HomeMy WebLinkAboutBuilding Permit (2) f ederal Phone: 954-784-2941 RE�EVEd -Fax: 954-784-7875 OQ ngineering a;mln@fed-eng.com www.fed-eng.com ®OQ esting, Inc. •• ST. Lucie County, Permitting I DATE: 10/17/19 Order No.: 19AR024 CLIENT: Advance Roofing,Inc. ADDRESS: 1950 N.W.22nd Street, Ft.Lauderdale,FL 33311 PROJECT: FPL—Land Utilization Building ADDRESS: 6501 S.Ocean Drive; Jensen Beach,FL 34957 ASCE 7-10 DESIGN PRESSURE CALCULATIONS In Accordance with Chapter 30,Part I Proiect Information: Flat Metal Deck Height= 15' Exposure: C Ultimate Windspeed: V„u= 170 mph Length= 65' Category: II Basic Windspeed: Vnd = 132 mph Width= 44' Slope: <7° KZ= 0.85 Parapet Wall: <3' Design Calculations: Velocity Pressure: q = 0.00256*[(0.85)(1.00)(1.00)(132)1] =37.9 psf Width of Pressure Coefficient: 0.1(44') = 4.4' 0.4(15') = 6.0' } use: 4.4' Effective Wind Tributary Area: <10ft1 For parapet height 3 feet or larger,zone three(3)can be treated as zone two(2)(ASCE 7-10). External Pressure Coefficient: Internal Pressure Coefficient: 1) GCP1 = -1.0 1) GCPi = 0.18 2) GCP2 = -1.8 3) GCP3 = -2.8 Design Pressures:. File Copy Zone 1 Field: P1 = 37.9*(-1.0-0.18)= -44.7 psf Zone 2 Perimeter: P2 = 37.9*(-1.8 -0.18)= -75.1 psf Zone 3 Corners: P3 = 37.9*(-2.8 -0.18)= -113.0 psf t NE 5th Avenu •. AS rton�enmeaa,a (a" 0�/1 1 7" M®- FD OTT �� Approved Laboratory ��_ f r Page 2 10/4/19 Flat Metal Deck 6501 S.Ocean Drive Jensen Beach,FL RAS 137 Design Pressure Calculations: Row Spacing = 114 inches Fastener Spacing = 6 inches Fastener Density = 4.75 ft2 Fy = 249.4 lbs per fastener Single Ply Membrane Attachment Requirements: Based on RAS-117 and N.O.A.#16-0217.01; with a design pressure of-52.5 psf;pages 83 and 84 of 114, the following are our recommended single ply fastening requirements: Zone 1 Field: 6" o.c.@ laps in rows spaced 114" o.c. (Full Sheet) Zone 2 Perimeter: 6" o.c. @ laps in rows spaced 57" o.c. (1/2 Sheet) Zone 3 Corners: 6" o.c. @ laps in rows spaced 28.5" ox (1/4 Sheet) Notes: Comers and perimeter area dimension shall not be less than a=4.4' All work shall be in compliance with the local building code product control notice of acceptance and manufacturer specifications and the Florida Building Code 2017 edition. Wind load calculations based on ASCE 7-10 and information provided by client. All work shall be inspected by our field engineer or city inspector to verify compliance With specifications. Sincerely, " a ;Keith LeBlanc;_P.E `="° >Fedcral•Engineer ;&.Testing,Inc. -':F1ori&:R g:.I`?o. 5, 3 4 er ficaf6.'bf hutlibrzation#5471 ' Miami-Dade. 'ou_'rity Certification#18-1105.02 ,. ."7 lam. _.O.C•. O.A i* __ ry� File Cop; 1 NE 5th Avenue •. .% -- "TOR18�m.a MVI / C MIA nmE FDOn Approved Laboratory ��— y Dederal Phone: 954-784-2941 E-Fax: 954-784-7875 d0i'lnglneer)ng admin@fed-eng.com www.fed-eng.com ® Q esting, Inc. _ Dated: October 16,2019 Job Order# 19AR028 RECEIVED Advanced Roofing 1950 NW 22md Street N O V 15 2019 Ft.Lauderdale,FL 33311 Attn: Connie Scott ST. Lucie County, Permitting RE: Field Withdrawal Resistance Test FPL-Land Utilization Building 6501 S Ocean Drive Jensen Beach,FL 34957 Dear: Sirs: Pursuant to your request, Federal Engineering & Testing, Inc. (FE&T) has performed a field withdrawal resistance test in compliance with Testing Application Standard TAS-105 and the Florida Building Code High Velocity Hurricane Zone at the above referenced site. The purpose of our test was to determine the uplift capacity of the mechanical fasteners at the above referenced project. FE&T is a Miami Dade Certified Testing Laboratory (Certification#18-1105.02). On 10/15/2019 our field representative visited the referenced site and conducted ten(10) field withdrawal resistance tests on the Drill-Tech XHD screw fasteners into the metal roof deck. All tests were found in compliance with the Florida Building Code and TAS-105. See attached copies of TAS-105 forms with test results. The test results presented reflect the condition of the roof system at the time of the test. These results are time and sample dependent since roof conditions are continuously changing due to exposure to the elements. All tests were conducted according to the Florida Building Code Test Protocol TAS-105 using a calibrated Comten Industries Fastener Tester Model No.DFG 2W2000 (see attached calibration). FE&T is an independent third party providing un-biased testing information and results. FE&T is not affiliated with our client nor do we have any financial interest in the project or determination of the test results. Federal Engineering&Testing, Inc., appreciates the opportunity to be of service to you at this phase of your project. If you have any questions or comments, please give us a call. It has been a pleasure working with you and look forward to doing so in the near future. File cu r z� -eith;I'eB-anc 'f" :'o' ,�.;/:�:- r Attachments include the following: f`eu`ezal<Engineering.anl Testing Inc. _ Field Withdrawal Resistance Test Results Field Sketch ..._.. .�.n - Florida,P:r,-g.l�umber.'SI��4: . . ted,•.. Certificate,�f,.'Autbonzat'ion'#5471 Comten Calibration Miami-Dade-County Certification# 18-1105.02 Oederal OQ ngineering Florida Building Code Test Protocol TAS-105 ®Oesting, Inc. Building Code Compliance Office Testing Application Standard TAS 105-11 Field Withdrawal Resistance Test Results General Information: Job Name: FPL-Land Utilization Building Job Address: 6501 S Ocean Drive Jensen Beach,FL 34957 Contact Individual at jobsite(if any) Connie Scott Testing Agency/Equipment Information: Note: The undersigned acknowledges that all testing has been conducted and results have been reported in compliance with Florida Building Code Test Protocol TAS-105 Testing Agency Name: Federal Engineering&Testing Inc. Company Address: 3370 NE 5th Avenue, Oakland Park,FL 33334 Company Telephone: (954)784-2941 Company Fax: (954)784-7875 Representative Name: Mr.Keith LeBlanc P.E. Representative Title: Professional Eng' eer Signature: Testing Apparatus: Comten Industries Fastener:Tester Model-l3FG2W2000; T Oederal ®OQ ngineering Building/Roof System Information: Area Number: 1 Oesting, Inc. Roof Area Height 12 ft. Roof Area Length 53 ft. Second Largest Dimension 43 ft. Total Roof Area 2055 ftz 21 sq. Perimeter Area 688 ftz (See RAS 117) Building/Roof System Information: Area Number: Roof Area Height ft. Roof Area Length ft. Second Largest Dimension ft. Total Roof Area ftz sq. Perimeter Area ftz (See RAS 117) Building/Roof System Information: Area Number: Roof Area Height ft. Roof Area Length ft. Second Largest Dimension ft. Total Roof Area ftz sq. Perimeter Area ftz (See RAS 117) Oederal ' Ongineering ®Oesting, Inc. Field Withdrawal Resistance Recording Sheet Component to be secured: Area Number 1 ❑ Insulation (Refer to deck dimensions on Page No.2) ❑ Membrane Fastener Type: XHD ❑ Anchor or Basesheet Fastener Manufacturer: Drill-Tech ❑ Woodblocking Predrilled: Yes ❑ No R1 ❑ Metal Profiles If Yes,Drill Bit Size: N/A "diameter 0 Resistance Verification Only Hole Depth: N/A See Section 8 to determine number of tests(If drill is high tolerance include range in 1/1000"tolerance) Sample&Plan Initial Failure Sample&Plan Initial Failure Identifier Load(lbf) Roof Area Identifier Load(Ibf) Roof Area 1 835 C 26 2 705 C 27 3 745 C 28 4 816 C 29 5 776 P 30 6 1010 P 31 7 863 P 32 8 910 P 33 9 896 F 34 10 757 F. 35 11 36 12 37 13 38 14 39 15 40 16 41 17 42 18 43 19 44 20 45 21 46 22 47 23 48 24 49 25 50 Fastener Installation Information: Is the fastener a self driller? R] Yes ❑ No If yes, list the type of tool used for fastener installation: Cordless Drill Speed of tool: Variable rpm's Number of tests conducted: n= 10 * See Section 8 of Test Protocol TAS 105 * Note the locations of all tests on'Building Information"Detail#1,attached) Oederal OQ ngineering Mean Failure Load F= 831.30 lbf (VOQ esting, Inc. Sample Standard Deviation Sf—� 91.62 lbf Minimum Characteristic Resistance Force F'= 809.67 lbf Notes: 1)Use of the results herein to determine the required number of fasteners for insulation attachment or an acceptable anchor or base sheet fastener spacing,as outlined in RAS 117,shall utilize the minimum characteristic resistance force(F),determined in compliance with Section 9 of TAS 105.No margin of safety shall be applied to field withdrawal resistance test results determined in compliance with TAS 105. 2) A safety factor of 2 to 1 shall be applied to all results of laboratory testing. 3) The following pages shall be completed for each roof area and included with all Field Withdrawal Resistance Test Recording Sheets. Roof Area 1 (If no parapet wall exists insert"N/A") 1 Foot y 12 Feet Ground Level Building Information-Detail# 1 J f _.._...-_.__.._ „___.._...,.-._. .-- __-...:-------- -^sem.._ .'_"'_--__•_ ._.-,._-. _ -. .T""'_'•�._.... - -- ..,.r__,_......_.«.._.._-._�...__-..._,_-...-._.._..._--_._._..... ---_-...—.-_-...-._..n..._.__=.�-- '311 -_''_-_•n_--«..—...-.-.._.v._-. = • _.;.... _- __.-�_��-. _-i•-_.r-_...._._a.•-_nom•-•._-...___.'.._.._'_._._.i..-_... _�_... .. �_ _ S 4 1 , _ , • NTS-JobAddress-City,State Products&Solutionsfor the Weighing Industry c ardinal. Miami Branch"Office,**Sales,*Service, Rentals Cardinal Scale Manufacturing Co. CERTIFICATE OF CALIBRATION OWNER OF ITEM: FEDERAL ENGINEERING REPORT NO.: 34050 SCALE TYPE: PUSH/PULL TESTER CALIBRATION DATE: 08/28/19 MANUFACTURER: COMTEN/ASHCROFT RECALIBRATION DUE: NOVEMBER 2019 MODEL NUMBER: DFG2W2000 TECHNICIAN: SCOTT SERIAL NUMBER: 21408"/WT#1 CAPACITY: 2,000 LB PROCEDURE USED: TEST WEIGHT DIVISIONS: .1 LB THIS DOCUMENT CERTIFIES THAT THE ABOVE INSTRUMENT HAS BEEN TESTED AND FOUND TO BE WITHIN 5%OF THE FIRST 500 LB.OF A TEST LOAD AND WITHIN 10%OF A TEST LOAD BETWEEN 501 LB AND 2,000 LB THE STANDARDS USED ARE ALSO TRACEABLE TO THE NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY(NIST). STANDARDS CALIBRATION DATE: 1112312017 FLORIDA STATE CERTIFICATION NO.: 137 CARDINAL o DETECTO Miami Branch Office: 3215 NW 20tl)Terrace,Suite 203 - Oakian'dPark,FL33309 EPA AF"nwo"Of jo m - www.6idinaiScale.domPhone: ; . )ederal Phone: 954-784-2941 E-Fax: 954-784-7875 031.6 i n ee ri n g admin@fed-eng.com www.fed-eng.com (gesting, Inc. WEIVE® NOV 16 2019 Dated:November 13, 2019 Sr. Lucie county., Permittinljp) Order# 19AR025 Advanced Roofing 1950 NW 22rnd Street Ft. Lauderdale, FL 33311 Attn: Connie Scott RE: TAS-126 Roof Moisture Survey FPL- Land Utilization Building 6501 S Ocean Drive Jensen Beach, FL 34957 Dear Sirs: In accordance with your authorization, Federal Engineering & Testing, Inc. has performed a Roof Moisture Survey in compliance with TAS-126 and the Florida Building Code Section 1521.12 on October 15, 2019 at the above referenced project site. The purpose of our survey was to determine the moisture content of the exterior roof. This is a roof moisture survey only and is not considered a roof top inspection. The subject building consists of a C.B.S. structure with a built up roof system over perlite insulation over ISO insulation over a metal roof deck. On FOctober 15, 2019 our field engineer visited the site and conducted a nuclear moisture survey. In addition, 4 core samples were secured to verify the oven dried moisture contents. All tests were performed according to the Florida Building Code Section 1521.12, Protocol TAS-126 and the Roof Consultants Institute "Standard Practice for the Detection and Location of Latent Moisture in Building Roofing Systems by Nuclear Thermalization" using a Troxler Model 3216. Pursuant to the Florida Building Code Section 1521.12; the moisture content of the existing roof .system shall not exceed 5% by weight in the roof membrane and 8% by weight in the insulation system. File COPY �3370 NE 5th Avenue I OaklandPark Florida 33334 (�ci MIMIAM FDOTT MSN70 RIBImemftl ■ ,J Approved Laboratory OQ ederal 1Ongineering November 13,2019 FPL-Land Utilization Building 8c ®esting, Inc. 6501 S Ocean Drive Jensen Beach,FL 34957 Page 2 The following is a summary of the core test results: Oven Dried Gravimetric Analysis % Moisture Core Number 1 2 3 4 Grid Core Locations D-9 E-5 H-4 1-1 Built Up Roof 0.9 0.4 0.4 0.2 Perlite Insulation 1.5 1.5 1.7 1.7 ISO Insulation 2.1 3.1 3.5 4.3 Nuclear Reading 5 14 18 32 The moisture content of the existing roof was in compliance with the Florida Building Code Section 1521.12 and Protocol TAS-126 at the time of the inspection. No grid locations were found with trapped moisture greater than 5% in the roof membrane layers or 8% in the insulation layers. (See attached roof top plan for locations of corings and results of each test grid). The test results presented reflect the condition of the roof system at the time of the test. These results are time and sample dependent since roof conditions are continuously changing due to exposure to the elements and roof top traffic. It has been a pleasure serving you at this phase of your project and look forward to doing so in the near future. � G6„�` M i S�rcEl Ely, Q o ,' J s f c r f C r f rs t e1t� LeBlane,PEr ,,, ,a. S �16ral Esagineerind-A'�" testing, Inc. S rI �ic('a F2eg. Num���X9394 Q _. f CeititGte of Auhorization 5471 IVliaml Dads Coun±y Certification#18-1105.02 , Cac!'Aar F"140 4 � 4' M®DARE FDGnT �® Approved Laboratory Moisture Gravimetric Analysis Qederal Client: Advanced Roofing Ongineering Address: 1950 NW 22rnd Street ®Oesting, Inc. Ft. Lauderdale, FL 33311 Work Order#: 19AR025 Project: FPL-Land Utilization Building Field Test Date: October 15, 2019 Project Address 6501 S Ocean Drive Laboratory Date: October 16, 2019 Jensen Beach, FL 34957 Test & Location Description Weight Before Drying Weight After Drying Moisture Weight Percent (%) Moisture Core 1 Grid Point Built Up Roof 9.91 9.82 0.09 0.9 Perlite Insulation 4.89 4.82- 0.07 1.5 5 D-9 ISO Insulation 3.36 3.29 0.07 2.1 Core 2 Grid Point Built Up Roof 13.38 13.33 0.05 0.4 Perlite Insulation 2.00 1.97 0.03 1.5 14 E-5 ISO Insulation 2.69 2.61 0.08 3.1 Core 3 Grid Point Built Up Roof 19.19 19.12 0.07 0.4 Perlite Insulation 2.43 2.39 0.04 1.7 18 H-4 ISO Insulation 2.36 2.28 0.08 3.5 Core 4 Grid Point Built Up Roof 75.11 74.99 0.12 0.2 32 I-1 Perlite Insulation 2.91 2.86 0.05 1.7 ISO Insulation 1.94 1.86 0.08 4.3 Federal Engineering & Testing Inc. 13370 NE 5th Ave Oakland Park, FL 33319 1954-784-2941 TAS 126 Nuclear Moisture Survey Drawing Oederal . Ongineering ®Oesting, Inc. A B C D E F G H I 1 9 9 8 12 14 14 _13 15 32 2 10 7 10 8 10 8 9 13 15 3 7 8 7 7 10 11 7 9 18 4 6 9 8 9 12 13 12 18 11 0 ❑ ❑ N 5 6 8 11 9 14 8 10 11 12 0 6 8 7 7 7 7 6 8 7 6 9 7 7 10 7 9 8 7 7 11 8 8 9 13 9 6 O5 10 7 8 8 6 10 9 11 0 9 9 10 8 10 11 9 8 11 8 8 13 11 Histogram Project Info 18 Mean: 9.64 16 Standard Deviation: 1 3.59 14 Name: FPL-Land Utilization Building 12 Address: 6501 S Ocean Drive a 10 Jensen Beach, FL 34957 Z 8 Legend " 6 = Roof Section O = Pipe 4 = A/C Unit ® =Drain 0 # = Cores M =Ponding Water El 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 '$% Moisture G� =Scupper Nuclear Readings ® =Vents ❑ =Mech.Vent �3 = Roof Hatch A' t RE"'" C! GAF WATER BLOCK EVERGUARD® CAULK NOV � 62019 DRILL-TEC TERMINATION BAR S r.Lucie County,Qermittin FASTENED 12"O.C.W/DRILL-TEC FASTENERS CAULKING BY OTHERS EVERGUARD®BONDING ADHESIVE 1 (0 P -1), * --- REGLET OF SURFACE MOUNT COUNTERFLASHING -FASTENED 8"O.C. -- DRILL-TEC'" PLATES& SCREWS 12"O.C. EVERGUARD REINFORCED MEMBRANE HEAT WELDED LAP EVEGU R ARD REINFORCED 6R in. MEMBRANE EXISTING ROOFING STEEL DECK NOTE: 1.EXISTING REGLET IS ACCEPTABLE IF METAL IS IN GOOD CONDITION. 2.FOR INSULATION THICKNESS GREATER THAN W,CONTACT GAFMC CONTRACTOR SERVICES FOR ALTERNATE MEMBRANE ATTACHMENT REQUIREMENTS. 3.PLATES&SCREWS 6"O.C.READ FOR BA SYSTEMS. 4.COUNTERFLASHING REQUIRED FOR 20 YEAR SYSTEM. 5.APPLY EVERGUARD® TPO CUT EDGE SEALANT TO ALL CUT REINFORCED TPO • EDGES(REFER TO DETAIL MAIBA(FA 116). .File cop , DRAWING# PARAPET WALL FLASHING WITH MA/FA/BA 301 W- i )RQOFIN GusrdES SYSTEMS® COUNTERFLASHING FIN caF►umMs SCALE ISSUE/REVISION TE CORPORMPON N.T.S. 11-01-06 www.gatcam C INTERMITTENT FASTENING KEY NAIL CLIP 54"WITH BONDING 12"Q.C. p ADHESIVE 18"DRY BA DE -- COPING CAP-STAINLESS STEEL EVERGUARD'BONDING ADHESIVE(OPTIONAL) r Ii r EVERGUAREf REINFORCED ;..: MEMBRANE —•—DRILL-TEC'"PLATES& SCREWS 12"O.C. HEAT WELDED LAP —EVERGUARD'REINFORCED MEMBRANE 8" in. r� EXISTING ROOFING STEEL DECK ALTERNATE BASE REFER TO 307 _x' , NOTE: 1.FOR INSULATION THICKNESS GREATER THAN 8",CONTACT GAFMC CONTRACTOR SERVICES FOR ALTERNATE MEMBRANE ATTACHMENT REQUIREMENTS.THESE METHODS MAY INCLUDE THE USE OF A HARD BOARD COVERING THE ASSEMBLY OR USE DETAIL MA/FA/BA 307. 2.PLATES&SCREWS 6"O.C.REQ'D FOR BA SYSTEMS. 3.APPLY EVERGUARD0 TPO AND PVC CUT EDGE SEALANT TO ALL CUT REINFORCED TPO AND PVC EDGES(REFER TO DETAIL MA/FA/BA 115). DRA'NfNG N )EverGuard' COPING CAP MNFA/BA 501 ROOFING SYSTEMS SCALE ISSUEl RENSION DATE GAF MATERIALS CORPORATION N.T.S. 7-01-07 waw.gsf.wm --24 GAUGE CONTINUOUS HOOK STRIP SECURED WITH DRILL—TEC'" FASTENERS @ 12"O.C. —EVERGUARD COATED METAL GRAVEL STOP WITH HEMMED EDGE GALVANIZED ANGULAR RING SHANK NAIL @ 4"O.C.STAGGERED OR DRILL-TEC'" SCREWS 12"O.C. HEAT WELDED LAP WOOD NAILER I EVERGUARD S"WIDE MEMBRANE FLASHING STRIP HEAT WELDED LAP EVERGUARD® REINFORCED MEMBRANE . ......................... .. .................. . ......... . C ......... ............................... ....................................... d� EXISTING ROOFING STEEL DECK i 1.APPLY EVERGUARD® TPO CUT EDGE SEALANT TO ALL CUT REINFORCED TPO EDGES(REFER TO DETAIL MA/FA/BA 115). GRAVEL STOP COATED METAL ROOF DRAWINti# MA/FA/BA 202 "j )EverGusrd" EDGE ROOFING SYSTEMS S ISSUEI REVISION DATE WF MATEEMS CORRPDRAmoN N.T.S. 11-01-W waw.geroom - - TEVERGUARD�CAULKING --EVERGUARD®COATED METAL SCUPPER DRILL-TEC` FASTENERS 6"O.C. UNREINFORCED FIELD FABRICATED CORNERS HEAT WELDED(OPTION 1) ----CONTINUOUS HEAT WELDED LAP J PREMANUFACTURED OUTSIDE CORNERS-HEAT WELDED(OPTION 2) j I EVE GUA E B NE R RD MMRA f -TYPICAL BASE ATTACHMENT CONTINUOUS PERIMETER HEAT WELDED LAP fill I (� EVERGUARD' REINFORCED MEMBRANE EXISTING ROOFING j 1 STEEL DECK l NOTE: 1.REMEMBER TO INSTALL EVERGUARD®UNREINFORCED OR PREMANUFACTURED OUTSIDE CORNERS TO THE SCUPPERS'FOUR ROOF SIDE CORNERS, 2.OPTIONS 1&2 EITHER PRE-FAB OR FIELD FAB. 3.PLATES&SCREWS 6"O.C.REQ'D FOR BA SYSTEMS. 4.APPLY EVERGUARD'TPO AND PVC CUT EDGE SEALANT TO ALL CUT REINFORCED TPO AND PVC EDGES(REFER TO DETAIL MA/FA/BA 115)IF l NEEDED. DRAWING N �JmverGuard* COATED METAL WALL SCUPPER MA/FA/BA 311 ROOFING SYSTEMS SCALE ISSUEi REVISION DATE CORPORATION N.T.S. 11-01-46 wwwgaf.cUm i REFER TO PARAPET AND WALL DETAIL FOR TERMINATION EVERGUARD'COATED METAL r' WITH HEMMED EDGE j t DRILL-TEC'" FASTENERS � i S DRILL-TEe PLATES& f:.. SCREWS 12 O.G. `...-::::::: ............ ................... ...........:.........:..... ........:....:.:::............ STANDARD EVERGUARD MEMBRANE A::............ .................................. ............................... ............. ::::•:; ': ;:;;;;: ;o:;•;:;::.:•... FIELD FABRICATED E:VERGUARO MEMBRANE ---- 1 ...................................... ................................_....................... EVERGUARD REINFORCED MEMBRANE DRILL-TEGm PLATES& .�::..... .... ` SCREWS 12"O.C. �.... r —HEAT WELDED LAP I I I #C f r E GU RD REINFORCED 5i:.iiii}:. i ?:.:i.?:i.i:�::i1:_is�i:�riii:�i:�:�?:�1:��r.:�:�::::'. MEMBRANE ::::::::::.-::: •:r:::::.:::::.::::•.:.. ........................... .............. EXISTING ROOFING STEEL DECK WOOD NAILER NI}N�2 SEC O DECK PTIONAL) NOTE 1.DETAIL TO BE USED IN CONJUNCTION WITH STANDARD GUIDE SPECIFICATION CONTAINING REQUIREMENTS FOR NAILERS,INSULATION ETC. 2.APPLY EVERGUARD® TPO CUT EDGE SEALANT TO ALL CUT REINFORCED TPO EDGES(REFER TO DETAIL FD 115). DRAWING# )&erGuard® METAL OPEN TOP OVERFLOW SCUPPER MA/FA/BA 323 ROOFING SYSTEMS GVMATERWB SCALE ISSUE/REVISION DATE CORP°RNnDN N.T.S. 11-01-06 w�►W.gaLcam STAINLESS STEEL CLAMP VENT STACK EVERGUARD® CAULKING -SAF WATER BLOCK EVERGUAR6 PREMOLDED BOOT DRILL-TEC''PLATES&SCREws 4 PER STACK HEAT WELDED LAP EVERGUARD® REINFORCED MEMBRANE EXISTING ROOFING STEEL DECK NOTE: 1.DO NOT CUT PREMOLDED BOOT. IT MUST BE PULLED OVER VENT PIPE. Z TPO SELF,ADHERED PIPE BOOTS MAY BE USED WITH TPO SYSTEMS FOR UP TO A 15 YEAR GUARANTEE. 3.IF THE PLATES AND FASTENERS INTRUDE INTO BOOT FLANGE AREA,THEN ATARGET MUST FIRST BE INSTALLED OVER PLATES AND FASTENERS BEFORE BOOT INSTALLATION. 4.APPLY EVERGUARDf TPO CUT EDGE SEALANT TO ALL CUT REINFORCED TPO EDGES(REFER TO DETAIL MAIFAIBA 115). DRAWING# Lit �EvvarGuard® PREMOLDED PENATRATION FLASHING MA/FA/BA 506 ROOFING SYSTEMS S ISSU REVISION DATE W MIATERM `O�",nDN N.T.S. 11-01-06 wuuw.getcam • � . . • Form NOV 2019 ■ :11 1 :11 � . /AAAM:MMAQQ:N: : M :: RICAN::::A w MANN AN AC■MAMA . ■AQ AA::Q iCMM■�■■M ■ M ■ QiEE EEE ■ ■'■MMM■ ■QE CriCCCCE:CC �QMA:g:EEEME EEOC■AM= M ■ `1� . . A.1 1 ■■.Q ■ E�Q M M ■ .MM . A A ■CAQM�� ■� E EEC M:■C CAAM ■ MCE:M MM Q ■ MM M M EeA MM C WQMMQ CE ■AEQ� EEa M . ..Q Q M .MA .. 11 r EC AMEQ■■E am a C■EQ EECMM■ C C QE��E E MM Q 111E:Q aQEE0 :ME R' EMCA.CA ::CEE MMQCCA.M. .AAM■ME EM� .A QEQ . ..A QA Q��.I QM .MQ Q EI i MMMAMC.M M M CCC: :::':MC■ MM MC Q■MM .■.MC MM /CC AAACQC MQQCQC ECEC . A ::CE: CEE QQCE CEE QMA �E E : MAC:QEE E'QEEEE ■ MA ■ ■ .. ■MM. EE " aj A : EEEE� E::E::.QA E E EMMEMCECE QQEnAz CSE ■ /■ MME . I CQA M moll MR ■E.M EAE . _ MM M ■M M .� ■ / ■ �ANN A EQ E ■ ■ ■ ■ AMM A CM MCC /■� ��■■ 1 Q AA �E Q E Q M . ■E AM ■ ■ :EA ■ EM MAME ■A rA M C C EEM. EE ■AE E E■ EQE M Q A A EIng..E...M c . ■ ■ .QQ QQQE :Slow ::EEE AEQ:QQ.E QE:: EQE QME:;:,.�QQE:. ::CQ:MM EC. A CQEQ : M MQ�AA C ■CAEQQAA■EE' M:MQ A :'CaCC EE�-:CC AMM : / MMA E CME CAC E AQA QE AMC ■ Q ■ ■ QMH ■ Q E EE E AQ EEM :E:Q Q ■E �: E�QQ � �MM AQ Q . ■ - � :,�.EE� �_r�E��e.. QE QaQ E E. QE =5t°aE ►�EIiI tt �i ii in/■-_n'-r�� I -/�ii ��E5 �z r �. AQ M A ..0 a CQA` NCA,.CC I�AMIn M::CA• , C'C'A iEEC° ,� ■ EE E E ' Q .A.�A E M CMAC QA AQ ■ E :■: M ■ �: E A ■ C.QEMQ CA : ■M�C EAC. ■■. E M MCC C EQE A. .. E'E E :CCAEE EE..Q E / . �QE A M ■ E AC A A AA M ■ A.E Q Q E AEE EE �A E: • C�C a IEEE E / C . Q■E : QA .. EE■ M ■ : EE r � M ■ C: EEC : *Q' E C ■ ■ E : CQ � � M ■M A . � AN ■ . . C Mt EQ M Q t.ma .. A E r :.:M■ AMf■A - Scuppers 44' 17' Drip Edge W. 17' 31' 65' 7' 30' 38' Scuppers ROOF PLAN LAND UTILIZATION BUILDING File Copy Florida Building Code 6th Edition (2017) High-Velocity Hurricane Zone Uniform Permit Application Form Section C (Low Sloped Roof System) Fill in Specific Roof Assembly Components Fastener Spacing for Anchor/Base Sheet and Identify Manufacturer Attachment (If a component is not used,identify as"NA') Field: 6 "oc @ Lap,#Rows 1 @ 114"oc System Manufacturer. GAF Perimeter:J___oc @ Lap,#Rows 1 @57 "oc NOA No.: 16-0217.01 Comer._-L- @ Lap,#Rows 1 @ 28.Soc Design Wind Pressures,From RAS 128 or Calculations: Pmax1: -44.7 Pmax2: -75.1 pmax3: -113.0 Number of Fasteners Per Insulation Board Max.Design Pressure,From the Specific NOA System: -52.5 Field Perimeter__Comer_ Deck Illustrate Components Noted and Type: Recover(Steel Decd Details as Applicable: Gauge/Thickness: Woodblocking, Gutter, Edge Termination, Stripping, Flashing, Continuous Cleat, Cant Slope: 1/4"/Ft. Strip, Base Flashing, Counter- Flashing, Coping, Etc. Anchor/Base Sheet&No.of Ply(s): NA Indicate: Mean Roof Height, Parapet Height, Height of Base Flashing, Component Material, Anchor/Base Sheet Fastener/Bonding Material: Material Thickness, Fastener Type, Fastener NA Spacing or Submit Manufacturers Details that Insulation Base Layer. DensDeck Comply with RAS 111 and Chapter 16. Base Insulation Size and Thickness: 4'x8'- 1/2" Base Insulation Fastener/Bonding Material: Preliminary Attachment-4 per 4'x8' Board Top Insulation Layer: NA FT. <3' Top Insulation Size and Thickness: NA Parapet Top Insulation Fastener/Bonding Material: Helaht NA Base Sheet(s)&No.of ply(s): NA TPO Membrane DensDeck Roof Board I FT. 15' Base Sheet Fastener/Bonding Material: NA Existing Roofing Mean Ply Sheet(s).&No.of Ply(s). NA RoofHeight Ply Sheet Fastener/Bonding Material: A Top Pty: EverGuard TPO Membrane-60 Mil Top Ply Fastener/Bonding Material: Drill-Tec 2 3/8" Barbed XHD Plates& Drill-Tec XHD Fasteners Surfacing: NA File COPY