DATE: 10/23/18 JOB ORDER#: 18-4689
CLIENT: All Area Roofing
ADDRESS: 3921 S. US Highway 1 Fort Pierce,Florida 34982
PROJECT: Tammy Ogden Residence Integrity Metals 5V Crimp Roof Panel
ADDRESS: 204 Smallwood Avenue Fort Pierce,Florida
2017 FBC/ASCE-7 DESIGN PRESSURE CALCULATIONS
Project Information:
Mean Height=Max. 15' Exposure: C Basic/Ultimate Wind Speed: Vuit=165 mph
Length= 72' Category: II Nominal Wind Speed: V.d=Vuit*q0.6
Width= 36' Slope: 6/12=26.5° (asd=allowable strength design)
Parapet Wall: N/A Residential KZ=0.85,Kzt= 1.0, Kd=0.85
Design Calculations:
Velocity Pressure: q= 0.00256*KZKztKdV2
Velocity Pressure (,,It): q=0.00256(0.85)(1.0)(0.85)(165)2] =50.36 psf
Velocity Pressure (aid): q=0.00256(0.85)(1.0)(0.85)(165* 0.6)2] =30.21 psf
Width of Pressure Coefficient: 0.1(36') = 3.6'
0.4(15') = 6.0' } use: 4'0"
Effective Wind Area: <1 W
External Pressure Coefficient: Internal Pressure Coefficient:
1) GCP 1 = -0.9 1) GCP; = 0.18
2) GCP2 = -1.7
3) GCP3 = -2.6
Design Pressures Based on Vasd:
1) Field P1 = 3 0.21*[(-0.9)—(0.18)] =-32.6 psf
2) Perimeter P2 = 30.21*[(-1.7)—(0.18)] =-56.8 psf
3) Corners P3 = 30.21*[(-2.6)—(0.18)] =-84.0 psf
f
V,Q `v
Quality' �\3A IV,
Page 2,10/23/18,Job Order#18-4689
All Area Roofing F1,0R1X3A
Tammy Ogden Residence
Integrity Metals 5V Crimp Roof Panel
204 Smallwood Avenue;Fort Pierce,FL: '
Attachment Requirements:
Based on the requirements of Florida Product Approval # FL27150.8 with maximum
design pressures of -63.5psf (Method 1) and -86psf (Method 2); the following are our
recommended fastening patterns to attach the min. 26 ga. 5V Crimp Roof Panels (24"
max. coverage) to the min. 15/32", plywood deck (attached to structural supports per
product appoval) with # 10 x 1-1/2" HiLo HWH fasteners with weather seal washer at
each seam and intermediate rib:
Area Field & Perimeter Corner
(Method 1) (Method 2)
Design Pressure -63.5psf -86psf
Fastener Row Spacing 16" O.C. 12"o.c.
(Max.)
Notes: Corners and perimeter (edge, hip, & ridge) area dimension shall not be less
than a = 4'0" (Zone 2: Perimeter (including along ridges) is a 4'0" wide
strip, Zone 3: Corners are 410" x 41011)
Contractor to verify that the fastening patterns meet manufacturer's
requirements for issuance of a warranty(as applicable).
All work shall be in compliance with the local building code product control
notice of acceptance and manufacturer specifications and Florida Building
Code 2017 Edition.
Wind load calculations based on ASCE-7, 2017 FBC, and information
provided by client. Client is responsible for verifying existing conditions as it
pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify compliance with
specifications.
Sincerely, `N�Pp%11 I I J I