NOTICE OF ACCEPTANCE (NOA) + +'n.miamidadc.t o+leconomv
GAF
I Campus Drive
Parsippany,NJ 07054
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction
materials.The documentation submitted has been reviewed and accepted by Miami-Dade County RER-
Product Control Section to be used in Miami Dade Countyand other.areas where allowed b the
y
Authority Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated.below.The Miami-Dade County Product
Control Section(in Miami Dade County)and/or the AHJ (in areas other than Miami.Dade County)
reserve the right to have this product or material tested for quality assurance purposes.If this product or
material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing
and the AHJ may-immediately revoke,modify,or suspend the use of such product or material within
their jurisdiction. RER reserves the right to revoke this acceptance,if it is determined by Miami--Dade
County Product Control Section that this product or material fails to meet the requirements of the
applicable building code.
This product is approved as described herein,and has been designed to comply with the Florida Building,
Code including the High Velocity Hurricane Zone of the Florida.Building Code.
DESCRIPTION: GAF EverGuard®TPO Single Ply Roofing'Systems over Recover Decks.
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state
and following statement: "Miami-Dade County Product Control Approved",unless otherwise noted
herein.
RENEWAL of this NOA shall be considered after_ r a renewal application has been filed and there has
been no change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or
change in the materials,.use, and/or manufacture of the product or process.Misuse of this NOA as an
endorsement of any product,for sales,advertising or any other purposes shall automatically terminate
this NOA.Failure'to comply with any'section of this NOA shall.be cause for termination and removal of
NOA.
ADVERTISEMENT; The NOA number preceded by the words Miami-Dade County,Florida,and
followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is
displayed,then'it shall be done in its entirety.
INSPECTION:A copy of this entire NOA shall be provided to the user by the.manufacturer or its
distributors and shall be available for inspection at the job site at the request of th uil, ing Official.
This NOA renews and revises NOA No. 13-0820.05 and consists of pages 1 thr ugh l 11 I
The submitted documentation was reviewed by Jorge L.Acebo. l `ti V61014'
EVIE� D 1
ODE COMPL NCE
ST, LUCIE C 16-0217.01
MIAMI•DADE COUNTY
BOC �
p e�`'U5/1 6
—`Page l of l 14
Irr'He 0
t ,
ROOFING SYSTEM APPROVAL
Categorv: Roofing
Sub'-Category:, Single Ply Roofing
Material:, TP.O
Deck Type: Recover
Maximum Design Pressure: See-Specific Deck Type
TRADE DAMES OF PRODUCTS MANUFACTURED OR LABELED By APPLICANT:
TABLE 1
Test Product
Product Dimensions Specification Description
EverGuard'TP.O. Various ASTM D6878 Thennoplastie.olefin reinforced single-ply
TAS 131 membrane.
EverGuard Extreme'TPO Various ASTM D6878 Thennoplastic olefin reinforced single-ply
TAS 131 membrane designed for advanced
protection agaifst heat aging and UV
degradation.
EverGuar&TPO FB Ultra Various ASTM D6878 Thennoplastic olefin reinforced,fleece
TAS 131 back single-ply membrane
EverGuard Extreme's TPO Various ASTM D6878 Thermoplastic olefin reinforced fleece
FB Ultra TAS.131 back single-ply,membrane designed,for
advanced protection against heat aging
and UV degradation.
GAF.GLAS'V Ply 4. 39.37 ASTM D2178 A smooth surfaced asphaltic ply sheet
(1 meter)Wide reinforced with.fiberglass mat:
Tri-Ply 'Ply 4 39.37" ASTM D2178 A smooth surfaced asphaltic ply sheet
(1 meter)Wide reinforced With'fiberglass mat.
GAFGLAS'1'FlexPly`°'6 39.37" ASTM D2178 A.smooth surfaced asphaltic ply-sheet
(1 meter)Wide reinforced with fiberglass mat.
GAFGLASI�'#75 Basc 39.37" ASTM_D4601 .A smooth asphaltic base or base/ply"sheet
Sheet (1 meter)Wide reinforced with fiberglass mat."
Tri-Ply'075 Base Sheet 39.37" ASTM D4601 A smooth asphaltic base or base/ply sheet
(l meter)Wide reinforced with fiberglass mat.
GAFGLAS°?#80 Ultima'" 39.37" ASTM D460.1 A smooth asphaltic base or base/ply sheet
Base'Sheet (1 meter)Wide reinforced with fiberglass mat.
Ruberoid'k'20 Smooth 39.37" ASTM D6163 A SBS polymer-modified asphalt base or
(1 meter)Wide ply sheet reinforced with a fiberglass mat.
Ruberoid"Mop,Smooth 39.37" ASTM D6164 Smooth surfaced mop applied SBS base or
1.5 (1 meter)Wide ply sheet reinforced"with a polyester mat.
Matrixni 307"Premium 1,5 or 55 ASTM D41 Asphalt concrete primer used to promote
Asphalt Primer Gallons adhesion of all types of asphalt-based
roofing materials:
NOA No.: 16-0217.01
IAA IADE CoURTr Expiration Date: .05/12/21
""' ' Approval Date: 05/05/16
Page 2 of 114
Test Product
Product Dimensions Specification Description
EverGuard�#1121 5 Gallons: Proprietary Adhesive for'fully adhered systems-and
Bonding Adhesive membrane flashing.
EverGuard'y WB 18l 5 Gallons Proprietary A water based adhesive for TPO based
Bonding Adhesive membranes.
EverGuard"Low VOC 5 Gallons Proprietary A contact type bonding adhesive for TPO
TPO Bonding Adhesive single ply roofing membranes and
flashings.
LRF Adhesive M 1:1 Applicator Proprietary A dual component foamablc adhesive.
LRF Adhesive O 1:1 Applicator Pro rietarY A dual comP`on_it. .o..) urethane adhesive
used'to adhere single ply roof covers.
GAF 2-Part Roofing- 1:1 Applicator Proprietary A dual component; low-rise;
Adhesive polyurethane.66th adhesive.
EverGuard`'TPO Coated 4'x 10 sheets Proprietary" 24 gauge steel with a 25 mil thick GAF
Metal TPO for edge detailing.
Ever'Guard Extreme'TPO �4'x;10'sheets Proprietary 24 gauge.steel with,a 25 mil thick GAF
CoatedUetal TPO for edge detailing and.designed for
advanced protection against heat aging
and-'LN'degradation.
Ev&Guard'TPO Cover 6"x 100' Proprietary, GAF TPO laminated to white butyl tape
Tape 10"z 160, prinaiily used for edge-metal details:
EverGuard'TPO Cover. 6"x 1.00' Proprietary. Flashing°strip manufacture&from
Tape Heat-Weld unreinforced GAF TPO laminated to a six
inch wide strip;half the strip with a.self
adfiered side_and'half-the strip,*.ith a heat=
weldable edge;used for edge metal
details.
EverGuard Extreme"TPO' 6"z;11)0' 'Proprietary Flashing stri .manufactured,from
P..
Cover Tape Heat-Weld unre�nforced GAF TPO designed for
advan.ced protection against heat aging
and UV degradation. Laminated to a six.
inch wide strip;half the"strip:with:a self-
' adhered side and.halfthe-strip with a heat-
Weldable.edge;used for edge metal
details:
EverGuard"TPO Detailing 24"x 50' Proprietary Unreinforced flashing material,
Membrane manufactured from GAF TPO.
EverGuard Extreme'TPO 24." x 50' Proprietary Unreinforced flashing.material
Detailing Membrane manufactured from GAF TPO designed
for advanced protection against heat aging
and UV degradation,
EverGuardO TPO Flashing Various_ Proprietary Reinforced flashing membrane
Strip manufactured-from GAF TPO.
NOA No.: 16-0217.01
MIAMI•DADE CO UMY Expiration Date: 05/12/21
Approval Date: 05/05/16
:Page-3 of n*
1
Test Product
Product Dimensions Specification Description
EverGuard Extreme"'TPO Various Proprietary Reinforced flashing membrane
Flashing Strip manufactured from GAF TPO designed
for advanced protection against heat aging
and UV degradation.
EverGuard'TP_O Pourable 9"X 6"X 4" Proprietary Pourable sealer pocket is molded with
Sealer Pocket Ovai With 3" GAF TPO compound to a nominal 70 mil
Base Flange thickness designed for waterproofing
'irregular shaped roof penetrations:
EverGuard Extreme"'TPO 9"X 6"X 4" Proprietary Pourable sealer pocket is molded from
Pourable Sealer Pocket Oval With 3" GAF TPO designed for advanced.
Base Flange protection against heat aging and UV .
degradation compounded to a nominal 70
mil thickness designed for waterproofing
irregular shaped roof penetrations.
EverGuard'TPO RTA 6"x 100'Roll Proprietary Reinforced GAF TPO membrane with
(Roof Transition Anchor) pressure sensitive adhesive primarily used
Strip"' to secure membrane transitions.from the.
field to vertical surfaces.
EverGuard'TPO Split 1"=2" Proprietary Reinforced GAF TPO membrane split to
Pipe Boot 3."=5" accommodate most common pipes,and
6"-8" conduits.
EverGuard Extreme'TPO 1"-2" Proprietary Reinforced GAF TPO designed for
Split_Pipe Boot 3 51.' advanced protection against heat aging
8" and UV degradation split to accommodate
most common pipes and conduits.
EverGuard'TPO Square 4"x 4" Proprietary. .Reinforced GAF TPO with split design
Tube Wrap 4"x 6" overlap to be wrapped around square or
6" x 6" rectangular tubing.
EverGuard Extreme' TPO 4"x 4 Proprietary Reinforced GAF TPO designed for
Square Tube Wrap 4"x 6" advanced protection against heat aging
6"x 6" and UV degradation with split design
overlap to be,wrapped around square or
rectangular tubing.
EverGuard'TPO Corner Various Proprietary Comers fabricated from reinforced GAF
Curb Wrap TPO.
EverGuard Extreme91'TPO Various Proprietary Corners fabricated from reinforced GAF
Corner Curb Wrap TPO designed for advanced protection
against heat aging and UV degradation.
EverGuard'TPO Scupper 4"x 6"x 12" Proprietary Scupper manufactured from coated metal
8"x 10"x 12" and unreinforced GAF TPO.
EverGuard'TPO T-Joint 100 Patches Proprietary T-Joint patch manufactured from
Cover Patch Per Box unreinforced GAF TPO.
NOA No.: 16-0217.01
MIAMI-RADE COUNTY Expiration Date: 05/12/21
MINVASM11 Approval Date: 05/05/16
Page 4 of 114
Test Product
Product. Dimensions Specification Description
EverGuard Extreine`g'TPO 100 Padres Proprietary T-Joint patch manufactured from
T-Joint Cover Patch Per Boxurirenforced GAF TPO designed for
advanced protection against heat aging
:and UV degradation:
EverGuard'TPO Vent 2 Vents.Per Proprietary Vent manufactured from reinforced GAF
Carton TPO membrane and galvanized steel..
EverGuard'TPO T=Top 0-or b" 'Proprietary, Vent manufactured from reinforced GAF
Vent. TPO;menibrane and galvanized steel.
EverGua_r_do TPO_ Walkway Rolls ,1/8"x Proprietary Standard.dutyTPO walkway ro_lls:,
Rolls. 30"x 3:0'
EverGuard''TPO Inside 6°x 6"x 5'/4" Proprietary inside comer manufactured from_
Comer unreinforced'GAF'TPO:
EverGuard Extrcme°�.TPO, 6."x6"x 5%4" Proprietary .Inside comer-manufactured from
Inside Corner unreinforced GAF TPO designed for
advanced,proteetion againsi%heat aging
and i)V degradation.
EverGuard'TPO Universal Various Proprietary. Universal comers manufactured:from
Corners: GAF TPO that are heat seamable and
designed to accommodate both,inside and'
outside corners'of.base arid.curb flashings
manufactured from GAF TPO.
EverGuard Extreme, TPO Various Proprietary Universal corners nnanufactured from
Universal Corneas: GAFTPO that`are heat seamable and
designed to accommodate bo,'th,inside and
outside:corners of base and curb,flashings
:manufactured from. TPO designed
for advanced protection_against heat aging.
:an :UV degradation,
EverGuard TPO Vent, 1"=-V"o.d. Proprietary Vent pipe boorinoWd..,from GAF°TPO
Boot 6 pcs;Crt'n:. and supplied with stainless steel clamping.
L :rings:
.EverGuard Extreme TPO 1.`-V'o.d. :Proprietary Vent 'pipe boot molded from GAF'TPO
Vent Boot 6 pcs.Crin. designed for advanced-protectionagainst
heat_aging and UV degradation.and'
supplied with stainless steel clamping,'
'rings:
EverGuard TPO Various. Proprietary Low profile joint cover manufactured
Expansion Joint Cover from-reinforced GAF TPO.
EverGuard'TPO Cut Edge 1 Quart Proprietary Clear solvent based sealant for TPO cut
Sealant Squeeze`Tube :edges.
EverGuard'TPO Drain, Various Proprietary Spun aluminum drain pre-flashedwith
unieinfomed GAF.TPO.
NOA NO.:164217.01
MIAMI•DA13 UNTY ERp1raC10n CODate: 05/12/21
"'• '
MIAMI
Date: 0/05/16
Page-5 of 114'
1
Test Product
Product. Dimensions Specification Description
EverGuard'TPO Seam I'Gallon Proprietary Solvent based"seam cleaner.,
Cleaner
EverGuard"TPO Primer, 1 gal]on Proprietary Solvent based TPO primer.
EverGuard"Low'VOC 1 gallon Proprietary Low VOC,solvent based TPO primer.
TPO Primer
EverGuard TPO Fluted 8" Diameter Propfi I etary. Flashing for outside corners of base and.
Corner Nominal..05" curb flashing manufactured from non-
Non.-Reinforced reinforced GAF'TPO.
EverGuard'Extremes'TPO 8"Diameter 'Proprietary -Flashing for outside,corners of base and
Fluted Comer Nominal .05" curb flashing manufactured from non-
Non-Reinforced reinforced GAF TPO designed for
advanced protection against heat;aging
arid.UV degradation.
EverGuard'Polymat 3 oz./yd:z Proprietary A non-woven polyester mat for use as a,
Separation Layer polyester mat slip,sheet below mechanically secured
single ply roof membranes:
EverGuard'Polymat 6 oz./yd." Proprietary A non-woven polyester mat for use as a
Cushioning Layer polyester mat slip sheet below mechanically secured
single ply roof membrancs.
Topcoat"`'Membrane 1,,5 or55 ASTM D6083 Acrylic,water based elastomeric
Gallons ineinbrane system designed to protect
various"types of roof surfaces.
Topcoat'TPO Red Primer I:Gallon Proprietary Tinted primer used on.TPO to improve
adhesion of-Topcoat'coatings.
Topcoat`s'FlezSeal 1 or 5 gallons or. TAS 139 S-o1Vcnt7-based elastomeric sealant.
1 qttube
NOA No.:16-6217.61
MIAMI-DADECOUNTY Expiraiion Date:- 05/12/21
Approval Date:05105/16
Page 6 of 114
APPROVED INSULATIONS:
TAIRLE.2
Product Name Pr6dtiet Descrip" tio-n Manufaciurer
1. Current NOM
tne gyQuOd"Pol iso' nsulation Pbly'isoi yanurate foam insulation GAF
Y. S
Ener Guard'."' P.plylso
High density,polyisocyanurat foam e- GAF
:Insulation insulation
-High densityi %6AV
pol�iwcyanur,te.'foam
lnsulafi.0n -insulation
Encrgy_Gpa,r&" a y1so,
:Qjtr-'P I' Pblyisocyanilratc;fbanib insulation. GAF
. P
Insulation
EnergyQuard'RA Pof PblyiscicWhurate foam insulation. GAF
1p9platiOn
8nqrgy0?IarrRH P61 is& Polyiso Vahurifte foam insulation.-Y GAF
inslowifori
EnergyGuard"'R-H HD Poiyiso High poyis density_ I 6cyanurate foam 'GAF
,
Insulation insulation:
Energyqpard7'kN Polyis6 -PI socy 06 fbAffi bsulkion
y Yj GAP
InO.lation,
Energyp
_uard"`R' XTAp Tapered.d. olVisodVanurat6 fdani(ins-blati6h
GAF
-Polinsulation
Mq-
.
Energy;Guard"Perlite Recover Teflitc.insulation-lation hoard.
- T9Y GAF
BoOrO'
E Roof Wil I i.te insulation'66Aed. GAF
Insulation
Se,curo k"'Gwsun_-Viber Roof Gypsumboard. United'States Gypsum Cork..
Board
SbcurocV'Glass-Mat Roof Board. Gypsum, crd
United States
Gypsum Corp
Den'sDe'cV. Roof Board 'Gypsumboard Georgia-Pacific G pufiI_LLC
Ddisl)ecO Pi-line"Roof.Board Gypsun,board Georgia
-Pacifc Gypsum LLC
-Structo.&V High,l)ensft ighAensi .�f
Y -ty ibetboaM Blue Ridge FibeiBoard,Inc.
Fiberboard Roof Insulation
NOA Nb:: i&0217.01
MLALMI-DADE COUNTY 'jExpjr'ation_ s6_L6e:"�.:05/12/2-.
.
Approval Daie:;05/65/1-6
'P40 of 114-
z
APPROVED FASTENERS:
TABLE 3
Fastener Product Product Manufacturer
Number Name Description Dimensions (With Current NOA)
1. Drill-Tec412 Phillips head,modified #12x 8" Max. GAF
Fastener buttress thread,pinch point; Length,#3
carbon steel fastener for.use in Phillips l-iead
steel or wood-decks.With CR-
10 coating._:Available,with a
pinch point or drill point.
2'. Drill-Tec" #14. Truss head,self-drilling,pinch #14 x 16"Max. 'GAF
Fastener point,high thread fastener for Length,##3
use in steel,wood or concrete Phillips Head.
_-- decks.
3. Drill=Tec`XHD Truss head,-self-drilling,pinch 415 x 16".Max. GAF
Fastener point,high thread fastener for Length,#3
,us in wood:orsteel decks. Phillips Head
4. Drill-Tec'"`2-3/8 in. Round galvanized steel stress 2-3/8" Round GAF
Barbed XHD Plate plates for use with DriliJec"
fasteners.
I
5: Drill-Tec"21n. Round galvanized steel stress 2"Round GAF
Double Barbed XHD plates for use with Drill-Tecl"
Plate fasteners.
"6;. Drill-Tec"'2 3/4 in. Round galvanized steel stress 2-3/4"Round GAF
Barbed SXHD Plate plates for use with_Drill-Tec"
fasteners.
7. Drill-Tec',"SXHD Truss headi self-drilling,drill. #21 x 16"'Max. GAF
point,high thread fastener for Length;#3.
i
use in.steel decks. Phillips Head
I
$. Dril TecAccuTme A2-SS aluminized steel plate 3" Square; GAF
Flat Plate for use with Drill-Tec"' 017"Thick
fasteners.
9. Drill-Tec"AccuTrac' Galvalume`'steel plate with 3" Square; GAF
Recessed Plate recess for use with Drill-Tec"' .017"Thick
fasteners.
I
10.. Drill-Tec'"ASAP 3S Drill-Tec"#12 Fastener with See GAF
Drill-Tec"'3" Standard Steel Components
Plate.
IL. Drill-Tec" Gold pritner coated plate for 3"Round GAF
RhinoBond"'TPO use with TPU membranes.
SXHD Plate
NOA No.: 16-0217.01
MIAM-DA®U� Expiration Date: 05112/21
Approval Date: 0$/05/16
Page 8 of 114
APPROVED FASTENERS:
TABLE.3
Fastener Pr,.d.du-ct' Product Manufacturer
NumbeY Name Demcriptioii Di-mefisiong (With'Pirrent NOA)
12, Drill=Tec`!
Gold primer,coatcA,plate f6r 3 Round -GAF
RhinoBon&TPO use with TPO rnerfibranes,
XHD Plates.
13. Drill-Tec Y"Steel Ro.und.Ga.1va.luiiie""stee.l.stress 3." Roilnd 'GAF
Plate's plate w- ith.rdihfbrc'ing.fibs:and
.tecessed.for use,will i Drill=
Tech''fasteners,.
T-
14; bnll-Te,,6-M
-T'Standard- Galva.lurneNwated steel stress .3!'Round GAF
Steel Plate plate for use witfi.approwd
'biii-17TOO.'-fasteners:
1. . ;eho6k Round Galvalumtiql steel plate -2-,3/8!'Round GAY
AccuSearn'Plates for use.wit I b Drifl-T
116. bfifl-Tec'"'J,in'.- k6und.GalV' afurn6g plated steel 3"Round GAF
.Ribbed i'baI'Va''I u m- e- stress plate with reinf6rcing.
Plat&(Flat) :ribs f6r use with Drill--Tec"'
-fasteners.
17'.- Drilh-Te"04"
Round,coaled'GalvalumeO' GAF
Rhih0'8on&'TP0 plate(Gold primer coating)
XHO-Tread'.,&fe Plate; used for.TPO membranes
M Drilf-iTe-6"Purlin .Hex head;'%4 i.n-?drill poi'nt
, 10" Maz. GAF
Pastener fastener used to attach mhglen
LengthiNith
Plyfo structural steel purlins. #3 Square Head
NPA No.-.16-70217.01
MIAMI MADE C!�.� 'Expiration DAte:,-05/12/21
Approval bate: "05/05/16
-Page.�.:of'114.
I
SIJ+VIDENCE SUBMITTER:
Test Agency/ldentifier Name Report Date
FM Approvals 4470 3014955 01/28/05
_4470 3020681 01/09/05
4470. 3022136: 03/17/05
4470 3023458 07/18/06
4470 3024051 03/28/06
4470 3026964 67/25/07
4470 3629;'32 05/11/07
4476 3030813 11/05/07
4470 303.1350 09/27/07
4470 3032172 '_06/12/09
4470 3032856 11/24/08
4476 3033135 11/24/08
4470. 3034394. 02/27/09
4470 3034749 10/16/08
4470 3035658 09/16/09
4470 3036141, 48!10/09
4470 3036.614 06/09/09
4470 3038278 .11/18/11
4470 3038318 12/10/10
44703040234 02/23/11
4470 3040377 03/08/11
4470 3041535 06/08/11
4470 3041685 03/24/11
4410 3041769 09/27/11
4470 3042905 01/10/12
4470 3045166 07%24/12
4470 '3045863 08/16/12
4470 3046054 12/21/12
4470 3046081 02/13/13
4470 3046328 09/ 13/22
4470 3046388 09/24/12
4470 3047636. 68/08/13
4470 3048122 04/29/13
4476 797-03825-267 07/14/08
4470 797-05045-267 30/12/09
4470 797-05204-267 01/11/09
441b 797-05550-267 05/10/10
4470 797-05593=267 05/26/10
4470 797-06178-267 12/09/1.0
4470 797-06254-267 12/10/10
4470 797-07183-267 11/09/ll
4470 797-09594-267 06/24/14
4470' 797-101237283 12/09/14
4470 797-10153-267 12111/I4
4470 797-10212-267 02165/15
NOA No.t 16=0217.01
M1aM1DaDEcatlrsrt Expiration Date: 05/12/21
Approval Date: 65/05/16
Page 10 of.l 14
EVIDENCE SUBMITTED: (CONTINUED)
Test Agency4dentifter Name, Repq# Date
FM Approvals 4470 197-RR1001 08 02/1915
44-7.0 FMI Letter 10/28/09
4470 FM Letter 12/06/11
4470 FM Letter Report 3048066. 12/13/1
4470 I'M Leiter Repo rt A051911 0.8/06./14
PRI C.' ionstfucton,Materials TAS'l 39 OAJF-'122-02--Gii '05/07/06
Technologies,LLC AS T- M D2178. GAF73 14-027'01 :08/23%11
ASTM,D21-78 GAF7315-02=61
ASTM C1289 GAF-369-02-01 10/22./12
ASTM-C1.2.91# 05/02113
ASTM Q.1289 'GAF-412,02-0I 05/02/13
ASTM C1289. 'GAF417.02-611 /28/13
�62-01' 10/23/13,
ASTM D6878/TAS.131 :GAF-4 ,
Agtm,[Y68"7' 8/TAS* i 3;1 'GAF-422=02-01 10/29/13:
ASTM D687 S/TAS1 31 GAF-424-b!-"01 i 1(11/13
ASTM D6979/tAS1 31 6AF425-02-0-1' 1,1111113
TAS 7 GAF455,02-01
TAS, 114 GAF435-02-0-8.: 01/29/14.
TAS 114. 6AF-41,35702-08,Addendum 1,2102,115
TAS 114
14 0 AF435-01-09
TAS 114 GAF.435-OM9 Ad'denduin 12/{12/15
TAS 114 0' �01/29*114
T-AS'j,1,4 GA; F435-024P Addendum I2/02/15
TAS 114 11 61/2,9/14
TAS 114 Addendum -12102/15
TA5'1-14 GAF457;-02-02 .01/20/14
' 2- M4
TAS 1114 -GAF451-0'2=96 VO
TAS,1.14. GAF457-02-08 02/05/14
ASTM 15413. �GAF 46Z=02-01 11/18/15
TAS 117 04 9./1
ASTM D1761 .GAJF-4627' 1,111.8/13
TAS"l 14 'QAF462.02=09 07/01/14
ASTM C1289 'GAF464701-:01 02/06/14
ASTM D6081 GAF-499-02-01 03/12/14,
TAS 114 GAF-506-0-40 03106/14
TAS
S 1141 Addendum
11
TAS 14 GAF-506-02.-14;' .04114/14
TAS 114 GAP-5'60-02A4 Addendum. 12/02/15'
Astm D1475 GAF-508-01-01 D3112/14
TAS 114 GAF 751040 --02 :04/68114
TAS 114 GA:F410-02'*-0'2 Addendum
d'00clum 12/02/15
TAS 114' GA-F-5 1 M27-04 '04/08/14
TAS 1-14 GAF-,5 1 O-M-04-Addendum 32/02/15
TAS-114 GAF-511-02=02_Q2 04/08/14
TAS 114 GA 42/02/15
V7511-02-02 Addendum
NOA No.- 1,6,-0217.01
M-MIAMI-DADECC) 1M Expiration,Date.: 05/12/21
Approval Date: WWI&
Page 11.of 114
EVIDENCE SUBMITTED: (CONTINUIED)
Test Agency/Identifier Name Report Date
PRI Construction Materials TATS 114 GAF-511-02-03 05/08/14
Technologies,LLC TAS 114 GAF-5.15-02-01 05/13114
TAS 114 GAF-516-62-01 05/13/14
TAS 114 GAF-516-02-02 06/06/14
TAS 114 GAF-516-02-03 05/13/14:
TAS 114, GAF-525-02-01 06/23/14
ASTM 06.878 GAF-584-02-01 12/07/15
ASTM D6878 GAF-585-02-01 12/07/15
ASTM D6878 GAF-586.-02-01 12/07/15
TA'8 114 GAF-52.5-02-02 06/23/14
TAS 114 GAF-525-02-02 Addendum 12102/15
TAS 114 GAF-525-02-03 06/23/14
TAS,114 GAF-525-02-03 Addendum 12/02/15
TAS 11.4 GAF-540`-02-02 08/06%14
TAS 114 GAF-540-02-03 0.8/06/14
TAS 114 GAF=540-02-04 08/06/14
TAS 117 GAF=559;02-�03 10/16/14
TAS 10.5 MCRF Letter 01/22/15
Underwriters Laboratories Inc. R1306 09CA$5838 1.1104/10
Exterior Research&Design,LLC TAS 114: 01509.03.04-2 03/16/04
TAS 131 18020.12.02-1 -12,/06/02
Trinity I ERD ASTM D6164 G31366.03.10 0 / 1/10
ASTM D6163 G34140.04.11-2 04125/11
ASTM D.4601 G34140:04.11-4-R2 06%04/15
TAS 105 MCRF Letter 01/12/15
Atlantic&Caribbean Roof TAS 11.4 07-03.0 .05/09/07
Consulting,LLC' TAS 114 08-032 05/1910$
TAS 114 11-064 03121/11
TA8 114 11-005 -03122111
TAS 114 11-011_ :03124!11
TAS 114 11-012 04/06/11
TA8 114 11-013 04/06/11
TAS 114 if-019 04/08/11
TAS, 114 11-020 64/68/11
TAS 114 11--042-RI 01/27112
TAS 114 1I-047 08/09/11
TAS 114 11-05&R2 01!26/15
TAS 114 11-067 11121/11
TAS 114 12-008 04'/10/12
TAS 114 12-012 04/23/12
TAS 114. 12-013 04/23/12
TAS 114 12-014 04/24/12
TAS 114, 12-01.6 04124%12
TAS 114. 12-024 05109112
T-AS 114 12-033 .08/10/12
TAS 105 MCRF Letter 01/26/15
NOA No.t 16-0217.01
M1AMMADe.. COUNTY Expiration Date: 05/12/21
, , Approval Date: 05/05/16
Page 12 of 114
I)EC,K-'S,TRESS.ANALYSIS-C'ALCULA-T-ION9,/REP--09-*"$.,
,Engineer%Agenc Dikte,
-
FM'.APiV0,p1-Mck Limitations. N/A c(9)', 01/01/13
D(2),-D( )- D.(.4)*i 1)(5)
bucthiihb NvyQ
eb,P.E. Signed/Sealed .2),C(4),(4),-C, )X(7),C( D(6), 12/02/15
C, culatiPhs C(ll),V(7),E(I)l E(
:NOA.No.: 1:6-021'7.01iAMI-OADECO Try tipirAtCo'ni.
D*#O: 5/12/21
COUNTY
=TY Approval Date:: 05/05/16
Paget 'of 4
Membrane Type: Single Ply,TPO
Deck Type 71: Recover Insulated
Deck Description: Minimum 22 gauge, Grade 80 steel deck secured to minimum 0.25"thick_structural
supports spaced at maximum 60"o.c. using Teks 4, Teks 5, ICH TRAXX/4 or ICH
TRAXX/5 fasteners spaced maximum 6"o.c. along each support. The deck side
laps are fastened with Stitch Teks 1 or ICH TRAXX/l fasteners spaced at maximum
24"o.c. along each side lap.
This Tested Assembly has been analyzed for allowable deck stress. See
Evidence Submitted Table.
System Type D(1): All insulation is loose laid with preliminary attachment to roof deck. Membrane is
subsequently mechanically fastened through insulation to the roof deck.
All General and System Limitations apply. Roof accessories not listed in Table 1 of this NOA are
not approved and shall not be installed unless said accessories demonstrate compliance with
prescriptive Florida Building Code requirements and are field fabricated utilizing the'approved
membranes listed in Table 1.
One or more layers of any of the following insulations.
Insulation Layer Insulation Fasteners Fastener
(Table 3) Density/ft',
DensDcck`'Roof Board,Securock'Gypsum-Fiber Roof Board,Securock®Glass-Mat Roof Board
Minimum 0.25" thick' N/A N/A
Structodek'High Density Fiberboard'Roof Insulation,EnergyGuard"'Perlite Recover Board,
EnergyGuard HD Polyiso Insulation, EnergyGuard HD Plus Polyiso Insulation,EnergyGuard RH
HD Polyiso Insulation
Minimum 0.5" thick N/A N/A
EnergyGuard"'Polyiso Insulation,EnergyGuard RA Polyiso Insulation,Energ}Guard'"'RH
Polyiso Insulation,EnergyGuard"'RN Polyiso Insulation, EnergyGuard"'Ultra Polyiso Insulation
Minimum l" thick N/A N/A
Note: All insulation shall hav preliminary attachment,. rior to the installation of the roofing
membrane at a minimum application rate of two fasteners per board for insulation boards having
no dimension greater than 4 ft.,and four fasteners for any insulation board having no dimension
greater than 8 ft. Please'refer to Roofing Application Standard,RAS 117 for insulation attachment
requirements.
Membrane: EverGuard°�'TPO, verGuard'Extreme'TPO,EverGuard"�TPO FB Ultra or
EverGuard"'Extremes'TPO FB Ultra attached through the preliminary attached
insulation as follows.
Fastening: Drill-Tec"2-3/8 in.Barbed XHD Plaiel or Drill-Tec"'Eyehook AccuSeam Plates
andl Drill-Tec."'.XHD Fasteners spaced 6"o.c. within laps spaced 114"o.c. Side laps
are minimum.6"wide and sealed with minimum 1.625"wide heat welds for
automatic machine welding. Weld width shall be minimum 2"wide for hand
welding.
NOA No.: 16-0217.01
CAMM=DUNTY Expiration Date: 05/12/21
Approval Date: 05/05/16
Page 8.3 of 1]4
1
.Surfacing: Chosen components must be applied in accordance-with manufacturer's:
( 'ptional) application.itistr actions,A.ny,!coating listed be :used;as.a surfacing must be
-listed within a current NOA:
1. TopcoatC'Membrane applied.at 1 to ;]:5 gal:/sq:.
2. Topcoat'TPO Red Primer applied at 0.5 gal./sq.prior to applying.Topcoat'-Membrane.
Maximum Design
Pressure: -5DCC Gencral limitation#7)
NOA No.: 16-0217.01
MIAM1•DADECOUPIT7 Expiration Dafc: :.US/12%2
"'a Approval Date::`05%05/16
.Page S.4 of 11.4
RECOVER SYSTEM DmITATIONS:
I. All System Limitations and General Limitations shall apply. See specific deck type Notice of Acceptance for
deck type System Limitations.
2, All assemblies listed herein shall be installed in compliance with the applicable sections of FBC 1521. Uplift
performance of assemblies bonged to existing roofing system shall be verified per 1521.10. Uplift
li performance cf'as�sembfies mechanically attached through existing roofing system shall be verified per
1521.11.
GENERAL DMITATIONS:
1. Fire classification is not part of this acceptance,refer to a current Approved Roofing Materials Directory for
fire ratings of this product.
2. Insulation may be installed in multiple layers. The first layer shall be attached in compliance with Product
Control Approval guidelines. All other layers shall be adhered in a full mopping of approved asphalt applied
within the EVT range and at a rate of 2040 lbs./sq., or mechanically attached using the fastening pattern of
the top layer
3. All standard panel sizes are acceptable for mechanical attachment. When applied in approved-asphalt,panel
size shall be 4'x 4'maximum.
4. An overlay and/or recovery board insulation panel is required on all applications over closed cell foam
insulations when the base sheet is fully mopped. If no recovery board is used the base sheet shall be applied
using spot mopping with approved asphalt, 12"diameter circles,24" o.c.; or strip mopped 8" ribbons in three
rows,one at each sidelap and one down the center of the sheet allowing a continuous area of ventilation.
Encircling of the strips is not acceptable. A 6"break shall be placed every 12'in each ribbon to allow cross
ventilation. Asphalt application of either system shall be at a minimum rate of 12 lbs./sq.
Note.: Spot attached systems shall be limited to a maximum design pressure of-45 psf..
5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force(F')value of 275 lbf,
as tested in compliance with Testing Application Standard TAS 105. If the fastener value,as field-tested,are
below 275 Ibf.insulation attachment shall not be acceptable.
6. Fastener spacing for mechanical attachment of anchor/base sheet or membrane attachment is based on a
minimum fastener resist'ance value in conjunction with the maximum design value listed within a specific
system. Should the fastener resistance be less than that required,as determined by the Building Official, a
revised fastener spacing,prepared, signed and scaled by a Florida Registered Engineer,Architect,or
Registered Roof Consultant may be submitted. Said revised fastener spacing shall utilize the withdrawal
resistance value taken from Testing Application Standards TAS 105 and calculations in compliance with
Roofing Application Standard RAS 117.
7. Perimeter and comer areas shall comply with the enhanced uplift pressure requirements of these areas.
Fastener densities shall be increased for both insulation and base sheet as calculated in compliance with
Roofing Application Standard RAS 117 and/or RAS 137. Calculations prepared, signed and sealed by a
Florida registered Professional Engineer,Registered Architect,or Registered Roof Consultant (When this
limitation is specifically referred within this NOA,General Limitation#9 will not be applicable.)
8. All Attachment and sizing of perimeter nailers,metal profile,and/or flashing termination designs shall conform
with Roofing Application Standard RAS 111 and applicable wind load requirements.
9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones(i.e. field,
perimeters,and comers).Neither rational analysis,nor extrapolation shall be permitted for enhanced fastening
at enhanced pressure zones(i.e. perimeters, extended corners and corners). (When this limitation is
specifically referred within this NOA, General Limitation#7 will not be applicable.)
10. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code
and Rule 61G20-3 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No.: 16-0217.01
o
IT, Expiration Date: 05112121
Approval Date: 05/05/16
Page ll of]14