EVALUATION REPORT
Soprema,Inc. Evaluation Report S18010.06.09-R12
1640 rue Haggerty FL2569-R14
Drummondville,Québec J2C 5P8 Canada Date of Issuance:06/15/2009
(819)478-2400 Revision 12:02/12/2018
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: Soprema Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to
the product(s),the Quality Assurance or the production facility location(s). NEMO I etc. requires a complete review of
this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOIetc. Evaluated" may be displayed i3
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request,a copy of this entire Evaluation Report shall be provided to the user by the manufacturerso r',
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8. 4141
ttj
Prepared by: •,�„��,,. Araz
,— /c,
Robert J.M.Nieminen,P.E. O•.�, r;'.-: The facsimile seal appearing was authorized by Robert
Florida Registration No.59166,Florida DCA ANE1983 ;;� ````` ele trop caly sign d d018.ocu�menLThis does not serve as an
CERTIFICATION OF INDEPENDENCE:
1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire,a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC,LLC is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen,P.E.doe's not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO'etc. nor Robert Nieminen, P.E. are, in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained'
specifically for that purpose.
I � �
(8
NEMO I etc.
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Underlayment
Compliance Statement:.Roof Underlayments, as produced by Soprema, have demonstrated compliance with the
following sections of the 6th Edition (2017) Florida Building Code through testing in accordance with the following
Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth
herein.
2. STANDARDS:
Section _ Property Standard Year
1504.3.1 Wind Resistance FM 4474 2011
1504.3.1 Wind Uplift UL 1897 2012
1507.2.4/1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015
1507.3.3 Physical Properties FRSA/TRI April 2012 2012
FRSA/TRI April 2012(04-12) Physical Properties ASTM D6163 2008
TAS 110 Accelerated Weathering ASTM D4798 2011
3. REFERENCES:
Entity Examination Reference Date
ERD(TST6049) ASTM D1970/TAS 110 2968.05.04-2 05/14/2004
ERD(TST6049) Physical Properties 2757.02.05 02/03/2005
ERD(TST6049) ASTM D1970/TAS 110 2974.03.05-2 05/17/2005 ,
ERD(TST6049) Wind Resistance 2778.07.05 07/15/2005
ERD(TST6049) Wind Resistance 2779.11.05-R1 04/18/2007
ERD(TST6049) TAS 103/TAS 110 57120.11.07-2 11/02/2007
ERD(TST6049) ASTM D1970/TAS 110 S13190.02.09-R1 04/01/2010
ERD(TST6049) ASTM D1970/TAS 110 S31370.03.10-1-R1 04/07/2010 I
ERD(T5T6049) Physical Properties/Tensile Adhesion S11150.05.10-R1 09/09/2010 I
ERD(TST6049) Physical Properties/Tensile Adhesion S11150.05.09-R2 10/05/2010
ERD(TST6049) ASTM D1970 537210.11.11 11/09/2011
ERD(TST6049) ASTM D1970 S40540.02.13-1 02/19/2013
ERD(TST6049) Physical Properties/Tensile Adhesion S43530.02.14-1 02/21/2014
ERD(TST6049) Physical Properties/Tensile Adhesion SOPC-SC7645.02.15 02/13/2015
ERD(TST6049) Accelerated Weathering SOPC-SC8520.14 04/17/2015
ERD(TST6049) Wind Resistance SOPC-SC14045.05.17-R1 06/07/2017
M-D(CER1592) HVHZ Compliance 15-0508.04 09/24/2015
ICC-ES(EVL2396) 2015 IBC Compliance ESR-1524 03/01/2017
PRI(TST5878) Physical Properties SOP-064-02-01 12/03/2013
Soprema,Inc.(PDM3511) Equivalency Declaration SA SMOOTH PLY 40 06/29/2015
UL,LLC(QUA9625) Quality Control Service Confirmation Exp.07/18/2020
4. PRODUCT DESCRIPTION:
4.1 Lastobond TU HT is a self-adhering, non-woven polyester fabric surfaced, SBS modified bitumen roof
underlayment;meets ASTM D1970 and FRSA/TRI April 2012(04-12).
4.2 Lastobond Shield is a self-adhering, woven polyethylene surfaced, SBS modified bitumen roof underlayment
available in two widths;36 and 45 inch;meets ASTM D1970.
4.3 RESISTO SA SMOOTH PLY 40 is a self-adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment;available in 3.3 ft x 65 ft rolls;meets ASTM D1970.
4.4 Lastobond Shield HT is a self-adhering,woven polyethylene surfaced,high temperature,SB5 modified bitumen roof
underlayment;meets ASTM D1970.
NEMO ETC,LLC Evaluation Report S18010.06.09-R12
Certificate of Authorization#32455 61H EDITION(2017)FBC NON-HVHZ EVALUATION FL2569-R14 i
Soprema Roof Underlayments Revision 12:02/12/2018
Page 2 of 8
NEMO I etc.
4.5 Lastobond Pro HT-N is a self-adhering, woven polyethylene surfaced, SBS modified bitumen roof underlayment
available in two widths;36 and 45 inch;meets ASTM D1970.
4.6 Lastobond Pro HT-S is a self-adhering,woven polyethylene surfaced, high temperature,SBS modified bitumen roof
underlayment;meets ASTM D1970.
4.7 EnviroShield is a self-adhering, woven polyethylene surfaced, high temperature, SBS modified bitumen roof
underlayment; meets ASTM D1970.
4.8 Lastobond 195 is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof underlayment;
meets ASTM D1970.
4.9 Lastobond Eaves Protection Sheet is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen
roof underlayment; meets ASTM 01970.
4.10 Lastobond Eco is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof underlayment;•;
meets ASTM D1970.
4.11 Lastobond Smooth Seal HT is a self-adhering, glass-mat reinforced, film-surfaced, SBS modified bitumen roof
underlayment;meets ASTM D1970.
4.12 -RESISTO LB1236 is a self adhering;,glass matrreinforced;sand surfaced,SBS,modified;bitumen roof underlayment;.
with_a 36 inch_sheetiwidth;.meets ASTM 019.7.0 .f • _. -
4.13 PrimeSource Grip-Rite Eave & Valley Protector is a self-adhering, glass-mat reinforced, sand-surfaced, SBS
modified bitumen roof underlayment,with a 36-inch sheet width; meets ASTM D1970.
4.14 RESISTO LB1244 is a self-adhering,glass-mat reinforced, sand-surfaced, SBS modified bitumen roof underlayment,
with a 44-inch sheet width;meets ASTM 01970.
4.15 Colphene FR GR is a self-adhering, fiberglass reinforced, granule-surfaced, SBS modified bitumen roof
underlayment;meets ASTM D1970 and FRSA/TRI April 2012(04-12).
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are,in any way,the Designer
of Record for any project on which this Evaluation Report,or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this report; refer to current Approved Roofing Materials Directory for fire ratings of'I
this product.
5.4 Soprema Roof Underlayments may be used with any prepared roof cover where the product is specifically!
referenced within FBC approval documents. If not listed, a request may be made to the Authority Having',
Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable Roof Covers:
TABLE 1: ROOF COVER OPTIONS
Wood or
Asphalt Nail-On Foam-On Composite Slate or ;I
Underlayment Shingles Tile Tile Metal Composite
Shakes&
• Shingles Slate
Lastobond TU HT Yes Yes Yes Yes Yes Yes
See 5.5.1
Lastobond Shield/Pro HT-N/
RESISTO SA SMOOTH PLY 40 •
Yes No No No Yes Yes
Lastobond Shield HT/I Pro HT-S Yes No No' Yes Yes Yes
EnviroShield Yes No No< Yes Yes Yes
NEMO ETC,LLC Evaluation Report S18010.06.09-R12
Certificate of Authorization#32455 6TH EDITION(2017)FBC NON-HVHZ EVALUATION FL2569-R14
Soprema Roof Underlayments Revision 12:02/12/2018 I
Page 3 of 8
$NEMoIetc.
TABLE 1: ROOF COVER OPTIONS
- Wood or Slate or,
Asphalt Nail-On Foam-On ' Composite
Underlayment Metal Composite
Shingles Tile Tile Shakes&
Shingles Slate
Lastobond Eaves Protection Sheet/
Yes - No No No Yes Yes
Lastobond 195 •
Lastobond ECO /RESISTO LB1236,
Grip-Rite Eave&Valley Protector/ Yes No No No Yes Yes
RESISTO LB1244 G
Lastobond Smooth Seal HT Yes No No Yes Yes Yes
Colphene FR GR Yes Yes Yes No Yes 'Yes
See 5.5.1
5.5.1 "Foam-On Tile"is limited to use of following Approved tile adhesives/underlayment combinations.
TABLE 1A:ALLOWABLE TILE ADHESIVE/UNDERLAYMENT COMBINATIONS'
Adhesive Florida Product Approval Underlayments
Dow TileBond'" FL22525 Lastobond TU HT
ICP Adhesives Polyset®AH-160 FL6332 Lastobond TU HT or Colphene FR GR
5.6 Allowable Substrates:
5.6.1 Direct-Bond to Deck:
Lastobond Shield,Lastobond Pro HT-N,RESISTO SA SMOOTH PLY 40,Lastobond Shield HT, Lastobond Pro HT-S,%
EnviroShield, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond ECO, RESISTO
LB1236,Grip-Rite Eave&Valley Protector,RESISTO LB1244 or Lastobond Smooth Seal HT applied to:
➢ Plywood;ASTM D41 primed plywood;OSB;ASTM D41 primed OSB;Southern Yellow Pine;ASTM 041 primed
Southern Yellow Pine;ASTM D41 primed structural concrete.
Colphene FR GR applied to:
y- Plywood;ASTM D41 primed plywood;ASTM D41 primed structural concrete.
Note:
• While not required over plywood, OSB or Southern Yellow Pine substrates, Soprema recommends priming'
with Elastocol Stick or Elastocol 600c if the final roof cover is not slated for installation within 24 hours.
➢ Soprema requires tongue-and-groove board decking be covered with plywood or OSB prior to installation of
the self-adhering underlayment.
5.6.2 Bond-to-Insulation:
Lastobond Shield,Lastobond Pro HT-N,RESISTO SA SMOOTH PLY 40,Lastobond Shield HT,Lastobond Pro HT-S,
EnviroShield, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond ECO, RESISTO
LB1236, Grip-Rite Eave & Valley Protector, RESISTO LB1244, Lastobond Smooth Seal HT or Colphene FR GR
applied to:
➢ Dens Deck Prime;SECUROCK Gypsum-Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum
requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam-on
tile systems (Lastobond TU HT only), insulation attachment shall be designed by a qualified design professional
and installed based on testing of the insulation/underlayment system in accordance with FM 4474,Appendix D,
Testing Application Standard TAS 114,Appendix J or UL1807.
'Refer to Tile Manufacturers or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
NEMO ETC,LLC Evaluation Report S18010.06.09-R12
Certificate of Authorization#32455 6TH EDITION(2017)FBC NON-HVHZ EVALUATION FL2569-R14
Soprema Roof Underlayments Revision 12:02/12/2018
Page 4 of 8
NEMO I etc.
5.6.3 Bond to Mechanically Attached Base Layer:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro HT-S,
EnviroShield, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond ECO, RESISTO
LB1236, Grip-Rite Eave & Valley Protector, RESISTO LB1244, Lastobond Smooth Seal HT or Colphene FR GR
applied to:
➢ ASTM D226,Type I or II felt;Sopra-G; Modified Sopra-G.
For installations under mechanically attached prepared roof coverings,base layer shall be attached per minimum
codified requirements. For installations under foam-on tile systems(Lastobond TU HT only), base layer shall be
attached in accordance with FRSA/TRI April 2012(04-12).
5.6.4 Wind Resistance for Underlayment Systems in Foam-On Tile Applications: FRSA/TRI April 2012(04-12)does not
address wind uplift resistance of all underlayment systems beneath foam-on tile systems, where the
underlayment forms part of the load-path. The following wind uplift limitations apply to underlayment system's
that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam-on tile applications. Maximum
Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the
ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied).
Refer to FRSA/TRI April 2012(04-12)or FBC 1609 for determination of design wind pressures.
#1 Maximum Design Pressure=-45.0 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: (Optional)Elastocol Stick, Elastocol 600c or RESISTO EXTERIOR PRIMER
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered.
#2 Maximum Design Pressure=-67.5 psf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: Elastocol 600c
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered.
#3 Maximum Design Pressure=-150.0 psf:
Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit adhesion. All
sheathing fasteners shall be driven flush with the surface. All sharp splinters and wood
projections shall be removed/sanded.
Primer: (Optional)RESISTO EXTERIOR PRIMER
Underlayment: Lastobond TU HT, self-adhered, shall be thoroughly roll using hand roller and/or weighted
roller to ensure there are no voids, and ensure there are no voids/bridging at side and end-
laps.
#4 Maximum Design Pressure=-60.0 psf:
Deck: , Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: Sopra-G or Modified Sopra-G mechanically attached with nails(FBC 1517.5.1)and tin caps(FBC
1517.5.2)spaced 6-inch o.c.at the 4-inch laps and 6-inch o.c.in three(3),equally spaced rows
in the center of the sheet.
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered
5.6.4.1 All other direct-deck, adhered Soprema underlayment systems beneath foam-on tile systems carry a Maximum
Design Pressure of-45 psf.
NEMO ETC,LLC Evaluation Report S18010.06.09-R12
Certificate of Authorization#32455 6"EDITION(2017)FBC NON-HVHZ EVALUATION FL2569-R14
Soprema Roof Underlayments Revision 12:02/12/2018
Pages of 8
NEMO I etc.
5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or
exceed that required under FRSA/TRI April 2012(04-12),Appendix A,Table 1A.
Alternatively,the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment
density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used
methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117.
Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention
Data Sheet 1-29(January 2016)for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Lastobond Eaves Protection Sheet,Lastobond 195,Lastobond Eco,Lastobond Smooth Seal HT,RESISTO LB1236,
Grip-Rite Eave,& Valley Protector or RESISTO LB1244 shall not be left exposed for longer than 30-days after
installation.
Lastobond Shield,Lastobond Pro HT-N,RESISTO SA SMOOTH PLY 40,Lastobond Shield HT or Lastobond Pro HT-
S,EnviroShield shall not be left exposed for longer than 90-days after installation.
Lastobond TU HT or Colphene FR GR shall not be left exposed for longer than 180-days after installation.
5.8 Tile Slippage Limitations(TAS 103 per FRSA/TRI April 2012(04-12)):
When loading roof tiles on the underlayment in direct-deck tile assemblies,the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
TABLE 2: TILE SLIPPAGE LIMITATIONS FOR DIRECT-DECK TILE INSTALLATIONS
Underlayment Tile Profile Staging Method Maximum;
Slope I
Flat Max.10-tile stack 6:12
Lugged Max.10-tile stack 5:12
Max.10-tile stack(bottom 2-tile stack
shall be inverted,followed by 8 tiles high 6:12
on slope,as shown below)
,
Lastobond TU HT '` "
Lugged �'.;.:3
' 1
Colphene FR GR Flat Max.10-tile stack 5:12
Lugged Max.10-tile stack 6:12
NEMO ETC,LLC Evaluation Report S18010.06.09-R12
Certificate of Authorization#32455 6TH EDITION(2017)FBC NON-HVHZ EVALUATION FL2S69-R14'
Soprema Roof Underlayments Revision 12:02/12/2018
Page 6 of 8
NEMO I etc.
6. INSTALLATION:
6.1 Soprema Roof Underlayments shall be installed in accordance with Soprema published installation requirements
subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to
remove any dust and debris prior to application, and prime the substrate with Elastocol Stick, Elastocol 600c or
RESISTO EXTERIOR PRIMER(if applicable).
6.3 Lastobond TU HT, Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond-Shield HT,
Lastobond Pro HT-S,EnviroShield,Lastobond Eaves Protection Sheet,Lastobond 195,Lastobond Eco,Lastobond
Smooth Seal HT,RESISTO LB1236,Grip-Rite Eave&Valley Protector,RESISTO LB1244 or Colphene FR GR:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table 1507.1.1 for
the type of prepared roof covering to be installed.
6.3.2 Non-Tile Applications:
While priming is optional,Soprema recommends priming with Elastocol Stick, Elastocol 600c or RESISTO EXTERIOR
PRIMER if the final roof cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3 ft of
release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel-off the release film diagonally while holding the membrane
tight. Firmly roll the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-inches and
staggered not less than 2-ft from vertical seams in the course below. All over-granule end-laps shall be sealed
using either heat-welding or hot air welding techniques.
When installing at slopes above 8:12, Soprema recommends back-nailing in the overlap area at the top of the
sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet over
valley or ridge. Drape and press sheet into place,working from the center of the valley or ridge in each direction.
For valleys,apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications(Lastobond TU HT or Colphene FR GR only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions
noted above as a guideline.
For foam-on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that fall
outside the scope of FRSA/TRI April 2012(04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. See
Table 2 herein,and Soprema published requirements for tile staging.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
NEMO ETC,LLC Evaluation Report 518010.06.09-R12
Certificate of Authorization#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL2569-R141
Soprema Roof Underlayments Revision 12:02/12/20181
Page 7 of 8
NEMO I etc.
8. MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered for F.A.C. 61G20-3 QA requirements.
The following plants have qualified products under their respective physical properties specifications.
Plant Specification Product(s)
Lastobond Shield,RESISTO SA SMOOTH PLY 40,Lastobond Shield HT,
Drummondville, Lastobond Pro HT-N,Lastobond Pro HT-S,EnviroShield,Lastobond 195,
QC(Canada) ASTM D1970 Lastobond Eaves Protection Sheet,Lastobond Eco,Lastobond Smooth
Seal HT,RESISTO LB1236,PrimeSource Grip-Rite Eave&Valley
Protector,RESISTO LB1244
ASTM D1970&FRSA/TRI 04-12 Colphene FR GR
Wadsworth,OH Lastobond 195,Lastobond Eaves Protection Sheet,Lastobond Eco,
ASTM 01970 Lastobond Smooth Seal HT,RESISTO LB1236,PrimeSource Grip-Rite
Eave&Valley Protector,RESISTO LB1244
ASTM 01970&FRSA/TRI 04-12 Lastobond TU HT;Colphene FR GR
Gulfport,MS Lastobond 195,Lastobond Eaves Protection Sheet,Lastobond Eco,
ASTM D1970 Lastobond Smooth Seal HT,RESISTO LB1236,PrimeSource Grip-Rite
Eave&Valley Protector,RESISTO LB1244
9. QUALITY ASSURANCE ENTITY:
UL,LLC—QUA9625;(314)578-3406;k.chancellor@us.ul.com
-END OF EVALUATION REPORT-