HomeMy WebLinkAboutProduct Approval -�- wrightsoft� Project Summary RECEIVED Da
Entire House B
QUICK CALCS, INC: SEP 11 2019
317 ST.LUCIE LANE,FORT PIERCE,FL34946 Phone:772466.6799 Email:QUICKCALCS@,AOL.COM
For. MARTIN RESIDENCE
8233 MAIDENCANE PL.,PORT ST.LUCIE, h I
Notes:
D- •n_Information
Weather: Fort Pierce,FL,US
Winter Design Conditions 'Summer Design Conditions
Outside db 42 OF Outside db 90 OF
Inside db 70 OF Inside db 75 OF
Design TD 28 OF Design TD 15 OF
Daily range M
Relative humidity 50 %
Moisture difference 61 grAb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 6336 Btuh Structure 8810 Btuh
Ducts 1260 Btuh Ducts 1726 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 7596 Btuh Use manufacturers data n
Ratelsv in multiplier 0.95
Infiltration Equipmenq sensible load 10010 Btuh,
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 9884 Bluh
Ducts 477 Btuh
Central vent(0 cfm) 0 Btuh
Heating Cooling (none)
Area(ftp 44 I 44'I Equipment latent load 2362 Btuh
Volume(ft) 3969 3969
Air thangges/hour 0.61 0.32 Equipment Total Load(Sen+Lat) 12371 Btuh
Equiv AVF(cfm) 40, 21 Req.total capacity at 0.70 SHR 1.2 ton
Heating Equipment Summary Cooling Equipment Summary
Make MITSUBISHI Make MITSUBISHI
Trade Trade
Model MUZ-HM15NA U1 Cond MUZ-HM15NA-U1
AHRI ref 201754434 Coil MSZ-HM15NArU1
AHRI ref 201754434
Efficiency 10 HSPF Efficiency 12.0 EER,18 SEER
Heating input Sensible cooling 9800 Btuh
Heating output 16000 Btuh @ 47°F Latent cooling 4200 Btuh
Temperature rise 28 OF Total cooling 14000 Btuh
Actual airflow 513 cfirn Actual airflow 513 tern
Airflowfactor 0.068 cfm/Btuh Airflowfactor 0.049 cfmBtuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.82
Capacity balance point=25 OF
Backup:
Input=2 kW, Output=7221 Btuh,100 AFUE
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
Al -rP-wr%ghtsoft- 2019-Aug-26 06:2433
Right Srite9)Uriversal 2019 19.0.07 RSU08101 Page 1
_Doamerts\WrlghtwftWACVNITCHEMRESIDENCE.rtp Calc=MJ8 FrortDoor faoes:NE
-�-wrightsoft Right-M Worksheet Job:
Entire House Date:
sy:
QUICK CALCS,INC.
317 ST.LUCIE LANE,FORT PIERCE,FL34946 Phone:772466.6799 Email:QUICKCALCS AOL.COM
1 Room name Entire House GARAGE
2 Expos_dvyall 46.0 It 46.0 ft
3 Room height 9.0'ft 9.0 ft heaUmol
4 Room dimensions 21.0 x 21.0 It
5 Room area 441.0 1$ 441.0 ft'
Ty Construction U-value Or HTM Area (ftp Load Area (ttF) Load
number (BtuhAfL'F) (Btuhfin or perimeter (fl) (Btuh) or perimeter (tt) (Btuh)
Heat Cod Gross N/P/S Heat Cool Gross N/P/S Heat Cool
�` m u 143{ItO H?F00 19 " x'188 77 30$ yI66 vlgg 2° ._'/ 30$ 166
6 x.. t"$ .. H sax*`+. L .,3 x$tj -a�°f$.a 5.;
zs Jilt—e .x .rs i .06� lt@ f68Q 7:x390 117 s 117 1882�.:_.u,<17,79 �36
W 13A-4ocs 0.143 se 4 00 219 36 36 144 79 36 36 144 79
13P�4oes z � 41$3 tw 4AO 219 189 Ni62 M X649 X354 189 3 1152 648 a 35d
11 1Arcto[rrz 270 a CtW 3558 7{F43 s 6 0 21 F 423x6 r R 213 : x423.
s �
tFt 2M" W21 ti
C 16B-30ad 0.032 0 90 1.60 441 441 395 706 441 441 395 706
22A tpk .k r2 t ,Nd 989 s T/ ., x 402 u.1274 � ,0. ..r � X46
0117. xzr u
^7 - f z "o ,M
'�'.�,z.`_.xi..?�k.'�;:s,> m......'aer�a:?�,.,Sa•.r �) --� k w�<.� � eG�..,:;:....su:.,Mb�3deL. !SE
tv : „ � 'b"k .r r E.S >.3 ixa
w.,.i-•; v„. .as....ri...r:4c:..:;.,. _ac.,. ...... .. .:.::.... :.x:k
k ..rL-w4 11-11'/, 14 : rr xM
2r,
I'll
""'»`�="` ".,�^'.,.,,.'.*-.-^ '>."'t a' --<. t- » _r
:tea.r-:.b., k....> � .�,.._,. _ a a:�,..� i.. ...
�z:,z `Y+ .owA- 'c r'.`-'.`, s flP'--^zs- t
:. �a`�..z.......ls...> ,,�4�.t��¢z.,,�..�:=>..a.,a..�.,.» s....,.�z-a.,.i.,-.. ..&_erN,x.,.e..".a?.,i
n;x.',;:. .._.
2,122 ._.c.�>; +�,� ...... .,... MK3t .'t.�.+a.. _�t^�,S,i.,._<> ...:k�
E.���.,:a�. M. .,.uar°.s.sxM -` .x,:r,.. ..w,..>5101 , �s.S,.. �.a... ti-
E;a.'S:�i^� `*ts` r C y,. `.'_' �,.�-.- _'' i 7 is '.r"��'�.`ate" lr�.�-l. z✓^ ..
_.�..z.Y. ,:-,.d.�j>$..� �.:�"�.,=�:�-sx.�.�.,.»�c•,;:�u ,,a�.:1,....�:�u>,>a 't,,cr.� += ?.-�3;:,.....�.�._z.��i*>..��...,..ag<,�>.>�5,_:r.
�-. Yu-MIT,AP - 21,1 z.* MM fi-.oe� � .4G 0.. rv--,. ,N, 111E
xr";:.,.. 111:_
"m" .� ...� ""r, `?' '. "� ""s "'F ;
a` ",!...r .�c"�,usr.�x._a,:k..,i A>:5s <n..,.s.n�.a.:a>._;.!c...m� _...,": .,,., ..u,_._�. fs .:. ,,su->.::z<._. _,_.,Yfz�r-
• ��:-ti�4R"",fit��'�"�.. � �- '.�x,� ` ��-���� '�.�;:�,.� .�.�s.-. `"�w._��,z. ..�<.... ._:.�'�' 7<,�.:;Nk`�.,'3a.�.�.��� ...t`�,?�.�'�.� -;c¢;., 4,�:
MX9 MnMMYt �" Aa .� 1 u15:11 z
n,^ny C'z <. -�.` ...., z.,r &2.: : rr" t 2"` yp
�.�.,r-�-'_..�,�».�:3tm__..._.y:a:=sx,,,,a.Fsa�<.�'r;k�t�.._ ., �....,:.:��_ _r��.-�<�r,.. ._-.:ami
.°�.,.2�.mi"r„"�,.ti:,,.. <a :s _,,... ,s ,�„ µ -` ,�` n.,,3i,: mm..,=fir..". ?' .s M Esq._
1w'- s� `s ..a,✓xt3 '"' >; ' ,M>r s E. _ a> ":. ,, ` , as-21 �,,.,.t--1V r
"";,'..k q =:.i""„,s-- ::m i S„''``�' i a,-»;. :. x ' - JT-�`, k., I;,s
ill
Y#s...sb.,�1�"uz,R�.r�.t&<...a . S.-.i�l=�s,.� "�...aw.°' ,.. .a.?a;...aw. zz :Lia.!�s..:w�*s._rr.G..vw....�c -.:.�!....-:,fi:t'-S¢ae t >�4;s.�'ic�.�b<�.:.;_"�,.-�. 3,+'.a
6 c)AED exausion 184 184
Envelopeloss/gain 5094 3911 5094 3911
12 a) Infittration 1242 349 1242 349
b) Room ventilation 0 0 0 0
13 Infernal gains: Oecvpants@ 230 5 1150 5 1150
Appliances(other 3400 3400
Subtotaloines(BW3) 6336 8810 6336 8810
Less exernal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 00 0
14 Subtotal 6336 8810 6336 8810
15 Dudloads 120%1 209/6 1260 1726 20% 20%1 1260 1726
Total mom load 7596 10536 7596 10536
Air required(dm) 513 513 513 513
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-1"{f wrlghtsoYt^
2019-Aug-26 06:24:33
Riga Suite®Uriversal 2019 19.0.07 RSU08101 Page 1
.-Doameris\WrighfsoftWAGUITCHEMRESIDENCE.rup Calc=MJ8 Front Door toes:NE
FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: MARTIN RESIDENCE Builder Name:
Street: 8233 MAIDENCANE PL. Permit Office: ST:LUCIE COUNTY
City,State,Zip: PORT ST.LUCIE,FL, Permit Number:
Owner: Jurisdiction: ST.LUCIE COUNTY
Design Location: FL,Fort Pierce County: St.Lucie(Florida Climate Zone 2)
1.'New construction or existing Addition 9. Wall Types(368.0 sqft.) - Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Ext Insul,Exterior R=4.1 368.00 ft2
b.N/A R= ft2
3. Number of units,if multiple family 1 c.N/A2
R= ft
4. Number of Bedrooms(Bedrms In Addition) 0(0) d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types (441.0 sgft.) Insulation Area
a.Under Attic(Vented) R=30.0 441.00 ft2
6. Conditioned floor area above grade(ft2) 441 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c.N/A R= ft2
11.Ducts R ft2
7. Windows(6.0 sgft.) Description Area
a. U-Factor. Sgl,U=0.79 .6.00 ft2
SHGC: SHGC=0.50
b. U-Factor. N/A ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: a.Central Unit 14.0 SEER:18.00
c. U-Factor: N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor. N/A ft2 a.Electric Heat Pump 14.0 HSPF:10.00
SHGC:
Area Weighted Average Overhang Depth: 2.000 ft.
Area Weighted Average SHGC: 0.500 14.Hot water systems-None required
8. Floor a. Cap:N/A Types (441.0 sgft.) Insulation Area EF:-1.75417E035
a.Slab-On-Grade Edge Insulation R=0.0 441.00 ft2 b. Conservation features
b.N/A R= ft2
c.N/A R= ft2 15.Credits Pstat
Glass/Floor Area: 0.014 Total Proposed Modified Loads: 10.47 PASS c
Total Baseline Loads: 13.11 ASS
I hereby certify that the plans and specifications covered by Review of the plans and
this calculation are in compliance with the Florida Energy specifications covered by this = O
Code. calculation indicates compliance
with the Florida Energy Code. tr
PREPARED BY: 0 A_ eola Before construction is completed f ,i
DATE: _- 8-26-19 this building will be inspected for
compliance with Section 553.908 :
hereby certify that this building, as designed,is in compliance Florida Statutes.
with the Florida Energy Code.
OWNER/AGENT: BUILDING OFFICIAL:
DATE: DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 7.00 ACH50(R402.4.1.2).
8/26/2019 6:29 AM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 4
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title: MARTIN RESIDENCE Bedrooms: 0 Address Type: Street Address
Building Type: User Conditioned Area; 441 Lot#
Owner Name: .Total Stories: 1 Block/Subdivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: Rotate Angle: 0 Street: 8233 MAIDENCANE PL
Permit Office: ST.LUCIE COUNTY Cross Ventilation: No County: St.Lucie
Jurisdiction: ST.LUCIE COUNTY Whole House Fan: No City,State,Zip: PORT ST.LUCIE,
Family Type: Single-family FL,
New/Existing: Addition
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
V Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Fort Pierce FL VERO_BEACH_MUNI 39 90 7b 75 299 62 Low
BLOCKS
Number Name Area Volume
1 Entire House 441 3528
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 GAR 441 3528 No 0 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio GAR 46 ft 0 441 ft2 0 1 0
ROOF
/ Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Ban- Absor. Tested Tested Insul. (deg)
1 Hip Composition shingles 478 ft2 0 ftZ Medium N 0.6 No 0.9 No 0 22.6
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area -RBS IRCC
1 Full attic Vented 300 441 ft2 N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) GAR 30 Blown 441 ft2 0.1 Wood
8/26/2019 6:29 AM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 2 of 4
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
_ 1 NE Exterior Concrete Block-Ext Insul GAR 4.1 21 0 8 0 168.0 ftz 0 0 0.6 0
_2 SE Exterior Concrete Block-Ext Insul GAR 4.1 4 0 8 0 32.0 ftZ 0 0 0.6 0
3 . NW Exterior Concrete Block-Ext Insul GAR 4.1 21 0 8 0 168.0 ftZ 0 0 0.6 0
DOORS
# Omt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 NE Insulated GAR None .6 16 7 112 ftZ
2 NW _Insulated GAR None .39 3 7 21 ft'
WINDOWS
Orientation shown is the entered,Proposed orientation.
Wall Overhang
1/ # Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 NW 3 Metal Single(Clear) Yes 0.79 - 0.5 N 6.0 ft' 2 ft 0 in 1 ft 4 in None None
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000356 411.6 22.6 42.5 .1233 7
HEATING SYSTEM
# System Type Subtype Efficiency Capacity Block Ducts
1 Electric Heat Pump/Suppleme Split HSPF:10 14 kBtu/hr 1 Ductless
COOLING SYSTEM
# System Type - Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central UniUEbsting/confirme Split SEER: 18 14 kBtu/hr cfm 0.7 1 Ductless
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
ft'
8/26/2019 6:29 AM EnergyGauge®USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 3 of 4
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
' Coolin Jan Feb MMa A r May Jun Jul X Auge Oct Nov Dec
HeatinHJan Feb Mar f Apr I
May Jun Jul 4 AuSep E Oct MNov Dec
VentingJan Feb Mar [X Apr may Jun Jul I Aug Se [X Oct Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10. 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 '68 68 68 66 66
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8 lbs/s .ft. 0 ftz Oft 0.3 GAR
8/26/2019 6:29 AM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 4 of 4'
2017 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: MARTIN RESIDENCE Builder Name:
Street: 8233 MAIDENCANE PL. Permit Office: ST.LUCIE COUNTY
City,State,Zip: PORT ST.LUCIE,FL, Permit Number: v
Owner. Jurisdiction: ST.LUCIE COUNTY W
Design Location: FL,Fort Pierce v
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material.
requirements Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit
Ceiling/attic the insulation and an gaps in the air barrier shall be sealed.
Y 9 P shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity
sealed. with a material having a thermal resistance of R-3
Knee walls shall be sealed. per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows,skylights The space between window/doorjambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including insulation. maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity insulation
and cantilevered shall be permitted to be in contact with the top side
floors) of sheathing,or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation
a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace
Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to
exterior or unconditioned s ace'shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
Narrow cavities cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spa s.
Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building
shall be sealed to the drywall. thermal envelope shall be air tight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
Pxtpnd behind 01ping and wiring,
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall
on exterior wall tubs shall separate them from the showers and tubs. be insulated.
Electrical/phone box or The air barrier shall be installed behind electrical or communication
exterior walls boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub-floor or drywall.
Concealed When required to be sealed,concealed fire sprinklers shall only be
sprinklers sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
I between cover plates and walls or cell
a.In addition,inspection of log walls shall be in accordance with the provisions of ICC-400.
8/26/2019 6:29 AM EnergyGauge®USA 6.0.02(Rev.1)-FlaRes2017 FBC 6th Edition(2017) Compliant Software Page 1 of 1
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX*= 80
The lower the Energy Performance Index, the more efficient the home.
1. New home or, addition 1. Addition 12. Ducts, location&insulation level
a) Supply ducts R
2. Single-family or multiple-family 2. Single-family b) Return ducts R
c)AHU location
3. No. of units(if multiple-family) 3. 1
4. Number of bedrooms 4. 0 13. Cooling system: Capacity14.0
a) Split system SEER - 18.0
.5. Is this a worst case?(yes/no) 5. No b) Single package SEER
c) Ground/water source SEER/COP
6. Conditioned floor area(sq.ft.) 6. 441 d) Room unit/PTAC EER
e)Other
7.Windows,type and area
a)U-factor:(weighted average) 7a. 0.790
b)Solar Heat Gain Coefficient(SHGC) 7b. 0.500 14. Heating system: Capacity14.0
c)Area 7c. 6.0 a).Split system heat pump HSPF 10.0
b)Single package heat pump HSPF
8. Skylights c) Electric resistance COP
a)U-factor:(weighted average) 8a. NA d) Gas furnace, natural gas AFUE
b)Solar Heat Gain Coefficient(SHGC) 8b. NA e)Gas furnace, LPG AFUE
f)Other
9. Floor type, insulation level:
a)Slab-on-grade(R-value) 9a. 0.0
b)Wood, raised(R-value) 9b. 15. Water heating system
c) Concrete, raised(R-value) 9c. a) Electric resistance EF
b)Gas fired, natural gas EF
10. Wall type and insulation: c)Gas fired, LPG EF
A. Exterior: d)Solar system with tank EF
1. Wood frame(Insulation R-value) 10A1. e) Dedicated heat pump with tank EF
2. Masonry(Insulation R-value) 10A2. 4.1 f)Heat recovery unit HeatRec%
B.Adjacent: g)Other
1.Wood frame(Insulation R-value) 1061.
2. Masonry(Insulation R-value) 1062.
16. HVAC credits claimed (Performance Method)
11. Ceiling type and insulation level a)Ceiling fans
a) Under attic . 11a. 30.0 b)Cross ventilation No
b) Single assembly 11b. c)Whole house fan No
c)Knee walls/skylight walls 11c. d)Multizone cooling credit
d) Radiant barrier installed 11d. No e)Multizone heating credit
f) Programmable thermostat Yes
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
Builder Signature: Date:
Address of New Home: 8233 MAIDENCANE PL. City/FL Zip: PORT ST. LUCIE, FL
8/26/2019 6:29:47 AM EnergyGauge®USA 6.0.03(Rev.1)-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1