REPORTEVALUATION
APOC,sub of Gardner Asphalt Corp. Evaluation Report 1-GG-18-001.02.18-R2
4161 E.7th Avenue FL26482-R2(NON-HVHZ)
Tampa, FL 33605 Date of Issuance:02/27/2018
(813)248-2101 Revision 2:06/19/2019
SCOPE'
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E.for use of the product under the Florida Building Code and Florida Building Code,Residential Volume. The products
described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted
herein.
DESCRIPTION: Gardner® Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E.of any changes to the
product(s),the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a complete review of
this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOIetc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 7.
Prepared by:
Y.
i
C4Q'.yi V��,e moi/°•.
Robert J.M.Nieminen,P.E. ==;'c` `rra: The facsimile seal appearing was authorized by Robert
•I'%E�^ :��� ' '.• Nieminen,P.E.on 06/19/2019.This does not serve as an
Florida Registration No.59166,Florida DCA ANE1983 ,.. „ .,,,:
•-'e. ....`.ii� electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEMO ETC,LLC does not have, nor does it intend to acquire or will it acquire,a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC,LLC is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO ETC,LLC nor Robert Nieminen,P.E.are,in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose. lb 0 — 1 *
°� FOR o
r�.11 Si Wtl aNp C�y(yq� File ®��
'% tom' f' �i NT tl
w, C", lVl
NEMO etc.
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Underlayment
Compliance Statement: Gardner®Roof Underlayments,as produced by Gardner Asphalt Corp.,have demonstrated
compliance with the following sections of the 6u'Edition(2017)Florida Building Code through testing in accordance
with the following Standards. Compliance is subject to the Installation Requirements and Limitations/Conditions of
Use set forth herein.
STANDARDS:2.
, Section_" Pro er Stantlard Year
�, � � , _R _ .. ._ _.. �.. ,. ._.
1504.3.1 Wind uplift UL1897 2012
1507.1.1,R905.1.1 Exception Mechanical properties ASTM D226 2009
1507.1.1,R905.1.1 Exception Tear Strength ASTM D4533 2015
1507.1.1,T1507.1.1,1507.2.9.2, Physical Properties ASTM D1970 2015
R905.1.1,TR905.1.1,R905.2.8.2
1507.3.3,R905.3.3 Physical Properties FRSA/TRI April 2012(04-12) 2012
TAS 110 Accelerated Weathering ASTM D4798 2011
3. REFERENCES:
En_ ttY, Examination Reference Date _
PRI(TST5878) ASTM D1970 µ GGI-178-02-01 mT A mmm^µ10/24/2016 ^
PRI(TST5878) ASTM D1970 GGI-176-02-01 02/03/2017
PRI(TST5878) ASTM D226 GGI-194-02-01 08/03/2017
PRI(TST5878) ASTM D1970 GGI-178-02-01 11/02/2017
PRI(TST5878) ASTM D4798 GGI-178-02-02 01/26/2018
PRI(TST5878) ASTM D1970 GGI-132-02-06 12/11/2017
PRI(TST5878) ASTM D226 GGI-199-02-02 12/11/2017
PRI(TST5878) Tensile-Adhesion/Long Term Aging GGI-201-02-01 01/26/2018
PRI(TST5878) FRSA/TRI April 2012(04-12) GGI-196-02-01 03/27/2018
PRI(TST5878) UL1897 GGI-212-02-01 05/09/2018
PRI(TST5878) Peel adhesion GGI-209-02-01 05/18/2018
PRI(TST5878) Peel adhesion GGI-211-02-01 06/06/2018
PRI(TST5878) Tensile-Adhesion/Long Term Aging GGI-202-02-01 08/09/2018
PRI(TST5878) UL1897 GGI-243-02-01 05/29/2019
PRI(QUA9110) Quality Assurance Service Confirmation 01/27/2017
4. • •• DESCRIPTION:
Product Specification Plants Descrlption w
4.1 Gardner®Gard-Lock ASTM D1970 Springville, nominal 60-mil thick,glass-fiber reinforced,polymer
AL modified asphalt,granulated self-adhering underlayment
4.2 Weather-Armor®FT3 FRSA/TRI Springville, nominal 60-mil thick,self-adhering membrane of elastic
Tile Underlayment April 2012 AL polymers,bitumen and polyester and glass reinforcement
4.3 Eagle-Armor by Apoc FRSA/TRI Springville, nominal 60-mil thick,self-adhering membrane of elastic
April 2012 AL polymers,bitumen and polyester and glass reinforcement
4.4 Weather-Armor®HT3 ASTM D1970 Springville, nominal 60-mil thick,self-adhering membrane composed
High Temp Premium AL of elastic polymers,bitumen,glass reinforcement and a
Roof Underlayment cross-laminated sheet surface
NEMO ETC,LLC Evaluation Report 1-GG-18-001.02.18-R2
Certificate of Authorisation 1132455 0 EDITION(2017)FBC NON-HVHZ EVALUATION FL26482-RZ(NON-HVHZ)
Gardner®Roof Underlayments;(813)248-2101 Revision 2:06/19/2019
Page 2 of 7
NEMO etc.
' s FrQductSpec cation i escription
4.5 Weather-Armor®SB-1 ASTM D1970 Springville, nominal 60-mil thick,glass-fiber reinforced,polymer
Self-Bond®Roof AL modified asphalt,granulated self-adhering underlayment
4.6 Gator-Skin''Synthetic FBC 1507.1.1 Hangzhou, synthetic roof underlayment comprised of layers of
Roof Underlayment &R905.1.1 China polyolefin film
(Exception)
4.7 Gator-Skin 1011 FBC 1507.1.1 India synthetic roof underlayment comprised of layers of
Synthetic Roof &R905.1.1 polypropylene film
Underlayment (Exception)
4.8 Weather-Armor® FBC 1507.1.1 Hangzhou, hybrid underlayment comprised of two layers of
Crossover CX-L &R905.1.1 China polyolefin and polyester synthetic fabric with a layer of
Premium Hybrid Roof (Exception) modified bitumen between the two
Underlayment
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way,the Designer
of Record for any project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report;refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Gardner®Roof Underlayments may be used with any prepared roof coverwhere the product is specifically referenced
within FBC approval documents. If not listed,a request maybe made to the Authority Having Jurisdiction for approval
based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable Roof Covers:
TABLE 10- ROOF CpVEROPTIONS
Undertayment` 5 Shingles .. ....Nai10n Tite, ,;Foam On„foie Metal.; &Shingles Slate
G 'f)te�®£iBrCiCOCK_,_..,. YES NO NO YES YES YES
Weather Arrrsor�FT3_T le
lnder)ayrnent Or8t = YES YES Yes (See 5.5.1) YES YES YES
Armarfby Apoc-
YES
Weather Armor®HTHI$h : (as base sheet or
Temp Premium ROOF` YES mid-ply in multi- NO YES YES YES
Underiayinent ply system per
f= 6.3.2)
WeaileY-Arrrtor®58 S2If YES NO NO YES YES YES
y Bondi Roof Underiayment
Gatrr Skln�""SyntheticRoof-
yYES NO NO YES YES YES
Urleeriayment z
Gator Sian J 0'”"Synthetic YES NO NO YES YES YES
Roof Uniierlayment ..
Weather Armor° YES
Crossover CX L Premium a YES las base sheet in NO YES YES YES
multi-ply system
HybFld Roof:t)nderlayment j per 6.3.2)
NEMO ETC,LLC Evaluation Report 1-GG-18-001.02.18-R2
Certificate of Authorization 1132455 0 EDITION(2017)FBC NON-HVHZ EVALUATION FL26482-112(NON-HVHZ)
Gardner®Roof Underlayments;(813)248-2101 Revision 2:06/19/2019
Page 3 of 7
MEMO etc.
5.5.1 "Foam-On Tile"is limited to use of the following Approved tile adhesive/underlayment combinations.
TABLE 1A: ALLOWABLE A.
tlnderl�yrnent Adhesive-;. . Florida`Product,Approval.:
DAP Touch'n Seal Storm Bond Roof Tile Adhesive FL14506
Weather-Armor®FT3 Tile Dow TILE BOND'" FL22525
Underlayment or Eagle-Armor by Apoc
ICP Adhesives Polyset®AH-160 FL6332
5.6 Allowable Substrates:
•
tndertayinent . substrates
Gardner®Gard-Lock, Weather-Armor"FT3 Tile Underlayment or Eagle-Armor by Apoc,Weather-Armor" plywood
HT High Temp Premium Roof Underlayment or Weather-Armor SB-1 Self-Bond"Roof Underlayment
Weather-Armor®FT3 Tile Underlayment or Eagle-Armor by Apoc or Weather-Armor"HT1 High Temp OSB
Premium Roof Underlayment
Weather-Armor®FT3 Tile Underlayment or Eagle-Armor by Apoc or Weather-Armor®HT1 High Temp Structural
Premium Roof Underlayment. *Note:minimum 73°F ambient application temperature for structural
concrete.
concrete*
5.6.1 Wind Resistance for Underlayment Systems in Foam-On Tile Applications: FRSA/TRI April 2012 (04-12) does not
address wind uplift resistance of all underlayment systems beneath foam-on tile systems,where the underlayment
forms part of the load-path. The following wind uplift limitations apply to underlayment systems that are not
addressed in FRSA/TRI April 2012(04-12)and are used in foam-on tile applications. Maximum Design Pressure is the
result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure
divided by 2(the 2 to 1 margin of safety per FBC 1504.9 has already been applied).Refer to FRSA/TRI April 2012(04-
12),Appendix A,Table 1A or FBC 1609 for determination of design wind loads.
#1 Maximum Design Pressure=-52.5 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: None
Underlayment: Weather-Armor®FT3 Tile Underlayment or Eagle-Armor by Apoc,self-adhered.
#2 Maximum Design Pressure=-135.0 psf:
Deck: Min. 19/32-inch APA span-rated CDX plywood to meet project requirements to satisfaction of
Authority Having Jurisdiction.
Primer: None.
Underlayment: Weather-Armor® FT3 Tile Underlayment or Eagle-Armor by Apoc,self-adhered.
5.7 Exposure Limitations:
Gator-Skin TM Synthetic Roof Underlayment, Gator-Skin 10111 Synthetic Roof Underlayment or Weather-Armor®
CrossOver CX-L Premium Hybrid Roof Underlayment shall not be left exposed for longer than 30-days after
installation.
Gardner® Gard-Lock or Weather-Armor® SB-1 Self-Bond® Roof Underlayment shall not be left exposed for longer
than 90-days after installation.
Weather-Armor® FT3 Tile Underlayment, Eagle-Armor by Apoc or Weather-Armor® HT1 High Temp Premium Roof
Underlayment shall not be left exposed for longer than 180-days after installation.
1 Refer to Tile Manufacturer's orAdhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
NEMO ETC,LLC Evaluation Report 1-GG-18-001.02.18-R2
Certificate of Authorization X32465 0 EDITION(2017)FBC NON-HVHZ EVALUATION FL26482-R2(NON-HVHZ)
Gardner®Roof Underlayments;(813)248-2101 Revision 2:06/19/2019
Page 4 of 7
`
'
-NEMOUetc.
5.8 Tile Sli a e Limitations per FRSA/TRI April 2012(04-12)1:
When loading roof tiles on the undedayment in direct-deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
TABLE 3: TiLE SLIPPAGE LIMITATIONS FOR DIRECT-DECK TILE INSTALLATIONS
Weather-Armor"FT3 Tile Underlayment Flat or Lugged 10-tile stack 6:12
or Eagle-Armor by Apoc
6. INSTALLATION'
6.1 GardnerO Roof Underlayments shall be installed in accordance with Gardnero Asphalt Corp. published installation
requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re-fasten any loose decking panels,and check for protruding nail heads. Sweep the substrate thoroughly tnremove
any dust and debris prior to application,and prime the substrate(if applicable).
6'3
6.3.1 Non-Tile Applications:
Shall be insta|ledin compliance with the requirements for ASTM D1970 underlayment in F8CTab|e 1507.1.1 or
R905.1.1 for the type of prepared roof covering to be installed,and Gardner Asphalt Corp. published requirements.
|
36' .Z Nail-On Tile Applications(Weather-Armor' FT3 Tile Underlayment or Eagle-Armor by Apoc only):
�
Reference is made to FR3A/TR| April 2012 (04'12) Installation Manual for Self-Adhered Membrane, and Gardner
Asphalt Corp.published requirements.
For mechanically fastened tile roofing over Z'p|ysystem' consisting ofBase Sheet and Self-Adhered Membrane,
fastening nfthe ASTM DZZ6,Type ||orVVeathepArmorOCros OverCX'LPnemiumHybhdRoofUnder|aymentbase
sheet shall be in accordance with Gardner Asphalt Corp.requirements,but not less than that the densities set forth
in FRSA/rm April 2012 (O4'1Z)' Tab|e 1. Note: |fusing VVeathepArmorl .CrosoOverCX'LPremium Hybrid Roof
Underlayment in this application,it shall be installed with a 5-inch wide side lap.
An optional mid-ply ofWeather-Armorl HT1 High Temp Premium Roof Underlayment may be installed between the
mechonica||yfastenedA5TW1DZ26'Type||nrVVeathepArmor'CrosxOverCX'LPremiumHybridRonfUndedayment
base sheet and the Weather-Armor' FT3 Tile Underlayment or Eagle-Armor by Apoc in these applications.
Refer to Section 5.8 for tile staging limitations.
63.3 Foam-On Tile Applications(Weather-Armor" FT3 Tile UnderlaVment or Eagle-Armor by Apoc only):
Reference is made to FRSA/TR| April 2012 (04'12) Installation Manual for Se|�Adhered Membrane, and Gardner
Asphalt Corp.published requirements.
Refer to Table 1A for allowable tile adhesives.
Refer uoSection 5.5.lfor wind uplift limitations.
Refer toSection 5.8for tile staging limitations.
NEMO ETC,uz Evaluation Report
Certificate ww"m"riz"tio"m32«55 0EDITION(2o17)FBCmom*xxzEVALUATION azo*ozna(mom*vxz
oanune+nvo,onue,/av�enu��(n�s ��'zm� n�umnz�u$zy/zozy
Page sofz
MEMO etc.
6.4 ator SkipTM'Synthetic Roof Underlayment or Gator Slcin lO_", Synthetic Roof Underlayment
6.4. Re-fasten any loose decking panels,and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application.
6.4.2 Shall be installed in compliance with the requirements for ASTM D226, Type I or II underlayment in FBC Table
1507.1.1 or R905.1.1 for the type of prepared roof covering to be installed, considering the wider sheet-width for
double-layer applications,and Gardner Asphalt Corp.published requirements.
6.4.3 Fasteners:
Mechanical attachment of Gator-Skin TM Synthetic Roof Underlayment or Gator-Skin 10Tm Synthetic Roof
Underlayment is limited to roofing nails with minimum 1-inch diameter plastic or steel caps.
Code Reference: The Exception statement in FBC 1507.1.1 and FBC R905.1.1 states: "...except metal cap nails shall
be required where the ultimate design wind speed, Vouio equals or exceeds 150 mph."
6.4.4 Slopes of 4:12 or greater:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 4-inches. End (vertical)
laps shall be offset from course to course not less than 6 feet.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. When batten systems are to be
installed atop the underlayment,the underlayment need only be preliminarily attached pending attachment of the
battens.
6.4.5 Slopes of 2:12 to less than 4:12:
End(vertical)laps shall be minimum 12-inches and side(horizontal)laps shall be minimum 22-inches. End(vertical)
laps shall be offset from course to course not less than 6 feet.
Begin by fastening a 22-inch wide strip along the eaves. Place a full-width sheet over the starter, completely
overlapping the starter course. Continue upslope,maintaining minimum 22-inch side(horizontal)laps, resulting.in
a double-layer application.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. When batten systems are to be
installed atop the underlayment,the underlayment need only be preliminarily attached pending attachment of the
battens.
6.5 Weather Armorer Crossover CX 1,Premium Hybrid Roof Underlayment:
6.5.1 Re-fasten any loose decking panels,and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application.
6.5.2 Shall be installed in compliance with the requirements for ASTM D226, Type I or II underlayment in FBC Table
1507.1.1 or R905.1.1 for the type of prepared roof covering to be installed, considering the wider sheet-width for
double-layer applications,and Gardner Asphalt Corp.published requirements.
6.5.3 Fasteners:
Mechanical attachment of Weather-Armor® CrossOver CX-L Premium Hybrid Roof Underlayment is limited to
roofing nails with minimum 1-inch diameter plastic or steel caps.
Code Reference: The Exception statement in FBC 1507.1.1 and FBC R905.1.1 states: "...except metal cap nails shall
be required where the ultimate design wind speed, Va it,equals or exceeds 150 mph."
6.5.4 Slopes of 4:12 or greater:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 4-inches. End (vertical)
laps shall be offset from course to course not less than 6 feet.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. When batten systems are to be
installed atop the underlayment,the underlayment need only be preliminarily attached pending attachment of the
battens.
NEMO ETC,LLC Evaluation Report 1-GG-18-001.02.18-R2
Certificate of Authorization#32455 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL26482-R2(NON-HVHZ)
Gardner"Roof Underlayments;(813)248-2101 Revision 2:06/19/2019
Page 6 of 7
MEMO O etc.
6.5.5 Slopes of 2:12 to less than 4:12:
End (vertical) laps shall be minimum 12-inches and side (horizontal) laps shall be minimum 19.25-inches. End
(vertical)laps shall be offset from course to course not less than 6 feet.
Begin by fastening a 19.5-inch wide strip along the eaves. Place a full-width sheet over the starter, completely
overlapping the starter course. Continue upslope,maintaining minimum 19.25-inch side(horizontal)laps,resulting
in a double-layer application.
Minimum attachment shall be in accordance with FBC Table 1507.1.1 or R905.1.1. When batten systems are to be
installed atop the underlayment,the underlayment need only be preliminarily attached pending attachment of the
battens.
BUILDING7. •
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PILANTS*.
Contact the manufacturer or the named CIA entity for plants covered under Rule 611320-3 QA requirements. Refer
to Section 4 herein for product&production locations having met codified physical properties specifications.
9. QUALITY AssU RANCE ENTITY:'
PRI Construction Materials Technologies, LLC.—QUA9110;(813)621-5777
-END OF EVALUATION REPORT—