EVALUATION REPORT
Onduline North America, Inc.
4900 Ondura Drive
Fredericksburg, VA 22407
Evaluation Report 039230.10.11-RZ
FL4081-R3
Date of Issuance: 10/27/2011
Revision 2: 08/24/2016
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
thcompliance with the 5 Edition (2014) Florida Building Code sections noted herein.
DESCRIPTION: Ondura® and Onduvilla® Corrugated Asphalt Roofing Systems
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the
referenced Quality Assurance documentation changes. Trinityl ERD requires a complete review of this Evaluation Report
relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 4, plus a 16-page Appendix.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
et'A'YY /'fp'*'44
:%22.0.- .2....>%*07.kNo-391,8-' ..s $../
-
=
E-i - * . ircE
t&\ "- sTATE »Op ...41
444'14·T..•··24-:
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 08/24/2016. This does not serve as an electronically signed
document. Signed, sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF |NDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity l ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity l ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither TrinityI ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically forthat purpose.
\J TRINITY ERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category:Roofing
Sub-Category:Products Introduced as the Result of New Technology
Compliance Statement: Ondura and Onduvilla® Corrugated Asphalt Roofing Systems, as produced by Onduline
North America, Inc., have demonstrated compliance with the following sections of the Florida Building Code through
testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and
Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
1504.3
1504.3
1504.6
3. REFERENCES:
Entitv
ICC-ES (EVL 2396)
ITS (TST 1509)
ITS (TST 1509)
ITS (TST 1509)
QAI (TST 9808)
QAI (QUA 7628)
Propertv
Wind
Wind
Physical Properties
Examination
IBC /IRC Compliance
Wind
Physical properties
Wind
Physical properties & wind
Quality Assurance
Standard
UL1897
FM 4470
ASTM G 154
Reference
ESR-1957
50484-C7-706400
50484-C7-706400
3181925COQ-003
RJ3539-1
Service Confirmation
Year
2004
1992
2006
Date
06/01/2016
10/11/1990
10/11/1990
08/26/2009
06/01/2015
07/13/2016
4. PRODUCT DESCRIPTION:
®
The following Ondura and Onduvilla® Corrugated Asphalt Roofing Systems are mechanically attached to an
approved substrate, as outlined in the Limitations / Conditions of Use herein.
®
> Ondura Corrugated Asphalt Roofing Sheet are corrugated sheeting made from mineral and organic fibers
impregnated with asphalt. Sheets are nominal 0.123-inch thick and measure nominal 48 x 79 inches with a
finished weight of 0.68 lb/ft2. Sheets have continuous 1.375-inch deep corrugations spaced 4-inch o.c. along
the sheet length.
Exterior Research and Design, LLC.
Certificate of Authorization #9503 FBC NON-HVHZ EVALUATION
Evaluation Report 039230.10.11-R2
FL4081-R3
Revision 2: 08/24/2016
Page 2 of 4
\J TRINITY IERD
® ®
> Ondura Corrugated Asphalt Roofing Tile are the same as Ondura Corrugated Asphalt Roofing Sheet, but
19.75-inch long.
®
> Onduvilla and Onduvilla® FR Corrugated Asphalt Roofing Tiles are corrugated sheeting made from mineral and
organic fibers impregnated with asphalt. Sheets are nominal 0.113-inch thick and measure nominal 42 x 15.75
inches with a finished weight of 0.60 lb/ft2. Sheets have continuous 1.5-inch deep corrugations spaced 7.5-inch
o.c. along the sheet length. Onduvilla® FR Corrugated Asphalt Roofing Tiles have a secondary fire-retardant
coating applied to the top surface.
Exterior Research and Design, LLC.
Certificate of Authorization #9503
Photograph No. 1
Anthracite Black Roof Tile
Photograph No.2
Slate Gray Roof Tile
Photograph No.3
Florentino Roof Tile
FBC NON-HVHZ EVALUATION
Evaluation Report 039230.10.11-R2
FL4081-R3
Revision 2: 08/24/2016
Page 3 of 4
8.
9.
\J TRINITY ERD
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityIERD nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for
permitting or design guidance unless retained specifically forthat purpose.
5.2 This evaluation report is not for use in HVHZ.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory
for fire ratings of this product.
5.4 The minimum roof slope per manufacturer's installation instructions is 3:12 (14').
5.5 The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural
members shall be in accordance with FBC requirements to the satisfaction of the AHJ. Load resistance of the
roof deck shall be documented through proper codified and/or FBC Approval documentation.
5.6 Appendix 1 outlines attachment requirements for design wind pressure resistance. "MDP" = Maximum Design
Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for
determination of design wind pressures. The MDP for the selected assembly shall meet or exceed the design
wind pressure requirements for the project for each pressure zone of the roof.
5.6.1 Reference to indicates the system performance exceeds requirements for that pressure zone. Reference
to "NO" indicates additional testing or rational analysis by a qualified design professional is required to
address that particular pressure zone.
5.7 For existing roof decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified
design professional shall review the data for comparison to the minimum requirements for the system.
5.8 Perimeter and ridge details shall be designed and installed to resist the wind load requirements of FBC
Chapter 16.
5.9 All products in the roof assembly shall have quality assurance audit in accordance with the FBC and F.A.C. Rule
61G20-3.
6. INSTALLATION:
6.1 Ondura and Onduvilla® Corrugated Asphalt Roofing Systems shall be installed in accordance with Onduline
North America, Inc. published installation instructions, subject to the Limitations / Conditions of Use noted
herein.
6.2
6.3
System components, including the sheets, tiles and fasteners shall be as supplied by Onduline North America,
Inc.
System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum
Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects
the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been
applied). Refer to FBC 1609 for determination of design wind loads.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
MANUFACTURING PLANTS:
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements.
QUALITY AssuRANCE ENTITY:
Quality Auditing Institute, Ltd. - QUA7628; (604) 527-8378
- THE 16-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT -
Exterior Research and Design, LLC.
Certificate of Authorization #9503 FBC NON-HVHZ EVALUATION
Evaluation Report 039230.10.11-R2
FL4081-R3
Revision 2: 08/24/2016
Page 4 of 4