HomeMy WebLinkAboutProduct Approval { r NEMO etc. - Certificate of Authorization#32455 353 Christian Street, Unit#13 Oxford, CT 06478 (203) 262-9245 ENGINEER EVALUATE TEST CONSULT CERTIFY EVALUATION REPORT Polyglass USA, Inc. Evaluation Report P12060.02.09-1124 1111 West Newport Center Drive FL5259-1128 Deerfield Beach, FL 33442 Date of Issuance:02/24/2009 (954)233-1230 Revision 24:01/24/2018 SCOPE: This Elvaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of constr,uction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Polyglass Roof Underlayments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the produIct(s), the Quality Assurance or the production facility location(s): NEMO I etc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOletc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Prepalred by: Robert J.M.Nieminen P.E. • The facsimile seal appearing was authorized by Robert Nieminen, Florida Registration No.59166,Florida DCA ANE1983 "'d,ry�-V ` ;�k P.E.on 01/24/2018. This does not serve as an electronically t., ` signed document. CERTIFICATION OF INDEPENDENCE: 1. NEMO I etc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMO I etc.is not owned,operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Niemineh,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither NEMO Ietc. nor Robert Nieminen, P.E. are, in any way,the Designer of Record for any project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained specifically for that purpose. ON EMO etc. ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub-Category: Underlayment Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations/Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1504.3.1 Wind Uplift FM 4474 2011 1504.3.1 Wind Uplift UL 1897 2012 1507.2.3/1507.1.1 Physical Properties ASTM D226 2009 1507.2.4/1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 2012 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 TAS 110 Accelerated Weathering ASTM D4798 2011 3. ; REFERENCES: I Entity Examination Reference Date FM Approvals(TST 1867) Wind Uplift 3004091 01/12/2000 PRI(TST 5878) Physical Properties PRI01111 04/08/2002 PRI(TST 5878) Physical Properties PUSA-005-02-01 01/31/2002 PRI(TST 5878) Physical Properties PUSA-013-02-01 12/23/2002 PRI(TST 5878) Physical Properties PUSA-013-02-02 12/23/2002 PRI(TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI(TST 5878) Physical Properties PUSA-018-02-01 07/14/2003 PRI(TST 5878) Physical Properties PUSA-028-02-01 07/13/2005 PRI(TST 5878) Physical Properties PUSA-033-02-01 01/12/2006 PRI(TST 5878) Physical Properties PUSA-035-02-01 09/29/2006 PRI(TST 5878) Physical Properties PUSA-055-02-02 12/10/2007 PRI(TST 5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI(TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 j PRI(TST 5878) Physical Properties PUSA-083-02-01 04/14/2008 PRI(TST 5878) Physical Properties PUSA-088-02-01 07/29/2009 MTI(TST 2508) Physical Properties JX20H7A 04/01/2008 MTI(TST 2508) Physical Properties RX14E8A 01/29/2009 ERD(TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD(TST 6049) Wind Uplift 11757.08.01-1 08/13/2001 ERD(TST 6049) Wind Uplift 11776.06.02 01/16/2003 ERD(TST 6049) Physical Properties 02200.07.03 07/14/2003 ERD(TST 6049) Wind Uplift P1740.01.07 01/04/2007 ERD(TST 6049) Physical Properties P5110.04.07-1 04/11/2007 ERD(TST 6049) Wind Uplift P9260.03.08 03/21/2008 ERD(TST 6049) Physical Properties P13450.08.09 08/13/2009 ERD(TST 6049) Wind Uplift P30540.11.09-R3 11/30/2009 ERD(TST 6049) Physical Properties P11030.11.09-1 11/30/2009 ERD(TST 6049) Wind Uplift P11030.11.09-2 11/30/2009 ERD(TST 6049) Physical Properties P11030.11.09-3 11/30/2009 ERD(TST 6049) Physical Properties P33360.06.10 06/25/2010 ERD(TST 6049) Physical Properties P33370.03.11 03/02/2011 ERD(TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD(TST 6049) Physical Properties P37300.10.11 10/19/2011 NEMO ETC,U.C. Evaluation Report P12060.02.09-R24 Certificate ofAuthorization#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 2 of 14 1 0. NEMOjetc. Entity Examination Reference Date ERD(TST 6049) Physical Properties P40390.08.12-1 08/06/2012 ERD(TST 6049) Physical Properties. P40390.08.12-2 08/07/2012 ERD(TST 6049) Physical Properties C41420.09.12-3 09/11/2012 ERD(TST 6049) Wind Uplift P39680.03.13 03/04/2013 i ERD(TST 6049) Physical Properties P45370.04.13 04/26/2013 ERD(TST 6049) Wind Uplift P1738.02.07-R2 04/29/2013 ERD(TST 6049) Wind Uplift 11757.04.01-1-R1 04/30/2013 ERD(TST 6049) Wind Uplift P41630.08.13 08/06/2013 ERD(TST 6049) Wind Uplift P11751.05.03-R1 11/26/2013 ERD(TST 6049) Wind Uplift P11781.11.03-R1 11/26/2013 ERD(TST 6049) Physical Properties P45270.05.14 05/12/2014 ERD(TST 6049) Physical Properties 6020.07.14-1 09/08/2014 ERD(TST 6049) Physical Properties 6020.09.14-2 09/08/2014 ERD(TST 6049) Physical Properties 6020.09.14-3 09/08/2014 ERD(TST 6049) Physical Properties 6020.09.14-4 09/08/2014 ERD(TST 6049) Physical Properties 6020.09.14-5 09/08/2014 ERD(TST 6049) Physical Properties 6020.09.14-6 09/08/2014 ERD(TST 6049) Physical Properties P46520.10.14 10/03/2014 ERD(TST 6049) Physical Properties P43290.10.14 10/17/2014 ERD(TST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015 ERD(TST 6049) Physical Properties P40390.04.15 04/03/2015 1 ERD(TST 6049) Physical Properties P44360.10.14-111 05/18/2015 j ERD(TST 6049) Physical Properties PLYG-SC8080.05.15-1 05/20/2015 ERD(TST 6049) Wind Uplift PLYG-SC8905.05.16-1 05/17/2016 ERD(TST 6049) Physical Properties PLYG-SC8080.07.16 07/16/2016 ERD(TST 6049) Wind Uplift PLYG-SC12025.10.16 10/12/2016 ERD(TST 6049) Physical Properties PLYG-SC13040.12.16 12/27/2016 ERD(TST 6049) Physical Properties PLYG-SC11900.03.17 03/10/2017 'ERD(TST 6049) Physical Properties PLYG-SC12115.08.17 08/08/2017 ICC-ES(EVL 2396) IBC Compliance ESR-1697 11/01/2014 1 Miami-Dade(CER 1592) HVHZ Compliance NOA 14-0717.08 01/22/2015 Polyglass USA Manufacturing Affidavit Products Current 02/18/2009 Polyglass USA PA Affidavit Mule-Hide Cross Ltg 03/01/2008 Polyglass USA Materials Affidavit Polystick SA Compound 08/18/2011 UL,LLC.(QUA9625) Quality Control Service Confirmation Exp.10/05/2018 4. PRODUCT DESCRIPTION: 4.1 Mechanically Fastened Underlayments: 4.1.1 Elastobase is a fiberglass reinforced,SBS modified bitumen base sheet. 1 4.1.2 Elastobase P is a polyester-reinforced,SBS modified bitumen base sheet. 4.1.3 Polyglass G2 Base is a fiberglass-reinforced,asphaltic base sheet. i 4.1.4 Polyglass APP Base is a fiberglass-reinforced,APP modified bitumen base sheet. i 4.2 Self-Adhering Underlayments: 4.2.1 Polystick MTS or Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced,surfaced with polyolefinic film surface; meets FRSA/TRI April 2012. 4.2.2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane,glass-fiber reinforced,with an aggregate surface;meets ASTM D1970. 1 4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane,glass fiber reinforced,with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. I I NEMO ETC,I.I.C. Evaluation Report P32060.02.09-R24 Certificate ofAuthorizatim#32455 6'EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 3 of 14 I I , ONEMOletc. 4.2.4 Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced,with a granular surface;meets FRSA/TRI April 2012. 4.2.5 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.6 Polyflex SAP, Polyflex SAP FR, Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet (FR) are polyester reinforced,APP modified bitumen cap sheets; meet FRSA/TRI April 2012. 4.2.7 Polystick Dual Pro'" is a nominal 60-mil thick dual-layer rubberized asphalt waterproofing membrane, fiberglass reinforced,with a polyester fabric surface;meets ASTM D1970. 4.2.8 Polystick Tile Pro"" is a nominal 60-mil thick dual-layer rubberized asphalt waterproofing membrane, fiberglass reinforced,with a polyester fabric surface;meets ASTM D1970 and FRSA/TRI April 2012. 4:2.9 Polystick MU-X is a nominal 54-mil thick dual-layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section 5.8). 4.3 Mechanically Fastened and/or Bonded Underlayments: 4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand-surfaced SBS modified bitumen back-side and granule-surfaced APP modified bitumen top-side. Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply System"from FRSA/TRI April 2012(04-12) beneath mechanically fastened or adhered tile roof systems. 4.3.2 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced,SBS modified bitumen cap sheets; meet ASTM D6164. Elastoflex S6 G and Elastoflex S6 G FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M)in the"Single Ply System"from FRSA/TRI April 2012(04-12)beneath mechanically fastened tile roof systems. Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System"from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FR is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FR is for use as an alternate to Heat i Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither NEMOIetc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in the HVHZ. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 1 5.4 Polyglass Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. i I NEMO ETC,U.C. Evaluation Report P12060.02.09-R24 Certificate ofAuth.dwtion#3245.5 6'"EDITION(2017)FBC NON-HVHZ EVALUATION FLS259-R28 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 I Page 4 of 14 I ONEMO etc. '5.5 Allowable Roof Covers: TABLE 1: ROOF COVER OPTIONS. Underlayment Asphalt Shingles Nail-On Tile Foam-On Tile Metal wood Shakes Slate &Shingles 'Elastobase Yes Yes Yes Yes Yes Yes (Base Sheet in 2-ply system) (Base Sheet in 2-ply system) Elastobase P Yes Yes Yes Yes Yes Yes (Base Sheet in 2-ply system) (Base Sheet in 2-ply system) Polyglass G2 Base No Yes Yes No No No (Base Sheet in 2-ply system) (Base Sheet in 2-ply system) Yes Yes Polyglass APP Base No No No No (Base Sheet in 2-ply system) (Base Sheet in 2-ply system) Polystick MTS or MTS PLUS Yes Yes' No Yes Yes Yes Polystick IR-Xe Yes No No No Yes Yes Polystick TU P No Yes Yes (See 5.5.1) No No No j Polystick TU Plus Yes Yes Yes (See 5.5.1) Yes Yes Yes Polystick TU Max No Yes Yes (See 5.5.1) Yes No No Polystick Dual Pro Yes No No Yes Yes Yes Polystick Tile Pro Yes Yes Yes (See 5.5.1) Yes Yes Yes Polystick MU-X Yes No No Yes Yes Yes j Elastoflex S6 G: Yes .Yes Yes (See 5.5.1) No Yes Yes Elastoflex S6 G FR Yes Yes No No Yes Yes Elastoflex G TU Yes Yes Yes (See 5.5.1) No Yes Yes Polyflex G Yes Yes Yes (See 5.5.1) No Yes Yes Polyflex G FR Yes Yes No No Yes Yes Polyflex SAP or SAP FR Yes Yes Yes (See 5.5.1) No Yes Yes Mule-Hide SA-APP Cap Sheet or SA-APP Cap Sheet(FR) Yes Yes Yes (See 5.5.1) No Yes Yes 5.5.1 "Foam-On Tile"is limited to use of the following Approved tile adhesives/underlayment combinations. TABLE IA:ALLOWABLE TILE ADHESIVE,/`UNDERLAYMENT COMBINATIONS) Adhesive Florida Product Underlayments Approval DAP Foam Touch'n Seal StormBond Roof Tile Adhesive FL14506 Polystick TU Plus,Polystick TU Max Dow TileBondT" FL22525 Polystick TU P,Polystick TU Plus,Polyflex SAP or Tile Pro Polystick TU P,Polystick TU Plus,Polystick TU Max,Polystick Tile Pro, ICP Adhesives Polyset®AH-160 FL6332 Elastoflex G TU,Elastoflex S6 G,Polyflex G,Polyflex SAP,Polyflex SA Cap FR, Mule-Hide SA-APP Cap Sheet or Mule-Hide SA-APP Cap Sheet(FR) Polystick TU P,Polystick TU Plus,Polystick TU Max,Polystick Tile Pro, ICP Adhesives Polyset®RTA-1 FL6276 Elastoflex G TU,Elastoflex S6 G,Polyflex G,Polyflex SAP,Polyflex SA Cap FR, Mule-Hide SA-APP Cap Sheet or Mule-Hide SA-APP Cap Sheet(FR) I i I Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. NEMO ETC,LLC. Evaluation Report P12060.02.09-R24 Certificate of Authorization#32455 CH EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 5 of 14 I i ON EMO etc. 5.6 Allowable Substrates: 5.6.1 Direct-Bond to Deck: Polystick(all variations), Dual Pro,Tile Pro, Polyflex SAP or SAP FR, Mule-Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR)self-adhered to: ➢ New untreated plywood;ASTM D41 primed new untreated plywood; Existing plywood;ASTM D41 primed existing plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or O58 sheathing. New or existing plywood or O58 sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU,Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch-applied to: ➢ ASTM D41 primed structural concrete. 5.6.2 Bond-to-Insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule-Hide SA-APP Cap Sheet or SA-APP Cap Sheet(FR) self-adhered to: ➢ ASTM C1289, Type 11, Class 1 polyisocya n u rate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime;or SECUROCK Gypsum-Fiber Roof Board. Elastoflex G TU,Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board. Polyflex G or Polyflex G FR torch-applied to: ➢ ASTM D41 primed structural concrete;Dens Deck Prime or SECUROCK Gypsum-Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam-on tile systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FBC Section 1504.3.1. 5.6.3 Bond to Mechanically Attached Base Laver: Polystick (all variations), Polyflex SAP or SAP FR, Mule-Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self-adhered to: ➢ ASTM D226,Type I or II felt; Elastobase;Elastobase P or Mule-Hide Nail Base. Elastoflex G TU,Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D226,Type I or II felt; Elastobase; Elastobase P, Mule-Hide Nail Base or Polyglass G2 Base. Polyflex G or Polyflex G FR torch-applied to: ➢ Elastobase;Elastobase P, Mule-Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam-on tile systems, base layer-shall be attached per minimum requirements of FRSA/TRI April 2012(04-12),Appendix A,Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC Section 1504.3.1. i MEMO ETC,LLC. Evaluation Report P12060.02.09-R24 Certificate of Authorization#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 6 of 14 ON EMO I etc. 5.6.4 Wind Resistance for Underlayment Systems in Foam-On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam-on tile systems, where.the underlayment forms part of the load-path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12)and are used in foam-on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012(04- 12),Appendix A,Table 1A or FBC 1609 for determination of design wind loads. #1 Maximum Design Pressure=-90 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: None Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. Underlayment:Polystick TU P,Polystick TU Plus, Polystick TU Max,Polyflex SAP,Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered. #2 Maximum Design Pressure=-97.5 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. 1 Primer: PG100 or ASTM D41 Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyflex SAP,Polyflex SAP FR, Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered and back-nailed within the selvedge-edge side laps using 12 ga.x 1'/0"ring shank nails through 32 ga.,1-5/8"diameter tin caps spaced 12-inch o.c. #3 Maximum Design Pressure=-105 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max, Polyflex SAP,Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered and back-nailed within the selvedge-edge side laps using 12 ga.x 1%"ring shank nails through 32 ga.,1-5/8"diameter tin caps spaced 12-inch o.c. #4 Maximum Design Pressure=-135 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional)PG100 or ASTM D41 Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. Joints: Min.4-inch wide strips of Elastoflex SA-V over all plywood joints. Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyflex SAP,Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered. #5 Maximum Design Pressure=-315 psf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 j Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. i Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max,Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered. #6 Maximum Design Pressure=-622.5 psf: i Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. #7 Maximum Design Pressure=-30.0 psf*: Deck: Min.15/32-inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule-Hide Nail Base(poly-film top surface) Fasteners: 11 ga.x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c.at the 3-inch wide side laps and 6-inch o.c.at two(2)equally spaced staggered center rows. Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyflex SAP,Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered. NEMO ETC,I.I.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization 1132455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-RZB Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 7 of 14 i ON EMO etc. #8 Maximum Design Pressure=-37.5 psf*: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule-Hide Nail Base(poly-film top surface) Fasteners: 11 ga.x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c.at the 3-inch wide side laps and 6-inch o.c.at two(2)equally spaced staggered center rows. Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. j Underlayment:Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyflex SAP,Polyflex SAP FR, Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered. #9 Maximum Design Pressure=-37.5 psf*: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One(1)or two(2)layers ASTM D226,Type II felt Fasteners: 11 ga.x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c.at the 3-inch wide side laps and 12-inch o.c.at two(2)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt. #10 Maximum Design Pressure=-45 psf*: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One(1)layer ASTM D226,Type II felt I Fasteners: 11 ga.x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 4-inch o.c.at the 2-inch wide side laps and 4-inch o.c.at two(2)equally spaced staggered center rows. Base Ply: (Optional;for use with self-adhering underlayment only)Polystick MTS or Polystick MTS PLUS,self-adhered. Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyflex SAP,Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered or Elastoflex G TU,applied in full mopping of hot asphalt. i #11 Maximum Design Pressure=-45 psf*: i Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Two(2)layers ASTM D226,Type 11 felt Fasteners: 11 ga.x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 9-inch o.c.at the 2-inch wide side laps and 9-inch o.c.at two(2)equally spaced staggered center rows. Base Ply: (Optional;for use with self-adhering underlayment only)Polystick MTS or Polystick MTS PLUS,self-adhered. Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyflex SAP,Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered or Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot 4 asphalt. j #12 Maximum Design Pressure=-45 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: .9-inch o.c.at the 2-inch wide side laps and 18-inch o.c.at two(2)equally.spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. i #13 Maximum Design Pressure=-52.5 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. i Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-inch o.c.at the 2-inch wide side laps and 12-inch o.c.at two(2)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. #14 Maximum Design Pressure=-52.5 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule-Hide Nail Base(poly-film top surface) Fasteners: Simplex Original Cap.Nails Spacing: 6-inch o.c.at the 3-inch wide side laps and 6-inch o.c.at four(4)equally spaced staggered center rows. Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyfiex SAP, Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered. NEMO ETC,LLC. Evaluation Report P12060.02.09-R24 Certificate of Authorization#31455 6'EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 8 of 14 I I ONEMO etc. #15 Maximum Design Pressure=-52.5 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: Simplex Original Cap Nails Spacing: 6-inch o.c.at the 3-inch wide side laps and 6-inch o.c.at four(4)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. #16 Maximum Design Pressure=-60 psf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: 11 ga.x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 8-inch o.c.at the 4-inch wide side laps and 87inch o.c.at three(3)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. #17 Maximum Design Pressure=-60 psf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: OMG#12 Standard Roofgrip with OMG Flat Bottom Metal Plates i g P Spacing: 12-inch o.c.at the 4-inch wide side laps and 12-inch o.c.at two(2)equally spaced staggered center rows. I Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. #18 Maximum Design Pressure=-67.5 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base(requires use of torch-applied underlayment) Fasteners: 12 ga.x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps jSpacing: 8-inch o.c.at the 4-inch wide side laps and 8-inch o.c.at four(4)equally spaced staggered center rows. i Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch-applied or Polyflex G, torch- applied. #19 Maximum Design Pressure=-75 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base(requires use of torch-applied underlayment) Fasteners: Dekfast#14 with Dekfast Hex plates, OMG#14 HD with OMG 3"Galvalume Steel Plates, OMG Roofgrip#14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 10-inch o.c.at the 4-inch wide side laps and 10-inch o.c.at three(3)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch-applied or Polyflex G, torch- applied. #20 Maximum Design Pressure=-90 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c.at the 2-inch wide side laps and 6-inch o.c.at two(2)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. #21 Maximum Design Pressure=-90 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: OMG#12 Standard Roofgrip or OMG#14 Heavy Duty with OMG 3"Round Metal Plates or OMG Flat Bottom Metal Plates . Spacing: 6-inch o.c.at the 4-inch wide side laps and 6-inch o.c.at three(3)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. 1 #22 Maximum Design Pressure=-90 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface) Fasteners: Trufast#12 DP or Trufast#14 HD with Trufast 3"Metal Insulation Plates Spacing: 6-inch o.c.at the 4-inch wide side laps and 6-inch o.c.at three(3)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt. r NEMO ETC,LLC. Evaluation Report P12060.02.09-R24 Certificate ofAuthorizatim#32455 6'EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-RZ8 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 9 of 14 i I i I MEMO l C'tC. i W23 Maximum Design Pressure=-90 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base(requires use of torch-applied underlayment) Fasteners: Dekfast#14 with Dekfast Hex plates,OMG#14 HD with OMG 3"Galvalume Steel Plates, OMG Roofgrip#14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap i Fasteners Spacing: 9-inch o.c.at the 4-inch wide side laps and 9-inch o.c.at four(4)equally spaced staggered center rows. 1 Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch-applied or Polyflex G, torch- applied. #24 Maximum Design Pressure=-97.5 psf: i Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule-Hide Nail Base(poly-film top surface) Fasteners: 11 ga.x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 4-inch o.c.at the 4-inch wide side laps and 4-inch o.c.at four(4)equally spaced staggered center rows. Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS,self-adhered. Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyflex SAP,Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered. #25 Maximum Design Pressure=-105 psf: iDeck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c.at the 2-inch wide side laps and 6-inch o.c.at three(3)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. #26 Maximum Design Pressure=-112.5 psf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule-Hide Nail Base(poly-film top surface) Fasteners: 11 ga.x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps 1 Spacing: 6-inch o.c.at the 4-inch wide side laps and 6-inch o.c.at four(4)equally spaced staggered center rows. Primer: PG100 or ASTM D41 primer at all tin-caps Base Ply: Polystick MTS or Polystick MTS PLUS,self-adhered Underlayment: Polystick TU P,Polystick TU Plus,Polystick TU Max,Polyflex SAP,Polyflex SAP FR,Mule-Hide SA-APP Cap Sheet and Mule-Hide SA-APP Cap Sheet(FR),self-adhered. #27 Maximum Design Pressure=-120 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. i Base Sheet: Elastobase(sanded top surface for hot-asphalt or torch-applied cap or poly-film surface for torch-applied cap) Fasteners: OMG#12 Standard Roofgrip or OMG#14 Heavy Duty with OMG 3"Round Metal Plates or OMG Flat Bottom Metal i Plates Spacing: 6-inch o.c.at the 4-inch wide side laps and 6-inch o.c.at five(5)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt or Polyflex G,torch-applied. I #28 Maximum Design Pressure=-120 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface) Fasteners: Trufast#12 DP or Trufast#14 HD with Trufast 3"Metal Insulation Plates Spacing: 6-inch o.c.at the 4-inch wide side laps and 6-inch o.c.at five(5)equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G,applied in full mopping of hot asphalt. 5.6.4.1 All other direct-deck, adhered Polyglass underlayment systems beneath foam-on tile systems carry a Maximum Design Pressure of-45 psf. NEMO ETC,LLC. Evaluation Report P12060.02.09-R24 C irtiFcote of Authorization#31455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-1128 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 10 of 14 NEMO j etc. 5.6.4.2 For mechanically attached Base Sheet,the maximum design pressure for the selected assembly shall meet or exceed 1 that required under FRSA/TRI April 2012(04-12),Appendix A,Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density j designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016)for Zone 2/3 enhancements. j 5.7 Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro,Tile Pro or Elastoflex G TU shall not be left exposed for longer than 180-days after installation. Polyflex SAP or SAP FR, or Mule-Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering is to be adhesive-set tile, in which case the maximum exposure is 30 days. Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering is to be adhesive-set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition,tested at standard laboratory conditions. Agreement between purchaser and seller,as set forth in Section 4.3, Note 1 of ASTM D197O-15,should be established as to slip resistance. 5.9 Tile Slippage Limitations(FRSA/TRI April 2012(04-12)): When loading roof tiles on the underlayment in direct-deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. TABLE 2: TILE SLIPPAGE LIMITATIONS FOR DIRECT-DECK TILE INSTALLATIONS Underlayment Tile Profile Staging Method Maximum Slope Elastoflex G TU Flat 10-tile stack 7:12 Lugged 8-tile stack(6 over 2) 6:12 Elastoflex S6 G or S6 G FR Flat or Lugged 6-tile stack(4 over 2) 4:12 Polystick MTS or MTS PLUS Flat 6-tile stack(4 over 2) 5:12 Lugged 6-tile stack(4 over 2) 4:12 Polystick Tile Pro Flat or Lugged 6-tile stack(4 over 2) 7:12 Flat 6-tile stack(4 over 2)or 10-tile stack 7:12 Polystick TU Max Lugged 6-tile stack(4 over 2) 7:12 Lugged 10-tile stack 6:12 PolystickTU P Flat 6-tile stack(4 over 2) 6:12 Lugged 6-tile stack(4 over 2) 4:12 Polystick TU Plus Flat or Lugged 6-tile stack(4 over 2) 7:12 Flat or Lugged 10-tile stack 6:12 i Polyflex G or G FR Flat or Lugged 6-tile stack(4 over 2) 4:12 Polyflex SA P or SA P FR Flat or Lugged 6-tile stack(4 over 2) 4:12 NEMO ETC,I.I.C. Evaluation Report P12060.02.09-R24 Certiwmte ofAuthorization#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 11 of 14 1 I i ON EMo etc. 6. INSTALLATION: i 16.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application,and prime the substrate(if applicable). 6.3 Elastobase,Elastobase}P or Mule-Hide Nail Base: 6.3.1 Non-Tile Applications: Shall be installed in compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. Elastobase, Elastobase P or Mule-Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA P FR, Mule-Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self-adhered, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are those associated with the top-layer underlayment,as set forth in Table 1. 6.3.2 Tile Applications: Elastobase,Elastobase P or Mule-Hide Nail Base are limited to use as a mechanically attached base sheet in the"Two Ply System"from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein,coupled with FRSA/TRI April 2012(04-12)Installation Manual. 6.4 Polystick MTS,MTS PLUS,IR-Xe,TU P,TU Plus,TU Max,Dual Pro,Tile Pro or MU-X or Polyflex SAP,Polyflex SAP FR, Mule-Hide SA-APP Cap Sheet or Mule-Hide SA-APP Cap Sheet(FR): 1 6.4.1 Shall be installed in compliance with the codified requirements for ASTM D1970 (except Polystick TU P) underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. 6.4.2 Direct-to-Deck with Mechanically Fastened Roof Covers: All self-adhering,materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule-Hide SA-APP Cap Sheet or SA-APP Cap Sheet(FR)should be back-nailed in selvage edge seam in accordance with Polyglass/Mule- Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring-shank type with a minimum 1-inch diameter metal disk or Simplex-type metal cap nail,at a minimum rate of 12" o.c. Polystick TU Plus should be back- nailed using the above noted fasteners and spacing, in area marked "nail area, area para clavar" on the face of membrane. The head lap membrane is to cover the area being back-nailed. All seal-lap seams (selvage laps) must be ;f, " firmly rolled with a minimum 28 Ib. hand roller to ensure full contact and adhesion. For Dual Pro and Tile Pro, align the edge of the top sheet to the end of the glue pattern (the sheet will overlap the fabric). q View of Ovelap Seam of Dual Pro and Tile Pro All over-fabric and over-granule end-laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement applied in between the application of the lap. 1 Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets,exposed valleys, or exposed roof to wall details I NEMO ETC,U.C. Evaluation Report P12060.02.09-R24 Certificate ofAuthorizatim#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-1128 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 12 of 14 i fONEMOjetc- Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of'like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-Ib weighted-roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied for the field membrane. Hand rollers are acceptable for rolling of patches,laps(min.28 Ib roller)or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 Tile Applications(not allowed for Polystick Dual Pro,IR-Xe or Polystick MU-X): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened the roofing over 2-ply system,consisting of Base Sheet and self-adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012(04-12),Table 1. For adhesive-set tile applications,refer to Section 5.6.4 herein. 6.4.4 Two(2)Ply Underlayment Systems: Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS,TU P,TU Plus,TU Max,Tile Pro, MU-X or Polyflex SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the top-layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. Polystick MTS or MTS PLUS followed by Polystick TU P,TU Plus,TU Max,Tile Pro or Polyflex SAP is allowable for use under foam-on tile systems. Limits of use are those associated with the top-layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. 6.5 Elastoflex G TU,Elastoflex S6 G or Elastoflex S6 G FR: 6.5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: j ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System"from FRSA/TRI April 2012(04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the"Two Ply System"from FRSA/TRI April 2012(04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G is for use as an alternate to"Mineral Surface Roll Roofing"(ASTM D6380,Class M)in the"Single Ply System" from FRSA/TRI April 2012 (04-12) beneath*mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System"from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G FR is for use as an alternate to"Mineral Surface Roll Roofing"(ASTM D6380,Class M) in the"Single Ply System"from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System"from FRSA/TRI April 2012(04-12)beneath mechanically fastened tile roof systems. i 6.5.2 For hot-asphalt-applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be fully asphalt-applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end-laps minimum 6-inch wide, off-set minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/8-inch beyond the lap edge. i 6.6 Polyflex;G or Polyflex G FR: i 6.6.1 Polyflex G or Polyflex G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet' in the"Two Ply System"from FRSA/TRI April 2012(04-12)beneath mechanically fastened or adhered tile roof systems(Base Sheet Limited per 5.6.3). ✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2012(04-12)beneath mechanically fastened tile roof systems(Base Sheet Limited per 5.6.3). I i NEMO ETC,I.I.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization#32455 6'EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-1128 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 13 of 14 MEMO etc. 6.6.2 Polyflex G or Polyflex G FR shall be fully torch-applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end-laps minimum 6-inch wide, off-set minimum 3 feet from course to course. Side and end laps shall be fully heat-welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap edge. 6.7 Tile Staging: 6.7.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer to Table 2 herein,and Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter-battens,as required by the tile manufacturer and FRSA/TRI April 2012(04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or nail- boards,to prevent tile sliding and/or damage to the underlayment during the loading process. 6.7.3 Polyglass specifies the minimum cure time after installation of self-adhering membranes and before loading of roofing tiles is forty-eight(48) hours. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. 1 MANUFACTURING PLANTS: Contact the noted QA agency for information on product locations covered for F.A.C.61G20-3 QA requirements. The following plants have,qualified products under their respective physical properties specifications. j Plant Specification Product s ! Fernley,NV,Hazleton,PA&Winter Haven,FL ASTM D1970 Polystick MU-X Hazleton,PA M-D 13-0004 Elastoflex G TU ASTM D1970 Polystick IR-Xe Hazleton,PA&Winter Haven,FL ASTM D1970&FRSA/TRI April 2012 Polystick TU Plus ASTM D1970&FRSA/TRI April 2012 Polystick TU Max Tuscaloosa,AL ASTM D4601,Type II Polyglass G2 Base ASTM D226(physicals) Elastobase,Elastobase P i ASTM D6509 Polyglass APP Base { FRSA/TRI April 2012 Polystick MTS,Polystick MTS PLUS FRSA/TRI April 2012 Polystick TU P Winter Haven,FL FRSA/TRI April 2012 Polyflex SAP,Polyflex SA P FR ASTM D1970 Polystick Dual Pro ASTM D1970&FRSA/TRI April 2012 Polystick Tile Pro ASTM D6164 Elastoflex S6,Elastoflex S6 G FR ASTM D6222 Polyflex G,Polyflex G FR 9. QUALITY ASSURANCE ENTITY: UL, LLC—QUA9625;(314)578-3406; k.chancellor@us.ul.com -END OF EVALUATION REPORT- f 1 NEMO ETC,I.I.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments;(954)233-1230 Revision 24:01/24/2018 Page 14 of 14 a 4� MIAMI-DADE COUNTY MAKCJ PRODUCT CONTROL SECTION t 11805 SW 26 Street,Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES(RER) Miami,Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T(786)315-2590 F(786)315-2599 NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy GAF 1 Campus Drive Parsippany,NJ 07054 SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials.The documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ). This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein,and has been designed to comply with the Florida Building Code including the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: GAF Timberline HD®,Timberline®Natural Shadow®,Timberline®American Harvest®,and FortitudeTM Shingles LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and following statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. i TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials,use,and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This NOA renews and revises NOA# 14-1022.20 and consists of pages 1 through 6. The submitted documentation was reviewed by Alex Tigera. i ' NOA No.: 16-0811.11 MIAMI•DAD;COUNTY Expiration Date:02/21/22 Approval Date:02/09/17 Page 1 of 6 I n i ROOFING ASSEMBLY APPROVAL Category Roofing Sub-Category: Asphalt Shingles Materials: Laminate Deck Type: Wood SCOPE This approves GAF Timberline HD®,Timberline®Natural Shadow®,Timberline American®Harvest®,and FortitudeTM Shingles as manufactured by GAF as described in this Notice of Acceptance. PRODUCT DESCRIPTION Product Dimensions Test Product Description Specifications j GAF Timberline HD® 13 1/4"x 39 3/8' TAS 110 Fiberglass reinforced heavy weight asphalt j Manufacturing roof shingle,with a laminate profile Locations#1,2,3,4,5,6,7 GAF Timberline Natural 13 '/4"x 39 3/s" TAS 110 Fiberglass reinforced heavy weight asphalt -Shadow® roof shingle,with a laminate profile Manufacturing Locations#1,2,3,4,5,6,7 GAF Timberline®American 13 '/4"x 39 3/8" TAS 110 Fiberglass reinforced heavy weight asphalt Harvest® roof shingle,with a laminate profile Manufacturing Locations#2,4,5,6 GAF FortitudeTM 13 1/4'x 393/8" TAS 110 Fiberglass reinforced heavy weight asphalt Manufacturing roof shingle,with a laminate profile Locations#1,4 MANUFACTURING LOCATION 1. Tampa,FL 2. Michigan City,IN 3. Baltimore,MD 4. Myerstown,PA 5. Ennis,TX 6. Tuscaloosa,AL 7. Dallas,TX 1 ' Mwrn•oaoEcout�rr NOA No.: 16-0811.11 Expiration Date:02/21/22 Approval Date:02/09/17 Page 2 of 6 EVIDENCE SUBMITTED Test Agency Test Identifier Test Name/Report Date 'Underwriters Laboratories,LLC ASTM D3462 4787344101 07/25/16 Underwriters Laboratories,Inc. ASTM D3462 I ICA48924 10/24/11 Underwriters Laboratories,Inc ASTM D3462 lOCA21994 04/22/11 Underwriters Laboratories,Inc ASTM D3462 IOCA28717 07/26/11 Underwriters Laboratories,Inc. ASTM D3462 05CA47541 11/10/06 Underwriters Laboratories,Inc. ASTM D3462 06CA31580 11/30/06 PRI Asphalt Technologies,Inc. ASTM D3462 GAF-101-02-02 11/02/05 Underwriters Laboratories,Inc. ASTM D3462 06NK05159 08/09/06 PRI Asphalt Technologies,Inc. ASTM D3462 GAF-098-02-02 11/08/05 Underwriters Laboratories,Inc. ASTM D3462 02NK41809 08/11/02 i Underwriters Laboratories,Inc. ASTM D3462 03NK26444 10/17/03 Center for Applied Engineering ASTM D3462 257989 05/13/97 Underwriters Laboratories,Inc. TAS 107 01NK45803 04/13/94 Underwriters Laboratories,Inc. TAS 107 06NK05159 08/09/06 Underwriters Laboratories,Inc. TAS 107 04NK04273 02/20/04 Underwriters Laboratories,Inc. TAS 107 05CA42840 11/11/05 Underwriters Laboratories,Inc. TAS 107 02NK41811 11/11/02 Underwriters Laboratories,Inc. TAS 107 03CA35209 10/17/03 Underwriters Laboratories,Inc. TAS 107 04CA13850 08/30/04 Center for Applied Engineering TAS 100 257989 04/01/97 PRI Asphalt Technologies,Inc. TAS 100 GAF-044-02-01 01/13/04 i PRI Asphalt Technologies,Inc. TAS 100 GAF-098-02-01 11/08/05 PRI Asphalt Technologies,Inc. TAS 100 GAF-101-02-01 11/09/05 PRI Asphalt Technologies,Inc. TAS 100 GAF-116-02-02 03/23/06 PRI Asphalt Technologies,Inc. TAS-100 ELK-083-02-01 10/16/02 ELK-084-02-01 10/15/02 ELK-085-02-01 10/14/02 ELK-086-02-01 10/24/02 ELK-087-02-01 10/21/02 ELK-088-02-01 10/16/02 r ELK-107-02-01 10/09/03 ELK-108-02-01 10/09/03 ELK-109-02-01 10/09/03 i LIMITATIONS 1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for fire ratings of this product. 2. Shall not be installed on roof mean heights in excess of 33 ft. f 3. All products listed herein shall have 6 quality assurance audit in accordance with.the Florida Building Code and Rule 61G20-3 of the Florida Administrative Code. I� f NOA No.. 16-OEll.11 CMI"AMIj-DMAMDE COUNTY Expiration Date:02/21/22 Approval Date:02/09/17 Page 3 of 6 INSTALLATION i 1. Shingles shall be installed in compliance with Roofing Application Standard RAS 115. j 2. Flashing shall be in accordance with Roofing Application Standard RAS 115 3. The manufacturer shall provide clearly written application instructions. 4. Exposure and course layout shall be in compliance with Detail W,attached. S. Nailing shall be in compliance with Detail'B',attached. LABELING Shingles shall bear the imprint or identifiable marking of the manufacturer's name or logo, city and state of manufacturing facility, and following statement: "Miami-Dade County Product Control Approved" or the Miami-Dade County Product Control Seal as shown below. MIAMI•DADE COUNTY i i BUILDING PERMIT REQUIREMENTS 1. Application for building permit shall be accompanied by copies of the following: 1.1 This Notice of Acceptance. 1.2 Any other documents required by the Building Official or the applicable code in order to properly evaluate the installation of this system. I i I f NOA No.: 16-0811.11 MIAMI•DADE COUNTY ...� � Expiration Date:02/21/22 Approval Date:02/09/17 Page 4 of 6 DETAIL A COURSE LAYOUT i DECK r i FULL 5th 17" OFF 4th 11" OFF 3rd I i I { 6" OFF 2nd FULL 1st NOA No.: 16-0811.11 QMUM% DDADE COUNTY Expiration Date:02/21/22 Approval Date:02/09/17 Page 5 of 6 DETAIL B i OVERALL DIMENSIONS AND NAILING PATTERN IIII 3� 3/i. 14=1/2' 17-1/2 (368-445mm),- '(368 '446mm) 6A/2' 6-1/2" 9=1/2 ail.guide line (155•741mm) (165 241fgT) 5-3/4'-6AW / T _ _ `� (146mm-159mm) (337mm) T' 1/2°-2=1/2" (t9 trom bottom of shingle elf seal adhesive on back ENHANCED'NAILING PATTERN - six nails per`shingle* required¢y'some'local codes;and required for enhanced wind cov_erage;on certain products. See limited warranty for details. 1 1 These shingles MUST be nailed a nominal 6" (152mm)from bottom of of shingle', above the-cutouts, as Shown..Nails must not be'expo'sed. i END OF THIS ACCEPTANCE I, I .: NOA No.: I6-0811.11 MIAM4DADECOUNTY Expiration Date:02/21/22 Approval Date:02/09/17 Page 6 of 6