Manufacturer: TAMKO BUILDING PRODUCTS, INC. Issued October 19, 2017
P.O. Box 1404
Joplin, MO 64802
(417)624-6644
htto://www.tamko.com
Quality Assurance: UL LLC(QUA9625)
SCOPE
Category: Roofing
Subcategory: U n d e rl ay m e n is
Code Sections: 1507.1.1
Properties: Physical properties
PRODUCT DESCRIPTION
TAMKO®ASTM Slate ASTM D 6380, Class M,Type II underlayment constructed from organic felt saturated
Surfaced Roll Roofing with asphalt and coated on both sides with asphalt and surfaced with granules.
TAMKO®ASTM Tile ASTM D 6380,Class M,Type II underlayment constructed from an organic felt saturated
Underlayment with asphalt then coated on both sides with asphalt and surfaced with granules.
TAMKO®Master ASTM D 6380,Class S,Type IV underlayment constructed from an organic felt saturated
Smooth with asphalt then coated on both sides with asphalt and surfaced with a fine mineral. For
use in non-HVHZ only.
TAMKO®Moisture Self-adhered, ASTM D 1970, fiberglass reinforced, modified bitumen sheet membrane
Guard® with a mineral surfacing and a removable release film on the adhesive side and
removable selvedge release tape.
TAMKO®No.15 ASTM ASTM D 226,Type I underlayment constructed from a non-perforated organic felt that is
Asphalt Saturated saturated with asphalt.
Organic Felt
TAMKOO No.15 UL ASTM D 226,Type I underlayment constructed from a non-perforated organic felt that is
Asphalt Saturated saturated with asphalt.
Organic Felt
TAMKO®No.30 ASTM ASTM D 226,Type II underlayment constructed from a non-perforated organic felt that is
Asphalt Saturated saturated with asphalt.
Organic Felt
TAMKO®No.30 UL ASTM D 226,Type II underlayment constructed from a non-perforated organic felt that is
Asphalt Saturated saturated with asphalt.
Organic Felt
TAMKO®TW Metal and Self-adhered,flexible,ASTM D 1970 and TAS 103, rubberized asphalt sheet membrane
Tile Underlayment with a polymer film on the surface and a removable release film on the adhesive side.
TAMKO®TW Self-adhered, flexible, ASTM D 1970, rubberized asphalt sheet membrane with a
Underlayment polymer film on the surface and a removable release film on the adhesive side.
TBP14001.4 FL12328-R8 Page 1 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
CRK TAMKO BUILDING PRODCUTS,INC.
TAMKO Undedayments
TECHNICAL SERVICES, LLC
TAMKO®TAM-FELT Alternate to ASTM D 226,Type I and Type II underlayment constructed from a non-
perforated organic felt that is saturated with asphalt.
APPLICATION METHOD
Installation shall be in accordance with the published manufacturer's installation instructions, the FBC, and the
requirements below.
Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck shall be
checked for protrusion and corrected prior to underlayment application.
The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. Plywood deck
shall be installed in accordance with FBC requirements. Roof decks shall have no more than 1/8" gap at abutting
joints.
The minimum application temperature shall be 50°F except as follows:
a) The minimum application temperature of TAMKO®TW Metal and Tile Underlayment and TAMKO®TW
Underlayment shall be 40°F.
b) The minimum application temperature of TAMKO®Moisture Guard®shall be 35*F.
The minimum roof slope shall be in accordance with FBC requirements except as follows:
a) The minimum slope of TAMKO®ASTM Slate Surfaced Roll Roofing shall be 2:12.
Underlayments shall be exposed in accordance with the manufacturer's recommendations, but in no case shall
exposure exceed 30 days.
Exception: TAMKOO TW Metal and Tile Underlayment may be exposed for a maximum 90 days.
Self-adhering underlayments may be adhered to primed or unprimed plywood substrates in the non-HVHZ.
All roof coverings shall be mechanically fastened through the underlayment to the roof deck.
Allowable Roof Coverings:
Metal Roof Mineral Wood
Asphalt Panels and Surfaced Roll Shingles and Slate Clay and
Underlayment Shingles Shingles Roofing Shakes Shingles Concrete Tile
TAMKOO ASTM Slate Y' N N N N Y
Surfaced Roll Roofing
TAMKO®ASTM Tile N N N N N Y
Underlayment
TAMKO®Master Smooth Y' N N N N N
TAMKO®Moisture Guard® Y N N N N N
TAMKO®No.15 ASTM
Asphalt Saturated Organic Y Y Y Y2 N N
Felt
TAMKO®No.15 UL Asphalt Y Y Y YZ Y N
Saturated Organic Felt
TAMKO®No.30 ASTM
Asphalt Saturated Organic Y Y Y Y Y Y
Felt
TAMKO®No.30 UL Asphalt Y Y Y N Y N
Saturated Organic Felt
TAMKO®TW Metal and Tile Y Y N N N Y
Underlayment
TAMKO®TW Underlayment Y Y N N N N
TAMKO®TAM-FELT Y N N N N N
Notes: 1)Open valley applications per 1507.2.9.2
2)Wood shingles only
TBP14001.4 FL12328-R8 Page 2 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
TAMKO BUILDING PRODCUTS,INC.
CREEKTAMKO Underlayments
TECHNICAL SERVICES, LLC
ILIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Wind uplift resistance in not within scope of this evaluation.
3) Installation of the evaluated product shall comply with this report,the FBC,and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Contact the manufacturer when installing at temperatures below the minimum application temperature.
5) Unless otherwise stated,the minimum roof slope shall be in accordance with FBC requirements.
6) All underlayments shall be installed with the roll length parallel to the eave, starting at the eave, and lapped
in successive courses installed up the deck in a manner that effectively sheds water from the deck. End
laps shall be staggered between courses in accordance with the manufacturer's application instructions.
7) The underlayment may be used as described in other current FBC product approval documents.
8) The underlayment shall not be installed over existing roof coverings.
9) Contact the manufacturer regarding specific exposure limits for each underlayment.
10) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
REFERENCES
ED-till Report No. Standard Year.
PRI Construction Materials Technologies(TST6049) TAP-192-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies(TST6049) TAP-193-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies(TST6049) TAP-214-02-01 ASTM D 4869 2016
PRI Construction Materials Technologies(TST6049) TAP-215-02-01 ASTM D 226 2009
PRI Construction Materials Technologies(TST6049) TAP-216-02-03 ASTM D 6380 2003(2013)
PRI Construction Materials Technologies(TST6049) TAP-217-02-01REV ASTM D 6380 2003(2013)
PRI Construction Materials Technologies(TST6049) TAP-218-02-01 ASTM D 226 2009
PRI Construction Materials Technologies(TST6049) TAP-219-02-01 ASTM D 226 2009
PRI Construction Materials Technologies(TST6049) TAP-220-02-01 ASTM D 6380 2003(2013)
PRI Construction Materials Technologies(TST6049) TAP-222-02-01 ASTM D 4869 2016
PRI Construction Materials Technologies(TST6049) TAP-245-02-01 TAS 103 1995
ASTM D 4798 2011
PRI Construction Materials Technologies(TST6049) TAP-311-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies(TST6049) TAP-319-02-01.1 ACC 188 2012
PRI Construction Materials Technologies(TST6049) TAP-387-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies(TST6049) TAP-388-02-01 ASTM D 1970 2015a
UL LLC(TST9628) 13CA12269 ASTM D 226 2009
TBP14001.4 FI-12328-R8 Page 3 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODCUTS,INC.
TAMKO Underlayments
TECHNICAL SERVICES,LLC
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code,6th Edition(2017)as evidenced in the referenced documents submitted by the named manufacturer.
t11111111111114..
` iR�1p��',i
E N S /F,j'.�' 2017.10.19
No 74021 12:15:58
. .
Qj
_04'00'
0:• STATE OF
' '�•' 'c Q::•_.� Zachary R.Priest,P.E.
Florida
Organization No!0on No. 21
A E9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services,LLC does not have,nor will it acquire,a financial interest in any company manufacturing or distributing products under this
evaluation.
CREEK Technical Services,LLC is not owned,operated,or controlled by any company manufacturing or distributing products under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any company manufacturing or distributing products under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity Involved in the approval process of the product.
END OF REPORT
TBP14001.4 FL12328-R8 Page 4 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
Xt
_� Certificate of Authorization No. 29824
CREEK 17520 Edinburgh Dr
Tampa,FL 33647
TECHNICAL SERVICES, LLC
(813)480-3421
EVALUATION REPORT FLORIDA BUILDING CODE,6TM EDITION(2017)
Manufacturer: TAMKO BUILDING PRODUCTS Issued September 25, 2017
220 West 4th Street
Joplin, MO 64801
(417)624-6644
Manufacturing Plants: Joplin, MO
Phillipsburg, KS
Frederick, MD
Dallas,TX
Tuscaloosa,AL
Quality Assurance: UL LLC(QUA9625)
SCOPE
Category: Roofing
Subcategory: Asphalt Shingles
Code Sections: 1504.1.1, 1507.2.5, 1507.2.7.1, 1523.6.5.1
Properties: Physical properties,Wind Resistance,Wind Driven Rain
REFERENCES
Eath Report No. Standard Year
PRI Construction Materials Technologies(TST5878) TAP-043-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-051-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-054-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-114-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-117-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-130-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-131-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-165-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-280-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-303-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-307-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-314-02-01 Rev 2 TAS 100 1995
PRI Construction Materials Technologies(TST5878) TAP-315-02-01 ASTM D 6381 2008(2013)e1
PRI Construction Materials Technologies(TST5878) TAP-317-02-01 TAS 100 1995
UL LLC(TST9628) 02NK9507 ASTM D 3161 2016
UL LLC(TST9628) 04NK24366 ASTM D 3462 2010A
UL LLC(TST9628) 05NK28006 ASTM D 6381 2008(2013)e1
UL 2390
ASTM D 7158 2011
UL LLC(TST9628) 06NK03898 ASTM D 3161 2016
ASTM D 3462 2010A
UL LLC(TST9628) 08CA59132 ASTM D 3161 2016
UL LLC(TST9628) 09NK07896 ASTM D 3161 2016
ASTM D 3462 2010A
UL LLC(TST9628) 1 OCA50498 ASTM D 3462 2010A
UL LLC(TST9628) 10CA64882 ASTM D 3161 2016
UL LLC(TST9628) 11NK14014 ASTM D 3161 2016
ASTM D 3462 2010A
UL LLC(TST9628) 12CA24551 ASTM D 3161 2016
UL LLC(TST9628) 4786110543 ASTM D 6381 2008(2013)e1
UL LLC(TST9628) 4787043752 ASTM D 3161 2016
UL LLC(TST9628) 4787148748 ASTM D 7158 2011
ASTM D 3161 2016
ASTM D 3462 2010A
CREEK Technical Services LLC(ANE11669) TBP15001.3 Calculations 2017
TBP15001.4 FL18355-R4 Pagel of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
PRODUCT DESCRIPTION
Elite Glass-Seal® 12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
(Frederick,Joplin& asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
Tuscaloosa) ceramic granules complying with ASTM D 3462.
Glass-Seal 12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
(Frederick& asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
Tuscaloosa) ceramic granules complying with ASTM D 3462.
Glass-Seal 12-1/4"x 36", ASTM D 7158, Class H self-sealing, 3-tab asphalt shingle with fiberglass
(Joplin) mat coated on both sides with asphalt and surfaced with ceramic granules complying
with ASTM D 3462. Shingles shall be used in the non-HVHZ only.
Heritage® 13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas,Frederick, reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Joplin, Phillipsburg& complying with ASTM D 3462.
Tuscaloosa)
Heritage®Premium 13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas, Frederick, reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Phillipsburg& complying with ASTM D 3462.
Tuscaloosa)
Heritage®Premium 12" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Frederick) laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage®Vintage® 17-1/2"x 40",ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Phillipsburg) laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage®Woodgate 13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas&Frederick) reinforced, laminated architectural asphalt shingle surfaced with mineral granules
complying with ASTM D 3462.
Heritage®Woodgate 12" x 36-3/8", ASTM D 3161, Class F fiberglass reinforced, laminated architectural
(Frederick) asphalt shingle surfaced with mineral granules complying with ASTM D 3462. Shingles
shall be used in the non-HVHZ only.
Hip and Ridge Shingles 12-1/4" x 12", ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt
(Frederick&Joplin) shingle surfaced with mineral granules complying with ASTM D 3462.
Vintage®Hip and Ridge 12" x 12", ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt shingle
(Phillipsburg) surfaced with mineral granules complying with ASTM D 3462.
TBP15001.4 FL18355-R4 Page 2 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKOBUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
INSTALLATION
Elite Glass-Seal® Basic Wind Speed (Vwt): Max. 194 mph
(Frederick,Joplin& Basic Wind Speed (Va,d): Max. 150 mph
Tuscaloosa) Deck(HVHZ): In accordance with FBC requirements;
& Solidly sheathed min. 19/32 in. plywood or wood plank for
Glass-Seal new construction; Min. 15/32 in. plywood existing
(Frederick,Joplin (Non- construction.
HVHZ)&Tuscaloosa) Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min.7/16 in. OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation(HVHZ): Installed with 5-1/8 inch exposure in accordance with RAS
115 and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ): Installed with 5-1/8-inch exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
NAILS
w
Nailing --- ---------------------------- ----------------------- 6-7ff
AreaD!----------------------------- --- -
5-118"
Butt Edge
Figure 1. Elite Glass-Seal&Glass-Seal
4 Nail Pattern(Non-HVHZ only)
NAILS
�1n 1n
Nailing --. ------------------------------ --------------- ----- -----------------.----------- -- 6-7/811
11
Area --------.......------------------------------------—---------------------------------------------
5-118"
Butt Edge
Figure 2. Elite Glass-Seal&Glass-Seal
6 Nail Pattern
TBP15001.4 FL18355-R4 Page 3 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Heritage® Basic Wind Speed (Vwt): Max. 194 mph
(Dallas, Frederick,Joplin, Basic Wind Speed(Vasd): Max. 150 mph
Phillipsburg&Tuscaloosa) Deck(HVHZ): In accordance with FBC requirements;
& Solidly sheathed min. 19/32 in. plywood or wood plank for
Heritage®Premium new construction; Min. 15/32 in. plywood existing
(Dallas, Frederick construction.
Phillipsburg&Tuscaloosa) Deck(Non-HVHZ): In accordance with FBC requirements;
& Solidly sheathed min. 15/32 in. plywood or wood plank for
Heritage®Woodgate new construction; Min.7/16 in.OSB existing construction.
(Dallas&Frederick) Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation(HVHZ): Installed with 5-5/8 in. exposure in accordance with RAS
115 and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ): Installed with 5-5/8 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
FASTENERS NAIL ZON E
COMMON
BOND
6-1/8" EXPOSURE 5-5/8"
1" �-- 12-11211--►�- 12-3/8" 12-112'"► �-1"
Figure 3. Heritage@, Heritage@ Premium, and Heritage@ Woodgate (Dallas)
4 Nail Pattern(non-HVHZ only)
FASTENERS NAIL ZONE
/COMMON
BOND
6-1/8" EXPOSURE 5-5/8"
i=-►I �7-1/2'�f-7-1/2"� 7-3/8"-►�f-7-112"-►h-7-1/2"� �--1"
Figure 4. Heritage@&Heritage@ Premium
6 Nail Pattern
TBP15001.4 FL18355-R4 Page 4 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
CREAK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
NAIL ZONEI
ASTENERS COMMON BOND
AM. EXPOSURE 5 518"
VL4 �7-1/2'+7-PI/2'41-0-7,V8+-112+7-1/22A �-1"
Figure 5. Heritage@ Woodgate
6 Nail Pattern
H1111 -12-1/2" ;.--12-1/2" >!1'ii"I�-
i i i i i i
Common Bond
FASTENERS
i ? I
ZZ
I?Q Ir
LOW
< 39-3/8"
Figure 6. Heritage@, Heritage@ Premium, & Heritage@ Woodgate
Alternate 6 Nail Pattern
PAINT
LINE
6-1l8" EDGE-OF
COMMON.
BOND
EXPOSURE
5=518
ACCEPTABLE
FASTENER LOCATION
DO NOT FASTEN
ALONG EDGE OF
------ --- --- COMMON BOND
PREFERRED
FASTENER
LOCATION
Figure 7. Heritage@(Tuscaloosa)
Expanded Nail Zone
Nail patterns from Figures 3, 4,and 6 may be placed in the nail zone as described above
TBP15001.4 FL18355-R4 Page 5 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Heritage®Premium Basic Wind Speed (Vit): Max. 194 mph
(Frederick) Basic Wind Speed (Vasa): Max. 150 mph
Deck(HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min.7/16 in. OSB existing construction.
Undedayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12. .
Installation(HVHZ): Installed with 5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ): Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
NAIL ZONE/
FASTENERS COMMON BOND
5112" EXPOSURE 5"
1"—+� �— 11"—►�— 12" —►�-11"—� �--1"
Figure 8. Heritage@ Premium (Frederick)
4 Nail Pattern (non-HVHZ only)
NAIL ZONE/
FASTENERS COMMON BOND
51/2 EXPOSURE 5"
u� I—gihii 9u_�'n 91/2" IL-1
I� Figure 9. Heritage-I@_'Premium(Frederick)
6 Nail Pattern
T131315001.4 FL18355-R4 Page 6 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
GREEK TAMKO BUILDING PRODUCTS
s c Asphalt Shingles
TECHNICAL SERVICES, LLC
Heritage®Woodgate Basic Wind Speed (Vwt): Max. 194 mph
(Frederick) Basic Wind Speed (Vnd): Max. 150 mph
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction;Min.7/16 in.OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation (Non-HVHZ): Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
NAIL ZONE/
FASTENERS WT
COMMON BOND
5-1/2° EXPOSURE Y
1'L 11" - -12-318"-+- 11" -1"
Figure 10. Heritage®Woodgate(Frederick)
4 Nail Pattern (non-HVHZ only)
NAIL ZON E/
FASTENERS COMMON BOND
t VT
5.112" EXPOSURE 5"
Figure 11. Heritage®Woodgate(Frederick)
6 Nail Pattern
TBP15001.4 FL18355-R4 Page 7 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
TAMKO BUILDING PRODUCTS
CREEK Asphalt Shingles
TECHNICAL SERVICES, LLC
Heritage®Vintage® Basic Wind Speed (Vwt): Max. 194 mph
(Phillipsburg) Basic Wind Speed (Vasd): Max. 150 mph
Deck(HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min.7/16 in.OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation(HVHZ): Installed with 5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ): Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"5 Nail
Pattem"or"6 Nail Pattem"detailed below.
40
Ecposvre
Z Notch
Fast-enes
- - — — — — — - - — — - - PJail
one
17-112^
s�
i pwue
47:0 41/4• 9-1/4•—�-41h1
.1 -1
�1a�4•� �+—la�nr--�
Figure 12. Heritage®Vintage®
5 Nail Pattern(non-HVHZ only)
r EXP=M
Notdf
ware
hers B41
— — — Zone
TL 17-1/Z'
�nsa�
Wle' A71i 7-]/i��73A1'
Figure 13. Heritage®Vintage®
6 Nall Pattern
TBP15001.4 FL18355-R4 Page 8 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
10MC R�E K TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Hip&Ridge Basic Wind Speed (Vw): Max. 194 mph
(Frederick&Joplin) Basic Wind Speed (Vasd): Max. 150 mph
Deck(HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min.7/16 in. OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements.
Installation: Installed with 5-1/8 inch exposure in accordance with the
FBC and manufacturer's published installation instructions.
The direction of the exposed end shall be away from the
prevailing wind.
Direction of prevailing wind
Star h5-1/8" exposure
Start
Figure 1 here 5-1/8"exposure
astener Fastener
Figure 2 Figure 3
Figure 14. Hip &Ridge(Frederick&Joplin)
TBP15001.4 FL18355-R4 Page 9 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
,
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
Vintage®Hip&Ridge Basic Wind Speed (Vwt): ' Max. 194 mph
(Phillipsburg) Basic Wind Speed (Vasa): Max. 150 mph
Deck(HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
Deck(Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min.7/16 in. OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min.slope: 2:12 and in accordance with FBC requirements.
Installation: Installed with 5 inch exposure in accordance with the FBC
and manufacturer's published installation instructions. The
direction of the exposed end shall be away from the
prevailing wind.
Direction of prevailing wind
Start 5" exposure
here "�
Fn-]'I
<Mheman
Figure 1 5" exposure
-• Fastener
Figure
,•�I Fastener r' .
-1/2„
Figure 2 Figure 3
Figure 15. Vintage®Hip&Ridge(Phillipsburg)
TBP15001.4 FL18355-R4 Page 10 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
C R E K TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) The roof deck and the roof deck attachment shall be designed by others to meet the minimum design loads
established for components and cladding and in accordance with FBC requirements.
3) The mean roof height shall be restricted to a maximum 33 ft in the HVHZ.
4) Classification to ASTM D 7158 applies to exposure B&C with a building mean roof height of 60-ft or less.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) Shingles shall be installed starting at the eave in horizontal layers such that the laps shed water from the
deck.
7) Installation of the evaluated products shall comply with this report, the FBC, and the manufacturer's
published application instructions. Where discrepancies exist between these sources, the more restrictive
and code compliant detail shall prevail.
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code,6Edition(2017)as evidenced in the referenced documents submitted by the named manufacturer.
. R
%��; ENSF•'Fs� 2017.09.25
No 74021
- *: — 11 .31 .41
STATE OF -04'00'
:?�:• ��
�i4% •:c4 O R 1 O P:•'�c��:� Zachary R.Priest, P.E.
S ........ �` Florida Registration No.74021
�
e�i,S�ONA; Organization No.ANE11669
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services,LLC does not have,nor will it acquire,a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services,LLC is not owned,operated,or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E.does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
TBP15001.4 FI-18355-R4 Page 11 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.