March 15, 2019
St. Lucie County Florida
Planning and Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
RE: Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
Dear Sirs:
In response to the comments for the above-referenced permit, we remit the following:
ENVIRONMENTAL REVIEW
Review 01/03/2019
Comment #1 – Need to submit a notice of vegetation removal permit exemption application
Response: Ahrens Companies
PLANS EXAMINER PLUMBING REVIEW
Review 01/02/2019
Comment #1 – Please show shower control location dimensions per Section 605.5.3 of the Florida
Accessibility Code 2017 (pertaining to showers with seats) page a 5.0.2 of the plans show them
in the center of the back wall this does not meet Florida Accessibility Code 2017
Response: Shower control location complies with the 2017 Florida Accessibility Code section
608.5.2 for standard roll-in type shower compartments. See figure 608.5.2 (b).
Comment #2 – Please list type of trap primers to be used per Section 1002.4.1 FPS 2017. Trap
guards do not meet Project Manual Specifications Book 1 Page 22 40 00-3 Sentence J
Response: Specification sections shall be revised to trap guards.
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 2 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
PLANS EXAMINER REVIEW
Review 12/31/2019
Comment #1 – Please submit the pre-engineered metal building plans for the air hanger and the
office building for review. See Section 107 of the 2017 Florida Building Code.
Response: These documents will be submitted during the construction submittal phase.
Comment #2 – Submit [ 3 ] St Lucie County " Product Review Affidavits completely filled out in
original format, or add the Product Review Affidavit for the components and cladding to the plans
for the air hanger and the office building to include all windows, doors, wall and roof sheeting, and
louvers. Signed sealed and dated by your design professional.
Response: See attached Product Review Affidavit signed and sealed by AOR. (Building
official: Please refer to the wind pressures that are listed on the structural drawings and the Florida
product approvals are listed on Sheet A6.0.6. and new sheet A0.0.2.1. Also see specification
manual for each component of cladding).
Comment #3 – Please submit the Geotechnical Report per page S0.02. Meeting the requirements
of Chapter 18, Section 1803, Subsection 1803.1. Reviewed and approved by the design
professional in charge.
Response: Note: The Geotechnical Report is included in the Appendices to the Project Manual
and is being furnished with this resubmittal. Also, the locations of Soil Borings and the Soil Boring
Logs are included as Drawing C3.0.3 through C3.0.7, included with this resubmittal.
Comment #4 – Plans are marked as bid documents, please submit the approved construction set
of plans for review. See Chapter 1, Section 107, Subsection 107.2.1 of the 2017 Florida Building
Code.
Response: The Title Blocks have been revised to “Construction Documents”.
Comment #5 – Please see index of drawings on page C0.02. Please submit all pages referenced
on the index sheet. C3.0.1 thru C8.0.3, C9.0.5 thru C9.0.6, C12.0.1, C12.0.3 thru C12.0.4, C13
thru C35.0.4, CE40.0.1 thru CE40.0.13 and A5.05 are not included with the submitted documents.
See section 107 of the 2017 Florida Building Code.
Response: We apologize for the unintended omission of these Drawings, and are including
them in this resubmittal. Please note Drawing A5.0.5 was “NOT USED”, and this has been
reflected in the revised INDEX OF DRAWINGS on page C0.0.2.
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 3 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
Comment #6 – Please see index of drawings on page C0.02. Page A7.0.1.1 was not added to
the index sheet. Please correct and submit. See section 107 of the 2017 Florida Building Code.
Response: The INDEX OF DRAWINGS on page C0.0.2 has been corrected to include this
sheet.
Comment #7 – The air hanger building meets the definition of a threshold building. Please submit
the information needed meeting the requirements of Chapter 1, Section 110, Subsection 110.8 of
the 2017 Florida Building Code.
Response: We will add the notes necessary to address FBC Subsection 110.8.
Review 01/02/2019
Comment #1 – See note 3 on page S0.0.2 for the cast in place concrete. Please submit the
concrete design mix in accordance with note 3. See Section 107 of the 2017 Florida Building
Code.
Response: These documents will be submitted during the construction submittal phase.
Comment #2 – See page S0.0.2, helical piles, please submit the shop drawings and calculation
meeting the requirements of note number #2 and 3. See Section 107 of the 2017 Florida Building
Code.
Response: These documents will be submitted during the construction submittal phase.
Comment #3 – See slab on grade note number three on page S3.0.1. Please submit plans for
joint spacing meeting the specifications of slab on grade note #3. See Section 107 of the 2017
Florida Building Code.
Response: These documents will be submitted during the construction submittal phase.
Comment #4 – Please submit a manual d for air distribution sizing and design. See C403.2.9.5
of the 2017 Florida Energy Code.
Response: Per phone conversation with William Durden, Trane Trace Report shall be
provided in lieu of manual d.
Comment #5 – Please submit a manual n for the design load associated with heating, ventilating
and air conditioning of the building. See chapter 4, section c403, and sub-section 403.2 of the
2017 Energy Code.
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 4 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
Response: Per phone conversation with William Durden, Trane Trace Report shall be
provided in lieu of manual n.
Comment #6 – Please submit a Manual J. See Chapter 4, Section C402 of the 2017 Energy Code.
Response: Per phone conversation with William Durden, Energy Gauge Report shall be
provided in lieu of manual j.
Comment #7 – Page S0.0.2 it alternate one, if the bid alternate is selected revised drawings will
need to be submitted for review.
Response: We will remove Bid Alternate No. 1 from the plans.
Comment #8 – All commercial documents submitted for permitting must be in triplicate. Any
documents that requires a signature or seal must be submitted in triplicate, with original seals and
signatures. Please see the 2017 Florida Building Code chapter 1, subsection 107.1.
Response: Resubmittal is made in triplicate as required with original Seals and Signatures.
Comment #9 – Please note that the comments are for the clarification or correction of the
submitted documents. Additional review may be required after submitting corrected documents
Response: Please see resubmittal for additional information.
Comment #10 – Please note: (1) all review comments when answered will require a cover letter
addressing where the changes were made, (2) all changes will be required to be clouded on the
plans and (3) the contractor when resubmitting will be required to insert the new updated pages
into the plans or if the contractor prefers, a revised complete set of plans can be submitted
Response: Comment responses are provided in this Narrative, and please see resubmittal for
the requested information.
ZONING REVIEW
Review 01/02/2019
Comment #1 – Please provide 2 signed and sealed sets of civil drawings for constructability
review of the engineering dep.
Response: An additional 2 sets of the Civil Drawings are included with this resubmittal.
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 5 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
Comment #2 – Plans are marked as bid documents, please submit the approved construction
documents.
Response: The Title Blocks have been revised to “Construction Documents”.
Review 01/04/2019
Comment #1 – Separate permit for the fence and gate is required.
Response: Ahrens Companies
Review 01/08/2019
Comment #1 – Please provide proposed finished floor elevation. Based on St Lucie County LDC
min. Required is 18" above center line of adjacent road.
Response: The finished floor elevation of the Office is set at 23.50. Hangar perimeter elevation
is 23.50 with a 0.50% slope to a central floor trench drain. The centerline of the access road is
approximately 21.00. Please refer to Drawing C12.0.1. Note that by necessity, airport grades are
minimal to enable aircraft ease of taxiing. Therefore, the Hangar FFE is dictated by the existing
elevation of Taxiway E, and the minimally allowed slope for aircraft aprons.
Comment #2 – Please provide elevation of center line adjacent road (Jet Center Terr.)
Response: The center line elevation of the Jet Center Terrace Extension varies from
approximately 23.30 at its current terminus, to approximately 21.3 at the intersection with the
reconstruction of Taxiway D to the Hangar access drive, all as shown on Drawing C12.0.1
included with this resubmittal. In front of the Hangar, the access drive has an elevation of
approximately 21.00.
Comment #3 – In case the 18" above center line of the road is creating a problem, the planning
director may grant relief of the code. A written request should be directed attention Leslie Olson,
AICP, director planning and development services department. Please include in your letter the
reason of the request, the proposed elevation, the elevation of the center line of the road, address
and permit number and if the property is in a flood zone the min. Required flood zone elevation.
Please submit the letter to my attention. A $ 50.00 fee is applicable and will be added to the permit
fee.
Response: See response to Comment #1 above. Note the entire site is located in “Zone X –
Area of Minimal Flood Hazard” as determined by the FEMA Flood Plain Map 12111C0176J.
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 6 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
Please see the following pages for a Narrative of the drawing changes made with this resubmittal.
Thank you.
Sincerely,
AVCON, INC.
Robert H. Palm, P.E.
Senior Project Manager
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 7 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
CHANGES TO ARCHITECTURAL DRAWINGS FOR THIS RESUBMITTAL
I. CHANGES TO DRAWINGS - ADDENDUM 2
1. Drawing C0.0.2 – Index of Drawings has been REVISED. Sheet A5.0.5 - Interior
Elevations is NOT USED. Sheet A7.0.1.1 - Hangar Door Geometry & Sheet E805 -
Security PACS Details is added to Index of Drawings.
2. Drawing A6.0.3 - Detail B3 - Roof Detail has been ADDED.
Drawing Detail B3/A6.0.3 is issued with this Addendum.
3. Drawing A3.0.1 - Detail B3 - Draft Curtain Detail has been ADDED.
Drawing Detail B3/A3.0.1 is issued with this Addendum.
4. Drawing A7.0.1.1 - Hangar Door Geometry has been REVISED: Pocket Doors are
deleted off sheet.
5. Drawing A6.0.6 - Wall Type UL Assemblies has been REVISED: Florida Product
Approvals has been edited to add “Guardian 275 Translucent Hurricane Wall System NO.
- FL#13504-R2”.
6. Drawing A8.0.1 - Detail C3 - Typical Bollard Detail has been REVISED: Keynote 03 30
00.0001 – “Typ. Grout Filled” has been revised to 03 30 00.0001 - “Concrete Filled Steel
Bollard”. Keynote 03 48 13.0000 – “Typ. Precast Concrete Bollard”, is deleted.
7. Drawing A0.0.1 - General Notes, Index, Keynotes has been REVISED: Keynotes 08 81
00.0001 & 08 81 00.0002, (Glass color) is changed from “Green VE2.45 #2” to “Blue
VE.42”.
8. Drawing S0.0.1 - General notes has been REVISED: Bid Alternate No. 1 is deleted.
II. CHANGES TO DRAWINGS – ADDENDUM 3
1. Drawing A1.0.1 - Floor Plan has been REVISED.
2. Drawing A5.0.1 - Detail B2 – Exterior Elevations has been REVISED.
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 8 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
III. CHANGES TO DRAWINGS - CHANGE ORDER CO#1
1. Drawing A0.0.1 - GENERAL NOTES, KEYNOTES has been REVISED. Keynotes
revised.
2. Drawing A0.0.2 - CODE ANALYSIS & LIFESAFETY has been REVISED. Note added
referencing Florida product Approvals sheet # A6.0.6, for clarity.
3. Drawing A1.0.1 - Floor Plan has been REVISED. Keynote for Epoxy Floor is deleted,
new Keynote added for Hangar floor 03 35 00.0001 “TYP. CONCRETE FLOOR FINISH
APPLICATION, CURE-DESIFIER-HARDENER SEALER”.
4. Drawing A3.0.1 - REFLECTED CEILING PLAN has been REVISED. (1) ceiling fan was
deleted at Hangar between Column lines 2 & 3.
5. Drawing A4.0.1 - ROOF PLAN has been REVISED. Roof Keynote 13 34 19.2400 is
edited.
6. Drawing A5.0.1 - EXTERIOR ELEVATIONS has been REVISED. Metal wall panel
keynotes 13 34 19.1501 & 13 34 19.1502 was edited. Roof panel Keynote 13 34 19.2400
was edited. Detail Section Mark C3/A8.0.2 was added for clarity. Translucent Panel
Assembly - (Plastic clearstory fixed windows) and keynote was deleted from project.
7. Drawing A6.0.1 - BUILDING SECTION has been REVISED. Metal wall panel keynote 13
34 19.1501 was edited. Roof panel Keynote 13 34 19.2400 was edited. Translucent Panel
Assembly - (Plastic clearstory fixed windows) and keynote was deleted from project.
8. Drawing A6.0.2 - BUILDING WALL SECTIONS has been REVISED. Metal wall panel
keynote 13 34 19.1501 was edited. Roof panel Keynote 13 34 19.2400 was edited.
Translucent Panel Assembly - (Plastic clearstory fixed windows) and keynote was deleted
from project. Keynote for Epoxy Floor was deleted, new Keynote added for Hangar floor
03 35 00.0001 “TYP. CONCRETE FLOOR FINISH APPLICATION, CURE-DESIFIER-
HARDENER SEALER”. Roof Insulation Keynote 07 21 16.019A was added. Roof
Insulation Keynotes 07 21 16.030 was edited. Detail Section Mark C3/A8.0.2 was added
for clarity.
9. Drawing A6.0.3 - BUILDING WALL SECTIONS has been REVISED. Metal wall panel
keynotes 13 34 19.1501 & 13 34 19.1502 was edited. Roof panel Keynote 13 34 19.2400
was edited. Translucent Panel Assembly - (Plastic clearstory fixed windows) and keynote
was deleted from project. Keynote for Epoxy Floor was deleted, new Keynote added for
Hangar floor 03 35 00.0001 “TYP. CONCRETE FLOOR FINISH APPLICATION, CURE-
DESIFIER-HARDENER SEALER”. Roof Insulation Keynote 07 21 16.019A was added.
Roof Insulation Keynotes 07 21 16.030 was edited. Metal Panel Soffit keynote 13 34
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 9 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
19.2408 was edited. Detail Section Mark C1/A8.0.2 was added for clarity. Detail B3 ROOF
INSULATION DETAIL was edited.
10. Drawing A6.0.4 - WALL TYPES has been REVISED. Metal wall panel keynote 13 34
19.1501 was edited. Roof panel Keynote 13 34 19.2400 was edited. Keynote for Epoxy
Floor was deleted, new Keynote added for Hangar floor 03 35 00.0001 “TYP. CONCRETE
FLOOR FINISH APPLICATION, CURE-DESIFIER-HARDENER SEALER”. Roof
Insulation Keynote 07 21 16.0030 was edited. Detail Section Mark C3/A8.0.2 was added
for clarity.
11. Drawing A6.0.5 - WALL TYPES has been REVISED. Metal wall panel keynote 13 34
19.1502 was edited. Roof panel Keynote 13 34 19.2400 was edited. Keynote for Epoxy
Floor was deleted, new Keynote added for Hangar floor 03 35 00.0001 “TYP. CONCRETE
FLOOR FINISH APPLICATION, CURE-DESIFIER-HARDENER SEALER”. Roof
Insulation Keynote 07 21 16.0030 was edited.
12. Drawing A6.0.6 - WALL TYPE - UL ASSEMBLIES has been REVISED. Metal wall panel
& metal roof panel Florida Product Approvals and notes was added.
13. Drawing A7.0.1 - DOOR/ROOM FINISH SCHEDULES AND DETAILS has been
REVISED. Hangar Epoxy Floor is deleted, new floor finish was added to Room Finish
Schedule and Legend for Hangar floor (03 35 00.0001 “TYP. CONCRETE FLOOR FINISH
APPLICATION, CURE-DESIFIER-HARDENER SEALER”). Glass types and Metal Panel
notes was edited in Room Finish legend.
14. Drawing A7.0.2 - WINDOW/LOUVER TYPES SCHEDULE AND DETAILS has been
REVISED. Detail Section Mark C1 & C2/A8.0.2 was added for clarity on Details A3 & A4.
Spandrel glass hatching pattern was added to Detail’s A1 & B1 for clarity.
15. Drawing A7.0.3 - DOOR AND LOUVER DETAILS has been REVISED. Metal wall panel
keynotes 13 34 19.1501 was edited.
16. Drawing A7.0.4 - DOOR AND STOREFRONT DETAILS has been REVISED. Metal wall
panel keynote 13 34 19.1501 was edited. Metal Panel Soffit keynote 13 34 19.2408 was
edited.
17. Drawing A7.0.5 - TRANSLUCENT PANEL DETAILS has been deleted. Translucent
Panel Assembly - (Plastic clearstory fixed windows) Details and keynote was deleted from
project. (Sheet A7.0.5 was issued after SLC Permit Review, with Addendum 3, and is now
NOT USED).
18. Drawing A8.0.1 - FOUNDATION DETAILS has been REVISED. Metal wall panel keynote
13 34 19.1501 was edited. Keynote for Epoxy Floor was deleted, new Keynote added for
Hangar floor 03 35 00.0001 “TYP. CONCRETE FLOOR FINISH APPLICATION, CURE-
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 10 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
DESIFIER-HARDENER SEALER”. New Keynote added 03 35 00.0002 “TYP.
CONCRETE JOINT FILLER”.
19. Drawing A8.0.2 - PEMB ROOF AND PLAN DETAILS has been REVISED. Metal wall
panel keynote 13 34 19.1501 was edited. Roof panel Keynote 13 34 19.2400 was edited.
Metal Panel Soffit keynote 13 34 19.2408 was edited. Roof Insulation Keynote 07 21
16.019A was added. Roof Insulation Keynotes 07 21 16.030 was edited.
IV. CHANGES TO DRAWINGS - PERMIT REVIEW COMMENTS
1. Drawing A0.0.1 - GENERALNOTES KEYNOTES has been REVISED. Title Block text
“Bid Documents” is changed to “Construction Documents”. (Note, this has been changed
on all sheets).
2. Drawing A0.0.3 - CODE ANALYSIS & LIFESAFETY FIRE PUMP BUILDING. has been
ADDED. New sheet was added in response to Permit Review comments by William
Durden on 12/31/2018.
3. Drawing A1.0.3 – FLOOR PLAN & ELEVATIONS FIRE PUMP BUILDING. has been
ADDED. New sheet was added in response to Permit Review comments by William
Durden on 12/31/2018.
4. Drawing A3.0.2 – RCP & ROOF PLAN FIRE PUMP BUILDING. has been ADDED. New
sheet was added in response to Permit Review comments by William Durden on
12/31/2018.
5. Drawing A5.0.2 - INTERIOR ELEVATIONS has been REVISED. ADA shower controls is
flipped, and dimensions added on Details C3 Women’s Shower RM 104 & D3 - Men’s
Shower RM 106 to meet Florida Accessibility Code. ADA fixture dimensions added to
Detail D2 for clarity.
6. Drawing A5.0.3 - INTERIOR ELEVATIONS has been REVISED. ADA fixture dimensions
added to Elevation - Single Accessible Restroom Detail for clarity.
7. Drawing A5.0.4 - INTERIOR ELEVATIONS has been REVISED. ADA fixture dimensions
added to ADA water cooler Detail C1 Hangar - Lockers North Elevation & D1 Office - MEP
Rooms West Elevation for clarity.
8. Drawing A6.0.7 – WALL SECTION FIRE PUMP BUILDING has been ADDED. New
sheet was added in response to Permit Review comments by William Durden on
12/31/2018.
St. Lucie County Florida
Permit No. 1812-0471
Treasure Coast International Airport
MRO Hangar with Associated Office/Shop Spaces
March 15, 2019
Page 11 of 11
Transforming Today’s Ideas into Tomorrow’s Reality
9. Drawing A7.0.3 - DOOR AND LOUVER DETAILS has been REVISED. Keynote 08 43
13.0002 “Typ. Pre-engineered 501 IR Aluminum out swing storefront door, L.M.I was
edited.
CHANGES TO STRUCTURAL DRAWINGS FOR THIS RESUBMITTAL
I. CHANGES TO DRAWINGS – ADDENDUM 2
1. Drawing S0.0.1 – GENERAL NOTES: “Design Loads”; Dead Loads; Item A. Metal Roof
Structure W/ Insulation 15 PSF note will be removed from the plans.
2. Drawing S0.0.2 – GENERAL NOTES: “Bid Alternate No. 1” Notes will be removed from
the plans.
3. Drawing S1.0.1 – FOUNDATION PLAN HANGAR AND OFFICES/SHOPS: Floating
Door System design basis note will be removed from the plans.
4. Drawing S1.0.3 – FOUNDATION PLAN PUMP HOUSE: Floating Door System design
basis note will be removed from the plans.
II. CHANGES TO DRAWINGS – ADDENDUM 3
1. Drawing S0.0.1 – GENERAL NOTES: “Pre-Engineered Metal Building” Note 5 was
added to include the drift limit.
2. Drawing S0.0.1 – GENERAL NOTES: “Design Loads” notes modified for clarification.