HomeMy WebLinkAboutProduct Approval MIAMbREVIEWED F O R MIAMI-DADE COUNTY
�0�y 9 N RODUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC REJ�iPLf" ( ��®� 11805 SW 26 Street,Room 208
BOARD AND CODE ADMINISTRATION DIVISION S'a'o LU O I E OO U N Miami,Florida 33175-2474
T(786)315-2590 F(786)315-2599
NOTICE OF ACCEPTANCE OA ®CC www.miamidade.eov/economy
Dynamic Metals;LLC '�
3201 SE Dominica Terrace RECEIVED
Stuart,FI.34997 gi'jle COPY�
DEC X19
SCOPE:
This NOA is being issued under the applicable rules and regulations governing
M
6lp d}4>1 ct��mrmaGe�ri ls.Thedocumentation submitted has been reviewed and accepted by Miami-Dade CountyR-Product Contro ection to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated below.The Miami-Dade County Product Control Section
(In Miami Dade County)and/or the AHJ(in areas other than Miami Dade County)reserve the right to have this product
or material tested for quality assurance purposes.If this product or material fails to perform in the accepted manner,the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke,modify, or suspend the use
of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,if it is
determined by Miami-Dade County Product Control Section that this product or material fails to meet the requirements
of the applicable building code.
This product is approved as described herein,and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Englert Series 1101 Steel Panel
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and following
statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use, and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product, for
sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the
expiration,date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA consists of pages 1 through 5.
The submitted documentation was reviewed by Hamley Pacheco,P.E.
A
NOA No.: 16-1003.07
MIAMNDADE COUNTY Expiration Date: 11/10/21
• �
Approval Date: 11/10/16
Page 1 of 5
V
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub-Category: Metal,Panels(Non-Structural)
Materials: Steel
Deck Type: Wood
Maximum Design Pressure —165 psf
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
Test Product
Product Dimensions Specifications Description
Series 1101 Length:various TAS 125 Corrosion resistant,BASF Fluoroceram
Width: 16" coated galvanized,standing seam,metal
Height: l" panels.
Thickness 0.024'(24 ga.)
Min.Yield Strength: 56 ksi
Trim Pieces Length: varies N/A Corrosion resistant,BASF Fluoroceram
Width: varies coated galvanized,standing seam,metal
Thickness 0.024"(24 ga.) panels.
EVIDENCE SUBMITTED:
Test Agency Test Identifier Test Name/Report Date
BASF Salt Spray 01/18/06
BASF Accelerated Weathering 01/18/06
Architectural Testing Inc. 97806.01-109-18 TAS 100 07/06/10
Architectural Testing Inc. 93745-.01-109-18 TAS 125 11/16/09
NOA No.:16-1003.07
M1AMI•DADECOUNTY Expiration Date: 11/10/21
,...0 1■
Approval Date: 11/10/16
Page 2 of 5
APPROVED ASSEMBLIES: '
System: Series 1101 Panel 16"Wide
Deck Type: Wood,Non-Insulated
Deck Description: New Construction 19/32"or greater plywood or wood plank.
Slope Range: 211: 12"or greater
Maximum Uplift See Table A below
Pressure:
Deck Attachment: In accordance with applicable building code,but in no case shall it be less than#8d annular
ring shank nails spaced 6"o.c. In reroofing,where the deck is less than 19/32"thick
(Minimum 15/32") the above attachment method must be in addition to existing attachment.
Underlayment: Minimum underlayment shall be an ASTM D 226 Type H installed with a minimum 4"
side-lap and 6"end-laps.Underlayment shall be fastened with corrosion resistant tin-caps
and 12 gauge 1 '/o"annular ring-shank nails,spaced 6"o.c. at all laps and two staggered
rows 12"o.c.in the field of the roll. Or,any approved underlayment having a current NOA.
Fire Barrier Board: Any approved fire barrier having a current NOA. Refer to a current fire directory listing for
fire ratings of this roofing system assembly as well as the location of the fire barrier within
the assembly. See Limitation# 1.
Valleys: Valley construction shall be in compliance with Roofing Application Standard RAS 133
and with Englert's current published installation instructions.
Metal Panels and Install the "Series 1101 Panel" and accessories in compliance with the current published
Accessories: installation instructions and details in Englert's Installation Manual. . Flashings,
penetrations, valley construction and other details shall be constructed in compliance with
Roofing Application Standard RAS 133.
Panels shall be secured at a spacing listed below in Table A with#10 pancake head screws
of sufficient length to penetrate through the sheathing a minimum 3/16 of an inch.
The adjacent panel shall overlap and be secured to each other with a snap-lock the full
length of the panel.
TABLE A
MAXIMUM DESIGN PRESSURES
Roof Areas Field Perimeter and Corner'
Maximum Design Pressures —150 psf —165 psf
Maximum Screw Spacing 6"o.c. 3"o.c.
Bostik 70-05A Sealant N/A (2) 1/8"beads.
Refer to drawing herein.
I. Extrapolation shall not be allowed
NOA No.: 16-1003.07
MIAMMADE COUNTY= Expiration Date: 11/10/21
Approval Date: 11/10/16
Page 3 of 5
Pr _
SYSTEM LIMITATIONS
1. Fire classification is not part of this acceptance;refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
-2. The maximum designed pressure listed herein shall be applicable to all roof pressure zones(i.e.field,perimeters,
and corners).Neither rational analysis,nor extrapolation shall be permitted for enhanced fastening at enhanced
pressure zones(i.e.perimeters,extended corners and corners).
3. Panels may be rolls formed in continuous lengths from eave to ridge.Maximum lengths shall be as described in
Roofing Application Standard RAS 133
4. All panels shall be permanently labeled with the manufacturer's name and/or logo, and the following statement:
"Miami-Dade County Product Control Approved" or with the Miami-Dade County Product Control Seal as seen
below. All clips shall be permanently labeled with the manufacturer's name and/or logo,and/or model.
MAWDADE C©LINTY
5. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 9N-3 of the Florida Administrative Code.
6. Panels may be jobsite roll formed with machine model#5150216 from Englert,Inc.
CI•oAoacaurrnr NOA No.:16-1003.07
• • Expiration Date: 11/10/21
Approval Date: 11/10/16
Page 4 of 5
PROFILE DRAWINGS
16"
Bostik 70-05A ~
Sealant
Field Condition Perimeter and Comer Condition
0
. o
e
FASTENER
SPACING AS PER
TABLE A HEREIN
SERIES 1101 PANEL SYSTEM
END OF TRIS ACCEPTANCE
EC U
NOA No.: 16-1003.07
••.f Expiration Date: 11/10/21
Approval Date: 11/10/16