HomeMy WebLinkAboutProduct Approval URNER RECEIVED 1239 Jabara Ave. North Port,FL 34288 ENGINEE N OCT 31 2018 Ph. 941-380-1574 Co FBPE C.O.A. #29779 Evaluation Report 867C August 29, 2017 Product Description: Series 8200 PVC Horizontal Slider Window, Large Missile Impact (Wind Zone 3), XO or OX 74"x63"unit size with design pressures of+1-50 psf(Fin or Flange window) Manufacturer: Custom Window Systems, Inc. 1900 SW 44`h Ave, Ocala, FL 34474 Statement of Compliance: This report evaluates the above-listed product per the requirements of FAC Product Approval Rule Chapter 61G20-3.005 (4). This product complies with the requirements of the 6h Edition(2017) Florida Building Code outside the High Velocity Hurricane Zone. The product testing standards performed are outlined below. Technical Documentation: 1) This report,prepared by Lucas A. Turner,P.E., at 1239 Jabara Ave.,North Port, FL 2) Approval drawing CWS-867C' signed and sealed by Lucas A. Turner, P.E. 3) Test Reports NCTL-210-3887-1B and-2B, by National Certified Testing Laboratories, Orlando, FL, signed and sealed by Gerard J. Ferrara,with testing performed: ASTM E 1886 '02/04/05, ASTM E 1996 '04/06/09 (large missile impacts in accordance with Wind Zone 3), and AAMA/WDMA/CSA 101/I.S.2/A440 '08 4) Supplemental Calculations to support CWS-867C, signed and sealed by Lucas A. Turner, P.E. Installation: Units must be installed according to approval document CWS-867C. Limitations of Use: This product: • May be used up to the sizes and daylight openings indicated in CWS-867C • Achieves design pressures of+1-50 psf • Is Large Missile-impact resistant and does not require the use of shutters • May not be used in the High Velocity Hurricane Zone or Wind Zone 4 areas • Requires Kuraray(Dupont)PVB Interlayer • Requires Quanex(Mikion)white rigid PVC frame extrusions Certification of Independence: I do not have,nor do I intend to acquire,nor will I acquire, a financial interest in Custom Window Systems or in any company manufacturing or distributing products for which this report is being issued. I do not have,nor do I intend to acquire,nor will I acquire, a financial interest in any other entity involved in the testing or approval process of this product. ........... Lucas • N 5201 o a --I Turner 2017-08-300 STATE OF -4/4U 8/29/2017 & 16:11+20:00 Lucas A. Turner, P.E. FL PE#58201 HORIZONTAL SLIDER - LARGE MISSILE IMPACT GENERAL NOTES: 1.THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED NVINDCiVI/SYSTEMS TO COMPLY WITH THE FLORIDA BUILDING CODE(FBC),CURRENT 1900 SW 44TH AVE. EDITION AND IS RATED FOR WIND ZONE 3 MISSILE LEVEL D IMPACT OCALA,FLORIDA 34474 USE AS DEFINED IN ASTM E 1996 PER THE FBC. W WW.CWS.CC THIS PRODUCT MAY NOT BE USED IN THE HIGH VELOCITY HURRICANE 751/4"MAX.OVERALL FLANGE WIDTH ZONE(HVHZ1 OR IN ASTM E 1996 WIND ZONE 4 AREAS, 8200 PVC 74'MAX.UNIT WIDTH 2.GLAZING OPTIONS:(SEE SHEET 2) HORZ.SLIDER 33'GLASS DLO 3.CONFIGURATIONS:"OX","XO". IMPACT A 4.DESIGN PRESSURE RATING: -- -- - -- -- -NEGATIVE DESIGN LOADS BASED ON,TESTED PRESSURE AND Z �: <Z O GLASS TABLES ASTM E-1300-04e01/09. 0 w 0 ¢w 0 W - -POSITIVE DESIGN LOADS BASED ON,TESTED PRESSURE,WATER z O Z ¢k 4'.2 I I INFILTRATION TEST PRESSURE AND GLASS TABLES ¢to 3 ¢3:m }O 1 I ASTM E-1300-04001/09. w ¢I-�M__ MAX 5.ANCHORAGE:THE 331/3%STRESS INCREASE HAS NOT BEEN USED U N OF U o-F to¢a FLANGE B B IN THE DESIGN OF THIS PRODUCT.SEE SHEET 5 FOR ANCHOR Z-co Z Z I 0 U) HEIGHT I DETAILS.WINDLOAD DURATION FACTOR Cd=1.6 WAS USED FOR WOOD O Z U U Z U ANCHOR CALCULATIONS. ¢ Lu S LL Z O () I } z 6.PRODUCT APPROVED FOR IMPACT RESISTANCE. SHUTTERS ARE NOT p p F Y 0 3 O uj ¢m0wLow �" REQUIRED.THE IMPACT ROTARY LOCKS ARE INTENDED TO BE LEFT www p�rn H MAX UNLATCHED DURING NORMAL OPERATION OF THIS PRODUCT,BUT z 2 D- a¢O U HUNfTEIGHT Ci �i wF0 O-2 CC> HEIGHT O X I 59 9118" MUST BE ENGAGED PRIOR TO EXPOSURE TO HURRICANE WINDS AND ¢ w w rn MAX FLYING DEBRIS. o ¢ a SASH HEIGHT 7.ALL FRAMES AND VENTS FULLY WELDED.SMALL JOINT SEAM SEALANT • P��`°u°°° °,'� I j USED AT FIXED MEETING RAIL AND HEAD/SILL. � •••••�PNOR....•T�,��� • GEM 5813!16" I e 8.SERIES/MODEL DESIGNATION HS-8200. GLASS No 58201 I - DLO 5 C 9.THE DESIGNATION X AND 0 STAND FOR THE FOLLOWING: X=OPERABLE SASH,0=FIXED SASH 5 STATE OF :4+� 10.SECTION CALLOUTS APPLY TO ALL ELEVATIONS IN A SIMILAR i0,p•. D I LOCATION. ��i,�Fss�O R 1�. p,`•` 11.EXTERNAL WEEP SLOT=1/4"x 1"LOCATED 4"FROM BOTH ENDS. f`����iveAilR •�`• D s A 33"GLASS DLO o::�32 38 5/16"MAX SASH WIDTH N 6!4rn 8/29/2017 O c o LUCAS A.TURNER,P.E. FL PE#58201 1239 JABARA AVE. NORTH PORT,FL 34288 PH.941.380-1574 SHEET DESCRIPTION: GENERAL NOTES AND ELEVATIONS TABLE OF CONTENTS DRAWN BY: DATE: ADE 10/10/13 GENERAL NOTES 8 ELEVATLAZINGIONS DETAI........1 MAX. UNIT SIZE DESIGN PRESSURE RATING IMPACT RATING DWG#: REV.: SECTION VIEWS 8,GLAZING DETAILS CWS-867 C EXTRUSIONS E B.O.M...............................................3 74"x 63" +/-50 PSF LARGE MISSILE IMPACT ANCHOR SCHEDULE&NOTES................4 �E: SHEET INSTALLATION DETAILS...........................5 1:15 1 OF 5 QgtrEMSM44 4 45 46 INTERIOR 1900 SW 44TH AVE. OCALA,FLORIDA 34474 ti 1 18 1 1 3 6 7 2 WWW.CWS.CC 8210 PVC HORZ.SLIDER IMPACT 0 0 z � ¢Z� ow0 < 0 II-:cuj zOz RFzIW_- PLu Z�3Mx 41 3 t 39SECTION VIEW ALTERNATE JAMB ROTARY LOCKS 0 O o a=of IL SECTION B-B MAY BE SUBSTITUTED FOR JAMB IMPACT HOOKS O—SO --mu- 11 Z?U w 6 1 t NOTE:FIXED LITE AT HEAD F Z LL 2 O( LL z AND SILL IS SIMILAR. NOTE:ROTARY LOCKS ARE TO BE ENGAGED ONLY <B:0 H F-0 - DURING HURRICANE CONDITIONS. cc r O 31 p D:ce 0 W In W LL p�m� 79 =~pct w=�co 3 F a cc 3'a 1 1 !tW TL%%% pREs ,� �, 47 AT 4 Z-4 No 58201 ;.P HEAD IMPACT HOOK(TYP.) �4 MIDSPAN OF SASH *' (ITEMS 35&36) 718'OVERALL %'P' STATE OF 1/8"ANNEALED of TEMPERED 'i�T•'•';(ORIO P•:;aA Q♦ INTERIOR ] 7116"AIRSPACE 10 I 5/16"LAM] 1B"ANNEALED FIN FRAME ONLY: MQ DUPONT PVB INTERLAYER JAMB IMPACT HOOKS q3 OR ROTARY LOCKS 1/8"ANNEALED 4 I I LOCATED AT THIRD POINTS 8/29/2017 EO 3 ] ] 4 SI/KAFLIX 522 "� LUCAS A.TURNER,P.E. FL PE#58201 4t 1239 JABARA AVE. 3 NORTH PORT,FL 34288 5 I PH.941.380-1574 ] I �— SHEET DESCRIPTION: I 1/2°GLASS BITE o SECTION VIEWS AND GLAZING DETAIL 4 O DRAWN BY: DATE: SECTION A-A HEAD IMPACT HOOK AND ADE 10/10/13 JAMB IMPACT HOOK/ROTARY LOCK LOCATIONS 1.20 DWG a: SECTION D-D GLASS TYPE A CWS-867 C ALTERNATE FIN FRAME 1:1 LE: SHEET 1:2 20F5 PARTS LIST 31/8^ CORNER CONSTRUCTION ITEM PART# DESCRIPTION VENDOR MATERIAL 31/g° 1 H•1497 Relnf.Sash Meet.Rall Keymark Alum 31 1 112" WINDOW SYSTEMS 2 H-1699 Relnf.S.B.R./S.S.R, Keymark Alum6 5 3 1900 SW 44TH AVE. 3 H•1836 Meet.Rall,Fxd. Keymark Alum WWW.OCALAFLORIDA 34474 1/16" www.cws.cc 4 H-6052 SashTcp/Bot.Rail Mikron PVC 211/16° 39/16^ 21/6" 1116" 5 H•6048 Main Fr.,SH,w/Fin.,PVC Mikron PVC 11161, o =11 CORNER WELD 8200 PVC 6 H-6050 Sash Meet Rail,PVC Mikron PVCL (ALL SIDES) 7 H-6051 Sash Side Rail,PVC Mikron PVC I�,° 1:8 HORZ.SLIDER 8 H 6049 Main Fr.,SH,w/Fig.,PVC Mikron PVC PVC FRAME FLANGE- FIXED RAIL-1838 IMPACT 9 P•3029 Screen Pull Tab Summit PVC FRAME FIN-6048 1 10 P-3033 Screen Spring,SS Hurley 1 15/1e° 13116"- 2 I 9n� 26 ? W 11 P-3113 Screw Support,PVC Team Plastic Rubber ^ I w�O ¢ D W 12 P-3218 Screen Frame Allmetal RoliForm j6 7 4 Z W z>O¢ m 13 P•3228 Screen Spline,.155 Dia.,Blk. Dapa 1 518" 1 sl8^ 1 5/a° 1 5ns• �ua ¢��2 x 14 P-3321 Screen Frame Corner Key Allmetal Nylon 1/16' g 1/16' 1/t 6° FIXED MEETING RAIL UO y 0(j a H LLJN roc 15 P-3342 Seam Sealer,SM-5504 Schnee Silicone SCREWED TOGETHER WITH Z-W-Z F U) OUTERFRAME O(9 -�O- 16 P-3352 Set.Bilk.,85 Dur.,116"x 5/8"x 2"Lg. FrankLowe Rubber PVC SASH MTG.RAIL-6050 PVC SASH SIDE RAIL-6051 PVC SASH TOP/BTM RAIL-6052 PVC FIXED RAIL COVER-6063 1:8 F-c�O O c 17 P-3429 Wstp.,0.270 x.187 back FinSeal,Gray Ultrafab 2 O IW-r= 09¢ » oN 18 P•3511 #8 x 516"SQUARE TEK 2 Zrx Fastenal Steel 5/6" �4 O 2 v�0 W�n w 1--r 2 Z rn W O J V)F 20 P-3 52 Cap Plug,Truss1/2"Hole M&M 2 Zinc Fastenal Nylon G 3/16" 1" 1 c0 a=�} I -1 15118° tn6" w2 a W W N P-3783 Or Q L ILEICC 21 P•5250 Spring Lock,Impact,PVC Interlock SASH MTG.RAIL-1497 SASH REINF.-1699 ��urr�rrr 22 P•3804 Roller,Tandem M&M Nylon `�%��`PNOREW 23 P•4051 #8 x 1 1/4 Ph FH TEK,W ht. Fastenal Steel 6^ 15116 3/4° Ing 1 1/4^ `GP°'.°�:O 24 P•4069 Keeper,Impact,PVC Interlock 718 ins I 3 �� No 58201 1/16° 25 P-4479 Weep Cover w/Flap M&M Nylon �— 3 1/16" ' 26 P•4638 #8 x 21/2 Ph Truss SMS Ajax Steel PLAN VIEW-1577 FRAME IMPACT HOOK-1577 1/16 �' '¢ S.B.RJS.S.R.-1498 ROLLER TRACK-1778 �9 t STATE OF : 29 P-4959 Wstp.,0.420 x.187 back FInSeal,Gray Ultrafab 40.x'•. P 4v 31 S•1112 Reinforcement Keymark Alum 32 S-1498 Reinf.rcemenS.S.R Keymark Alum 0 3116" 114' r7/8"1 '�iiS��.. 33 S•1577 Frame Hook,PVC Impact Keymark Alum 41 T- I 31 O 7/B" g g• 34 S-1776 Roller Track Keymark Alum - 35 S-1999 Frame Hook,Head,Impact Keymark Alum ills, P Y I -I PVC GLAZESEAD-6064 GLAZE BEAD-1112 36 S-2000 Panel Catch,Head,Impact Keymark Alum r 6° 15/16 37 S-6005 Antl Uft Mikron PVC 8/29/2017 76° 12° 11/8^ 3/8° 15/i6°�I 38 38 S-6013 Scrn.Adapt.,w/Nib,PVC Mikron PVC L fns• 39 S-6014 Scrn.Adapt.,PVC Mikron PVC L— .. 3 LUCAFL PE#58201 S A.TURNER,P E PLAN VIEW-1999 HEAD IMPACT HOOK-1999 Ing^ 40 S-6063 Fixed Rall Coker Mikron PVC 1/18° 1239 JABARA AVE. 41 S-6064 Glazing Bead Mikron PVC PVC SCREEN CATCH-6013 PVC ANTI-LIFT-6005 NORTH PORT,FL 34288 42 GLASS SEE SHEET 2 CARDINAL GLASS 0 3/16^ PH.941.380-1574 43 Purfect Glaze"H",SlkaFlex 552 Henkel/Sika Silicone O 5/16' 1 ifir SHEET DESCRIPTION:I�_� 44 P-3539 #8 x 3/4"Square PH Tek,Wht. Fastenal Steel - 8• -I 5/8- T- BOM AND EXTRUSIONS 45 P-4958 Rotary Lock Interlock PVC SCREEN SUPPORT-6014 DRAWN BY: DATE: 46 P-4633 8-32 x 1/2"Barrel Fastener Interlock TEL 1/16° ADE 10/10/13 47 P-4952 Keeper,Rotary Lock Interlock PLAN VIEW-2000 PANEL IMPACT CATCH-20003/1 6° owe x: REV.: �f�--3" �}-if2° CWS-867 C LINE ITEMS NOT USED: NOT E:ALL EXTRUSIONS ARE ALUMINUM 6063-T6 UNLESS OTHERWISE NOTED. 7- 0►--�11, SCALE: SHEET 27-28,30 r SCREW SUPPORT-3113 1:2 3 OF 5 WINDOW SYS7TT6S 121/2"MAX.O.C.(TYP.) 1900 SW 44TH AVE. �I 3'(TYP.) 4"MAX(TYP.) 6"MAX O.C.(TYP.) OCALA,FLORIDA 34474 6"MAX.(fYP.) I�3„�P) SEE NOTE 2 SEE NOTE 2 W WW.CWS.CC 6"MAX(TYP) I` 4"MAX.(TYP.) - -- -- -- -- -- - -— ——— 8200 PVC INSTALLATION ANCHOR(TYP.) I I HORZ.SLIDER I I I I I INSTALLATION 1 I I ANCHOR(TYP.) IMPACT I 6" MAX O.C. (TYP.) I Z ¢ 17" I I wJ0 ¢kZw MAX.O.C. I I �/ 1 1 I 1 1 1 z O z --~ (TYP.) I O �mm<mwoo I I c0-1��va��a I I Z(7Z1-=co OZOmZ0LLU I I � �o ¢ OWF�Oz- IO�CQ�Y�?�zc a V I OmWmOJ(n ?- F- aCC 0 -- -- -- -- -- -- -- - w0 w=¢� I � CL ¢SDI.. ANCHOR LAYOUT-(FLANGE) ANCHOR LAYOUT-(FIN) 0����°11°B1°p°°j� `.y PNOREW No 58201 *� * :*= L9� STATE OF :�4/ NOTES: 1.INSTALL ONE ANCHOR AT EACH INSTALLATION LOCATION.SILL ANCHOR SPACING SAME AS HEAD. 2.SHIM AS REQ AT EACH INSTALLATION ANCHOR USING LOAD BEARING SHIMS. MAX.ALLOWABLE SHIM STACK TO BE 1/4". USE SHIMS WHERE SPACE GREATER THAN 1/16"IS PRESENT. LOAD BEARING SHIMS SHALL BE x;Z- CONSTRUCTED OF HIGH DENSITY PLASTIC OR BETTER.WOOD SHIMS ARE NOT ALLOWED. 8/29/2017 3.ANCHOR TYPE,SIZE,SPACING AND EMBEDMENT SHALL BE AS SPECIFIED IN THESE DRAWINGS,SEE TABLE 1,SHEET 5. LUCAS A.TURNER,P.E. 4.ALL INSTALLATION ANCHORS MUST BE MADE OF OR PROTECTED WITH A CORROSION RESISTANT MATERIAL OR COATING. DISSIMILAR METALS OR MATERIALS IN CONTACT WITH PRESSURE TREATED WOOD MUST FL PE#58201 BE PROTECTED TO PREVENT REACTION. 1239 JABARA AVE. 5.INSTALLATION ANCHORS SHALL BE IN ACCORDANCE WITH ANCHOR MANUFACTURER'S INSTALLATION INSTRUCTIONS,AND ANCHORS SHALL NOT BE USED IN SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM NORTH PORT, 34288 PH.941380-1-1 574 SPECIFIED IN TABLE 1,SHEET S. SHEET DESCRIPTION: 6.ANCHOR EMBEDMENT TO SUBSTRATE SHALL BE BEYOND WALL DRESSING OR STUCCO. FOR CONCRETE/CMU OPENINGS,EMBEDMENT SHALL BE BEYOND WOOD BUCKS,IF USED,INTO SUBSTRATE. ANCHOR SCHEDULE AND INSTALLATIONS TO SOLID CONCRETE OR GROUT-FILLED CMU MAY INCLUDE BUT DO NOT REQURE 1X WOOD BUCKS BETWEEN THE PRODUCT AND SUBSTRATE. NOTES INSTALLATIONS TO HOLLOW CMU REQUIRE THE USE OF 1X BUCKS BETWEEN THE PRODUCT AND SUBSTRATE. DRAWN BY: DATE: 7.A MINIMUM CENTER-TO-CENTER SPACING SHALL BE MAINTAINED BETWEEN ALL FASTENERS:3"FOR MASONRY,1"FOR WOOD AND METAL. ADE 10/10/13 8.WOOD OR MASONRY OPENINGS,BUCKS AND BUCK FASTENERS SHALL BE PROPERLY DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD AND INSTALLED TO TRANSFER WIND LOADS TO THE STRUCTURE. DWG#: REV.: SUBSTRATES SHALL MEET THE MINIMUM STRENGTH REQUIREMENTS AS SHOWN IN TABLET,SHEET 5. CONCRETE AND MASONRY SUBSTRATES MAY NOT BE CRACKED. CWS-867 C 9.SEALING AND FLASHING STRATEGIES FOR OVERALL WATER RESISTANCE OF INSTALLATION SHALL BE DONE BY OTHERS FOLLOWING THE CURRENT VERSION OF THE REFERENCE DOCUMENTS: SCALE: SHEET FMA/AAMA 100(FIN WINDOWS),FMA/AAMA 200(FLANGE WINDOWS), FMANVDMA 250(BOX WINDOWS),FMA/AAMAJWDMA 300(EXTERIOR DOORS) 1:20 4 OF 5 MIN.EMBEDMENT TYPICAL HEAD ANCHORAGE SEE TABLE 1 SUBSTRATE MIN.EDGE DIST. 1/4"MAX SHIM BY OTE 1 MIN.EDGE DIST. SUBSTRATE 1900 SSW 44THAVE. SEE TABLE 1 SEE TABLE 1 BY OTHERS SEE TABLE 1 OCALA,FLORIDA 34474 SUBSTRATE BY OTHERS1/4"MAX.SHIM WWW.CWS.CC SEE TABLE 1 IN.EDGE DIST. PERIMETER SEALANT SEE TABLE 1MEM SEE TABLE 1 8200 PVC BY INSTALLER INSTALLATION ANCHOR INSIDE AND OUT SEETABE 1 HORZ.SLIDER SEALANT BEHIND SEE TAB DMENTEIMPACT FLANGE BY INSTALLER 114"MAX SHIM aZp PERIMETER SEALANT W J p a W O w PERIMETER SEALANT BYINSTALLER Z O Z IY I BY NSTALLER INSIDE AND OUT -w Z o 3 3 INSIDE AND OUT INSTALLATION ANCHORFo m¢Q WO O SEE TABLE 1 OFO ¢=�Q SEALANT BEHIND U H Z a I-CO a INSTALLATION ANCHOR FLANGE BY INSTALLER SEALANT BEHIND Z-coZ I.-=W SEE TABLE 1 RN BY INSTALLER 00'( J u--mo- HORIZONTAL Z m U- g HORIZONTAL SECTION C HORIZONTAL SECTION < LL W O O LLO Z 5RAGE' TYPICAL JAMB ANCHORAGE 5 HEAD AND SILL SIM TYPICAL FIN OILAR FOR FIN INSTALLATION OgC[ �}b§OPF p of NJ Lu0 It co O uj Er ~¢ w=¢v}i 1/4"MAX SHIM a ¢ a FLANSEAGE BYENSTALER o ���HIND �P�10 RE W�T*,�� IS. G . PERIMETER SEALANT ,��GQ.•;��C E N gF.,�Qy PERIMETERSBY INSTALLER MIN.EMBEDMENT ��• No 58201 INSIDE AND OUT SEE TABLE 1 90:• STATE OF :�<+/ SUBSTRATE BY OTHERS SEE TABLE 1 —MIN.EDGE SEE TABLE 1ST. �'�SS�ONAL, �A1 VERTICAL SECTION 5 TYPICAL SILL ANCHORAGE O 8/29/2017 LUCAS 8/TURNER,TABLE 1:APPROVED INSTALLATION FASTENERS R,P.E. FRAME TYPE SUBSTRATE TYPE ANCHOR TYPE MIN.EMBEDMENT MIN.EDGE DIST. FL PE#A. 58201 RNE FLANGE CONCRETE(20 KSI MIN.) 3/16"TTW TAPCON 1-1/2" 1-1/8" PERIMETER SEALANT-11239 JABARA AVE. FLANGE HOLLOW OR GROUT-FILLED CMU(117 PCF MIN.) 3/16"RW TAPCON 1" 2" BY INSTALLER NORTH PORT,FL 34288 FLANGE CONCRETE(285 KSI MIN.) 3/16"ELCO ULTRACON 1. 1° INSIDE AND OUT D HORIZONTAL SECTION PH.941380-1574 FLANGE GROUPFILLED CMU(ASTM G90) 3/16°ELCO ULTRACON 1-1/4" 2-1/2° 5 BOX FRAME INSTALLATION SHEET DESCRIPTION: 3116°ITW TAPCON HEAD AND SILL SIMILAR FOR BOX INSTALLATION FLANGE 2X MIN.SOUTHERN PINE(G 0.55) OR ELCO ULTRACON 1`318" 7/8° INSTALLATION DETAILS FLANGE 2X MIN.SOUTHERN PINE(G=0.55) #10 WOOD SCREW 13/8" 7/8" FLANGE REMOVAL NOTE:PARTIALLY OR FULLY REMOVING THE FLANGE, DRAWN BY: DATE: 16 GAUGE(0.060")MIN.STEEL STUD #10.16 HILT?KWIK-FLEXOR RW FULL THREAD UP TO AND INCLUDING A BOX-FRAME APPLICATION IS ACCEPTABLE PROVIDED: FLANGE (33 KSI YIELD MIN) TEKS SELF-DRILLING SCREW THRU 0.060" 7/16" ADE 10/10/13 -MIN.1/4"FILLET OF CONSTRUCTION-GRADE ADHESIVE CAULK IS APPLIED DWG#: REV.: 1/8"ALUM.(6063-T5 MIN.)OR 010 GRADE 5 SELF-TAPPING/ FULL THREAD INSIDE AND OUT,FULL PERIMETER,BY INSTALLER. FLANGE 1/8"STEEL(33 KSI MIN.) DRILLING SCREW THRU 0.125" 7/16" PRODUCT ANCHORAGE IS IN ACCORDANCE WITH REQUIREMENTS AS CWS-867 C FIN 2X MIN.SOUTHERN PINE(G_=0.55) #8 WOOD SCREW 1-1/2° 1/2° SHOWN FOR FLANGE WINDOWS.' SHEET 1:2 50F5