6 2018 353 Christian Street
:1 1.!Nl 1... 1 . Oxford,CT 06478
ST. Lucie County, Perr>91m (203)262-9245
EVALUATION REPORT o
TRI-BUILT Materials Group,LLC ' r nation Report A42970.10.12-R2
PO Box 70 4 ,h FL16027-R2
Rutherford,NJ 07070 s Da%Wd Issuance:10/23/2012
(800)516-1485 Revision 2:09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the a Edition(2017)Florida Building Code sections noted herein.
DESCRIPTION: TRI-BUILT Modified Bitumen Roof.Systems
LABELING: Labeling shall be in accordance with the requirements the.Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE:This Evaluation Report is valid until such time as the named products)changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity)ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with-each Code Cycle.
ADVERTISEMENT:The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION:Upon request,a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 4,plus a 26-page Appendix.
Prepared by.:
3 f�itt�lenry r-^_
r
'ice�-�Na•S?t�'S'::
RobertJ.M.Nieminen P.E. t.� T•• -
r ,��,•;,:-•*='.• The facsimile seal appearing was authorized by Robert Nieminen,
Florida Registration No.59166,Florida DCA ANE1983 �'as%+o\���;:�` PX an 09/25/2017.This does not serve as an electronically signed
t�irmuPrr` document. -
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research&Design,I.I.C.d/b/a Trinity I ERD does not have,nor does it intend to acquire or will it acquire,a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, I.I.C. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being Issued.
4. Robert Nieminen,P.E.does not have,nor will acquire,a financial interest in any other entity involved in-the approval process of the
product.
S. This is a building code evaluation. Neither TrinitvlERD nor Robert Nieminen, P.E.are, in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
"'�P
TRNNNTY ERD
Table Deck Application Type Description Page
1A-1 Wood New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 4
1A-2 Wood New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded insulation,Bonded Roof Cover 5
1B Wood New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 5
1C Wood New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 6
1D Wood New,Reroof(Tear-Off)or Recover D Prelim.Attached insulation,Mech.Attached Base Sheet,Bonded Roof Cover 6
1E-1 Wood New or Reroof(Tear-Off) E Non-insulated,Mech.Attached Base Sheet,Bonded Roof Cover 7
Wood New,Reroof(Tear-Off)or Recover E Nen Insulated Mech.Attached Base Sheet,Bonded Roof Cover 8
iF Wood New or Reroof(Tear-Offl . F Non-Insulated,Bonded Roof Cover 8
2A Steel ar Structural concrete New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 9
28 Steel or Structural concrete New,Reroof{Tear-Off)or Rernver C _ Mech.Attached insulation,Bonded Roof Cover 9
2C SYeel or Structural concrete New,Reroof(Tear-Off}or Recover D Prelim.Attached insulation,Mech.Attached Base Sheet,Bonded Roof Cover 10
3A Structural concrete New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 11-14
3B Structural concrete New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 14
4A LWIC New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 15-16
48 LWIC New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 16
4C LWIC New or Reroof(Tear-off) E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 17-19
SA CWF New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 20
58 CWF New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 21
5C CWF New,Reroof(Tear-Off)or Recover B Mech.Attached Base insulation,Bonded Top insulation,Bonded Roof Cover 22
SD CWF New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 22
5E CWF New,Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 22
6A Gypsum New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 23
6B Gypsum New,Reroof(fear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded insulation,Bonded Roof Cover 24
6C Gypsum New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 24
6D Gypsum New,Rerdof(Tear-Off)or Recover E Non-insulated,Mech.Attached Base Sheet,Bonded Roof cover 24
7A Various Recover A-1 Bonded Insulation,Bonded Roof Cover 25-26
76 Various Recover F Non-insulated,Bonded Base Sheet,Bonded Roof Cover 26
The followintt notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FEC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Insulation/base sheet fasteners shall be of sufficient length for the following deck engagement:
D Wood: Minimum 0.75-inch penetration.
D Steel: Minimum 0.754nch penetration and engage the top flute of the steel deck.
A Structural concrete: Minimum 1-Inch embedment Into pilot hole in accordance with fastener manufacturer's published installation instructions.
3. Unless otherwise noted,insulation.may be any one layer or combination of polylsocyanurate, polystyrene,wood fiberboard,perlite,gypsum-based roof board or mineral-wool roof board that meets the CIA
requirements of-F.A.C.Rule 61G20-3 and is documented as meeting FBC 1505.1 and,for foam plastic,FBC Chapter 26,when installed with the roof cover.
Exterior Research and Design,LLC.d/b/a Trinity(ERD Evaluation Report A42970.10.12-R2 for FU6027-R2
Certificate of Authorization#9503 e"EDITION(2017)FBC NON-HVH2 EVALUATION Revision 2:09/25/2017
Prepared by: Robert Nieminen,PE-59166 TRI-BUILT Modified Bitumen Roof Systems;(800)516-1485 Appendix 1,Page 1 of 26
QO
TRINITY ERD
.b ..,..r ..' .. �. µ :',.;, .,.'d,.• Su' h ...,-vC•l "t.N+ ..Maki :r,:.Y`h,. 4.-i.�. .F� .,..c. .h. .. 'i..:•.>S N ,;ly Y i. '. SAL'S YW'%vV.`L.Sf vl 'S ^V"'..,far ,,,xt
..'!?" ¢ •rna.�,1 y. ,.,� .. Y�,• #..
r�l..;, ti-? r .,• ,,t•� >a?,t;-�,y�,- .eas..... .z� :r�1 tm:ry,...- .s'�1011
�fi
rca,.�a..su� {.a.�',..,t�t �h, cetdw, G'�rt ...., :^.w'i•. �.:°F„.,�fi ttV,i. v ., •p« ,� �, ,.�. ,�, � ���
„�•5?N a.u'�•s-e .�,e,« *,xS x, i!: f�.. ..�`"��r � v$� fr mr;�'�,y;. .,.�,. a* �. .� a?, k `�^. r ..�. .. 7 �� -F; '�".
IC�it,.a,a`+.`i:� ,.•�.:"%+,:ra�•r �,4rr���.r���i...M.,�";xv„�"`aa"n�n?..?(,r� .�.a:.nm.....�4� � r•1�. .�.a.�.,.A1 ,�� :�.H. �.�5»,;, v.:r.,s�.,e..o . "-{"'.�r' � r'�i`e �i.�' k,
system Base Sheet Roof Cover(Note 15) MDP
No. Deck(Note 1) Base Fasteners Attach Base Ply Cap Ply (Pso
Min.15/32-inch
W-14 plywood at max.24- Polyglass Elastobase Simplex MARX Cap equally
o.c.at 2-inch lap and center
inch s in two, (Optional)BP-AA or SBS-AA,SBS-TA -45.0•
Inch spans equally spaced,staggered center rows APP-TA or APP-TA
Min.15/32-inch 9-inch o.c.at 2-inch lap and 12-inch o.c.in two, (Optional)BP-AA or - SBS-AA,SBS-TA
W-15 plywood at max.24- Polyglass Elastobase Simplex MAXX Cap equally spaced,staggered center rows APP-TA or APP-TA -52.5
Inch spans
Min.19/32-inch Polyglass Elastobase P�olyglass1Ela�s base,. (Optional)One or
r g"y Poly Polyglass G2 Base;�Certain`T4ed 32 ga.,1-5/8-inch diameter tin caps 8-inch o.c.in 4-inch lap and 8-inch o.c.in three, SBS-AA,SBS-
plywood at max. f � ao g g equally p staggered more BP-AA or -60.0
24-inch spans Ei.Glagb5se,:Firestone MB Base,JM Parma- with 11 a annular ring shank nails a uall spaced,sta ered center rows )APP TA IT =7A
Ply 28,Tamko Glass Base or GAFGLAS#75
Min.19/32-inchPolygiass Elas
W-17 plywood at max. BS-SA or SA,SBS-TA or -60.0
more S(Optional)One or SBS-SA,APP-
tobase or Polyglass 32 ga.,1-5/8-inch diameter tin.caps 8-inch o.c.in 4-inch lap and 8-inch o.c.in three,
24-inch inch spans Elastobase Poly with poly top surface with 11 ga.annular ring shank nails equally spaced,staggered center rows moreAPP- S APP-TA
Min.15/32-inch 6-Inch o.c.at 2-inch lap and 6-inch o.c.in two, (Optional)BP-AA or SBS-AA,SBS-TA
W-18 plywood at max.24- Polyglass Elastobase Simplex MAXX Cap equally spaced,staggered center rows APP TA or APP-TA -90.0
inch spans
Min.19/32-inch Polyglass Elastobase or Polyglass 32 ga.,1-5/8-inch diameter tin caps 4-inch o.c,in 4-inch lap and 4-inch o.c.in four, (Optional)One or SBS-SA,APP-
W-19 plywood at max. more SBS-SA or SA,SBS-TA or 97.5
24-inch spans Elastobase Poly with poly top surface with 11 ga.annular ring shank nails. equally spaced,staggered center rows
APP-TA APP-TA
Min.15/32-Inch 6-inch o.c.at 2-inch lap and 6-Inch o.c.in three, (Optional)BP-AA or SBS-AA,SBS-TA
W-20 plywood at max.24- Polyglass Elastobase Simplex MAXX Cap equally spaced,staggered center rows APP-TA or APP-TA -105.0
Inch spans
Min.19/32-inch (Optional)One or
Polyglass Elastobase or Polyglass 32 ga.,1-5/8-inch diameter tin caps 6-inch o.c.in 4-inch lap and 6-inch o.c.in four, SBS-AA,SBS-
W-21 plywood at max. Elastobase Poly with it ga.annular ring shank nails equally spaced,staggered center rows more BP-AA or TA,APP-TA iiz.s
24-inch spans APP-TA
32 ga.,1-S/8-inch diameter tin caps
Min.19/32-Inch SBS-SA,APP-
W-22 plywood at max. Polyglass Elastobase or Polyglass with 11 ga:annular ring shank,nails. 6-inch o.c.in 4-inch lap and 6-inch o.c.in four, (Optional)One or SA,SBS-TA or -112.5
24-inch spans Elastobase Poly with poly top surface Note:Tin caps are to be primed with equally spaced,staggered center rows more APP-TA APP-TA
ASTM D41 primer.
Exterior Research and Design,I.I.C.d/b/a Trinity(ERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION Revision 2:09/25/2017
Prepared by: Robert Nieminen,PE-59166 TRI-BUILT Modified Bitumen Roof Systems;(800)516-1485 Appendix 1,Page 7 of 26
QOTRINITYIERD
System Base Sheet
Roof Cover(Note 35) jylpp
No. Deck(Note i)
Base- Fasteners Attach Base Ply Cap Ply (PsQ'
Polyglass Elastobase,Polyglass Elastobase
Min.19/32-Inch One or OMG Flat Bottom Plates(square)with 12-inch o.c.in 4-inch lap and 12-Inch (Optional)O
Poly,Polyglass G2 Base,CertainTeed SBS-AA SBS-
W-1 plywood at max. Roofgrip#14,Dekfast Hex with Dekfast#14 o.c.in two,equally spaced,staggered more BP-AA or
GlasbaseFirestone MB BaJM P -52.5
24-inch spans ; , se, erma- or TruFast MP-3 with TruFast HD center rows APP-TA TA,APP-TA
Ply 28,Tamko Glass Base or GAFGLAS#75
Min.19/32-inch Polyglass Elastobase or Polyglass Dekfast Hex with Dekfast#14 or TruFast MP- 12-inch o.c.in 4-inch lap and 12-inch One or more SBS- SBS-SA,APP
W-2 plywood at max. ;Elastobase Poly with poly top surface 3 with TruFast HD o.c.In two,equally spaced,staggered SA SA,SBS-TA or -52.5•
24-Inch spans center rows APP-TA
Min.19/32-inch Polyglass Elastobase or Polyglass OMG Flat Bottom Plates(square)with 12-Inch o.c.in 4-inch lap and 12-Inch (Optional)One or
W-3 plywood at max. yg yg ( q ) SBS-AA,SBS-
Elastobase Poly Roofgrip#12 o.c.in two,equally spaced,staggered more BP-AA or TA,APP-TA 60.0
24 inch spans center rows APP-TA
Min.19/32-Inch Polyglass Elastobase or Polyglass OMG Flat Bottom Plates(square)with 12-inch o.c.in 4-Inch lap and 12-Inch SBS-SA,APP-
W-4 plywood at max. ( q ) o.c.in two,equally spaced,staggered One or more SBS- SA,SBS TA or -60.0!
24-inch spans Elastobase Poly with poly top surface Roofgrip#12 SA APP-TA
P center rows
System Deck Primer Roof Cover(Note 15) MDP'
No. Joint Treatment Base ply Ply Cap ply (psf)
W-5 M1n.15/32-inch plywood (Optional)ASTM D41 None (Optional)SBS-SA or SBS-SA,APP-SA,SBS-TA
at max.24 Inch spans SBS-SA APP-TA or APP-TA -90.0
W-6 Min.15/32-inch plywood O tlonal ASTM D41 Plywood joints are covered with 4-inch wide strips of TriBuilt SA (Optional)SBS-SA or SBS-SA,APP-SA,SBS-TA
at max.24-inch spans ( p ) SBS Base,rolled Into place to create continuous bond. Trieuilt SA SBS Base APP-TA or APP-TA -97.5
11
Exterior Research and Design,U.C.d/b/a Trinity ERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Certificate of Authorization#9503 6TM EDITION(2017)FBC NON-HVHZ EVALUATION Revision 2:09/25/2017
Prepared by: Robert Nieminen,PE-59166 TRI-BUILT Modified Bitumen Roof Systems;(800)516-1485 Appendix 1,Page 8 of 26