Loading...
HomeMy WebLinkAboutProduct approvals cgaP Olp EVALUATION REPORT OF METAL SALES MANUFACTURING CORPORATION `26 GA. 5V-CRIMP PANEL' FLORIDA BUILDING CODE 6TH EDITION (2017) FLORIDA PRODUCT APPROVAL FL 14645.3-R3 j ROOFING METAL ROOFING j i i Prepared For: Metal Sales Manufacturing Corporation 545 South 3rd Street, Suite 200 Louisville, KY 40202 Telephone: (502) 855-4300 Fax: (502) 855-4200 Prepared By: Bala Sockalingam, Ph.D., P.E. File Cop'} Florida Professional Engineer#62240 1216 N Lansing Ave., Suite C �Q��O � Tulsa, OK 74106 E�/I WED FOR Telephone: (918) 492-5992 CODE C® P������ FAX: (866) 366-1543 ST.s LUCIE COUNTY e BOCC This report consists of j Evaluation Report (3 Pages including cover) Installation Details (1 Page) ee°° SOCKA/ �� �.Q; •°GENS' �-y `. ® No 62240 STATE OF U v Report No. 02182-3 o�0 All O \ P•(moi n _ Date: 9.9.17 ° ? • Br I FL 14645.33- C21182-31 9.9.17 Page 2 of 3 Manufacturer: Metal Sales Manufacturing Corporation Product Name: 5V-Crimp Panel Description: 24" wide coverage with(5) 1/2" high ribs Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). 4 Deck Description: Min. 19/32" plywood or min. 3/4" thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2017. I Deck Attachment: 8d x 2.5" long ring shank nails or#8 x 2" long wood screws @ 6" o.c.: (Minimum) in the field and @ 4" o.c. at edges. Designed as per FBC 2017. New Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1. Required for new construction and optional for reroofing constructions Existing Underlayment: One layer of asphalt shingles over one layer of#30 felt. For reroofing (Optional) construction only. Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 3:12. Design Uplift Pressure: 41.6 psf @ fastener spacing of 36" o.c. j (Factor of Safety =2) 74.8 psf @ fastener spacing of 16" o.c. 196.75 psf @ fastener spacing of 8" o.c. Fastener Pattern: Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener shall be of sufficient length to penetrate through the deck a minimum of 3/8". At panel ends @ 6" o.c. across panel width At intermediate @ 12" o.c. across panel width Test Standards: Roof assembly tested in accordance with TAS 125-03 `Standard Requirements for Metal Roofing Systems'. I Code Compliance: The product described herein has demonstrated compliance with FBC 2017 Section 1507.4. Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress design. The maximum support spacing listed herein shall not be exceeded. This evaluation report is not applicable in High Velocity i I I i I .. FL 14645.3-R3 C21 82-31 I 9.9.1 I Page 3 of 3 Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2017 Section 1505 and current approved roofing materials directory or ASTM E108/UL790 report from an accredited laboratory for fire ratings of this product. Supporting Documents: TAS 125 Test Reports Farabaugh Engineering and Testing Inc Project No. T181-05, Reporting Date 7/21/05 (Tests#1 & 2) Project No. T240-09, Reporting Date 9/22/09 Architectural Testing, Inc.—West Palm Beach, FL (Formerly Hurricane Test Laboratory, LLC) Project No. 0103-0712-09, Reporting Date 9/1/09 i Ir i i I I i i DMWN 9t: CKEOKFD 0Y: 8.5. D.S. P OT: DATE J/IJ/1J EXISTING SHINGLES SEE DETAIL 2 SEE DETAIL 1 NEW UNDERREQUIRED LAYMENT FASTENER AT PANEL FLAT 5V-CRIMP H (OPTIONAL) (PANEL OVERLAP) NEW CONSTRUCTION)LY R ENDSIRONLY.OR PANEL g G II EXISTING UNDERLAYMENT / PANEL FASTENER PER ALLOWABLE (OPTIONAL) MINIMUM ATTACHMENT: PRESSURE TABLE ON THIS SHEET. o 8d x 2.5 LONG-RING SHANK NAIL OR #8 x 2" LONG WOOD SCREWS SPACED ® 6" O.C. IN THE FIELD & o MIN. 2X_ WOOD RAFTER/JOIST/ 4" O.C. AT PLYWOOD EDGES TRUSS AT MAX. 24" O.C. a TYPICAL PANEL INSTALLATION X—SECTION g N C9 w N Z H=O NCO #9-16 OR #10-14 WOODSCREWS ALLOWABLE UPLIFT PRESSURE NYS WITH SELF SEALING WASHER AT M NEW UNDERLAYMENT �w n MAXIMUM SPACING OF 36" O.C. FASTENER PRESSURE D1 (REQUIRED ONLY FOR M� I NEW CONSTRUCTION) SPIN) G (PSF) �NC4 5V-CRIMP 00 EXISTING SHINGLES MIN 26 GA. 36 41.6 (OPTIONAL) 16 74.8 LL�i B 196.75 i,i Lu a T zd c U m EXISTING UNDERLAYMENT PLYWOOD a a I= (OPTIONAL) 19/32" THICK (MIN.) GENERAL NOTES: ' DETAIL 1 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE L) max„ FLORIDA BUILDING CODE (FBC). I 2. ROOF PANELS SHALL BE MIN. 26 GA. (t = 0.0169"). EFFECTIVE COVERINGr #9-16 OR #10-14 WOODSCREWS WIDTH OF PANEL = 24". o z NEW UNDERLAYMENT WITH SELF SEALING WASHER AT 3 SPECTHE IFIED PANELS SHALL ON THIS DRAWING. INSTALLED OVER SHEATHING & STRUCTURE ASN n (REQUIRED ONLY FOR JMAXIMUM SPACING OF 36" O.C. 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS o NEW CONSTRUCTION) PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS o g R ARE GREATER THAN THE ALLOWABLE WIND LOADS SPECIFIED ON THIS DRAWING. EXISTING SHINGLES 5V-CRIMP 5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA (OPTIONAL) MIN 26 GA. BUILDING CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM REQUIREMENTS OF THIS DRAWING & THE CODE, THE CODE SHALL CONTROL. 6. RAFTERS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS REQUIRED FOR EACH APPLICATION AND ARE THE RESPONSIBILITY OF OTHERS. EXISTING UNDERLAYMENT PLYWOOD (OPTIONAL) 19/32" THICK (MIN.) 2182-3 - - -- -DETAIL--2---- — -- -- -- -- - -- --- — SHEEP No. _______- ___ _- _ __ __ _ _' a G °o� ®10 EXTERIOR RESEARCH &DESIGN, LLC. Certificate of Authorization#9503 353 CHRISTIAN STREET, UNIT#13 •? TRI MY E�® OXFORD,CT 06478 li (203) 2621-9245 EVALUATION REPORT TRI-BUILT Materials Group,LLC Evaluation Report A42960.10:12-116 PO Box 70 FL16048-R6 Rutherford, NJ 07070 Date of Issuance: 10/2512012 (800)516-1485 Revision 6: 09/25/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volumel The products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: TRI-BUILT Roof Underlayments i LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency*ted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes,the referenced Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinity I ERD requires a complete review�of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity)ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety. I INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 6. REVIEWED FOR Prepared by: •••�ta�a,r�r,,,.,-- CODE COMPLIAW.FE . •``i . • BOCC File, Cop, Robert J.M.Nieminen, P.E. j'^*� 1L Thefacsimilesea[appearing was authorized byRobert Nieminen, ��..., Florida Registration No.59166,Florida DCA ANE1983 P.E.on 09/25/2017.This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. Trinity IERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufactiuring or distributing products it evaluates. 2. Trinity)ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire,a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither Trinity)ERD nor Robert Nieminen, P.E. are, in any way, the Designer of,Record for any project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidanceunless retained specifically for that purpose. I i TRINITY R® ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing t. Sub-Category: Underlayment Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have demonstrated compliance with the following sections of the 61h Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations/ Conditions of Use set forth herein. 2. STANDARDS: ! Section Property Standard Year 1504.3.1 Wind Resistance FM 4474 2011 1504.3.1 Wind Uplift UL 1897 2012 1504.6 Accelerated Weathering ASTM G155 2005 1507.2.4/1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012(04-12) 2012 3. REFERENCES: Entity Examination Reference Date ERD(TST6049) Physical Properties 540540.02.13-1 02/19/2013 ERD(TST6049) Physical Properties 540540.11.13 11/19/2013 ERD(TST6049) Physical Properties 540540.03.14 03/26/2014 ERD(TST6049) Physical Properties 544870.04.14-2 04/02/2014 ERD(TST6049); Physical Properties S44870.04.14-3 04/02/2014 ERD(TST6049) Physical Properties S44870.04.14-1 04/10/2014 ERD(TST6049) Physical Properties S44870.04.14-4 04/10/2014 ERD(TST6049) Physical Properties S43530.02.14-1-R1 05/14/2014 ERD(TST6049) Physical Properties S43530.05.14 05/28/2014 ERD(TST6049) Physical Properties 540540.10.14 10/31/2014 ERD(TST6049) Physical Properties SC7645.02.15 02/13/2015 ERD(TST6049) Accelerated Weathering SC8520.04.15 05/27/2015 ERD(TST6049) Wind Resistance SC14045.05.17-R1 06/07/2017 UL,LLC.(QUA9625) Quality Control Multiple-Listing R16814 12/10/2015 UL,LLC.(QUA9625) Quality Control Service Confirmation Exp.07/18/2020 4. PRODUCT DESCRIPTION: 4.1 Tri-Built Sand-R SA Shingle Underlayment is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof underlayment,with a 36-inch sheet width;meets ASTM D1970. 4.2 Tri-Built S/A HT TU Underlayment is a self-adhering, non-woven polyester fabric surfaced, SBS modified bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI April 2012. b. 4.3 Tri-Built Smooth HT S/A Underlayment is a self-adhering, glass-mat reinforced, film-surfaced, SBS modified bitumen roof underlayment; meets ASTM D1970. 5. LIMITATIONS: 5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. Exterior Research and Design,I.I.C. Evaluation Report A42960.10.12-116 Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-116 TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6:09/25/2017 Page 2 of 6 I a I i TRINIRD I 5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. 5.5 Allowable Roof Covers: TABLE 1: ROOF COVER OPTIONS Underlayment Asphalt Nail-On Tile Foam-On Tile Metal Wood Shakes Slate Shingles &Shingles Tri-Built Sand-R SA Shingle Yes No No No Yes Yes $. Underlayment Tri-Built S/A HT TU Yes Yes Yes Yes Yes Yes Underlayment See 5.5.1 Tri-Built Smooth HT S/A Yes NoNo Yes Yes Yes Underlayment i 5.5.1 "Foam-On Tile"is limited to use of the following Approved tile adhesives/underlayment combinations. TABLE lA:ALLOWABLE TILE ADHESIVE/UNDERLAYMENT COMBINATIONS) Adhesive Florida Product Approval Underlayments ICP Adhesives Polyset®AH-160 FL6332 Tri-Built S/A HT TU Underlayment Dow TileBond'" FL22525 Tri-Built S/A HT TU Underlayment 5.6 Allowable Substrates: I 5.6.1 Direct-Bond to Deck: I Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ Plywood; ASTM D41 primed plywood; OSB;ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine;ASTM D41 primed structural concrete. While not required over plywood,OSB or Southern Yellow Pine substrates,TRI-BUILT Materials Group;LLC recommends priming the deck if the final roof cover is not slated for installation within 24 hours l Note: TRI-BUILT Materials Group, LLC requires tongue-and-groove board decking be covered with plywood or OSB prior to installation of the self-adhering underlayment. 5.6.2 Bond-to-Insulation: Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ Dens Deck Prime;SECU ROCK Gypsum-Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For instaIIlations under foam-on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FM 4474,Appendix D or TAS 114,Appendix J. a. I i Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. Exterior Research and Design,LIC. Evaluation Report A42960.I 0.12-R6 Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6 TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6:09/25/2017 Page 3 of 6 I 1N1 ER® 5.6.3 Bond to Mechanically Attached Base Laver: Tri-Built Sand-R SA Shingle Underlayment,Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ ASTM D226,Type I or II felt. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam-on tile systems (Tri-Built S/A AT TU Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04- 12). 5.6.4 Wind Resistance for Underlayment Systems in Foam-On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam-on tile systems, where the underlayment forms part of the load-path. The following wind uplift limitations apply to direct-deck underlayment systems that are not addressed in FRSA/TRI April 2012(04-12)and are used in foam ion tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin ofj safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012(04-12),Appendix A,Table 1A or a FBC 1609 for determination of design wind pressures. #1 Maximum Design Pressure=-45.0 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional)ASTM D41 or RESISTO EXTERIOR PRIMER Underlayment: Tri-Built S/A HTTU Underlayment,self-adhered. #2 Maximum Design Pressure=-67.5 psf: Deck: Structural concrete to meet project requirements to satisfaction of Authority;Having Jurisdiction. Primer: Soprema Elastocol 600c Underlayment: Tri-Built S/A HT TU Underlayment,self-adhered. #3 Maximum Design Pressure=-150.0 psf: Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project requirements to satisfaction of Authority Having Jurisdiction. Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that mayl inhibit adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp splinters and wood projections shall be removed/sanded. ' Primer: (Optional) RESISTO EXTERIOR PRIMER Underlayment: Tri-Built S/A HT TU Underlayment, self-adhered, shall be thoroughly roll usi r�g hand roller and/or weighted roller to ensure there are no voids, and ensure there are no voids/bridging at side and end-laps. #4 Maximum Design Pressure=-60.0 psf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1) and tin caps(FBC 1517.5.2)spaced 6-inch o.c.at the 4-inch laps and 6-inch o.c. in three, equally spaced rows in the center of the sheet. Underlayment: Tri-Built S/A HT TU Underlayment,self-adhered. i i i Exterior Research and Design,LLC. Evaluation Report A42960.10.12-R6 Certificate of Authorization##9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6 TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6:09/25/2017 Page 4 of 6 i k i TRINITY ER® 5.6.4.1 For mechanically attached Base Sheet,the maximum design pressure for the selected assembly shall;meet or exceed that required under FRSA/TRI April 2012(04-12),Appendix A,Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 I design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an 3. attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29(January 2016)for Zone 2/3 enhancements.] 5.7 Exposure Limitations: Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left exposed for longer than 30-days after installation Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installatiin. 5.8 Tile Slippage Limitations(TAS 103 per FRSA/TRI April 2012(04-12)): When loading roof tiles on the underlayment in direct-deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. TABLE 2: TILE SLIPPAGE LIMITATIONS FOR DIRECT-DECK TILE INSTALLATIONS Underlayment Tile Profile Staging Method Maximum Slope Flat Max.10-tile stack 6:12 Lugged Max.10-tile stack 5:12 Max.10-tile stack(bottom 2-tile stack shall be inverted,followed by 8 tiles high 6:12 on slope,as shown below) Tri-Built S/A HT TU Underlayment Lugged LZZI oz5a t"7 Ki I Exterior Research and Design,LLC. Evaluation Report A4296010.12-R6 Certificate of Authorization#9503 6"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6 TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6:09/25/2017 Page 5 of 6 I TRINITY : RD 6. INSTALLATION: 6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC published installation requirements subject to the Limitations set forth in Section 5 herein a d the specifics noted below. 6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application,and prime the substrate(if applicable). 6.3 Tri-Built Sand-R SA Shingle Underlavment,Tri-Built S/A HT TU Underlavment or Tri-Built Smooth HT S/A Underlavment: 6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC!Table 1507.1.1 for the type of prepared roof covering to be installed. 6.3.2 Non-Tile applications: While priming is optional, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof 3_. cover is not slated for installation within 24 hours. Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3 ft of release film. Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible. Once the entire length of membrane is in place, peel-off the release film diagonally while holding the membrane tight. Firmly roll, broom or hand-press the membrane into place to achieve a bond. Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6- inches and staggered not less than 2-ft from vertical seams in the course below,sealed in accordance with TRI-BUILT Materials Group,LLC requirements. When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back-nailing) in the overlap area at the top of the sheet at 12-inch o.c. I For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in each direction. For valleys,apply the sheet starting at the lowest point and work upward. j 6.3.3 Tile Applications(Tri-Built S/A HT TU Underlavment only): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the ' instructions noted above as a guideline. For foam-on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that i fall outside the scope of FRSA/TRI April 2012(04-12). Tile shall'be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile staging. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: Gulfport, MS 9. QUALITY ASSURANCE ENTITY: UL, LLC—QUA9625;(314)578-3406;k.chancellor@us.ul.com -END OF EVALUATION REPORT- Exterior Research and Design,L'LC. Evaluation Report A42960I10.12-116 Certificate of Authorization#9503 6T"EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6 TRI-BUILT Roof Underlayments;(800)516-1485 Revision 6:0025/2017 Page 6 of 6