Order(Ref)#: 57720(43802-4591435185) Project Details: TANNEHILL CONDO DOOR REPLACEMENT
Contractor: AG CARPENTRY, INC 9600 S. OCEAN DRIVE, UNIT 507
7030 S.W. 16TH COURT PEMBROKE JENSEN BEACH, FL
PINES, FL
Subject: Wind Load Design Pressure Calculations (Components &Cladding)
Site Information General Calculation
Building Classification: enclosed Directionality Factor(Kd): 0.85
Wind Speed (V„lt): 170 mph Gust-Effect Factor(G): 0.85
Exposure Category: d Internal Pressure
0.18
Roof Type: monoslope Coefficient (GCp; .
±
Roof Slope (0): 1.2 deg Topographical Factor (K,t): 1.0
Mean Roof Height (h): 127.0 ft Velocity Pressure Exposure
K 1.49
Min. Building Dimension (L): 94.0 ft Coefficient ( n)�
Parapet>: 3 feet? No Velocity Pressure (qh): 93.94 psf
End Zone (a): 9.4 ft
ASD Method: P =0.6w
Mark Qty Elev (ft) Size: W x H (in) Zone Shutter?Area (ft2) K, (Kh) QZ (9 h) GCp+ GCp_ Pressures (psf)
1 (1) 44.0 36.0 x 80.0 4 No 20.0 1.24 78.12 0.90 -0.90 +52.3/—60.9
Lti
112 14 11) r110 4e
1111
Ql
NOTES:Design is in accordance with ASCE 7-10(ASD method)and the Florida Building Code Sixth Edition(2017).Results NO PE
are not valid for use unless approved via original signature and raised engineer seal of a PE from Engineering Express. — Valid Only Wit Raised,
are -
Results are based on contractor-supplied data and shall be field verified by others prior to use.Selection&installation CT_ '`' Enginder Seal _—
products shall be approved using these dimensions and pressures as verified by others. LLJ J
to
ST E CI
Note.For openings to be properly rated in Zone 4,no part of the opening shall be within 9.4 feet of any building corner.
TeA0 019
This engineer has not field visited this location and if this cannot be clearly identified by others,the opening shall be re- // nit't to\
,'P.E.
evaluated prior to installation of any fenestration. All other information provided above including mean roof height, Gordon
building minimum dimensions,opening sizes,&other supporting data was provided by others. For definitions of the PE82328
above terms,visit EngineeringExpress.com/Wiki" #9885