RISER DIAGRAM
NEW 2 INCH GRC RISER AND WEATHER HEAD MOUNTED
TO THE STRUCTURE AND STRAPED IN ACCORDANCE
WITH THE NEC THE RISER FEEDERS WILL BE 3-2/0
COPPER THHN FEEDERS
THE NEW 200 AMP METER WILL REPLACE THE EXISTING
100 AMP EXISTING METER
THE EXISTING 100 AMP METER
200 AMP NEMA CAN THAT IS BACK TO BACK WITH
3-2/0 IN A 2 — - THE ELECTRICAL METER WILL BE
INCH CONDUIIT 3R MAIN BREAKER OLD ELECTRICAL PANEL
ELECTRICAL PANEL WILL BE USED ASA USED AS A JUNCTION BOX AND
0 JUNCTION BOX FOR ALL THE BRANCH CIRCUITS WILL
THE BRANCH CIRCUITS
TO BE FEED TO THE BE FEED FROM THE NEW 3R
METER MAIN COMBO ELECTRICAL PANEL.THE EXISTING
LOCATION OF THE 100 AMP
PANEL IN THE LAUNDRY ROOM
DOES NOT MEET THE CLEARENCE
REQUIREMENTS.
THE SCOPE OF WORK ON THIS PROJECT IS TO UPGRADE THE
New meter main EXISTING 100 AMP ELECTRICAL SERVICE TO A 200 AMP
combo with 32 SERVICE.THE ELECTRICAL SERVICE WILL BE CHANGED IN ITS
spaces. ENTIRETY INCLUDING THE GROUNDING SYSTEM,THE EXISTING
100 AMP ELECTRICAL PANEL THAT IS BACK TO BACK WITH THE
METER WILL BE USED ASA JUNCTION BOX.THE BRANCH CIRCUITS
THE EXISTING GROUNDING SYSTEM WILL BE UPDATED TO MEET WILL NOW BE FEED FROM THE NEW NEMA 3R PANEL ALL BRANCH
ALL CURRENT NEC CODES ALONG WITH A NEW GROUNDING
BRIDGE THERE WII.I.BE tt4 GROUND CONDUCTOR CONNECTED CIRCUITS WILL HAVE THE PROPER OVERCURRENT PROTECTION IN
TO 2-BFTCOPPER CLAD GROUNDING RODS SPACED NO CLOSER ACCORDANCE WITH THE BRANCH CIRCUIT WIRE SIZE.
TINA 6 FEET APART
Ford Residence
7705 Lockwood Drive
Fort Pierce Florida 34951
Qualifier Michael Hourtz
EC13006338