R301.2.1.2
Wood structural panel schedule to include:
1. Window opening size
,2. Panel,size and Panel type (thickness)
3. Space dimension between panel & window
j4. Panel type, thickness
5. Fastener type and spacing based on table R301.2.1.2
6. Exterior wall type (ie wood frame/cmu)
I
I
I
j
I
i
I ,
Home I Hardware I Fasteners I Specialty Fasteners / Composite Fasteners
ITO
' _
rl AP
Home / Hardware / Fasteners / Specialty Fasteners / Composite Fasteners
I
I
I Qlm
1 , �, ..
Plywood Hurricane Panels
Wood structural panels with a minimum thickness of 7/16 inch and a maximum span of 44"between lines of
fasteners shall be permitted for opening protection in one and two-story buildings. Panels shall be precut and
pre-drilled to cover the window openings with attachment hardware permanently installed on the building.
The panels must lap over the sides of the walls at least 3 inches for wood frame construction and 3 %2" for
masonry.or concrete construction. Do not fit the shutters inside the opening.
1) FASTENER SIZE—1/4 inch diameter.
2) FASTENER LENGTH—must go 2 inches deep into the wall.
3) FASTENER SPACING—no more than 16 inches apart.-
4) FASTENERS—must be vibration-resistant&permanently installed.
5) FASTENERS—must be corrosion resistant.
For larger openings or other code approved shutters and panels, please submit the certified test report or
certification by an engineer. For more information refer to.Florida Building Code (Sec. 1609.1.2).
1-Inch minimum
woodframe 2 inches minimum
1.54nch minimum
masonry/concrete
Edge of opening
i
Fasteners required to be installed
I�r I on the longer side of the panel.
r 1s
r
I 1 `
l
L TM aximum 16 inches on center U
J.
T:
Maximum 44 inches
between lines of
-fasteners �?
c
Wood structural panel opening protection attachment
I
* Please note--Maximum 44 inches between lines of Fasteners.