Product Approval
Public User -
Product Approval Menu>Application Detail
t a FL# FL1654-1124
fi r
Application Type Revision
i t
Ens Code Version 2017
Application Status Approved
Comments
z t Archived
4
Product Manufacturer POLYGLASS USA
Address/Phone/Email 1111 W.Newport Center Drive
I }, Deerfield Beach, FL 33442
K954)233-1330 Ext242
malpert@polyglass.com
E ' Authorized Signature Maury Alpert
aF mal ert@poi lass.com
P Y9
" Technical Representative Maury Alpert
r 4 Address/Phone/Email 1111 W. Newport Center Drive
Deerfield Beach, FL 33442
� )429-8610
MAIpert@polyglass.com
x�At �
�. - Quality Assurance Representative G
c Address/Phone/Email �f
Category Roofing
Subcategory Modified Bitumen Roof Systteen-
�� f •�� � _
Compliance Method Evaluation Report fro r `FIQ eXLW, t � a sad Florida ;
x s Professional'Engineer �dJJ ``���
w
Evaluation,Report-� cgpkRUQd®CC
Florida Engineer or Architect Name who developed Robert Nieminen
4 the Evaluation Report
t {•� f Florida License PE,59166
Quality Assurance Entity - UC LLC
h k }' Quality Assurance Contract Expiration Date 09/13/2021
Validated By John W. Knezevich, PE
r01 Validation Checklist-Hardcopy Received
3
Certificate of Independence FL1654 R24_COI 2019 01 COI_NIEMINEN.pd
Referenced Standard and Year(of Standard) Standard Year
ASTM D6162 2008 sty �
txy ASTM D6163 2008
° ASTM D6164 2011
ASTM D6222 2011
https;//www.floridabuilding.org/pr/pr_app_dti,aspx?param=wGEV...u2w%2bnFgUPv2pw6pKxAh9%2fJTtiNgcLHGglZFglMqIA%3d%3d 8/2/19;7:35 PM
Page 1 of 2
OMEMO etc.
SISTANC E TABLE pECKa
L'!�t�]ENDIX ATTACHM��ENTSFO�WINDLIPLIFtIRE
"ik � APPLI CRIPTION
IA Wood New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover
IB Wood New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 5-9
IC Wood New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 10-11
ID Wood New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 12
IE Wood New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 12-14
IF Wood New,Reroof(Tear-Off)or Recover D Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 15-17
1G Wood New or Reroof(Tear-Off) E Non-Insulated,Mech.Attached Base Sheet(nails),Bonded Roof Cover 18-21
1H Wood New,Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet(screws&plates),Bonded Roof Cover 21-25
11 Wood New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 26
2A Steel or Structural concrete New,Reroof(Tear-Off)or Recover B Mech,Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 27-29
2B Steel or Structural concrete New,Reroof(Tear-Off)or Recover C Mech,Attached Insulation,Bonded Roof Cover 30-34
2C Steel or Structural concrete New,Reroof(Tear-Off)or Recover D Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 35-37
3A Structural concrete New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 38-46
3B Structural concrete New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 46
4A Lightweight concrete New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 47-49
4B Lightweight concrete New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 50
4C Lightweight concrete New or Reroof-(Tear-Off) E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 51=53
5A Cementitious wood fiber New or Reroof(Tear-Off) A-1 Bonded insulation,Bonded Roof Cover 54
5B Cementitious wood fiber New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 55
5C Cementitious wood fiber New,Reroof(Tear-Off)or Recover B Mech.Attached Base insulation,Bonded Top Insulation,Bonded Roof Cover 56
SD Cementitious wood fiber New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover, 56
5E Cementitious wood fiber New,Reroof,(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 56
6A Existing gypsum Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 57-59
6B Existing gypsum Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 59
6C Existing gypsum Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover., 60
6D Existing gypsum Reroof(Tear-off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 60
7A Various Recover A-I Bonded Insulation,Bonded Roof Cover 61-65
7B Various Recover F Non-Insulated,Bonded Base Sheet,Bonded Roof Cover 65
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be In accordance with FBC requirements to the satisfaction ofthe Authority Having Jurisdiction,
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation,
2. Insulation/base sheet fasteners shall be of sufficient length for the following deck engagement:
> Wood: Minimum 0.75-Inch penetration.
>Steel: Minimum 0.75-Inch penetration and engage the top flute of the steel deck.
> Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation,instructions.--
NEMO ETC,LLC Evaluation Report P9290.02.08-R21 for 171.1654-1123
Certificate of Authorization#32455 6-EDITION(2017)FBC NON-HVHZ EVALUATION Revision 21:10/08/2018
Prepared by: Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(954)233-1330 Appendix 1,Page 1 of 65
NNEMOletc.
3. Unless otherwise noted,insulation maybe anyone layer or combination of polyisocyanurate,polystyrene,wood fiberboard,perlite,gypsum-based roof board or mineral-wool roof board that meets the CIA requirements
of F.A.C.Rule 61G20-3 and is documented as meeting FBC 1505.1 and,for foam plastic,FBC Chapter 26,when installed with the roof cover.
4. Minimum 200 psi,minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D(mechanically attached base sheet,bonded roof cover),whereby the base'sheet
fasteners are installed through the LW IC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural
members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval
documentation.
S. Preliminary insulation attachment for System Type D:Unless otherwise noted,refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29(January 2016).
6. - Unless otherwise noted,insulation adhesive application rates are as follows. Ribbon or bead width,is at the time of application;the ribbons/beads shall expand as noted in the manufacturer's published instructions.
➢ Hot asphalt(HA): Full coverage at 25-30 Ibs/square,
➢ Dow INSTA STIK Quik Set Insulation Adhesive(D-IS): Continuous 0.75 to 1-inch wide ribbons,12-inch o.c.
➢ Millennium One Step Foamable Adhesive(M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons,12-inch o.c.
➢ Millennium PG-1 Pump Grade Adhesive(M-PG1): Continuous 0,25 to 0.5-inch wide ribbons,12-inch o.c,
➢ OMG OlyBond 500(OB500): Continuous 0.75 to 1-inch wide ribbons,12-inch o.c.(PaceCart orSpotShot). Note: OlyBond Green may be used where OlyBond 500 is referenced.
➢ OlyBond Classic(OB Classic): Full coverage at 1 gal/square,
➢ ICP Adhesive&Sealants Polyset CR-20: Continuous 2.5-3.5-inch wide ribbons,12-inch o.c.
➢ Note: When multiple loyers(s)of insulation and/or coverboard are installed in ribbon-applied adhesive,board joints shall be staggered.
➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted,all insulations are flat-stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations maybe substituted with the following Maximum
Design Pressure(MDP)limitations. In no case shall these values be used to'increase'the MDP listings in the tables;rather if MDP listing below meets or exceeds that listed for a particular system in the tables,then the
thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table:
➢ Millennium One Step Foamable Adhesive(M-OSFA): MDP -157.5 psf (Min.0.5-inch thick)
➢ Millennium PG-1 Pump Grade Adhesive(M-PG1): MDP -157.5 psf (Min.0.5-inch thick)
➢ OMG OlyBond 500(OB500): MDP -45.0 psf (Min.0.5-inch thick Multi-Max FA-3)
➢ OMG OlyBond 500(OB500): MDP -187,5 psf (Min.0.5-inch thick ISO 95+GL)
➢ OMG OlyBond 500(OB500): MDP -315.0 psf (Min.0,5-inch thick ENRGY 3)
➢ OMG OlyBond 500(OB500): MDP -487.5 psf (Min.0.5-inch thick ACFoam II)
➢ ICP Adhesives&Sealants Polyset CR-20: MDP -117.5 psf (Min.1.0-inch thick)
8. Bonded polyisocyanu rate insulation boards shall.be maximum 4 x 4 ft.
9. For mechanically attached components or partially bonded insulation,the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16,and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1,FM Loss Prevention
Data Sheet 1-29,Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk*carry the limitations set-forth in Section 2,2.10,1 of FM Loss Prevention Data
Sheet 1-29(January 2016)for Zone 2/3 enhancements.
10. For fully bonded assemblies,the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16,and no rational analysis is permitted.
11, For mechanically attached components over existing decks,fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum
requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12. For existing substrates in a bonded recover or re-roof installation,the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive,and the existing
roof system(for recover)shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction,as documented through field uplift testing in accordance with
ANSI/SPRI IA-1,ASTM E907,FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Recover Applications using System Type D,the insulation is optional;however,the existing roof system shall be suitable for a recover application.
NEMO ETC,LLC Evaluation Report P9290.02.08-R21 for FL1654-R23
Certificate of Authorization#32455 6'"EDITION(2017.)FBC NON-HVHZ EVALUATION Revision,21:10/08/2018
Prepared by: Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(954)233-1330 Appendix 1,Page 2 of 65
ONEMOjetc.
14. Lightweight Insulating Concrete(LWC)shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced,refer to current LWC
Product Approval for specific deck construction and limitations. Unless otherwise noted,for systems where specific LWC is not referenced,the minimum design mix shall be 300 psi. In all cases,the minimum top-coat
thickness is 2-inches. For LWC over structural concrete,reference is made to FBC Section 1917.4.1,Point 1. For"pre-existent'LWC references,listings were established through testing over lightweight concrete cast
using only foaming agent(ASTM C896),water and Portland cement(ASTM C150),with no proprietary additives,in accordance with procedures adopted by Miami-Dade BCCO(FBC CER1592), Unless otherwise noted,
use of these listings In new constructiori'or're-roof(tear-off)applications is at the discretion of the Designer or Record and Authority Having Jurisdiction.
15. Unless otherwise noted,refer to the following references for bonded base,ply or cap sheet applications.
�. R0
REFERENCE LAYER,.i, -' ;INATERIAL APPLICATION';
BP-AA Base Ply One or more plies Polyglass G2 Base;FBC Approved ASTM U4601,Type II Hot Asphalt at 20-40
(Base and Ply sheets, Ply One or more plies Polyglass Ply IV,Polyglass-Ply VI,FBC Approved ASTM D2178,Type IV or VI Ibs/square
Asphalt-Applied) Note: Asphalt-applled`sheets or Insulation shall not be applied Fo poly film surfaced membranes.
Base Ply One ply Elastobase(sand/sand),Elastoflex V,Elastoflex S6,Elastoflex S6 Type II,Polyglass HT Base 650 PG350 at 1.5-2.0
SBS-CA1 Cap Ply Elastoflex VG,Elastoflex VG FR,Elastoflex S6,Elastoflex S6 Type II,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G,Elastoshield gal/square
TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed)
Base Ply One ply Elastobase(sand/sand),Elastoflex V,'Elastoflex S6,Elastoflex S6 Type II Polyplus 35 at 1.5-2.0
SBS-CA2 Elastoflex VG Elastoflex VG FR,Elastoflex S6 Elastoflex S6 Type II,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G,Elastoshield
Cap Ply TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed) gal/square
Base Ply or Ply One or more plies Elastobase(sand/sand or poly/sand),Elasto base•P.(sand/sand or poly/sand),Elastoflex V,Elastoflex S6,Elastoflex
- ,_ S6 Type II,Polyglass HT Base 650
SBS-AA Hot Asphalt at 20-40
Elastoflex V,.Elastoflex VG,Elastoflex VG FR,Elastoflex S6,Elastoflex S6 Type II,Elastoflex S6 G,Elastoflex 56'G FR,Elastoshield TS-G,
(SBS,Asphalt-Applied) Cap Ply Elastoshield TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed) Ibs/square
Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes.
650 or more plies Elastobase(sand/poly),Elastobase(poly/poly),Elastoflex V,Elastoflex S6;Elastoflex S6 Type II,Polyglass HT Base
SBS-TA Base Ply or Ply
_. (SBS,Torch-Applied) Elastoflex V,Elastoflex VG,Elastoflex VG FR,Elastoflex S6,Elastoflex S6 Type II,Elastoflex S6 G,Elastoflex S6 G_FR,Elastoshield TS Torch-Applied
Cap Ply G,Elastoshield TS-G FR,Polyfresko G SBS(poly-film backed),Polyfresko G SBS FR(poly-film backed)
Base Ply One or more plies Elastoflex SA V Base,Elastoflex SA V FR Base,Elastoflex SA V Plus,Elastoflex SA V Plus FR
SBS-SA Cap Ply Elastoflex SA P,Elastoflex SA P FR,Polyreflect Self-Adhering
(SBS,Self-Adhering) Note: Unless otherwise noted,permissible membrane substrates for SBS-SA are limited to the SBS-SA Base Ply options herein,
Elastobase(poly/sand)or Elastobase(poly/poly).
APP-CA1 Cap Ply Polyflex G FR PG350 at 1.5-2,0
gal/square
APP-TA Base Ply or Ply One or more plies Polyglass APP Base,Polyflex,Polybond '
Torch-Applied
(APP,Torch-Applied) Cap Ply Polyflex,Polyflex G,Polyflex G FR,Polybond,Pollybond G,Polyfresko G,Polyfresko G FR
APP SA Cap Ply Polyflex SA P,Polyflex SA P FR,Polyfresko G SA,Polykool
(APP,Self-Adhering)
Note: Unless otherwise noted,permissible membrane substrates for APP-SA are limited to the SBS-SA Base Ply options herein, Self-Adhering
Elastobase(poly/sand)or"Elastobase(poly/poly):
MEMO ETC,LLC Evaluation Report P9290.02,08-R21 for FL3654-1123
Certificate of Authorization#32455 6-EDITION(2017)FBC NON-HVHZ EVALUATION Revision 21:10/08/2018
Prepared by: Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(954)233-1330 Appendix 1,Page 3 of 65
4
J
NNEMOI etc.
16, Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure(MDP)limitations. The lesser of the MDP listings below vs.those in Table 3A
applies:
VAPORILL BAARIMOPTIQ
OPTION VAPOR BARRIER"
RRIMER INSULATION ADHESIVE MDP'(PSF)':
TYPE ATTACH
VB-1, PG100 Elastoflex SA V Plus Self-Adhering Inta-Stik or CR-20,12-inch o.c. -60.0
VB-2. PG100 Polyglass APP Base Torch-applied Inta-Stik or CR-20,12-inch o,c. -75.0
VB-3. PG100 Elastoflex SA P Self-Adhering Insta-Stik,12-inch o.c. -75.0
VB-4. PG100 Elastoflex SA P Self-Adhering Millennium One Step Foamable Adhesive,12-inch o.c. -157.5
VB-5. PG100 Elastoflex SA P Self-Adhering CR-20,12-inch o,c. -270.0
VB-6. PG1'00 Elastoflex SA V Base,Elastoflex SA V PR Base, Self-Adhering Millennium One Step Foamable Adhesive,Millennium PG-1 Pump Grade -290.0
Elastoflex SA V Plus,Elastoflex SA V Plus FIR Adhesive,OlyBond 500 or CR-20,12-inch o.c.
17, The following surfacing maybe applied to the Cap Ply without adverse effect on the system wind load performance. Refer to current Florida Product Approval for approved Polyglass and KM Coatings roof coatings for
application limitations and a Roofing Materials Directory for fire ratings associated with coating usage.
ORPOLYGLASS MODIFIED BITUMEN�OMSY�
d tion#' Surfacing. Florida Product Approval
SURF-1. PG300 Fibered Roof Coating FL10291
SURF-2. PG600 Non-Fibered Aluminum Roof Coating FL10291
SURF-3. PG650 Fibered Aluminum Roof Coating FL10291
SURF-4. PG700 High Quality Elastomeric Roof Coating FL10291
SURF-5. PG700QS(Quick Set)High Quality Elastomeric Roof Coating FL10291
SURF-6. PG800Asphalt Emulsion Roof Coating 11-10291
SURF-7. Polyplus 60 Premium Non-Fibered Aluminum Roof Coating FL10291
SURF-8. Polyplus 65 Premium Fibered Aluminum Roof Coating FL10291
SURF-9. Polybrite 70 Premium Grade Elastomeric Roof Coating FL10291
SURF-10. Polybrite 70QS(Quick Set)Premium Grade Elastomeric Roof Coating FL10291
SURF-11. Polybrite 71 HS FL10291
SURF-12. Polybrite 90 High Solids Silicone Roof Coating FL10291
SURF-13. Polybrite 95 Silicone Roof Coating FL10291
SURF-14. KM Acryl 15 FL27409
SURF-15. KM Acryl 15 QS FL27409
SURF-16. KM Acryl 25 FL27409
SURF-17, KM Acryl 25 QS FL27409
SURF-18. KM Acryl 40 HS FL27409
SURF-19. KM Acryl 85 FL27409
SURF-20. KM PS#2.50 FL27409
SURF-21. KM PS#220 FL27409
18. "MDP"=Maximum Design Pressure is the result oftestingfor wind load resistance based on allowable wind loads,Refer to FBC 1609 for determination of design wind loads.
NEMO ETC,LLC Evaluation Report P9290.02.08-R21 for FL3654-R23
Certificate of Authorization#32455 6-EDITION(2017)FBC NON-HVHZ EVALUATION Revision 21:10/08/2018
Prepared by: Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(954)233-1330 Appendix 1,Page 4 of 65
I
I
X4
OMEMO I'etc.
5YSTEIVITYPEF:NONANSULATE0,BONDED ROOF COVER
System < Roof Cover'(Note'15)
Deck(Note 1) Pnmer MDp(psf)
No4 lointTreatment+ Base PIy ply,;. Cap Ply
W-170 Min.15/32- None None SBS SA (Optional)SBS-SA,SBS- SBS-SA,A'PP-SA,SBS- 90.0
inch plywood TA,APP-TA TA,APP-TA
W-171 Min. (Optional)PG100 None Polyflex SA Base (Optional)APP-TA APP-TA -90.0
inch plywood
Min.15/32- (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS-
W-172 inch plywood PG100 None _ SBS-SA TA,APP-TA TA,APP-TA g7.5
Min.15/32- V Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus,rolled into Elastoflex.SA Base or (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS-
W-173 inch plywood (Optional)PG100 place to create continuous bond. Elastoflex SA V FR Base TA,APP-TA TA,APP-TA 97.5
W-174 Min.15/32- POLYBRITE 745 None SBS-SA (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS- -105.0
inch plywood TA,APP-TA TA,APP-TA
Min.15/32- Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus,rolled into Elastoflex SA V Plus or (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS- 135.0
W-175 inch plywood (Optional)PG100 place to create continuous bond. Elastoflex SA V Plus FR TA,APP-TA TA,APP-TA
Min.15/32- Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus,rolled intTolyflex
W-176 inch plywood (Optional)PG100 place to create continuous bond. SA Base (Optional)APP-TA APP-TA 135.0
NEMO ETC,LLC Evaluation Report P9290.02.08-R21 for FL1654-R23
Certificate of Authorization#32455 6'"EDITION(2017)FBC NON-HVHZ EVALUATION Revision 21:10/08/2018
Prepared by:'Robert Nieminen,PE-59166 Polyglass Modified Bitumen Roof Systems;(954)233-1330 Appendix 1,Page 26 of 65