Order(Ref)#: 58838 (43850-4059490741) Project Details: PEREZ CONDO DOOR REPLACEMENT
Contractor: AG CARPENTRY, INC. 10044 S. OCEAN DRIVE, UNIT 906
7030 S.W. 16TH COURT PEMBROKE JENSEN BEACH, FL
PINES, FL
Subject: Wind Load Design Pressure Calculations(Components&Cladding)
Site Information General Calculation
Building Classification: enclosed Directionality Factor(Kd): 0.85
Wind Speed (Vult): 170 mph Gust-Effect Factor(G): 0.85
Exposure Category: d Internal Pressure
0.18
Roof Type: monoslope Coefficient (GCP;):
±
Roof Slope (0): 1.2 deg Topographical Factor(K,t): 1.0
Mean Roof Height(h): 106.0 ft Velocity Pressure Exposure
K
Min. Building Dimension (L): 134.0 ft Coefficient( n): 1.45
Parapet>:3 feet? No Velocity Pressure (qh): 91.03 psf
End Zone (a): 13.4 ft
ASD Method: P=0.6w
Mar- Qty Elev(ft) Size: W x H (in) Zone Shutter? gree(ft2)° KZ (K;n) 9 z°(a n) GCP+ .GC p PressuCes (p`sf)
1 (1) 80.0 36.0 x 80.0 4 No 20.0 1.38 86.68 0.90 -0.90 +56.6/—59.0
0
B.
R,
erx
rr v�� =a ua
ST. WGIE C OUN o
No PEa2
NOTES:Design is in accordance with ASCE 7-10(ASD method)and the Florida Building Code Sixth Edition(2017).Results
are not valid for use unless approved via original signature and raised engineer seal of a PE from Engineering Express-- valid Only With Raised/Sti3rt �
Results are based on contractor-supplied data and shall be field verified by others prior to use.Selection&installation`o< +Ditisto,
�(/
products shall be approved using these dimensions and pressures as verified by others. % �\
i T �\�
Note:For openings to be properly rated in Zone 4,no part of the opening shall be within 13.4 feet of any building corner. '(�%) 2020
This engineer has not field visited this location and if this cannot be clearly identified by others,the opening shall be re- Go P.E.evaluated prior to installation of any fenestration. All other information provided above including mean roof height,building minimum dimensions,opening sizes,&other supporting data was provided by others. For definitions of the above terms,visit EngineeringExpress.com/Wiki"
160 SW 12TH AVENUE,SUITE 106, DEERFIELD BEACH,FLORIDA 33442
58838(43850-4059490741) PHONE:(954)354-0660—FAX:(954)354-0443
AutoPrint ENGINEERINGEXPRESS.COM PAGE 1 OF 1