HomeMy WebLinkAboutRiser Diagram Jan. 15. 2019 2:51PM No. 2368 P. 6 RISER DIAGRAM NEW 2 INCH GRC RISER AND WEATHER HEAD MOUNTED TO THE STRUCTURE AND STRAPED IN ACCORDANCE WITH THE NEC THE RISER FEEDERS WILL BE 3-2/0 COPPER THHN FEEDERS THE NEW 200 AMP METER WILL REPLACE THE EXISTING 100 AMP EXISTING METER THE EXISTING 100 AMP METER 200 AMP NEMA CAN THAT IS BACK TO BACK WITH 3-2/0 IN A 2 — - THE ELECTRICAL METER WILL BE INCH CONDUIIT 3R MAIN BREAKER OLD ELECTRICAL PANEL ELECTRICAL PANEL WILL BE USED ASA USED AS A JUNCTION BOX AND 0 JUNCTION BOX FOR ALL THE BRANCH CIRCUITS WILL THE BRANCH CIRCUITS TO BE FEED TO THE BE FEED FROM THE NEW 3R METER MAIN COMBO ELECTRICAL PANEL.THE EXISTING LOCATION OF THE 100 AMP PANEL IN THE LAUNDRY ROOM DOES NOT MEET THE CLEARENCE REQUIREMENTS. THE SCOPE OF WORK ON THIS PROJECT IS TO UPGRADE THE New meter main EXISTING 100 AMP ELECTRICAL SERVICE TO A 200 AMP combo with 32 SERVICE.THE ELECTRICAL SERVICE WILL BE CHANGED IN ITS spaces. ENTIRETY INCLUDING THE GROUNDING SYSTEM,THE EXISTING 100 AMP ELECTRICAL PANEL THAT IS BACK TO BACK WITH THE METER WILL BE USED ASA JUNCTION BOX.THE BRANCH CIRCUITS THE EXISTING GROUNDING SYSTEM WILL BE UPDATED TO MEET WILL NOW BE FEED FROM THE NEW NEMA 3R PANEL ALL BRANCH ALL CURRENT NEC CODES ALONG WITH A NEW GROUNDING BRIDGE THERE WII.I.BE tt4 GROUND CONDUCTOR CONNECTED CIRCUITS WILL HAVE THE PROPER OVERCURRENT PROTECTION IN TO 2-BFTCOPPER CLAD GROUNDING RODS SPACED NO CLOSER ACCORDANCE WITH THE BRANCH CIRCUIT WIRE SIZE. TINA 6 FEET APART Ford Residence 7705 Lockwood Drive Fort Pierce Florida 34951 Qualifier Michael Hourtz EC13006338