(203)262-9245
EVALUATION REPORT 4P -
Owens Corning RECLd EE) Evaluation Report 037940.02.12-118
One Owens Corning Parkway FL10674-1113
Toledo,OH 43659 JAN 2 3 20119 Date of Issuance:02/06/2012
(740)404-7829 Revision 8: 10/09/2017
ST. Luc[(,9eeut#Y, I'cia�tl.>In�
SCOPE: w-
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products describe gated for compliance with the 6th Edition (2017) Florida Building Code
secti o ed herein.
DES ON Owens Corning Asphalt Roof Shingles
LABELING: Label! in accordance with the requirements the Accredited Quality Assurance Agency noted
herein and FBC 1507.2.7.1/R905.2.6.1. ,
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. Trinity IERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity)ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by: �Mur;�f`,,�,,,'
�e.*;"c1I
't9r
•+�a-i�.,A.:.. -, rte•
Robert J.M.Nieminen,P.E. ,��7r�S:' j'c^rF!'- Thefacsimileseala appearing was Robert
Y;..� `z10 k4lEti., PP g Y
Florida Registration No.59166,Florida DCA ANE1983
lnn,mn Nieminen,P.E.on 10/09/2017.This does not serve as an
a"-.
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. Trinity lERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity]ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity lERD nor Robert Nieminen, P.E. are, in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
—1
TRINITY ERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles,as produced by Owens Corning,have demonstrated
compliance with the following sections of the 6th Edition (2017) Florida Building Code and Florida Building Code,
Residential Volume through testing in accordance with the following Standards. Compliance is subject to the
Installation Requirements and Limitations/Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1507.2.5,R905.2.4 Physical Properties ASTM D3462 2010
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D3161 2016
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D7158 2011
3. REFERENCES:
Entity Examination Reference Date
UL LLC(CER9626) Physicals&Wind Resistance File R2453,Vol.3 02/15/2007
UL LLC(CER9626) Physicals&Wind Resistance 20120516-112453 05/16/2012
UL LLC(TST9628) Physical Properties 06CA20263 04/18/2006
UL LLC(TST9628) Wind Resistance 11CA34308 02/18/2012
UL LLC(TST9628) Physicals&Wind Resistance 4786093137 02/01/2014
UL LLC(TST9628) Wind Resistance 4786126532 02/10/2014
UL LLC(TST9628) Physical Properties Classification letter 02/13/2014
UL LLC(TST9628) Physical Properties Classification letter 10/02/2015
Miami-Dade(CER1592) FBC HVHZ Compliance Various NOAs Various
UL LLC (QUA9625) Quality Control Service Confirmation Exp.05/16/2020
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Classic and Supreme®are fiberglass reinforced,3-tab asphalt roof shingles.
4.1.2 Berkshire®are fiberglass reinforced,4-tab asphalt roof shingles.
4.1.3 Devonshire TM are fiberglass reinforced,5-tab asphalt roof shingles.
4.1.4 Duration®, TruDefinition® Durat' ura ' ® remium Cool, TruDefinition® Duration® Designer Color
Collection, TruDefinition®Oakrid ®, Oakridge® and eatherGuard® HP are fiberglass reinforced, laminated
asphalt roof shingles.
4.2 Hip&Ridge Shingles:
4.2.1 Berkshire Hip & Ridge Shingles, High Ridge, WeatherGuard® HP Hip & Ridge Shingles, ProEdge Hip & Ridge
Shingles and DuraRidgeT1 Hip&Ridge Shingles are fiberglass reinforced,hip and ridge asphalt roof shingles.
.4.3 Accessory Starter Strips:
4.3.1 Starter Strip Shingle,Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report,or previous versions thereof,is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 -This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report;refer to current Approved Roofing Materials Directory
for fire ratings of this product.
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-R8
Certificate of Authorization#9503 6'EDITION(2017)FBC NON-HVHZ EVALUATION FL10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 2 of 8
C�o
TRINITY1 ERS
5.4 Wind Classification:
5.4.1 All Owens Corning asphalt shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161,Class F and/or ASTM D7158,Class H,indicating the shingles are acceptable
for use in all wind zones up to Vasa = 150 mph (Vast = 194 mph). Refer to Section 6 for installation
requirements to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are
Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the
shingles are acceptable for use in all wind zones up to Vasd=150 mph(Vnit=194 mph). Refer to Section 6 for
installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C, as defined in FBC 1609.4.3, and a mean
roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions
outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C.Rule 611520-3.
6. INSTALLATION:
6_1 'Underlayment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product
Approval,or be Locally Approved per Rule 61G20-3,per FBC 1507.2.3,1507.2.4 or R905.2.3.
6.2 Asphalt Shingles:
6.2.1 Installation of asphalt shingles shall comply with the Owens Corning current published instructions, using
minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following
exceptions:
➢ Berkshire shingles require minimum five(5)nails per shingle.
➢ WeatherGuarde HP shingles require minimum six(6)nails per shingle.
➢ DevonshireTm shingles require minimum six(6)nails per shingle.
➢ Starter Strip Shingle and Starter Strip Plus require minimum five(5)nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing—Starter Strip Shingle and Starter Strip Plus:
Felt underlayment Deck Feh underlaymem Deck SeN-adherd
Weathedacka
Self-adhered underlaymerrt
WeatherLocke
underlayment
Drip Drip edge
Drip edge dB
fJa h low
Nails located td
2"-3•from eave
2"--3"from eave
Install first Self-sealing adhesive SaerJ ng adhesive
Starter Strip \ positioned along eave I"v�ttrT�srrcmoved rSMp PWs peslyond along cave
shingle with
6 removed r StarterStrr Plusoverhan s eaves and rakes 1141-3/4"
Starter Strip shingle overhangs eaves and rakes/i='/i' p g
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R8
Certificate of Authorisation#9503 6TH EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 3 of 8
TRINITY I ERD
6.2.6 Minimum Nailing—Classic®&Supreme:
Normal Mansard or Area para Normal Mansard or Area pan
Wind Areas Higfi Wind desysnes y Wind Areas High Wtnd deevanea.y
Area pare vientos nsrmales =6 Weritos Mertes Area,para vientos normales Areas visntos fuertes
r IAI �" z• (B z' �. �" (A► r� t• 2•. iB1 Z• 1"
++' »• �z� t21
5"E�iposure 6 6ltd"Exposure
Exposiefdn Eaposicidn
6.2.7 Minimum Nailing—Berkshire®:
SealarR gip. Sealant strip
•La ibs da sellador is tka de sellador
0-0
8 Vi" 9 YP B lh" SW •e Yt' a IV. 8W a W
r
Standard Fastening Pattern 6-Nail Fastening Pattern
Sealant strip
La!(ra de saltador
`t"'8 W. 8Id, 8 yr a vp
�:.
2• AsphaftrQ64oerfikt
Csmento,de 1who da Wafto
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-R8
Certificate ofAuthorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 4 of 8
TRINITY ERD
6.2.8 Minimum Nailing—Devonshire TM:
1, 71t 8" 8" Bn 7e •
Na a
cirm
Nails
5518°exposure Sealant location "'
Exposidbn de 5.5/8 pulg Ubieaddn del sellador st
Ten 1n Spots of Asphalt Roof Cement
Standard 6-Nail Fastening Pattern Mansard or Steep Slope Fastening Pattern
6.2.9 Minimum Nailing — Duration®, TruDefinition® Duration, Duration® Premium Cool & Tru Definition
Duration Designer Color Collection:
4-Nail Fastening Pattern 6-Nail Fastening Pattern
St••N001amning=2%ldtff S=N=fatenitry area Mmn
ILS.TY&W !+�.1Yptco
7" 1Y• 14" 7' 1" 12'- 17" 1"
p...c.:ss •e .�+••-o • o..m c.��n..vu° • o..^.�.^�a w.'m • •m•^•s .+•—a •w..�maa.xa •
E= P
w..° F] F� F�
Standard Fastening Pattern 6-Nail Fastening Pattern
Fastening for Slopes Greater Than 21:12
SmNaMntafning-kith
.%+ypicat
r 1z^ I 1r
e.ve•ss�e^
0_Tg-
F..V Spob of Aspha t RooMg Cemant
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-RB
Certificate ofAuthoriration#9503 6'EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 5 of 8
TRINITY ERD
6.2.1 Minimum Nailing—TruDefinition•Oakridge®,Oakridge®:
4 Nall Pattern 6 Nall Pattorn
Esgyema con 4 davos Esguema con 6 efavos
I
12 -sl 1r. Imo— 12•
L6/a"ExposureNails 561a"Exposure Nails
posicidPd'. tiepulg Clavas 'Erposfadnde'56/8pufg. 55ff'Exposute Clavor 6b/a"Exposute
FxposfCfda.de 66/8pufg fxpaSFefda de 6 6/8pufg.
Standard Fastening Pattern 6-Nail Fastening Pattern
Fastening for Slopes Greater Than 21:12
seeNe10tatenNg arae MIEN
• Nrt0.1!'Plwt
1" 12- 3wry '12* t'
pa(rwfueu • •U+rf
L
15-1 5X"
0
Four 1°Spate ofAep6etl RooMg Cement
Mansard or Steep Slope Fastening Pattern
6.2.1 Minimum Nailing—WeatherGuard®HP:
1■ �� �••1 1 ilYbb
61ilde-View
1111iiiinuo MI Ilk=
inif.Wfib Qdie
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-R8
Certificate o/Authorization 119503 6'EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 6 of 8
TRINITY I ERD
6.3 Hip&Ridge Shingles:
6.3.1 Installation of Berkshire Hip and Ridge Shingles, High Ridge, WeatherGuard® HP Hip and Ridge Shingles
and ProEdge Hip & Ridge Shingles shall comply with the Owens Corning current published instructions,
using four (4) nails per shingle. Installation of DuraRidgeTm Hip & Ridge Shingles shall comply with the
Owens Corning current published instructions, using two (2) nails per shingle. Refer to Owens Corning
published information on wind resistance and installation limitations, including the use of hand-sealing for
wind warranties.
6.3.2 Fasteners shall be in.accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing—Berkshire®Hip&Ridge and High Ridge:
flg,1 4. Fig.
2
'Pnoralllllgwnd'
�Dtrecllon a... ToRwm _SiCeView
Halls— —j A ;'NalsNails
4
\ .t.•.'r TOP Lanfrlated� 2 1
\\ 4" 'Pisa,
A I I I I I
I ml
i y •v ;r _ �I
osufB :ul
I
I
- 1
I
I.
6.3.4 Minimum Nailing—WeatherGuard®HP Hip and Ridge:
Fi
Fig.C Hip&Ridge Shingle Fastening
g•A 44 7opVlew
Preualling Wlnd
F—Dlmclbn A
P -
Ralls
F Nails Nails
A I ri
I I 1 I
Exposure
Exposure
72'
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-118
Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 7 of 8
TRINITY I ERD
6.3.5 Minimum Nailing-ProEdge Hip&Ridge Shingles:
Prevailing Standardtt`�
Wind Direction Sealant Strip Pattering
L-" 6'Exposure I'.� il'I I•t•
' 12` I I f•. Sealant
Fasten 71(? 7y: 6"Exposure
Cover Exposed 1
Fasteners with
Roof Cement
6.3.6 Minimum Nailing—DuraRidgeTm Hip&Ridge Shingles:
Note:The drawings below pertain to minimum,as-tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
Pfaraiingwiid Diroction Top View
t—DIia2 domimnta ckjywt Vue en plan
DirocdCndo]riontoprodornimnto I Vlstasuperlor I'
zs;
J `" 1
Gou
1. Ovnns CordMJ$urrd-Jall' cr"
p �
�lom —t �t I
aios I I
AI I Ia
L
p d k V V ivla�
Mfg
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1/R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625;(631)546-2458;Kanchi.Agrawala-Dokania@ul.com
- END OF EVALUATION REPORT-