HomeMy WebLinkAboutProduct Approval-FL1654_R22_2017 Building Code EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 (203) 262-9245 EVALUATION REPORT Polyglass USA, Inc. 150 Lyon Drive Fernley, NV 89408 (570) 384-1230 Evaluation Report P9290.02.08-R20 FL1654-R22 Date of Issuance: 02/11/2008 Revision 20: 09/12/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Polyglass SBS and APP Modified Bitumen Roof Systems LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinity|ERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words “Trinity | ERD Evaluated” may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 6, plus a 58-page Appendix. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE1983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 09/12/2017. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. Exterior Research & Design, LLC. d/b/a Trinity | ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Exterior Research & Design, LLC. d/b/a Trinity | ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing produ cts for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval proc ess of the product. 5. This is a building code evaluation. Neither Trinity|ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. Exterior Research and Design, LLC. Evaluation Report P9290.02.08-R20 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-R22 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017 Page 2 of 6 ROOFING SYSTEMS EVALUATION: 1. SCOPE: Product Category: Roofing Sub-Category: Modified Bitumen Roof Systems Compliance Statement: Polyglass SBS and APP Modified Bitumen Roof Systems, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1504.3.1 Wind FM 4474 2011 1504.3.1 Wind UL 1897 2012 1504.7 Impact FM 4470 2012 1507.11.2 Physical Properties ASTM D6162 2008 1507.11.2 Physical Properties ASTM D6163 2008 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 1507.11.2 Physical Properties ASTM D6509 2009 3. REFERENCES: Entity Examination Reference Date ERD (TST6049) Physical Properties P10490.10.08-2 10/30/2008 ERD (TST6049) FM 4470/4474 P13760.09.09 09/10/2009 ERD (TST6049) FM 4470/4474 P13770.09.09 09/10/2009 ERD (TST6049) FM 4470/4474 P30540.11.09-R1 11/30/2009 ERD (TST6049) FM 4470/4474 P30550.12.09 12/02/2009 ERD (TST6049) Physical Properties P33960.12.10 12/30/2010 ERD (TST6049) FM 4470/4474 P33970.03.11 03/15/2011 ERD (TST6049) Physical Properties P37590.03.13-3A 03/06/2013 ERD (TST6049) FM 4470/4474 P39680.03.13 03/04/2013 ERD (TST6049) Physical Properties P37590.03.13-1-R1 06/26/2013 ERD (TST6049) Physical Properties P37590.03.13-2-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-2 07/01/2013 ERD (TST6049) Physical Properties P37590.03.13-5-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-1 07/02/2013 ERD (TST6049) FM 4470/4474 P41630.08.13 08/06/2013 ERD (TST6049) Physical Properties P45940.09.13 09/04/2013 ERD (TST6049) Physical Properties P44370.10.13 10/04/2013 ERD (TST6049) Physical Properties P39520.09.14-2 09/11/2014 ERD (TST6049) FM 4470/4474 SC6160.11.14 11/10/2014 ERD (TST6049) Physical Properties PLYG-P45440SC.03.15-1 03/31/2015 ERD (TST6049) Physical Properties SC5170.05.15 05/08/2015 ERD (TST6049) FM 4474 SC8085.05.15 05/19/2015 ERD (TST6049) Physical Properties SC5170.12.15 12/29/2015 ERD (TST6049) FM 4470/4474 SC9455.15 04/01/2016 ERD (TST6049) FM 4470/4474 PLYG-SC8905.05.16-1 05/17/2016 ERD (TST6049) FM 4470/4474 PLYG-SC8905.05.16-2 05/17/2016 ERD (TST6049) FM 4470/4474 PLYG-SC10815.07.16-R1 09/23/2016 ERD (TST6049) UL 1897 PLYG-SC12025.10.16 10/12/2016 ERD (TST6049) FM 4470/4474 PLYG-SC11475.16 11/17/2016 ERD (TST6049) FM 4470/4474/UL1897 PLYG-SC13235.01.17 01/17/2017 ERD (TST6049) FM 4474/UL1897/TAS 114 PLYG-SC13920.05.17 05/30/2017 ERD (TST11294) FM 4474/UL1897/TAS 114 PLYG-CTL13945.05.17-1 05/30/2017 Exterior Research and Design, LLC. Evaluation Report P9290.02.08-R20 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-R22 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017 Page 3 of 6 Entity Examination Reference Date ERD (TST11294) FM 4474/UL1897/TAS 114 PLYG-CTL13945.05.17-3 05/30/2017 ERD (TST6049) FM 4474/UL1897 PLYG-SC13945.05.17 05/30/2017 ERD (TST6049) FM 4474/TAS 114 PLYG-SC15760.09.17 09/11/2017 FM Approvals (TST1867) FM 4470 2W7A7.AM 08/04/1994 FM Approvals (TST1867) FM 4470 0D3A3.AM 04/04/1997 FM Approvals (TST1867) FM 4470 2D0A0.AM 12/23/1998 FM Approvals (TST1867) FM 4470 2D5A9.AM 06/22/1999 FM Approvals (TST1867) FM 4470 3006646 01/04/2000 FM Approvals (TST1867) FM 4470 3001334 01/25/2000 FM Approvals (TST1867) FM 4470 3001334 02/15/2000 FM Approvals (TST1867) FM 4470 3000857 01/12/2000 FM Approvals (TST1867) FM 4470 3004091 01/12/2000 FM Approvals (TST1867) FM 4470 3006115 05/02/2001 FM Approvals (TST1867) FM 4470 3012321 07/29/2002 FM Approvals (TST1867) FM 4470 3014692 08/05/2003 FM Approvals (TST1867) FM 4470 3014751 08/27/2003 FM Approvals (TST1867) FM 4470 3007170 01/13/2004 FM Approvals (TST1867) FM 4470 3019317 06/30/2004 FM Approvals (TST1867) FM 4470 3020703 07/30/2004 FM Approvals (TST1867) FM 4470/4474 3018332 01/31/2006 FM Approvals (TST1867) FM 4470/4474 3023368 03/20/2006 FM Approvals (TST1867) FM 4470/4474 3024594 05/23/2006 FM Approvals (TST1867) FM 4470/4474 3023458 07/18/2006 FM Approvals (TST1867) FM 4470/4474 3030668 09/12/2007 FM Approvals (TST1867) FM 4470/4474 3032172 06/12/2009 FM Approvals (TST1867) FM 4470/4474 3049631 04/21/2014 FM Approvals (TST1867) FM 4470/4474 3057029 02/02/2017 PRI (TST5878) Physical Properties PUSA-062-02-01 12/04/2007 PRI (TST5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI (TST5878) Physical Properties PUSA-064-02-02 02/27/2008 PRI (TST5878) Physical Properties PUSA-062-02-02 12/04/2008 PRI (TST5878) TAS 114 PUSA-188-02-01 02/08/2017 PRI (TST5878) TAS 114 PUSA-188-02-02 02/08/2017 PRI (TST5878) TAS 114 PUSA-188-02-03 02/08/2017 PRI (TST5878) TAS 114 PUSA-202-02-01 05/17/2017 PRI (TST5878) TAS 114 PUSA-202-02-02 05/17/2017 Miami-Dade (CER1592) HVHZ Compliance Various NOAs Various Miami-Dade (CER1592) Proposal for Review 10-0823 10/12/2010 UL LLC (QUA9625) Quality Control Service Confirmation, R14571 Exp. 10/06/2018 4. PRODUCT DESCRIPTION: This Evaluation Report covers Polyglass Modified Bitumen Roof Systems installed in accordance with Polyglass USA, Inc. published installation instructions and the Limitations / Conditions of Use herein. The following Polyglass membranes make up the subject systems. TABLE 1: ROLL-GOODS FOR POLYGLASS MODIFIED BITUMEN ROOF SYSTEMS Type Product Specification Reference Grade Type Base Sheets Polyglass G2 Base ASTM D4601 N/A II Polyflex SA Base ASTM D4601 N/A II Polyglass APP Base ASTM D6509 N/A N/A Exterior Research and Design, LLC. Evaluation Report P9290.02.08-R20 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-R22 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017 Page 4 of 6 TABLE 1 (CONTINUED): ROLL-GOODS FOR POLYGLASS MODIFIED BITUMEN ROOF SYSTEMS Type Product Specification Reference Grade Type SBS Membranes Polyglass HT Base 650 ASTM D6162 S III Elastobase ASTM D6163 S I Elastoflex V ASTM D6163 S I Elastoflex SA V Base ASTM D6163, Table 2 S I Elastoflex SA V FR Base ASTM D6163, Table 2 S I Elastoflex SA V Plus ASTM D6163 S I Elastoflex SA V Plus FR ASTM D6163 S I Elastobase Poly ASTM D6164 S I Elastoflex S6 ASTM D6164 S I Elastoflex S6 Type II ASTM D6164 S II Elastoflex VG ASTM D6163 G I Elastoflex VG FR ASTM D6163 G I SBS Membranes Elastoflex S6 G ASTM D6164 G I Elastoflex S6 G FR ASTM D6164 G I Polyfresko G SBS (sand or poly-film backed) ASTM D6164 G I Polyfresko G SBS FR (sand or poly-film backed) ASTM D6164 G I Elastoshield TS G ASTM D6164 G I Elastoshield TS G FR ASTM D6164 G I Elastoflex SA P ASTM D6164 G I Elastoflex SA P FR ASTM D6164 G I Polyreflect ASTM D6164 S I APP Membranes Polyflex ASTM D6222 S I Polyflex G ASTM D6222 G I Polyflex G FR ASTM D6222 G I Polyfresko G ASTM D6222 G I Polyfresko G FR ASTM D6222 G I Polybond ASTM D6222 S I Polybond G ASTM D6222 G I Polyflex SA P ASTM D6222 G I Polyflex SA P FR ASTM D6222 G I Polyfresko G SA ASTM D6222 G I Polykool ASTM D6222 S I 5. LIMITATIONS: 5.1 This is a building code evaluation. Neither Trinity|ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. 5.3 Refer to a current Approved Roofing Materials Directory for fire ratings of this product. 5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance with FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply. 5.5 The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1511. Exterior Research and Design, LLC. Evaluation Report P9290.02.08-R20 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-R22 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017 Page 5 of 6 5.7 For mechanically attached insulation or membrane or strip-bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.8 For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is permitted for these systems. 5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124 shall be conducted on mock-ups of the proposed new roof assembly. 5.11 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or Roofing Application Standard RAS 111, except the basic wind speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or 1609.3(3). 5.13 All products in the roof assembly shall have quality assurance in accordance with FAC Rule 61G20-3. 6. INSTALLATION: 6.1 Polyglass Modified Bitumen Roof Systems shall be installed in accordance with Polyglass USA, Inc. published installation instructions, subject to the Limitations / Conditions of Use noted herein. 6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. ”MDP” = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, LLC. Evaluation Report P9290.02.08-R20 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-R22 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017 Page 6 of 6 6.3 Any of the following FBC Approved coatings may be applied to the top roof membrane without adverse effect on the system wind load performance. Refer to current Roofing Materials Directory for fire ratings associated with coating usage.  PG200 Non-Fibered Roof Coating;  PG300 Fibered Roof Coating;  PG600 Non-Fibered Aluminum Roof Coating;  PG650 Fibered Aluminum Roof Coating;  PG700 High Quality Elastomeric Roof Coating or KM Acryl 25;  PG700QS (Quick-Set) High Quality Elastomeric Roof Coating or KM Acryl 25-QS (over granule-surfaced APP or SBS only);  PG800 Asphalt Emulsion Roof Coating;  Polyplus 60 Premium Non-Fibered Aluminum Roof Coating;  Polyplus 65 Premium Fibered Aluminum Roof Coating;  Polybrite 70 Premium Grade Elastomeric Roof Coating or KM Acryl 15;  Polybrite 70QS (Quick-Set) Premium Grade Elastomeric Roof Coating or KM Acryl 15-QS (over granule- surfaced APP or SBS only);  Polybrite 90 High Solids Silicone Roof Coating;  Polybrite 95 Silicone Roof Coating. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: Contact the noted QA agency for information on product locations covered for F.A.C. Rule 61G20-3 QA requirements 9. QUALITY ASSURANCE ENTITY: UL LLC – QUA9625; (314) 578-3406, k.chancellor@us.ul.com - THE 58-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT - Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 1 of 58 APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE Table Deck Application Type Description Page 1A Wood New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 5 1B-1 Wood New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 5-9 1B-2 Wood New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 10-11 1C Wood New, Reroof (Tear-Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 11 1D Wood New, Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 12-13 1E Wood New, Reroof (Tear-Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 14-15 1F-1 Wood New or Reroof (Tear-Off) E Non-Insulated, Mech. Attached Base Sheet (nails), Bonded Roof Cover 16-18 1F-2 Wood New, Reroof (Tear-Off) or Recover E Non-Insulated, Mech. Attached Base Sheet (screws & plates), Bonded Roof Cover 19-21 1G Wood New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 21 2A Steel or Structural concrete New, Reroof (Tear-Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 22-24 2B Steel or Structural concrete New, Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 25-28 2C Steel or Structural concrete New, Reroof (Tear-Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 29-31 3A Structural concrete New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 32-40 3B Structural concrete New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 40 4A LWIC New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 41-42 4B LWIC New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 43 4C LWIC New or Reroof (Tear-Off) E Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 44-46 5A CWF New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 47 5B CWF New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 48 5C CWF New, Reroof (Tear-Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 49 5D CWF New, Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 49 5E CWF New, Reroof (Tear-Off) or Recover E Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 49 6A Gypsum Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 50-52 6B Gypsum Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 52 6C Gypsum Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 53 6D Gypsum Reroof (Tear-Off) or Recover E Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 53 7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 54-58 7B Various Recover F Non-Insulated, Bonded Base Sheet, Bonded Roof Cover 58 The following notes apply to the systems outlined herein: 1. The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement:  Wood: Minimum 0.75-inch penetration.  Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck.  Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer’s published installation instructions. 3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, gypsum-based roof board or mineral-wool roof board that meets the QA requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover. Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 2 of 58 4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically atta ched base sheet, bonded roof cover), whereby the base sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 5. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016). 6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer’s published instructions.  Hot asphalt (HA): Full coverage at 25-30 lbs/square.  Dow INSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c.  Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.  Millennium PG-1 Pump Grade Adhesive (M-PG1): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.  OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot). Note: OlyBond Green may be used where OlyBond 500 is referenced.  OlyBond Classic (OB Classic): Full coverage at 1 gal/square.  ICP Adhesive & Sealants CR-20: Continuous 2.5-3.5-inch wide ribbons, 12-inch o.c.  Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon-applied adhesive, board joints shall be staggered.  Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing. 7. Unless otherwise noted, all insulations are flat-stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to ‘increase’ the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table:  Millennium One Step Foamable Adhesive (M-OSFA): MDP -157.5 psf (Min. 0.5-inch thick)  Millennium PG-1 Pump Grade Adhesive (M-PG1): MDP -157.5 psf (Min. 0.5-inch thick)  OMG OlyBond 500 (OB500): MDP -45.0 psf (Min. 0.5-inch thick Multi-Max FA-3)  OMG OlyBond 500 (OB500): MDP -187.5 psf (Min. 0.5-inch thick ISO 95+ GL)  OMG OlyBond 500 (OB500): MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3)  OMG OlyBond 500 (OB500): MDP -487.5 psf (Min. 0.5-inch thick ACFoam II)  ICP Adhesives & Sealants CR-20: MDP -117.5 psf (Min. 1.0-inch thick) 8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted. 11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 12. For existing substrates in a bonded recover or re-roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 13. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application. 14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top-coat thickness is 2-inches. For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 3 of 58 15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications. TABLE 1: POLYGLASS ROOF COVERS Reference Layer Material Application BP-AA (Base and Ply sheets, Asphalt- Applied) Base Ply One or more plies Polyglass G2 Base, FBC Approved ASTM D4601, Type II Hot Asphalt at 20-40 lbs/square Ply One or more plies Polyglass Ply IV, Polyglass Ply VI, FBC Approved ASTM D2178, Type IV or VI Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes. SBS-CA1 Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 Type II, Polyglass HT Base 650 PG350 at 1.5-2.0 gal/square Cap Ply Elastoflex VG, Elastoflex VG FR, Elastoflex S6, Elastoflex S6 Type II, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS-G, Elastoshield TS-G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed) SBS-CA2 Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 Type II Polyplus 35 at 1.5-2.0 gal/square Cap Ply Elastoflex VG, Elastoflex VG FR, Elastoflex S6, Elastoflex S6 Type II, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS-G, Elastoshield TS-G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed) SBS-AA (SBS, Asphalt-Applied) Base Ply or Ply One or more plies Elastobase (sand/sand or poly/sand), Elastobase P (sand/sand or poly/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 Type II, Polyglass HT Base 650 Hot Asphalt at 20-40 lbs/square Cap Ply Elastoflex V, Elastoflex VG, Elastoflex VG FR, Elastoflex S6, Elastoflex S6 Type II, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS-G, Elastoshield TS-G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed) Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes. SBS-TA (SBS, Torch-Applied) Base Ply or Ply One or more plies Elastobase (sand/poly), Elastobase (poly/poly), Elastoflex V, Elastoflex S6, Elastoflex S6 Type II, Polyglass HT Base 650 Torch-Applied Cap Ply Elastoflex V, Elastoflex VG, Elastoflex VG FR, Elastoflex S6, Elastoflex S6 Type II, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS-G, Elastoshield TS-G FR, Polyfresko G SBS (poly-film backed), Polyfresko G SBS FR (poly-film backed) SBS-SA (SBS, Self-Adhering) Base Ply One or more plies Elastoflex SA V Base, Elastoflex SA V FR Base, Elastoflex SA V Plus, Elastoflex SA V Plus FR Self-Adhering Cap Ply Elastoflex SA P, Elastoflex SA P FR, Polyreflect Note: Unless otherwise noted, permissible membrane substrates for SBS-SA are limited to the SBS-SA Base Ply options herein, Elastobase (poly/sand) or Elastobase (poly/poly). APP-CA1 Cap Ply Polyflex G FR PG350 at 1.5-2.0 gal/square APP-TA (APP, Torch-Applied) Base Ply or Ply One or more plies Polyglass APP Base, Polyflex, Polybond Torch-Applied Cap Ply Polyflex, Polyflex G, Polyflex G FR, Polybond, Polybond G, Polyfresko G, Polyfresko G FR APP-SA (APP, Self-Adhering) Cap Ply Polyflex SA P, Polyflex SA P FR, Polyfresko G SA, Polykool Self-Adhering Note: Unless otherwise noted, permissible membrane substrates for APP-SA are limited to the SBS-SA Base Ply options herein, Elastobase (poly/sand) or Elastobase (poly/poly). 16. Any of the following FBC Approved coatings may be applied to the top roof membrane without adverse effect on the system wind load performance. Refer to current Roofing Materials Directory for fire ratings associated with coating usage.  PG200 Non Fibered Roof Coating;  PG300 Fibered Roof Coating;  PG600 Non-Fibered Aluminum Roof Coating;  PG650 Fibered Aluminum Roof Coating;  PG700 High Quality Elastomeric Roof Coating or KM Acryl 25;  PG700QS (Quick Set) High Quality Elastomeric Roof Coating or KM Acryl 25-QS (for granule-surfaced APP or SBS only);  PG800 Asphalt Emulsion Roof Coating;  Polyplus 60 Premium Non-Fibered Aluminum Roof Coating;  Polyplus 65 Premium Fibered Aluminum Roof Coating;  Polybrite 70 Premium Grade Elastomeric Roof Coating or KM Acryl 15;  Polybrite 70QS (Quick Set) Premium Grade Elastomeric Roof Coating or KM Acryl 15-QS (for granule-surfaced APP or SBS only);  Polybrite 90 High Solids Silicone Roof Coating or Polybrite 95 Silicone Roof Coating. Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 4 of 58 17. Dens Deck shall be field-primed with PG100 prior to self-adhering membrane application. Refer to tables herein for other priming requirements. 18. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in Table 3A applies: VAPOR BARRIER OPTIONS; STRUCTURAL CONCRETE DECK; ADHERED INSULATION PER TABLE 3A Option # Primer Vapor Barrier Insulation Adhesive MDP (psf) Type Attach VB-1. PG100 Elastoflex SA V Plus Self-Adhering Inta-Stik or CR-20, 12-inch o.c. -60.0 VB-2. PG100 Polyglass APP Base Torch-applied Inta-Stik or CR-20, 12-inch o.c. -75.0 VB-3. PG100 Elastoflex SA P Self-Adhering Insta-Stik, 12-inch o.c. -75.0 VB-4. PG100 Elastoflex SA P Self-Adhering Millennium One Step Foamable Adhesive, 12-inch o.c. -157.5 VB-5. PG100 Elastoflex SA P Self-Adhering CR-20, 12-inch o.c. -270.0 VB-6. PG100 Elastoflex SA V Base, Elastoflex SA V FR Base, Elastoflex SA V Plus, Elastoflex SA V Plus FR Self-Adhering Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade Adhesive, OlyBond 500 or CR-20, 12-inch o.c. -290.0 19. ”MDP” = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 5 of 58 TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply SELF-ADHERING BASE PLY: W-1 Min. 15/32- inch plywood Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H- Shield CG, Multi-Max FA3 D-IS, M-OSFA, OB500 or CR-20 (Optional) additional layers(s) of base insulation D-IS, M-OSFA, OB500 or CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -52.5 W-2 Min. 15/32- inch plywood Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H- Shield CG, Multi-Max FA3 D-IS, M-OSFA, OB500 or CR-20 (Optional) additional layers(s) of base insulation D-IS, M-OSFA, OB500 or CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -52.5 TABLE 1B-1: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-3 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS- AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -45.0* W-4 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -45.0* W-5 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS- AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -52.5 W-6 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -52.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 6 of 58 TABLE 1B-1: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply W-7 Min. 19/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28, Tamko Glass Base or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS- AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -60.0 W-8 Min. 19/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28, Tamko Glass Base or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-9 Min. 19/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS- AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -60.0 W-10 Min. 19/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-11 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in four (4), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -67.5 W-12 Min. 15/32-inch plywood Polyglass G2 Base Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -82.5 W-13 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. in 4-inch lap and 6-inch o.c. in five (5) equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -90.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 7 of 58 TABLE 1B-1: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply W-14 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -90.0 W-15 Min. 19/32-inch plywood Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. in 4-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows Min. 2-inch Polytherm, ACFoam II, III, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or ENRGY-3 D-IS, OB500, CR-20 or M- OSFA, atop fastener rows, 7-inch o.c. Min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS, OB500, CR-20 or M-OSFA BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0* SELF-ADHERING BASE PLY: W-16 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two, equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -45.0* W-17 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two, equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -45.0* W-18 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two, equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -52.5 W-19 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two, equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -52.5 W-20 Min. 19/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28, Tamko Glass Base or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 8 of 58 TABLE 1B-1: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply W-21 Min. 19/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top), CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28, Tamko Glass Base or GAFGLAS #75 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -60.0 W-22 Min. 19/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 W-23 Min. 19/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap Fasteners 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -60.0 W-24 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in four (4), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -67.5 W-25 Min. 15/32-inch plywood Polyglass G2 Base Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -82.5 W-26 Min. 15/32-inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. in 4-inch lap and 6-inch o.c. in five (5) equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -90.0 W-27 Min. 15/32-inch plywood Elastobase, Elastobase P (sanded-top) Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -90.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 9 of 58 TABLE 1B-1: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply W-28 Min. 19/32-inch plywood Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. in 4-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows Min. 2-inch Polytherm, ACFoam II, III, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or ENRGY-3 D-IS, OB500, CR-20 or M- OSFA, atop fastener rows, 7-inch o.c. (Optional) Additional layers of base insulation D-IS, OB500, CR-20 or M-OSFA SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0* W-29 Min. 19/32-inch plywood Elastobase, Elastobase P (sanded-top) 32 ga., 1-5/8- inch diameter tin caps with 12 ga. annular ring shank nails 6-inch o.c. in 4-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows Min. 2-inch Polytherm, ACFoam II, III, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or ENRGY-3 D-IS, OB500, CR-20 or M- OSFA, atop fastener rows, 7-inch o.c. (Optional) Additional layers of base insulation D-IS, OB500, CR-20 or M-OSFA Polyflex SA Base (Optional) APP-TA APP-TA -60.0* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 10 of 58 TABLE 1B-2: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-30 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -52.5 W-31 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA or SBS-AA (Optional) BP-AA or SBS-AA SBS-AA, SBS-TA, APP-TA -60.0 W-32 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-33 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -82.5 SELF-ADHERING BASE PLY: W-34 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -52.5 W-35 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 11 of 58 TABLE 1B-2: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply W-36 Min. 19/32- inch plywood Elastobase, Elastobase P (sanded-top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -60.0 W-37 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P (sanded-top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows (Optional) Min. 1.5-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -82.5 TABLE 1C: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Base Ply Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-38 Min. 19/32- inch plywood Min. 1.5-inch ENRGY 3, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #12 or Trufast 3” Metal Insulation Plate with Trufast DP 1 per 1.33 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -60.0 W-39 Min. 15/32- inch plywood Min. 2-inch Polytherm, ACFoam II, ENRGY-3, EnergyGuard Polyiso Insulation, H-Shield or Multi-Max FA3 Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast HD with Trufast 3-inch Insulation Plates 1 per 1 ft2 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum Fiber Roof Board Hot asphalt SBS-AA, SBS- TA, APP-TA (Optional) SBS-AA, SBS-TA, APP-TA SBS-AA, SBS-TA, APP-TA -75.0 SELF-ADHERING BASE PLY: W-40 Min. 15/32- inch plywood Min. 2-inch Polytherm, ACFoam II, ENRGY-3, EnergyGuard Polyiso Insulation, H-Shield or Multi-Max FA3 Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast HD with Trufast 3-inch Insulation Plates 1 per 1 ft2 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -75.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 12 of 58 TABLE 1D: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-41 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 1 per 2 ft2 BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP- AA, SBS-AA, SBS- TA, APP-TA SBS-AA, SBS- TA, APP-TA -30.0 W-42 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast HD with Trufast 3-inch Insulation Plates 1 per 1.78 ft2 SBS-AA, SBS- TA, APP-TA (Optional) SBS- AA, SBS-TA, APP- TA SBS-AA, SBS- TA, APP-TA -45.0 W-43 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast HD with Trufast 3-inch Insulation Plates 1 per 1 ft2 SBS-AA, SBS- TA, APP-TA (Optional) SBS- AA, SBS-TA, APP- TA SBS-AA, SBS- TA, APP-TA -75.0 W-44 Min. 19/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation or min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP 1 per 1.33 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -82.5 SELF-ADHERING BASE PLY: W-45 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast HD with Trufast 3-inch Insulation Plates 1 per 2.67 ft2 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP- SA, SBS-TA, APP-TA -30.0 W-46 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast HD with Trufast 3-inch Insulation Plates 1 per 2.67 ft2 Polyflex SA Base (Optional) APP- TA APP-TA -30.0 W-47 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 1 per 2 ft2 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP- SA, SBS-TA, APP-TA -30.0 W-48 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 1 per 2 ft2 Polyflex SA Base (Optional) APP- TA APP-TA -30.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 13 of 58 TABLE 1D: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Ply Cap Ply W-49 Min. 15/32- inch plywood (Optional for recover) One or more layers, any combination, min. 1- inch, loose laid Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board optionally primed with WB-3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2 ft2 SBS-SA None SBS-SA -45.0 W-50 Min. 15/32- inch plywood (Optional for recover) One or more layers, any combination, min. 1- inch, loose laid Min. 0.25-inch Dens Deck Prime optionally primed with WB-3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2 ft2 SBS-SA None SBS-SA -45.0 W-51 Min. 15/32- inch plywood (Optional for recover) One or more layers, any combination, min. 1- inch, loose laid Min. 0.25-inch SECUROCK Gypsum- Fiber Roof Board optionally primed with WB-3000 Polygrip #14 with Polygrip Hex Plate or Dekfast DF- #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.78 ft2 SBS-SA (Optional when using torch- applied Cap Ply) SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 W-52 Min. 15/32- inch plywood (Optional for recover) One or more layers, any combination, min. 1- inch, loose laid Min. 0.25-inch Dens Deck Prime optionally primed with WB-3000 OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.78 ft2 SBS-SA (Optional when using torch- applied Cap Ply) SBS-TA, APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 W-53 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast HD with Trufast 3-inch Insulation Plates 1 per 1.78 ft2 Polyflex SA Base (Optional) APP- TA APP-TA -45.0 W-54 Min. 15/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H- 2-7/8), OMG #14 HD with OMG 3” Galvalume Steel Plates or Trufast HD with Trufast 3-inch Insulation Plates 1 per 1 ft2 SBS-SA (Optional) SBS- TA, APP-TA SBS-TA, APP-TA -60.0 W-55 Min. 19/32- inch plywood (Optional) One or more layers, any combination, loose laid Min. 1.5-inch ENRGY 3, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP or Trufast 3” Metal Insulation Plate with Trufast DP 1 per 1.33 ft2 SBS-SA (Optional) SBS- SA, SBS-TA, APP- TA SBS-SA, APP- SA, SBS-TA, APP-TA -82.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 14 of 58 TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten Attach Base Ply Cap Ply ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-56 Min. 19/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28, Tamko Glass Base or GAFGLAS #75 OMG Flat Bottom Plates (square) with Roofgrip #14, Dekfast Hex (aka, Dekfast PLT- H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 12-inch o.c. in 4-inch lap and 12- inch o.c. in two (2), equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -52.5 W-57 Min. 19/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase or Elastobase P OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12- inch o.c. in two (2), equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -60.0 W-58 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Polyglass G2 Base, Elastobase, Elastobase P Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 10-inch o.c. in 4-inch lap and 10- inch o.c. in three (3), equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -75.0 W-59 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Polyglass APP Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 10-inch o.c. in 4-inch lap and 10- inch o.c. in three (3), equally spaced, staggered center rows (Optional) APP-TA APP-TA -75.0 W-60 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Polyglass G2 Base, Elastobase, Elastobase P Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS- TA, APP-TA -90.0 W-61 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Polyglass APP Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows (Optional) APP-TA APP-TA -90.0 W-62 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows (Optional) BP-AA or SBS-AA SBS-AA -90.0 W-63 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA, APP-TA SBS-AA, SBS- TA or APP-TA -90.0 W-64 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Polyglass APP Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows (Optional) APP-TA APP-TA -90.0 W-65 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows (Optional) BP-AA or SBS-AA SBS-AA -120.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 15 of 58 TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Insulation Layer(s) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten Attach Base Ply Cap Ply W-66 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA, APP-TA SBS-AA, SBS- TA or APP-TA -120.0 W-67 Min. 15/32- inch plywood One or more layers, any combination Prelim. Attached Polyglass APP Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows (Optional) APP-TA APP-TA -120.0 SELF-ADHERING BASE PLY: W-68 Min. 19/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 12-inch o.c. in 4-inch lap and 12- inch o.c. in two, equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -52.5* W-69 Min. 19/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 12-inch o.c. in 4-inch lap and 12- inch o.c. in two, equally spaced, staggered center rows Polyflex SA Base APP-TA -52.5* W-70 Min. 19/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12- inch o.c. in two, equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -60.0* W-71 Min. 19/32- inch plywood One or more layers, any combination Prelim. Attached Elastobase, Elastobase P (poly- film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12- inch o.c. in two, equally spaced, staggered center rows Polyflex SA Base APP-TA -60.0* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 16 of 58 TABLE 1F-1: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap Ply NO BASE PLY: W-72 Min. 15/32- inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -45.0* W-73 Min. 15/32- inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -52.5 W-74 Min. 15/32- inch plywood Elastobase, Elastobase P Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at 3-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -52.5 W-75 Min. 15/32- inch plywood Elastobase, Elastobase P (poly-film top) Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at 3-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -52.5 W-76 Min. 15/32- inch plywood Polyglass APP Base Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at 3-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows None APP-TA -52.5 W-77 Min. 19/32- inch plywood Elastobase, Elastobase P, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28, Tamko Glass Base or GAFGLAS #75 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -60.0 W-78 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows None SBS-SA, APP-SA -60.0 W-79 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -67.5 W-80 Min. 15/32- inch plywood Polyglass APP Base 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in four (4), equally spaced, staggered center rows None APP-TA -67.5 W-81 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P Simplex MAXX Cap 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -75.0 W-82 Min. 15/32- inch plywood Polyglass APP Base Simplex MAXX Cap 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows None APP-TA -75.0 W-83 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -90.0 W-84 Min. 15/32- inch plywood Polyglass APP Base Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows None APP-TA -90.0 W-85 Min. 15/32- inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -90.0 W-86 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. 4-inch o.c. in 4-inch lap and 4-inch o.c. in four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -97.5 W-87 Min. 15/32- inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -105.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 17 of 58 TABLE 1F-1: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap Ply W-88 Min. 19/32- inch plywood Elastobase, Elastobase P 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 6-inch o.c. in 4-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -112.5 W-89 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. Note: Tin caps are to be primed with PG100 or ASTM D41 primer. 6-inch o.c. in 4-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -112.5 ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-90 Min. 15/32- inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 18-inch o.c. in two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -45.0* W-91 Min. 15/32- inch plywood Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. at 2-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -52.5 W-92 Min. 15/32- inch plywood Elastobase, Elastobase P Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at 3-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -52.5 W-93 Min. 15/32- inch plywood Polyglass APP Base Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at 3-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows APP-TA APP-TA -52.5 W-94 Min. 19/32- inch plywood Elastobase, Elastobase P, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28, Tamko Glass Base or GAFGLAS #75 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -60.0 W-95 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -67.5 W-96 Min. 15/32- inch plywood Polyglass APP Base 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in four (4), equally spaced, staggered center rows APP-TA APP-TA -67.5 W-97 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P Simplex MAXX Cap 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -75.0 W-98 Min. 15/32- inch plywood Polyglass APP Base Simplex MAXX Cap 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows APP-TA APP-TA -75.0 W-99 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -90.0 W-100 Min. 15/32- inch plywood Polyglass APP Base Simplex MAXX Cap 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows APP-TA APP-TA -90.0 W-101 Min. 15/32- inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -90.0 W-102 Min. 15/32- inch plywood Elastobase, Elastobase P Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -105.0 W-103 Min. 19/32- inch plywood Elastobase, Elastobase P 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 6-inch o.c. in 4-inch lap and 6-inch o.c. in four (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -112.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 18 of 58 TABLE 1F-1: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap Ply SELF-ADHERING BASE PLY: W-104 Min. 15/32- inch plywood Elastobase, Elastobase P (poly-film top) Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at 3-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS- TA, APP-TA -52.5 W-105 Min. 15/32- inch plywood Polyglass APP Base, Elastobase, Elastobase P (poly-film top) Original Simplex Cap Nails (1-inch metal head diameter, 11 gauge x min. 1.25-inch long annular grooved shank) 6-inch o.c. at 3-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows Polyflex SA Base APP-TA -52.5 W-106 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS- TA, APP-TA -60.0 W-107 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 8-inch o.c. in 4-inch lap and 8-inch o.c. in three (3), equally spaced, staggered center rows Polyflex SA Base APP-TA -60.0 W-108 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. 4-inch o.c. in 4-inch lap and 4-inch o.c. in four (4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS- TA, APP-TA -97.5 W-109 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. 4-inch o.c. in 4-inch lap and 4-inch o.c. in four (4), equally spaced, staggered center rows Polyflex SA Base APP-TA -97.5 W-110 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. Note: Tin caps are to be primed with PG100 or ASTM D41 primer. 6-inch o.c. in 4-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows Elastoflex SA V Plus, Elastoflex SA V Plus FR SBS-SA, APP-SA, SBS- TA, APP-TA -112.5 W-111 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails. Note: Tin caps are to be primed with PG100 or ASTM D41 primer. 6-inch o.c. in 4-inch lap and 6-inch o.c. in four (4), equally spaced, staggered center rows Polyflex SA Base APP-TA -112.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 19 of 58 TABLE 1F-2: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap NO BASE PLY: W-112 Min. 19/32- inch plywood Elastobase, Elastobase P, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28, Tamko Glass Base or GAFGLAS #75 OMG Flat Bottom Plates (square) with Roofgrip #14, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -52.5 W-113 Min. 19/32- inch plywood Elastobase, Elastobase P OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -60.0 W-114 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -75.0 W-115 Min. 15/32- inch plywood Polyglass APP Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows None APP-TA -75.0 W-116 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA, APP- TA -90.0 W-117 Min. 15/32- inch plywood Polyglass APP Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows None APP-TA -90.0 W-118 Min. 15/32- inch plywood Elastobase, Elastobase P Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows None SBS-AA -90.0 W-119 Min. 15/32- inch plywood Elastobase, Elastobase P OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows None SBS-AA, SBS-TA or APP-TA -90.0 W-120 Min. 15/32- inch plywood Polyglass APP Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows None APP-TA -90.0 W-121 Min. 15/32- inch plywood Elastobase, Elastobase P Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows None SBS-AA -120.0 W-122 Min. 15/32- inch plywood Elastobase, Elastobase P OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows None SBS-AA, SBS-TA or APP-TA -120.0 W-123 Min. 15/32- inch plywood Polyglass APP Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows None APP-TA -120.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 20 of 58 TABLE 1F-2: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY: W-124 Min. 19/32- inch plywood Elastobase, Elastobase P, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma-Ply 28, Tamko Glass Base or GAFGLAS #75 OMG Flat Bottom Plates (square) with Roofgrip #14, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -52.5 W-125 Min. 19/32- inch plywood Elastobase, Elastobase P OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -60.0 W-126 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -75.0 W-127 Min. 15/32- inch plywood Polyglass APP Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 10-inch o.c. in 4-inch lap and 10-inch o.c. in three (3), equally spaced, staggered center rows APP-TA APP-TA -75.0 W-128 Min. 15/32- inch plywood Polyglass G2 Base, Elastobase, Elastobase P Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -90.0 W-129 Min. 15/32- inch plywood Polyglass APP Base Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Round Metal Plate with OMG HD, OMG Flat Bottom Plate (Accutrac) with Roofgrip #14 or Trufast 3” Metal Insulation Plate with Trufast HD. 9-inch o.c. in 4-inch lap and 9-inch o.c. in four (4), equally spaced, staggered center rows APP-TA APP-TA -90.0 W-130 Min. 15/32- inch plywood Elastobase, Elastobase P Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows BP-AA or SBS-AA SBS-AA -90.0 W-131 Min. 15/32- inch plywood Elastobase, Elastobase P OMG #12 Standard Roofgrip or OMG #14 Heavy Duty (min. 1-5/8-inch long) with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -90.0 W-132 Min. 15/32- inch plywood Polyglass APP Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in three (3), equally spaced, staggered center rows APP-TA APP-TA -90.0 W-133 Min. 15/32- inch plywood Elastobase, Elastobase P Trufast #12 DP or Trufast #14 HD with Trufast 3” Metal Insulation Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows BP-AA or SBS-AA SBS-AA -120.0 W-134 Min. 15/32- inch plywood Elastobase, Elastobase P OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows BP-AA, SBS-AA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- AA, SBS-TA, APP-TA -120.0 W-135 Min. 15/32- inch plywood Polyglass APP Base OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3” Round Metal Plates or OMG Flat Bottom Metal Plates 6-inch o.c. at 4-inch lap and 6-inch o.c. in five (5), equally spaced, staggered center rows APP-TA APP-TA -120.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 21 of 58 TABLE 1F-2: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap SELF-ADHERING BASE PLY: W-136 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS- TA, APP-TA -52.5* W-137 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows Polyflex SA Base APP-TA -52.5* W-138 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA, SBS- TA, APP-TA -60.0* W-139 Min. 19/32- inch plywood Elastobase, Elastobase P (poly-film top) OMG Flat Bottom Plates (square) with Roofgrip #12 12-inch o.c. in 4-inch lap and 12-inch o.c. in two (2), equally spaced, staggered center rows Polyflex SA Base APP-TA -60.0* TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE F: NON-INSULATED, BONDED ROOF COVER System No. Deck (Note 1) Primer Roof Cover (Note 15) MDP (psf) Joint Treatment Base Ply Ply Cap Ply W-140 Min. 15/32- inch plywood None None SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- TA, APP-TA -90.0 W-141 Min. 15/32- inch plywood (Optional) PG100 None Polyflex SA Base (Optional) APP-TA APP-TA -90.0 W-142 Min. 15/32- inch plywood PG100 None SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- TA, APP-TA -97.5 W-143 Min. 15/32- inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into place to create continuous bond. Elastoflex SA V Base or Elastoflex SA V FR Base (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- TA, APP-TA -97.5 W-144 Min. 15/32- inch plywood WB-3000 None SBS-SA (Optional) SBS-SA, APP-SA, SBS- TA, APP-TA -105.0 W-145 Min. 15/32- inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into place to create continuous bond. Elastoflex SA V Plus or Elastoflex SA V Plus FR (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS- TA, APP-TA -135.0 W-146 Min. 15/32- inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into place to create continuous bond. Polyflex SA Base (Optional) APP-TA APP-TA -135.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 22 of 58 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Base Ply Ply Cap Ply SELF-ADHERING BASE: SC-1. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 4 ft2 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board PRIMER: WB-3000 D-IS SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -30.0* SC-2. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.6 ft2 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board PRIMER: WB-3000 D-IS SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0 SC-3. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 4 ft2 Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board PRIMER: WB-3000 M-OSFA or M-PG1 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -30.0* SC-4. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.6 ft2 Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board PRIMER: WB-3000 M-OSFA or M-PG1 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0 SC-5. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 4 ft2 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Matg Roof Board or SECUROCK Gypsum-Fiber Roof Board PRIMER: WB-3000 OB500 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -30.0* SC-6. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.6 ft2 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Matg Roof Board or SECUROCK Gypsum-Fiber Roof Board PRIMER: WB-3000 OB500 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0 SC-7. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 4 ft2 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board PRIMER: WB-3000 CR-20 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -30.0* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 23 of 58 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Base Ply Ply Cap Ply SC-8. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.6 ft2 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board PRIMER: WB-3000 CR-20 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0 ASPHALT-APPLIED BASE: SC-9. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast HD or OMG 3-inch Galv Plate with OMD HD 1 per 2 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* SC-10. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, H- Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast HD or OMG 3-inch Galv Plate with OMD HD 1 per 4 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* SC-11. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete Min. 1.5-inch ENRGY 3, H- Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.33 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -90.0 SC-12. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete Min. 1.5-inch ENRGY 3, H- Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14 or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.33 ft2 Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA, SBS- AA (Top surface primed with PG100 primer) SBS-SA, SBS-TA or APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -90.0 COLD-APPLIED BASE: SC-13. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 4 ft2 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -30.0* SC-14. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.6 ft2 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 24 of 58 TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Base Ply Ply Cap Ply SC-15. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 4 ft2 Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -30.0* SC-16. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.6 ft2 Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0 SC-17. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 4 ft2 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Matg Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -30.0* SC-18. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.6 ft2 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Matg Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0 SC-19. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 4 ft2 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -30.0* SC-20. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete Min. 2-inch Polytherm, ACFoam II, ENRGY 3, EnergyGuard Polyiso Insulation, Polytherm H, H- Shield or Multi-Max FA3 Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) with Dekfast #14, OMG 3” Galvalume Ribbons Plates with OMG #14 Roofgrip or Trufast 3” Metal Insulation Plate with Trufast HD 1 per 1.6 ft2 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 25 of 58 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Ply Cap Ply SELF-ADHERING BASE: SC-21. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.67 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -30.0 SC-22. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch Polytherm, ACFoam II, H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2.67 ft2 Polyflex SA Base (Optional) APP-TA APP-TA -30.0 SC-23. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch Dens Deck Prime optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.67 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -37.5* SC-24. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch Dens Deck Prime optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.67 ft2 Polyflex SA Base (Optional) APP-TA APP-TA -37.5* SC-25. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.67 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -37.5* SC-26. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.67 ft2 Polyflex SA Base (Optional) APP-TA APP-TA -37.5* SC-27. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DEXcell FA Glass Mat Roof Board optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), isofast PLT-S-2-3/4X2-3/4 or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.67 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -37.5* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 26 of 58 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Ply Cap Ply SC-28. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch DEXcell FA Glass Mat Roof Board optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8), isofast PLT-S-2-3/4X2-3/4 or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2.67 ft2 Polyflex SA Base (Optional) APP-TA APP-TA -37.5* SC-29. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch H-Shield or Polytherm OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -45.0* SC-30. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch H-Shield or Polytherm OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2 ft2 Polyflex SA Base (Optional) APP-TA APP-TA -45.0* SC-31. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14, OMG 3” Galvalume Ribbed Plates with OMG #14 RoofGrip or Trufast 3” Metal Insulation Plates with Trufast #14 HD Fasteners 1 per 2 ft2 SBS-SA None SBS-CA1, SBS-CA2, APP-CA1 -45.0* SC-32. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2 ft2 SBS-SA (Optional) SBS-SA, SBS-TA or APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -45.0* SC-33. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or Dekfast Galvalume Steel 3” Round (aka, Dekfast PLT-R-3) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2 ft2 SBS-SA None SBS-SA -45.0 SC-34. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch Dens Deck Prime optionally primed with WB-3000 Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD Fasteners with Trufast 3” Metal Insulation Plate 1 per 2 ft2 SBS-SA None SBS-SA -45.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 27 of 58 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Ply Cap Ply SC-35. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.78 ft2 SBS-SA (Optional when using torch-applied Cap Ply) SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -45.0 SC-36. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch Dens Deck Prime optionally primed with WB-3000 OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1.78 ft2 SBS-SA (Optional when using torch-applied Cap Ply) SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -45.0 SC-37. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch H-Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14 1 per 2 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -60.0 SC-38. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 1.6 ft2 SBS-SA (Optional) SBS-TA or APP-TA SBS-TA or APP-TA -60.0 SC-39. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 OMG 3 in. Galvalume Plate (non-ribbed) with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 1.33 ft2 SBS-SA (Optional) SBS-TA or APP-TA SBS-TA or APP-TA -72.5 SC-40. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 0.5-inch SECUROCK Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per 1.78 ft2 SBS-SA (Optional) SBS-TA SBS-TA -75.0 SC-41. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 1.5-inch ENRGY 3, H- Shield or Polytherm Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 (steel only) or #14 or Trufast 3” Metal Insulation Plate with Trufast DP (steel only) or HD 1 per 1.33 ft2 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -82.5 SC-42. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1 ft2 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -90.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 28 of 58 TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Ply Cap Ply SC-43. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, min. 1-inch, loose laid Min. 0.25-inch Dens Deck Prime optionally primed with WB-3000 Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or Dekfast DF-#14 or DF-#15 with Dekfast Hex (aka, Dekfast PLT-H-2-7/8) or OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal Plate or Trufast #14 HD or Trufast #15 EHD Fasteners with Trufast 3” Metal Insulation Plate 1 per 1 ft2 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -97.5 ASPHALT-APPLIED BASE: SC-44. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination, loose laid Min. 0.75-inch JM Fesco Board (homogeneous) or min. 1.5-inch JM Fesco Board (laminated) OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 2 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* SC-45. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination, loose laid Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation or G-P FiberBase HD or HD Excel OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 4 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* SC-46. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 4 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* SC-47. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 2-inch H-Shield WF OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate with #12 Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 DP (steel only) or Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast #12 DP (steel only) or Trufast #14 HD 1 per 4 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* SC-48. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional) One or more layers, any combination, loose laid Min. 0.5-inch SECUROCK Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per 1.78 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -75.0 SC-49. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination, loose laid Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation or min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #12 (steel only) or #14 or Trufast 3” Metal Insulation Plate with Trufast DP (steel only) or HD 1 per 1.33 ft2 (Optional if using AA Ply) BP-AA, SBS- AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -82.5 COLD-APPLIED BASE: SC-50. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete (Optional for recover) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board Dekfast Galvalume Steel Hex with Dekfast #14, OMG 3” Galvalume Ribbed Plates with OMG #14 RoofGrip or Trufast 3” Metal Insulation Plates with Trufast #14 HD Fasteners 1 per 2 ft2 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS-CA2, APP-CA1 -45.0* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 29 of 58 TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER NOTE: INSULATION IS OPTIONAL FOR RECOVER APPLICATIONS System No. Deck (Note 1) Insulation Layer(s) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten Attach Base Ply Cap Ply SC-51. Min. 22 ga., type B, 40 ksi steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastoflex S6 (film surfaced) Trufast #14 HD with Trufast 2” Barbed Seam Plates 18-inch o.c. within the 4-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA -30.0 SC-52. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Polyglass HT Base 650 Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast 2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal Seam Plates or Dekfast #15 with Dekfast Galvalume Steel 1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2-3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B) 18-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA -37.5 SC-53. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastobase, Elastobase P or JM Perma-Ply 28 Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at 4-inch lap and 18-inch o.c. at two, equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -45.0* SC-54. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Loose laid Elastobase Trufast #12 DP (steel only), #14 HD or #15 EHD with Trufast 3” Metal Insulation Plate 12-inch o.c. at 4-inch lap and 12-inch o.c. at one staggered center row (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -45.0* SC-55. Min. 22 ga., type B, 33 ksi steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal Seam Plates 12-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA -45.0 SC-56. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastobase, Elastobase P, Polyglass G2 Base, CertainTeed Glasbase, Firestone MB Base, JM Perma- Ply 28, Tamko Glass Base or GAFGLAS #75 Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -52.5 SC-57. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -52.5* SC-58. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #14 with OMG Flat Bottom Plates (square), Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) or Trufast #14 HD with Trufast 3” Metal Insulation Plate 12-inch o.c. at 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows Polyflex SA Base APP-TA -52.5* SC-59. Min. 22 ga., type B, 33 ksi steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 6-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA -60.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 30 of 58 TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER NOTE: INSULATION IS OPTIONAL FOR RECOVER APPLICATIONS System No. Deck (Note 1) Insulation Layer(s) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten Attach Base Ply Cap Ply SC-60. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Type II Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 18-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA (D6164 only) -60.0 SC-61. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P Roofgrip #12 (steel only) or #14 with OMG Flat Bottom Plates (square) 12-inch o.c. at 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -60.0 SC-62. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #12 (steel only) or #14 with OMG Flat Bottom Plates (square) 12-inch o.c. at 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows SBS-SA SBS-SA, APP- SA, SBS-TA or APP-TA -60.0* SC-63. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastobase or Elastobase P with poly top surface Roofgrip #12 (steel only) or #14 with OMG Flat Bottom Plates (square) 12-inch o.c. at 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows Polyflex SA Base APP-TA -60.0* SC-64. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Loose laid Elastobase Trufast #12 DP (steel only), #14 HD or #15 EHD with Trufast 3” Metal Insulation Plate 12-inch o.c. at 4-inch lap and 12-inch o.c. at two, equally spaced, staggered center rows (Optional) SBS- CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -67.5 SC-65. Min. 22 ga., type B, 33 ksi steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Type II Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 12-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA (D6164 only) -82.5 SC-66. Min. 22 ga., type B, 33 ksi steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Polyglass HT Base 650 Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast 2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal Seam Plates or Dekfast #15 with Dekfast Galvalume Steel 1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2-3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B) 12-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA (D6164 only) -82.5 SC-67. Min. 22 ga., type B, Grade 80 steel One or more layers, any combination Prelim. Attached Polyflex Dekfast #15 HS with Dekfast Galvalume Steel 2-3/8” Round Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B) 12-inch o.c. within the 5-inch wide, torch-sealed side lap (Optional) APP- TA SBS-TA, APP- TA -82.5 SC-68. Min. 22 ga., type B, Grade 80 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Polybond or Polyflex Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4 in. Barbed Seam Plates 12-inch o.c. within the 6-inch wide, torch-sealed side lap (Optional) APP- TA SBS-TA, APP- TA -82.5 SC-69. Min. 22 ga., type B, 40 ksi steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Type II Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 6-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA (D6164 only) -97.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 31 of 58 TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER NOTE: INSULATION IS OPTIONAL FOR RECOVER APPLICATIONS System No. Deck (Note 1) Insulation Layer(s) Base Sheet Roof Cover (Note 15) MDP (psf) Type Attach Type Fasten Attach Base Ply Cap Ply SC-70. Min. 22 ga., type B, 40 ksi steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Polyglass HT Base 650 Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast 2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal Seam Plates or Dekfast #15 with Dekfast Galvalume Steel 1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2-3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B) 6-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA (D6164 only) -97.5 SC-71. Min. 22 ga., type B, Grade 33 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Polybond, Polyflex Dekfast #14 with Dekfast Hex (aka, Dekfast PLT-H-2- 7/8) or OMG Roofgrip #14 OMG Flat Bottom Plates 12-inch o.c. at the 4-inch lap and 18-inch o.c. at two, equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, APP-TA -112.5 SC-72. Min. 22 ga., type B, Grade 40 steel or min. 2,500 psi structrual concrete One or more layers, any combination Prelim. Attached Elastoflex S6 Type II Trufast #15 EHD (steel only) or Trufast #14 HD (concrete only) with Trufast 2.75” Barbed Metal Seam Plates 6-inch o.c. within the 5-inch wide, torch-sealed or heat- welded side laps (Optional) SBS- TA SBS-TA (D6164 only) -135.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 32 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply SELF-ADHERING BASE WITH BASE INSULATION AND OPTIONAL TOP INSULATION OF THE SAME TYPE: C-1 Structural concrete (Optional) PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -67.5 C-2 Structural concrete (Optional) PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation D-IS Polyflex SA Base (Optional) APP-TA APP-TA -67.5 C-3 Structural concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA or Polyflex SA Base (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -122.5 C-4 Structural concrete (Optional) PG100 Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -135.0 C-5 Structural concrete (Optional) PG100 Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation D-IS Polyflex SA Base (Optional) APP-TA APP-TA -135.0 C-6 Structural concrete None Min. 1.5-inch, min. 1.5 pcf Insulfoam D-IS (Optional) additional layers of base insulation D-IS SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -157.5 C-7 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield D-IS (Optional) additional layers of base insulation PRIMER: PG100 D-IS Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -170.0 C-8 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -120.0 C-9 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA or Polyflex SA Base (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -122.5 C-10 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -127.5 C-11 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional layers(s) of base insulation OB500 Polyflex SA Base (Optional) APP-TA APP-TA -127.5 C-12 Structural concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -150.0 C-13 Structural concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 Polyflex SA Base (Optional) APP-TA APP-TA -150.0 C-14 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield OB500 (Optional) additional layers of base insulation PRIMER: PG100 OB500 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -170.0 C-15 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 (Optional) additional layers(s) of base insulation M-OSFA or M-PG1 SBS-SA or Polyflex SA Base (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -122.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 33 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply C-16 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield M-OSFA or M-PG1 (Optional) additional layers of base insulation PRIMER: PG100 M-OSFA or M-PG1 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -170.0 C-17 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -232.5 C-18 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation M-OSFA Polyflex SA Base (Optional) APP-TA APP-TA -232.5 C-19 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax. M-OSFA or M-PG1 (Optional) additional layers(s) of base insulation, optionally primed with WB-3000 M-OSFA or M-PG1 SBS-SA None SBS-CA1, SBS- CA2 -290.0 C-20 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H-Shield CR-20 (Optional) additional layers(s) of base insulation CR-20 SBS-SA or Polyflex SA Base (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -122.5 C-21 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield CR-20 (Optional) additional layers of base insulation PRIMER: PG100 CR-20 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -170.0 C-22 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -240.0 C-23 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) (Optional) additional layers(s) of base insulation OB Classic (full- coverage) SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -270.0 C-24 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) (Optional) additional layers(s) of base insulation OB Classic (full- coverage) Polyflex SA Base (Optional) APP-TA APP-TA -270.0 C-25 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt (Optional) additional layers(s) of base insulation Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -480.0 C-26 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt (Optional) additional layers(s) of base insulation Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -480.0 SELF-ADHERING BASE WITH BASE INSULATION AND COVERBOARD: C-27 Structural concrete None Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -67.5 C-28 Structural concrete None Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS Polyflex SA Base (Optional) APP-TA APP-TA -67.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 34 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply C-29 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield D-IS Min. 0.25-inch Dens Deck Prime D-IS SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5 C-30 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch Dens Deck, Dens Deck Prime D-IS SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -120.0 C-31 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch Dens Deck, Dens Deck Prime D-IS Polyflex SA Base (Optional) APP-TA APP-TA -120.0 C-32 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield D-IS Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board PRIMER: PG100 D-IS Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -172.5 C-33 Structural concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -247.5 C-34 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch Dens Deck Prime optionally primed with WB-3000 D-IS SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-35 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board optionally primed with WB-3000 D-IS SBS-SA or Polyflex SA Base (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-36 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or ISO 95+GL OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5 C-37 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch Dens Deck, Dens Deck Prime OB500 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -127.5 C-38 Structural concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch Dens Deck, Dens Deck Prime OB500 Polyflex SA Base (Optional) APP-TA APP-TA -127.5 C-39 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, H-Shield or ISO 95+GL OB500 Min. 0.25-inch Dens Deck, Dens Deck Prime OB500 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -150.0 C-40 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, H-Shield or ISO 95+GL OB500 Min. 0.25-inch Dens Deck, Dens Deck Prime OB500 Polyflex SA Base (Optional) APP-TA APP-TA -150.0 C-41 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield OB500 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board PRIMER: PG100 OB500 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -172.5 C-42 Structural concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -247.5 C-43 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 35 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply C-44 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board OB500 SBS-SA or Polyflex SA Base (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-45 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch Dens Deck Prime M-OSFA SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5 C-46 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield M-OSFA or M-PG1 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board PRIMER: PG100 M-OSFA or M-PG1 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -172.5 C-47 Structural concrete None Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -232.5 C-48 Structural concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -247.5 C-49 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch Dens Deck Prime M-OSFA or M-PG1 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-50 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board M-OSFA or M-PG1 SBS-SA or Polyflex SA Base (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-51 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min. 2- inch Polytherm, ACFoam II, min. 1.5-inch Ultra- Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch Dens Deck, Dens Deck Prime CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5 C-52 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield CR-20 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board PRIMER: PG100 CR-20 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -172.5 C-53 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min. 1.5- inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch Dens Deck, Dens Deck Prime CR-20 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -240.0 C-54 Structural concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam, Min. 1.5- inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch Dens Deck, Dens Deck Prime CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -240.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 36 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply C-55 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 C-56 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -240.0 C-57 Structural concrete None Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -247.5 C-58 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch Dens Deck Prime CR-20 SBS-SA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-59 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board CR-20 SBS-SA or Polyflex SA Base (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-60 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -350.0 C-61 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) Polyflex SA Base (Optional) APP-TA APP-TA -350.0 C-62 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -350.0 C-63 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP-TA APP-TA -350.0 ASPHALT OR TORCH APPLIED BASE: C-64 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-65 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch Dens Deck Prime D-IS SBS-TA, APP-TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-66 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board D-IS SBS-TA, APP-TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-67 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-68 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-TA, APP-TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 37 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply C-69 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board OB500 SBS-TA, APP-TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-70 Structural concrete None Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield M-OSFA or M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA or M-PG1 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-71 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch Dens Deck Prime M-OSFA or M-PG1 SBS-TA, APP-TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-72 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield M-OSFA or M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board M-OSFA or M-PG1 SBS-TA, APP-TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-73 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-74 Structural concrete None Min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H- Shield CG or ENRGY 3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-TA (Optional) APP-TA APP-TA -232.5 C-75 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch Dens Deck Prime CR-20 SBS-TA, APP-TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -282.5 C-76 Structural concrete None (Optional) Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or DEXcell FA Glass Mat Roof Board CR-20 SBS-TA, APP-TA (Optional) SBS-TA, APP-TA SBS-TA, APP-TA -322.5 C-77 Structural concrete None (Optional) Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-78 Structural concrete None (Optional) Min. 2-inch Polytherm, ACFoam II, Polytherm H or H-Shield OB Classic (full- coverage) Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB Classic (full- coverage) APP-TA (Optional) APP-TA APP-TA -232.5 C-79 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA (Optional) BP-AA, SBS-AA SBS-AA -225.0 C-80 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board Hot asphalt APP-TA (Optional) APP-TA APP-TA -232.5 C-81 Structural concrete PG100 Min. 0.75-inch Fesco Board (homogeneous) Hot asphalt None N/A (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -277.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 38 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply C-82 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.75-inch Fesco Board (homogeneous) Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -290.0 C-83 Structural concrete PG100 Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt None N/A (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -285.0 C-84 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -480.0 C-85 Structural concrete PG100 Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck Prime Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -480.0 C-86 Structural concrete PG100 Min. 0.25-inch Dens Deck Prime Hot asphalt None N/A (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -510.0 COLD-APPLIED BASE: C-87 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H or H-Shield D-IS Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 C-88 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield D-IS Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board D-IS SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-89 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-90 Structural concrete None Min. 1-inch ENRGY 3, Polytherm H or H-Shield D-IS Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 C-91 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5- inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 39 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply C-92 Structural concrete None Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5- inch SECUROCK Cement Roof Board M-OSFA, M-PG1 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-93 Structural concrete None Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA, M-PG1 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-94 Structural concrete None Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5- inch SECUROCK Cement Roof Board M-OSFA, M-PG1 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 C-95 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 C-96 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board OB500 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-97 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-98 Structural concrete None Min. 1-inch Polytherm, ACFoam II, ENRGY 3 or Multi-Max FA3 OB500 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 C-99 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 C-100 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 40 of 58 TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 18 System No. Deck (Note 1) Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply C-101 Structural concrete None Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 C-102 Structural concrete None Min. 1-inch ENRGY 3, Polytherm H, H-Shield, Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 TABLE 3B: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE F: NON-INSULATED, BONDED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Primer Roof Cover (Note 15) MDP (psf) Base Ply Ply Cap Ply C-103 Structural concrete None SBS-CA1 None SBS-CA1, SBS-CA2, APP-CA1 -105.0 C-104 Structural concrete PG100 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -117.5 C-105 Structural concrete PG100 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -315.0 C-106 Structural concrete PG100 Polyflex SA Base (Optional) APP-TA APP-TA -315.0 C-107 Structural concrete PG100 (Optional) SBS-TA (Optional) SBS-TA SBS-TA -495.0 C-108 Structural concrete PG100 BP-AA (Optional if using asphalt applied Ply) (Optional if using asphalt applied Base) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -622.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 41 of 58 TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Insulation Layer Coverboard Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply SELF-ADHERING BASE WITH BASE INSULATION AND OPTIONAL TOP INSULATION OF THE SAME TYPE: LWC-1 Structural concrete Min. 200 psi, min 2-inch Elastizell Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) Additional layers of base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -120.0 LWC-2 Structural concrete Min. 200 psi, min 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 (Optional) Additional layers of base insulation OB500 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -225.0 LWC-3 Structural concrete Min. 200 psi, min 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 (Optional) Additional layers of base insulation OB500 Polyflex SA Base (Optional) APP-TA APP-TA -225.0 LWC-4 Structural concrete Min. 200 psi, min. 2-inch Elastizell Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -180.0 LWC-5 Structural concrete Min. 200 psi, min. 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -180.0 LWC-6 Structural concrete Min. 200 psi, min. 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -180.0 LWC-7 Structural concrete Min. 200 psi, min. 2-inch Celcore or Mearlcrete Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -222.5 LWC-8 Structural concrete Min. 200 psi, min. 2-inch Celcore or Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -222.5 LWC-9 Structural concrete Min. 200 psi, min. 2-inch Celcore or Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 CR-20 (Optional) Additional layers of base insulation CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -222.5 SELF-ADHERING BASE WITH BASE INSULATION AND COVERBOARD: LWC-10 Structural concrete Min. 200 psi, min 2-inch Elastizell Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -120.0 LWC-11 Structural concrete Min. 200 psi, min 2-inch Elastizell Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 Polyflex SA Base (Optional) APP-TA APP-TA -120.0 LWC-12 Structural concrete Min. 200 psi, min 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -225.0 LWC-13 Structural concrete Min. 200 psi, min 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 Polyflex SA Base (Optional) APP-TA APP-TA -225.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 42 of 58 TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Insulation Layer Coverboard Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply LWC-14 Structural concrete Min. 200 psi, min. 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -180.0 LWC-15 Structural concrete Min. 200 psi, min. 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -180.0 LWC-16 Structural concrete Min. 200 psi, min. 2-inch Celcore or Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -222.5 LWC-17 Structural concrete Min. 200 psi, min. 2-inch Celcore or Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -222.5 ASPHALT OR TORCH APPLIED BASE: LWC-18 Structural concrete Min. 200 psi, min 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, ISO 95+ GL, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 BP-AA, SBS- AA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -225.0 LWC-19 Structural concrete Min. 200 psi, min. 2-inch Elastizell Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 BP-AA, SBS- AA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -180.0 LWC-20 Structural concrete Min. 200 psi, min. 2-inch Celcore or Mearlcrete Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, ISO 95+ GL, Polytherm H, H-Shield, H-Shield CG, Multi-Max FA3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 BP-AA, SBS- AA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -222.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 43 of 58 TABLE 4B: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply LWC-21 Min. 22 ga., Type B, vented steel at max. 5 ft spans Min. 300 psi Approved cellular LWC GAFGLAS #75 OMG CR BSF 7-inch o.c. at 4- inch lap and 7- inch o.c. in two, equally spaced center rows (Optional) Min. 1.5- inch Polytherm, ACFoam II, Polytherm H, H-Shield, Multi- Max FA3 or Polytherm HA Min. 1.5-inch Thermaroof Composite, Polytherm Composite, or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation or min. 0.75-inch Fesco Board (homogeneous) HA (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0 LWC-22 Min. 22 ga., Type B, vented steel at max. 5 ft spans Min. 300 psi Approved cellular LWC GAFGLAS #75 OMG CR BSF 7-inch o.c. at 4- inch lap and 7- inch o.c. in two, equally spaced center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H- Shield, Multi-Max FA3 or Polytherm HA None N/A SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -45.0 LWC-23 Min. 22 ga., Type B, vented steel at max. 5 ft spans Min. 300 psi Approved cellular LWC GAFGLAS #75 OMG CR BSF 7-inch o.c. at 4- inch lap and 7- inch o.c. in two, equally spaced center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm H, H- Shield, Multi-Max FA3 or Polytherm HA None N/A Polyflex SA Base (Optional) APP-TA APP-TA -45.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 44 of 58 TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap Ply ‘GENERIC’ CELLULAR LIGHTWEIGHT INSULATING CONCRETE: LWC-24 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick cellular LWC. Note: To qualify the LWIC under this assembly, an OMG CR BPF shall achieve an average withdrawal of 53 lbf when tested per TAS 105 or ANSI/SPRI FX-1 B3 OMG CR BPF 7-inch o.c. in a 3-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet (Optional) BP- AA, SBS-AA SBS-AA, APP- TA -45.0 CELCORE CELLULAR LIGHTWEIGHT INSULATING CONCRETE: LWC-25 Min. 0.0179-inch Tensilform S-75 or min. 0.0205-inch Tensilform 75 at max. 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Celcore B1, B2, B3 or B7 Trufast FM-90 or OMG CR BPF 8-inch o.c. in a 3-inch lap and 16-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -37.5 LWC-26 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Celcore B1 through B12 Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 3-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -45.0 LWC-27 Min. 26 ga., type HF steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF B1, B2, B3, B4, B7, B8, B10, B11 or B12 OMG CR BPF 9-inch o.c. in a 3-inch lap and 9-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -45.0 LWC-28 Min. 22 ga., type B steel at max 6 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF B1, B2, B3, B4, B7, B8, B10, B11 or B12 OMG CR BPF 7-inch o.c. in a 3-inch lap and 14-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -45.0 LWC-29 Min. 22 ga., type B steel at max 6 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF B1, B2, B3, B4, B7, B8, B10, B11 or B12 OMG CR BPF 9-inch o.c. in a 3-inch lap and 9-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -45.0 LWC-30 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF B1 or B2 Trufast Twin Loc-Nail 9-inch o.c. in a 4-inch lap and 18-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, or APP-TA -45.0 LWC-31 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF B2 (with poly-film top surface) Trufast Twin Loc-Nail 9-inch o.c. in a 4-inch lap and 18-inch o.c. in two, equally spaced, staggered rows in the field of the sheet SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 LWC-32 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 225 psi, min. 2-inch thick Celcore MF B2 (with poly-film top surface) Trufast Twin Loc-Nail 9-inch o.c. in a 4-inch lap and 18-inch o.c. in two, equally spaced, staggered rows in the field of the sheet Polyflex SA Base APP-TA -45.0 LWC-33 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF B2 Trufast FM-90 8-inch o.c. in a 4-inch lap and 8-inch o.c. in three equally spaced, staggered center rows BP-AA, SBS-AA, SBS-TA or APP- TA SBS-AA, SBS- TA, or APP-TA -60.0 LWC-34 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF B2 (with poly-film top surface) Trufast FM-90 8-inch o.c. in a 4-inch lap and 8-inch o.c. in three equally spaced, staggered center rows SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -60.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 45 of 58 TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap Ply LWC-35 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF B2 (with poly-film top surface) Trufast FM-90 8-inch o.c. in a 4-inch lap and 8-inch o.c. in three equally spaced, staggered center rows Polyflex SA Base APP-TA -60.0 LWC-36 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore B1 through B12 Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 3-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, APP-TA SBS-AA, APP- TA -75.0 LWC-37 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Celcore MF Elastobase P Trufast FM-290 10-inch o.c. in a 4-inch lap and 10-inch o.c. in three equally spaced, staggered center rows (Optional) BP- AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS- TA, APP-TA -90.0 ELASTIZELL CELLULAR LIGHTWEIGHT INSULATING CONCRETE: LWC-38 Min. 0.0179-inch Tensilform S-75 or min. 0.0205-inch Tensilform 75 at max. 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Elastizell Range II B1 through B12 Trufast FM-90 or OMG CR BPF 7.5-inch o.c. in a 3-inch lap and 7.5-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, or APP- TA SBS-AA, SBS- TA, or APP-TA -30.0 LWC-39 Min. 0.0179-inch Tensilform S-75 or min. 0.0205-inch Tensilform 75 at max. 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Elastizell Range II B2 (with poly-film top surface) Trufast FM-90 or OMG CR BPF 7.5-inch o.c. in a 3-inch lap and 7.5-inch o.c. in two, equally spaced, staggered rows in the field of the sheet SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -30.0 LWC-40 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Elastizell Range II B1 through B12 Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 3-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, or APP- TA SBS-AA, SBS- TA, or APP-TA -45.0 LWC-41 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Elastizell Range II B2 (with poly-film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 3-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 LWC-42 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Elastizell Range II B2 (with poly-film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 3-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet Polyflex SA Base APP-TA -45.0 LWC-43 Min. 22 ga., type B vented steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 Elastobase P (with poly-film top surface) Trufast FM-290 8-inch o.c. in a 4-inch lap and 8-inch o.c. in three, equally spaced, staggered rows in the field of the sheet (Optional) BP- AA, SBS-AA, SBS- TA, or APP-TA SBS-AA, SBS- TA, or APP-TA -52.5 LWC-44 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 B2 Trufast Twin Loc-Nails (min. 1.8-inch) 6-inch o.c. in a 4-inch lap and 6-inch o.c. in three, equally spaced, staggered rows in the field of the sheet BP-AA or SBS-AA SBS-AA, SBS- TA, SBS-SA, APP-TA or APP-SA -60.0 LWC-45 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 B2 (with poly-film top surface) Trufast Twin Loc-Nails (min. 1.8-inch) 6-inch o.c. in a 4-inch lap and 6-inch o.c. in three, equally spaced, staggered rows in the field of the sheet SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -60.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 46 of 58 TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap Ply LWC-46 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 350 psi, min. 2-inch thick Elastizell with Zell-Crete Fibers, supplemental attached with Roofgrip #21 and 3-inch plates at 1 per 8 ft2 B2 (with poly-film top surface) Trufast Twin Loc-Nails (min. 1.8-inch) 6-inch o.c. in a 4-inch lap and 6-inch o.c. in three, equally spaced, staggered rows in the field of the sheet Polyflex SA Base APP-TA -60.0 MEARLCRETE CELLULAR LIGHTWEIGHT INSULATING CONCRETE: LWC-47 Min. 24 ga., type B steel at max 5 ft spans or structural concrete Min. 200 psi, min. 2-inch thick Mearlcrete B1 through B12 Trufast FM-90 or OMG CR BPF 7.5-inch o.c. in a 3-inch lap and 10-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA SBS-AA -30.0 LWC-48 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B1, B2 or B12 Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 4-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, or APP- TA SBS-AA, SBS- TA, or APP-TA -45.0 LWC-49 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly-film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 4-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -45.0 LWC-50 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly-film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 4-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet Polyflex SA Base APP-TA -45.0 LWC-51 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B1, B2, B3, B7 or B11 Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 4-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet BP-AA, SBS-AA, SBS-TA, or APP- TA SBS-AA, SBS- TA, or APP-TA -52.5 LWC-52 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly-film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 4-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet SBS-SA, SBS-TA or APP-TA SBS-SA, APP- SA, SBS-TA or APP-TA -52.5 LWC-53 Min. 22 ga., type B steel at max 5 ft spans or structural concrete Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly-film top surface) Trufast FM-90 or OMG CR BPF 7-inch o.c. in a 4-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the field of the sheet Polyflex SA Base APP-TA -52.5 A. Base Sheets options in Table 4C are coded as follows:  B1: Polyglass G2 Base; B2: Elastobase or Elastobase P; B3: GAFGLAS #75; B4: GAFGLAS Stratavent Nailable Venting Base Sheet; B5: GAFGLAS Ply 4; B6: GAFGLAS FlexPly 6; B7: JM Perma Ply No. 28; B8: JM Vensulation; B9: JM GlasPly IV; B10: JM GlasPly Premier; B11: Tamko Glass-Base; B12: Tamko Vapor-Chan Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 47 of 58 TABLE 5A: CEMENTITIOUS WOOD FIBER DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply CWF-1 Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H- Shield, Polytherm, ENRGY-3 D-IS or OB500 Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation D-IS or OB500 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0 CWF-2 Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H- Shield, Polytherm, ENRGY-3 D-IS or OB500 Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board D-IS or OB500 SBS-TA, SBS-SA or APP-TA (Optional) SBS-TA, SBS-SA or APP-TA SBS-TA, SBS- SA, APP-TA, APP-SA -45.0 CWF-3 Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H- Shield, Polytherm, ENRGY-3 D-IS or OB500 Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board D-IS or OB500 Polyflex SA Base (Optional) APP-TA APP-TA -45.0 CWF-4 Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H- Shield, Polytherm, ENRGY-3 CR-20 Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation CR-20 BP-AA, SBS-AA (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -52.5 CWF-5 Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H- Shield, Polytherm, ENRGY-3 CR-20 Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-TA, SBS-SA or APP-TA (Optional) SBS-TA, SBS-SA or APP-TA SBS-TA, SBS- SA, APP-TA, APP-SA -52.5 CWF-6 Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 1.5-inch Polytherm, ACFoam II, ISO 95+GL, Polytherm H, H- Shield, Polytherm, ENRGY-3 CR-20 Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -52.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 48 of 58 TABLE 5B: CEMENTITIOUS WOOD FIBER DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply CWF-7 Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Polyglass G2 Base Trufast Inuldek Loc-Nail 9-inch o.c. in 4-inch lap and 12-inch o.c. in two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3, Polytherm or Multi-Max FA3, Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board, Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5- inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA, SBS-AA (Optional) BP- AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS-TA, APP-TA -30.0* CWF-8 Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Polyglass G2 Base Trufast Inuldek Loc-Nail 9-inch o.c. in 4-inch lap and 12-inch o.c. in two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3, Polytherm or Multi-Max FA3, Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-TA, SBS-SA or APP-TA (Optional) SBS- TA, SBS-SA or APP-TA SBS-TA, SBS-SA, APP-TA, APP-SA -30.0* CWF-9 Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Polyglass G2 Base Trufast Inuldek Loc-Nail 9-inch o.c. in 4-inch lap and 12-inch o.c. in two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3, Polytherm or Multi-Max FA3, Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP- TA APP-TA -30.0* CWF-10 Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Polyglass G2 Base Trufast Twin Loc- Nail 9-inch o.c. in 4-inch lap and 18-inch o.c. in two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3, Polytherm or Multi-Max FA3, Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board, Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5- inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA, SBS-AA (Optional) BP- AA, SBS-AA, SBS- TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* CWF-11 Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Polyglass G2 Base Trufast Twin Loc- Nail 9-inch o.c. in 4-inch lap and 18-inch o.c. in two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3, Polytherm or Multi-Max FA3, Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt SBS-TA, SBS-SA or APP-TA (Optional) SBS- TA, SBS-SA or APP-TA SBS-TA, SBS-SA, APP-TA, APP-SA -45.0* CWF-12 Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Polyglass G2 Base Trufast Twin Loc- Nail 9-inch o.c. in 4-inch lap and 18-inch o.c. in two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3, Polytherm or Multi-Max FA3, Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board Hot asphalt Polyflex SA Base (Optional) APP- TA APP-TA -45.0* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 49 of 58 TABLE 5C: CEMENTITIOUS WOOD FIBER DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Base Ply Ply Cap Ply CWF-13 Min. 2.5-inch Tectum Plank or Tectum LS Plank Min. 2-inch H- Shield or Polytherm OMG Polymer GypTec Plate with Polymer GypTec or Trufast TL 3 in. Plate with TL Fastener 1 per 4 ft2 Min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* TABLE 5D: CEMENTITIOUS WOOD FIBER DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Ply Cap Ply CWF-14 Min. 2.5-inch Tectum Plank or Tectum LS Plank (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Trufast Twin Loc-Nails (min. 1-inch embedment) 1 per 2 ft2 (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* TABLE 5E: CEMENTITIOUS WOOD FIBER DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap Ply CWF-15 Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Polyglass G2 Base Trufast Inuldek Loc-Nail 9-inch o.c. in 4-inch lap and 12-inch o.c. in two, equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -30.0* CWF-16 Min. 2.5-inch Tectum Plank or Tectum LS Plank Elastobase, Elastobase P, Polyglass G2 Base Trufast Twin Loc-Nails 9-inch o.c. in 4-inch lap and 18-inch o.c. in two, equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 50 of 58 TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply SELF-ADHERING BASE: G-1 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-2 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch min. 2.0 pcf, Insulfoam OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -112.5 G-3 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -112.5 G-4 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation OB500 Polyflex SA Base (Optional) APP-TA APP-TA -112.5 G-5 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -112.5 G-6 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 Polyflex SA Base (Optional) APP-TA APP-TA -112.5 G-7 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch Dens Deck Prime M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-8 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -202.5 G-9 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA Polyflex SA Base (Optional) APP-TA APP-TA -202.5 G-10 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch, min. 2.0 pcf EPS insulation board, Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H- Shield, H-Shield CG or Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 G-11 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA -240.0 G-12 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 51 of 58 TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply G-13 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -240.0 G-14 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -257.5 G-15 Existing, sound poured gypsum or gypsum plank deck Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-Shield CG or Multi-Max FA3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -257.5 ASPHALT-APPLIED BASE: G-16 Existing, sound poured gypsum or gypsum plank deck Min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 None N/A (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -245.0 COLD APPLIED BASE: G-17 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 G-18 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 G-19 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 G-20 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or UltraMax or min. 2-inch DECKMATE Plus or DECKMATE Plus FA M-OSFA Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -202.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 52 of 58 TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply G-21 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 OB500 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS- CA2, APP-CA1 -112.5 G-22 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 (Optional) SBS-CA1, SBS- CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 G-23 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 G-24 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi-Max FA3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 G-25 Existing, sound poured gypsum or gypsum plank deck Min. 1-inch ENRGY 3, Polytherm H, H- Shield, Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS- CA2 None SBS-CA1, SBS- CA2 -232.5 TABLE 6B: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP (psf) Type Fasten Attach Type Attach Type Attach Base Ply Ply Cap Ply G-26 Existing, sound poured gypsum or gypsum plank deck Elastobase, Elastobase P, Polyglass G2 Base Trufast FM-75 or FM-90 or Twin Loc-Nails 9-inch o.c. in 4- inch lap and 18- inch o.c. in two, equally spaced, staggered center rows Min. 1.5-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ISO95+GL, Polytherm H, H-Shield, ENRGY 3, Polytherm or Multi-Max FA3 Hot asphalt Min. 0.25-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum-Fiber Roof Board, Min. 0.75-inch Fesco Board (homogeneous) or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Hot asphalt BP-AA, SBS-AA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 53 of 58 TABLE 6C: GYPSUM DECKS – REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Ply Cap Ply G-27 Existing sound poured gypsum or gypsum plank deck (Optional) One or more layers, any combination, loose laid Min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board or min. 0.5-inch Structodek High Density Fiberboard Roof Insulation Trufast Twin Loc- Nails (min. 1-inch embedment) 1 per 2 ft2 (Optional if using AA Ply) BP-AA, SBS-AA (Optional if using AA Base) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* TABLE 6D: GYPSUM DECKS – REROOF (TEAR-OFF) SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten Attach Base Ply Cap Ply G-28 Existing sound poured gypsum or gypsum plank deck Elastobase, Elastobase P, Polyglass G2 Base Trufast FM-75 or FM-90 or Twin Loc-Nails 9-inch o.c. in 4-inch lap and 18-inch o.c. in two, equally spaced, staggered center rows (Optional) BP-AA, SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0* Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 54 of 58 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply SELF-ADHERING BASE: R-1 Existing asphaltic roof Min. 1.5-inch Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or Dens Deck Prime D-IS SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -67.5 R-2 Existing asphaltic roof Min. 1.5-inch Multi-Max FA3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board or Dens Deck Prime D-IS Polyflex SA Base (Optional) APP-TA APP-TA -67.5 R-3 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3 or Multi-Max FA3 or min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch Dens Deck Prime D-IS SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 R-4 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS (Optional) additional layers(s) of base insulation D-IS SBS-SA (Optional) SBS-SA SBS-SA -90.0 R-5 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -90.0 R-6 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS Polyflex SA Base (Optional) APP-TA APP-TA -90.0 R-7 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -90.0 R-8 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board D-IS Polyflex SA Base (Optional) APP-TA APP-TA -90.0 R-9 Existing smooth- or granule-surfaced asphalt built-up roof or SBS modified bitumen or existing granule-surfaced APP modified bitumen (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield D-IS Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board PRIMER: PG100 D-IS Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -93.8 R-10 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield or min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch Dens Deck Prime OB500 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 R-11 Existing smooth- or granule-surfaced asphalt built-up roof or SBS modified bitumen or existing granule-surfaced APP modified bitumen (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield OB500 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board PRIMER: PG100 OB500 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -93.8 R-12 Existing asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA -120.0 R-13 Existing asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -120.0 R-14 Existing asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 Polyflex SA Base (Optional) APP-TA APP-TA -120.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 55 of 58 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply R-15 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -127.5 R-16 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, Polytherm H or H-Shield OB500 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 Polyflex SA Base (Optional) APP-TA APP-TA -127.5 R-17 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch Dens Deck Prime M-OSFA SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 R-18 Existing smooth- or granule-surfaced asphalt built-up roof or SBS modified bitumen or existing granule-surfaced APP modified bitumen (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield M-OSFA or M-PG1 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board PRIMER: PG100 M-OSFA or M-PG1 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -93.8 R-19 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -157.5 R-20 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA Polyflex SA Base (Optional) APP-TA APP-TA -157.5 R-21 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam, Min. 2-inch Polytherm, ACFoam II, min. 1.5-inch Ultra-Max or Multi-Max FA-3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H- Shield, H-Shield CG or ENRGY 3 CR-20 Min. 0.25-inch Dens Deck Prime CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -72.5 R-22 Existing smooth- or granule-surfaced asphalt built-up roof or SBS modified bitumen or existing granule-surfaced APP modified bitumen (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, Polytherm H or H-Shield CR-20 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board PRIMER: PG100 CR-20 Polyflex SA Base primed with PG100 None SBS-SA, APP-SA -93.8 R-23 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers(s) of base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA -240.0 R-24 Existing asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 R-25 Existing asphaltic roof Min. 1.5-inch Ultra-Max or Multi-Max FA- 3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -240.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 56 of 58 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply R-26 Existing asphaltic roof Min. 1.5-inch Ultra-Max or Multi-Max FA- 3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -240.0 R-27 Existing asphaltic roof Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA, SBS- TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -247.5 R-28 Existing asphaltic roof Min. 2-inch Polytherm, ACFoam II, ENRGY-3, Polytherm H or H-Shield CR-20 (Optional) additional layers(s) of base insulation and/or min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 Polyflex SA Base (Optional) APP-TA APP-TA -247.5 ASPHALT OR TORCH APPLIED BASE: R-29 Existing asphaltic roof Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA or APP-TA -67.5 R-30 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II or ENRGY 3 or min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board D-IS BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, or APP-TA -90.0 R-31 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or ISO 95+GL OB500 Min. 0.25-inch Dens Deck, Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board OB500 BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, or APP-TA -127.5 R-32 Existing asphaltic roof Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA BP-AA, SBS- AA, SBS-TA, APP-TA (Optional) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, or APP-TA -157.5 R-33 Existing asphaltic roof Min. 1.5-inch Ultra-Max or Multi-Max FA- 3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 BP-AA, SBS- AA (Optional) BP-AA, SBS- AA SBS-AA -225.0 R-34 Existing asphaltic roof Min. 1.5-inch Ultra-Max or Multi-Max FA- 3, min. 1.3-inch Polytherm G, ACFoam III or min. 1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-Shield CG or ENRGY 3 or min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 APP-TA (Optional) APP-TA APP-TA -232.5 COLD APPLIED BASE: R-35 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H or H-Shield D-IS Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board D-IS SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -90.0 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 57 of 58 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply R-36 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield ISO 95+ GL, Multi- Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass- Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA or M-PG1 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 R-37 Existing asphaltic roof (Optional) Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi- Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA, M-PG1 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-38 Existing asphaltic roof (Optional) Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi- Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board M-OSFA, M-PG1 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-39 Existing asphaltic roof (Optional) Min. 1-inch Polytherm or ACFoam II, Polytherm G, ACFoam III, EnergyGuard Polyiso Insulation, ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL, Multi- Max FA3, RESISTA or UltraMax or min. 2- inch DECKMATE Plus or DECKMATE Plus FA M-OSFA, M-PG1 Min. 0.25-inch Dens Deck, Dens Deck Prime, DEXcell FA Glass Mat Roof Board, SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass- Mat Roof Board, min. 7/16-inch DEXcell Cement Roof Board or min. 0.5-inch SECUROCK Cement Roof Board M-OSFA, M-PG1 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2 -157.5 R-40 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi- Max FA3 OB500 Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass Mat Roof Board or SECUROCK Gypsum- Fiber Roof Board OB500 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 R-41 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi- Max FA3 OB500 Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board OB500 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-42 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi- Max FA3 OB500 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 Exterior Research and Design, LLC. d/b/a Trinity|ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 6TH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 58 of 58 TABLE 7A: RECOVER APPLICATIONS SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Attach Type Attach Base Ply Ply Cap Ply R-43 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi- Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 (Optional) SBS-CA1, SBS-CA2 SBS-CA1, SBS- CA2, APP-CA1 -120.0 R-44 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi- Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-45 Existing asphaltic roof (Optional) Min. 1-inch Polytherm, ACFoam II, Polytherm G, ACFoam III, ENRGY 3, Polytherm H, H-Shield or Multi- Max FA3 CR-20 Min. 0.25-inch SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2, APP-CA1 -127.5 R-46 Existing asphaltic roof (Optional) Min. 1-inch ENRGY 3, Polytherm H, H-Shield, Multi-Max FA3 CR-20 Min. 0.25-inch Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-CA2 None SBS-CA1, SBS- CA2 -232.5 TABLE 7B: RECOVER APPLICATIONS SYSTEM TYPE F: NON-INSULATED, BONDED BASE SHEET, BONDED ROOF COVER System No. Substrate (Notes 1 & 12) Primer Roof Cover (Note 15) MDP (psf) Base Ply Ply Cap Ply R-47 Existing asphaltic roof PG100 BP-AA (Optional if using asphalt applied Ply) (Optional if using asphalt applied Base) BP-AA, SBS- AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0