Loading...
HomeMy WebLinkAboutWind load design pressure calcs I , -`moi' ENGINEERING EXPRESS Order(Ref)#: 54345 (43704-4328240741) Project Details: ROLLAN CONDO DOOR REPLACEMENT Contractor: J&G CARPENTRY, INC. 9490 S. OCEAN DRIVE, UNIT 315A 7030 S.W. 16TH COURT PEMBROKE JENSEN BEACH, FL PINES, FL Subject: Wind Load Design Pressure Calculations (Components &Cladding) Site Information General Calculation Building Classification: enclosed Directionality Factor (Kd): 0.85 Wind Speed (Volt): 170 mph Gust-Effect Factor(G): 0.85 Exposure Category: d Internal Pressure ±0.18 Roof Type: monoslope Coefficient (GCp;),. Roof Slope (0): 1.2 deg Topographical Factor (K,t): 1.0 Mean Roof Height (h): 88.0 ft Velocity Pressure Exposure Min. Building Dimension (L): 53.0 ft Coefficient(Kh): 1.40 Parapet>— 3 feet? No Velocity Pressure (qh): 88.13 psf End Zone (a): 5.3 ft ASD Method: P= 0.6w' Mark Qty 'Eley (ft) Size: W x H (in) Zone Shutter?Area (ft) K,.(Kh) qz (9h) GCp+ GCp_ Pressures (psf) 1 (1) 26.0 36.0 x 80.0 4 No 20.0 1.13 71.29 0.90 -0.90 +48.0/—57.1 CZ k_ictvu 9� NOTES:Design is in accordance with ASCE 7-10(ASD method)and the Florida Building Code Sixth Edition(20tZ).Aesplts 8232 O - are not valid for use unless approved via original signature and raised engineer seal of a PE from EngineeringExpuss. Valid?ply ly A aped/Stamped Results are based on contractor-supplied data and shall be field verified by others prior to use.Selection&in5affoe idn of Engine Sear products shall be approved using these dimensions and pressures as verified by others. O -� SrArF of ss ORIDP. Note:For openings to be properly rated in Zone 4,no part of the opening shall be within 5.3 feet of any building corfy. p, a 120,19 This engineer has not field visited this location and if this cannot be clearly identified by others,the opening shall be re' ��'ondmfiditisto, P.E. a s /r y evaluated prior to installation of any fenestration. All other information provided above including mean roof height, � building minimum dimensions,opening sizes,&other supporting data was provided by others. For definitions of the PE8 28 above terms,visit EngineeringExpress.com/Wiki" #9885 I 160 SW 12TH AVENUE,SUITE 106, DEERFIELD BEACH,FLORIDA 33442 54345 (43704-4328240741) PHONE:(954)354-0660—FAX: (954)354-0443 AutoPrint ENGINEERINGEXPRESS.COM PAGE 1 OF 1