HomeMy WebLinkAboutProduct Approval OLTERS ENGINEER Il�TG� ����°�7VE ,
;
ENGINEERING,DRAFTING,CONSULTING FEB20'301521 97th Road N
[ST. Lucie County, Permi 'Nest
aim Beach,FL 33412
(561)225-1982
PRODUCT EVALUATION
PRODUCT: DYNAMIC 5V CRIMP 26 GAUGE STEEL ROOF PANEL (FLPA#21082.4)
MANUFACTURER: DYNAMIC METALS, LLC
340 PIKE ROAD
WEST PALM BEACH, FL 33411
To all concerned,
The Dynamic 5v Crimp 26 Ga. Steel Roof Panel, manufactured by Dynamic Metals LLC, is a non-structural
galvalume coated steel roof panel (50 ksi min)that meets the requirements of Section 1507.4.3 of the 6th Edition
(2017) Florida Building Code, The panel has been tested per UL580-06 by Intertek-ATI,with results shown in test
report G1195,02-450-44.
Technical Documentation:
1. Drawing"5VS"dated 6/18/18, signed and sealed by Scott Wolters, PE.
2. Test Reports listed above by Architectural Testing, Inc. signed and sealed by Vinu Abraham, PE.
3. Supplemental Calculations to support"5VS"drawing, signed and sealed by Scott Wolters, PE.
I have reviewed this submittal per the requirements of FAC Product Approval Rule Chapter 61G20-3.005
(4). Based on the limitations listed below and those provided in the documents above, this product meets all the
requirements of the 6th Edition (2017) Florida Building Code generally, and chapter 15 specifically,for use outside
of the HVHZ.
Limitations: This panel is approved for use outside of the HVHZ.
Overall Limitations: Maximum Panel Width: 24"
Fastener spacing across panel: 12"O.C. (at overlaps¢er rib)
Field Installation
Maximum Design Pressure: 101 psf.
Fastener Spacing: 2"from ends, 16" max. O.C.
Min. Panel Fastener: #10x1%2'Woodzac HiLo HWH screw
with weather-seal washer
T- FCI&IZIN6 IN IMPACT M, 5151-ANT CUPUAINWAU5, 5i0�E p a , & 111d ��I15
Perimeter and Corner Installation
Maximum Design Pressure: 206 psf
Panel Clip Anchor Spacing: 2"from ends, 8"max. O.C.
Min. Panel Fastener: #10x1 1/2"Woodzac HiLo HWH screw
with weather-seal washer
Underlayment: 1 layer of 30 Ib,organic felt paper with 4"overlaps
(or)
Any underlayment with a valid FLPA or Miami-Dade NOA
Fire Barrier: 1 layer of VersaShield with 4"overlaps
(or)
Any fire barrier with a valid FLPA or Miami-Dade NOA
Minimum Substrate: % (15/32"min)4-ply CDX Plywood, nailed to 2x rafters spaced 24"max.
O.C. with 8d ring-shank nails spaced 4"O.C.
Other Limitations: Roof slope must meet requirements of FBC Section 1507.4.2.
Fire classification is not a part of this evaluation.
Shear diaphragm values are not a part of this evaluation.
Design of substrate is by others and is not a part of this evaluation.
If you have any questions or need more information concerning this approval please contact me.
419HThank you, y�q �° T N 6�•pg�8
Scott Wolters
FL PE# 62354 .�
,SUN 19 7016 -
IVAF L sS A-,
I
i
a
i
519�CIA(.IZING IN IMPACT F,1�515fANT CUP AINW&L5, 5TOf:TFC;ONf5, & WINPOW5
4
Ln
OD
N
I
` Z
I �
v
� � N
o P
0
V
� � v
O (D r n>
$N � 3
% a t(
o �m
S
m obi 0) I o 0
CL CD
mCD
I na {{
O -s Nc 1 O S
G I p {
Ii E
4
s
C C
sCDTi WOLIMS AL:
DYNAMIC METALS nPEg823Da
•• waL1ER5 ENGINEERING27194
340 PIKE ROAD www.dynamkmetaLnet t52nG9ia ftoAo w —
�-. WEST PALM BEACH,FL 33782 FAX:(561)629-7291 wEsr PALM REACH.Fi ata+z`: ,n`• J(jN l�.�Q1$? 15T SU6MITTAL _ 6/18 18
(sst)zzs 1sez
PH:(561)629-7288 EMAIL:info@dynamicmeiaLnet �J PRINis TssUED>Dft REV.4 DATE
•+�s�setenes3a'
� ' T
RECEIVED
MIAMI-DADE FEB 2 4 2020 MIAMI-DARE COUNTY
e
T. Lucie County, Permitting
CT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES 41 805 SW 26 Street,Room 208
BOARD AND CODE ADMINISTRATION DIVISION Miami,Florida 33175-2474
T(786)315-2590 F(786)315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.aw/economy
Polyglass USA Inc.
1111 W.Newport Center Drive
Deerfield Beach,FL 33442
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials.The
documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be
used in Miami-Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated below.The Miami-Dade County Product Control Section
(in Miami-Dade County)and/or the AHJ(in areas other than Miami-Dade County)reserve the right to have this
product or material tested for quality assurance purposes.If this product or material fails to perform in the accepted
manner,the manufacturer will incur the expense of such testing and the AHJ may immediately revoke,modify,or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein,and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Polyglass Polystick Underlayments
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city,state and following
statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use, and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product,
for sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT:.The NOA number preceded by the words Miami-Dade County, Florida, and followed
by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then
it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Oficial.
This NOA renews and revises NOA No.15-0410.04 and consists of pages 1 through 8.
The submitted documentation was reviewed by Freddy Semino.,
NOA No.: 17-0614.22
MtAMI-DADEMiffl OUNTY Expiration Date: 09/13/21
File Copy Approval Date: 07/06/17
Page 1 of 8
ROOFING COMPONENT APPROVAL
Category: Roofing
Sub-Category: Underlayment
Material: SBS ,APP Self-Adhering Modified Bitumen
PRODUCTS DESCRIPTION:
Test Product
Product Dimensions Specification Description
Polystick IR-Xe 65'x 3'3-3/8" ASTM D 1970 A fine granular/sand top surface self-adhering,APP
Manufacturing Or 65'x 3' polymer modified,fiberglass reinforced,bituminous
Location#1  60 mils thick sheet material for use as an underlayment in sloped roof
assemblies. Designed as an ice&rain shield.
Polystick Dual Pro 61'x 3'33/8" TAS 103 and A rubberized asphalt self-adhering,glass-fiber/polyester
Manufacturing 60 mils thick ASTM D 1970 reinforced waterproofing membrane. Designed as a
Location#2 metal roofing and roof tile underlayment.
Polystick Tile Pro 61'x 3'33/8" TAS 103 and A rubberized asphalt self-adhering,glass-fiber/polyester
Manufacturing 60 mils thick ASTM D 1970 reinforced waterproofing membrane.Designed as a metal
Location#2 roofing and roof tile underlayment.
Polystick TU Max 65'8"x 3'3-3/8" TAS 103 and A rubberized asphalt self-adhering,polyester reinforced
Manufacturing 60 mils thick ASTM D 1970 waterproofing membrane. Designed as a a roof tile
Location#1  underlayment.
Polystick TU P 32'10"x 3'33/8" TAS 103 and A rubberized asphalt waterproofing membrane,glass-
Manufacturing 130 mils thick ASTM D 1970 fiber/polyester reinforced,with a granular surface
Location#2 designed for use as a tile roof underlayment.
Polystick TU Plus 65'x 3'33/8" TAS 103 and A rubberized asphalt self-adhering,glass-fiber/polyester
(Surface Printing) 80 mils thick ASTM D 1970 reinforced waterproofing membrane.Designed as a metal
Manufacturing roofing and roof tile underlayment.
Location#1 
Polystick MTS 6518"x 3133/8" TAS 103 A homogeneous,rubberized asphalt waterproofing
Manufacturing 60 mils thick membrane,glass fiber reinforced with polyolefinic film
Location#2 on the upper surface for use as an underlayment for metal
roofing,roof tile,slate tiles and shingle underlayment.
Polystick MTS Plus 6518"x 3133/8" TAS 103 A homogeneous,rubberized asphalt waterproofing
Manufacturing 60 mils thick membrane,glass fiber reinforced with polyolefinic film
Location#2 on the upper surface for use as an underlayment for metal
roofing,roof tile,slate tiles and shingle underlayment.
Elastoflex S6 G 32'10"x 3'3 3/8" TAS 103 and Polyester reinforced, SBS modified bitumen membrane
Manufacturing ASTM D 6164 with a sanded back face and a granule top surface. For
Location#2 use in roof tile underlayment systems.
NOA No.: 17-0614.22
MIAMI•DADE COUNTY Expiration Date: 09/13/21
Approval Date: 07/06/17
Page 2 of 8
MANUFACTURING PLANTS:
1. Hazelton,PA
2. Winter Haven,FL
EVIDENCE SUBMITTED
Test Agency Test Identifier Test Name/Reuort Date
Trinity ERD P10870.09.08-R1 TAS 103 12/04/08
P10870.04.09 TAS 103/ASTM D4798&G155 04/13/09
P33360.06.10 ASTM D1970 07/01/10
P33370.03.11 TAS 103 03/02/11
P33370.04.11 ASTM D 1623 04/26/11
P36900.09.11 TAS 103/ASTM D4798 &G155 09/01/11
P37300.10.11 TAS 110/ASTM D4798&D1970 10/19/11
P40390.08.12-2 ASTM D 1623 08/07/12
P37590.07.13-1 ASTM D6164 07/02/13
P45270.05.14 TAS 103,TAS 110&ASTM D1623 05/12/14
P46520.10.14 ASTM D1623 10/03/14
P44360.10.14 TAS 103 &TAS 110 10/07/14
P43290.10.14 ASTM D 1970&TAS 110 10/17/14
PLYG-SC10130.06.16-3 TAS 103 &TAS 110 06/27/16
PLYG-10130.06.16-1 ASTM D1970&TAS.110 06/27/16
PRI Asphalt Technologies PUSA-035-02-01 TAS 103 09/29/06
PUSA-055-02-02 TAS 103 12/10/07
PUSA-089-02-01 TAS 103/ASTM D4798 &G155 07/06/09
Momentum Technologies,Inc. JX20H7A TAS 103/ASTM D4798 &G155 04/01/08
RX14E8A TAS 103/ASTM D4798&G155 11/09/09
DX23D8B TAS 103/ASTM D4798&G155 02/18/10
DX23D8A TAS 103/ASTM D4798 &G155 02/18/10
LABELING:
1. All membranes or packaging shall bear the imprint or identifiable marking of the manufacturer's name or logo,city
and state of manufacturing facility and the following statement: "Miami-Dade County Product Control Approved"
or the Miami-Dade County Product Control Seal as shown below.
MIAMI-DAD,COUNTY
BUILDING PERMIT REQUIREMENTS:
Application for building permit shall be accompanied by copies of the following:
1.This Notice of Acceptance.
2.Any other documents required by the Building Official or applicable building code in order to properly evaluate the
installation of this materials.
NOA No.: 17-0614.22
Q-DAF-Ty.-9=EC=UNTY Expiration Date: 09/13/21
Approval Date: 07/06/17
Page 3 of 8
INSTALLATION PROCEDURES:
Deck Type 1: Wood,non-insulated
Deck Description: Min. 19/32"plywood or wood plank
System Type E(1): Anchor sheet mechanically fastened to deck,membrane adhered
Anchor/Base Sheet: One or more plies of ASTM D 226 Type II or ASTM D 2626.
Fastening: Per FBC 1518.2& 1518.4 Nails and tin caps 12"grid, 6"o.c.at a minimum 4"head lap. (for
base sheet only)
Membrane: Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick
TU P,Polystick TU Plus,Polystick MTS or Polystick MTS Plus,self-adhered.
Surfacing: See General Limitations Below.
Deck Type 1: Wood,non-insulated
Deck Description: Min. 19/32"plywood or wood plank
System Type E(2): Anchor sheet mechanically fastened to deck,membrane adhered
Anchor/Base Sheet: One or more plies of ASTM D 226 Type II or ASTM D 2626.
Fastening: Per FBC 1518.2& 1518.4 Nails and tin caps 12" grid, 6"o.c.at a minimum 4"head lap. (for
base sheet only)
Membrane: Elastoflex S6 G,hot asphalt applied
Surfacing: See General Limitations Below.
Deck Type 1: Wood,non-insulated
Deck Description: Min. 19/32"plywood or wood plank
System Type E(3): Base sheet mechanically fastened to deck, subsequent cap membrane self-adhered.
Anchor/Base Sheet: One or more plies of ASTM D 226 Type II or ASTM D 2626.
Fastening: Per FBC 1518.2& 1518.4 Nails and tin caps 12"grid,6"o.c. at a minimum 4"head lap. (for
base sheet only)
Ply Sheet: Polystick MTS Plus,self-adhered with minimum 3"horizontal laps and minimum 6"
vertical laps.
Membrane: Polystick TU Plus,self-adhered.
Surfacing: See General Limitations Below.
NOA No.: 17-0614.22
Mu�hnLMMG COUNTY Expiration Date: 09/13/21.
Approval Date: 07/06/17
Page 4 of 8
INSTALLATION REQUIREMENTS:
1. All nails in the deck shall be carefully checked for protruding heads. Re-fasten any loose deck panels, and
sweep the deck thoroughly to re move any dust and debris prior to application.
2. Place the underlayment over metal drip edge in accordance with RAS 111.
3. Place the first course of membrane parallel to the eave,rolling the membrane to obtain maximum contact.
Remove the release film as the membrane is applied. All side laps shall be a minimum of 3"and end laps shall
be a minimum of 6". Roll the membrane into place after removing the release strip. Vertical strapping of the
roof with Polystick is acceptable. Membrane shall be back nailed in accordance with applicable building code.
4. When applying the membrane in the valley,start at the low point and work to the high point,rolling the
membrane from the center outward in both directions.
5. For ridge applications,center the membrane and roll from the center outward in both directions.
6. Roll or broom the entire membrane surface so as to have full contact with the surface,giving special attention
to lap areas.
7. Flash vent pipes, stacks,chimneys and penetrations in compliance with Roof Assembly current Product Control
Notice of Acceptance.
8. All protrusions or drains shall be initially taped with a 6"piece of underlayment. The flashing tape shall be
pressed in place and formed around the protrusion to ensure a tight fit. A second layer of Polystick shall be
applied over the underlayment.
GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance.
2. Polystick Dual Pro,Polystick Tile Pro,Polystick TU Plus,Polystick MTS and Polystick MTS Plus may be
used in asphaltic shingles,wood shakes and shingles,non-structural metal roofing,roof tile systems and quarry
slate roof assemblies.
Polystick TU P may be used in all the previous assemblies listed except metal roofing.
Polystick IR-Xe may be used in all the previous assemblies listed except metal roofing and roof tile systems.
Polystick TU Max may be used in non-structural metal roofing and roof tile systems.
Elastoflex S6 G may be used in roof tile systems only.
3. Deck requirements shall be in compliance with applicable building code.
4. Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick TU
Plus,Polystick MTS and Polystick MTS Plus shall be applied to a smooth, clean and dry surface. The deck
shall be free of irregularities.
5. Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick TU
Plus,Polystick MTS and Polystick MTS Plus shall not be adhered directly over a pre-existing roof membrane
as a recover system.
6. Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick TU
Plus,Polystick MTS and Polystick MTS Plus shall not be left exposed as a temporary roof for longer than the
amount of days listed in the table below after application. Polyglass reserves the right to revise or alter product
exposure times;not to exceed the preceeding maximum time limitations.
Exposure Limitations(Days)
MTS IR-Xe Elastoflex TU TU PTile Pro Dual Pro TU Max MTS Plus
S6 G Plus
Winter Haven,FL 180 90 180 180 180 180 180 180 180
Hazelton,PA N/A 90 N/A 180 N/A N/A N/A 180 N/A
7. All products listed herein shall have a quality assurance.audit in accordance with the Florida Building Code and
• MIAMI•DADE COUNTY
NOA No.: 17-0614.22
Expiration Date: 09/13/21
Approval Date: 07/06/17
Page 5 of 8
Rule 61 G20-3 of the Florida Administrative Code.
8. In roof tile application,data for the attachment resistance of roof tiles shall be as set forth in the roof tile
manufacturer's Notice of Acceptance.
Polystick Tile Pro,Polystick TU Max,Polystick TU Plus or Elastoflex S6 G may be used in both adhesive
set and mechanically fastened roof tile applications.
Polystick Dual Pro is limited to mechanically fastened roof tile applications.
Polystick MTS and Polystick MTS Plus are limited to mechanically fastened with the limitations outlined in
Section 9.
Polystick TU P may be used in mechanically fastened roof tile applications with the exception of mortar set tile
applications.
9. When loading roof tiles on roof file underlayment for(direct-to-deck)file assemblies,the maximum roof slope
shall be as follows: (See Table Below)
Tile Polystick Elastoflex Polystick TU Plus, Polystick Polystick System(E3)
Profile MTS S6 G TU P,Tile Pro, TU Max MTS Plus MTS Plus with
Dual Pro TU Plus
Flat Tile Prohibited 4:12 6:12 6:12 5:12 6:12
without battens
Profiled Prohibited 4:12 6:12 6:12 4:12 6:12
Tile without battens
The above slope limitations can be exceeded only by using battens in accordance with the Approved Tile System
Notice of Acceptance and applicable Florida Building Code requirements. When battens are required,they shall
be utilized during loading and installation of tiles.
10. Care should be taken during the loading procedure to keep foot traffic to a minimum and to avoid dropping of
tile directly on the underlayment.Refer to Polyglass' Tile loading detail below for loading procedure—two tiles
laid perpendicular to slope followed by a maximum four file stack parallel to the slope, for a total of 6 tiles—for
all underlayments except Polystick MTS which shall be loaded onto battens.
(6 Max.Per Stack)
N
r
• 'ULYJIILA IU MUS
NOA No.: 17-0614.22
CMLAAMMI-DADMECOUNTY
Expiration Date: 09/13/21
Approval Date: 07/06/17
Page 6 of 8
11. Refer to prepared roofing system Product Control Notice of Acceptance for listed approval of this product with
specific prepared roofing products. Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU
Max,Polystick TU P,Polystick TU Plus,Polystick MTS,Polystick MTS Plus or Elastoflex S6 G may be
used with any approved roof covering Notice of Acceptance listing Polystick IR-Xe,Polystick Dual Pro,
Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick TU Plus,Polystick MTS,Polystick MTS
Plus or Elastoflex S6 G as a component part of an assembly in the Notice of Acceptance.
If Polystick IR-Xe,Polystick Dual Pro,Polystick Tile Pro,Polystick TU Max,Polystick TU P,Polystick
TU Plus,Polystick MTS,Polystick MTS Plus or Elastoflex S6 G are not listed,a request may be made to the
Authority Having Jurisdiction(AHJ)or the Miami-Dade County Product Control Section for approval provided
that appropriate documentation is provided to detail compatibility of the products,wind uplift resistance,and fire
testing results.
POLYGLASS GENERAL APPLICATION GUIDELINES FOR POLYSTICK MEMBRANES
PLEASE CHECK WITH LOCAL BUILDING CODES REGARDING LIMITATIONS OF SPECIFIC APPLICATIONS.
LOCAL CODES MAY SUPERSEDE POLYGLASS REQUIREMENTS AND RECOMMENDATIONS.
1. Polyglass does accept the direct application of Polystick underlayment membranes to wood decks. Installers are
cautioned to refer to applicable local building codes prior to direct deck installation to ensure this is acceptable.
Please also refer to applicable Product Data Sheets of the corresponding products.
2. All rolls,with the exception of Polystick TU Plus should be back-nailed in selvage edge seam as per Polyglass
Back Nailing Guide. Nails shall be, 11 gauge ring shank type,applied with a minimum 1 V metal disk as
required in Miami-Dade County or simplex type nail as otherwise allowable in other regions,at a minimum rate
of 12" o.c. Polystick TU Plus should be back nailed in designated area marked"nail area,area para clavar"on
the face of membrane,with the above stated nails and/or disks.The head lap membrane is to cover the area being
back-nailed. (Please refer to applicable local building codes prior to installation.)
3. All seal lap seams(selvage laps)must be rolled with a hand roller to ensure full contact.
4. All fabric over fabric;and granule over granule end laps,shall have a 6"wide,uniform layer of Polyglass
Polyplus 55 Premium Modified Flashing Cement,Polyglass Polyplus 50 Premium MB Flashing Cement,
XtraFlex 50 Premium Modified Wet/Dry Cement,Polyglass PG500 MB Flashing Cement,applied in between
the application of the lap.The use of mastic between the laps does not apply to Polystick MTS.
5. A maximum of 6 tiles per stack are allowed when loading tile on the underlayments.Refer to the Polyglass Tile
Loading Guidelines. See General Limitations#9 and#10.
6. Battens and/or Counter-battens,as required by the tile manufacturers NOA,must be used on all projects for
pitch/slopes of 7712" or greater. It is suggested that on pitch/slopes in excess of 6 '/4"/12",precautions should be
taken, such as the use of battens to prevent tile sliding during the loading process.
7. Minimum cure time after membrane installation&before loading of roofing tiles is Forty-Eight(48)Hours.
8. Polystick membranes may not be used in any exposed application such as crickets,exposed valleys,or exposed
roof to wall details.
9. Repair of Polystick membranes is to be accomplished by applying Polyglass Polyplus 55 Premium Modified
Flashing Cement,Polyglass Polyplus 50 Premium MB Flashing Cement,XtraFlex 50 Premium Modified
Wet/Dry Cement,Polyglass PG500 MB Flashing Cement to the area in need of repair,followed by a patch of the
Polystick material of like kind should be set and hand rolled in place over the area needing such repair.Patching
membrane shall be a minimum of 6 inches in either direction. The repair should be installed in such a way so
that water will run parallel to or over the top of all laps of the patch.
NOA No.: 17-0614.22
CMAMMADECMOUNTY Expiration Date: 09/13/21
Approval Date: 07/06/17
Page 7 of 8
10. All self-adhered membranes must be rolled to ensure full contact with approved,substrates. Polyglass requires a
minimum of 40 lbs for a weighted roller for the rolling of the field membrane. Hand rollers are acceptable for
rolling of patches or small areas of the roof. Brooming may be used where slope prohibits rolling.
11. All approved substrates should be dry,clean and properly prepared,before any application of Polystick
membranes commences. An approved substrate technical bulletin can be furnished upon request.It is
recommended to refer to applicable building codes prior to installation to verify acceptable substrates.
12. The Polyglass Miami-Dade Notice of Acceptance(NOA) approval for Polystick membranes can be furnished
upon request by our Technical Services Department by calling 1 (800) 894-4563.
13. Questions in regards to the application of Polyglass products should be directed to our Technical Services
'Department at 1 (800) 894-4563.
14. Polyglass recommends that applicators follow good roofing practices and applicable procedures as outlined by
the National Roofing Contractors Association(NBCA).
PLEASE CHECK WITH LOCAL BUILDING CODES REGARDING LIMITATIONS OF SPECIFIC APPLICATIONS.
LOCAL CODES MAY SUPERSEDE POLYGLASS REQUIREMENTS AND RECOMMENDATIONS.
END OF THIS ACCEPTANCE
NOA No.: 17-0614.22
MIAMI-DAD,COUNTY Expiration Date: 09/13/21
Approval Date: 07/06/17
Page 8 of 8
RECEIVED
M1AMl,f FEB 2 4 2020
E MIAMI-DADS COUNTY
ST. Lucie County, Permit&U DUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES 11805 SW 26 Street,Room 208
BOARD AND CODE ADMINISTRATION DIVISION Miami,Florida 33175-2474
T(786)315-2590 F(786)315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.eov/economy
Polyglass USA,Inc.
150 Lyon Drive
Fernley,NV 89408
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials.The
documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated below.The Miami-Dade County Product Control Section
(In Miami Dade County)and/or the AHJ(in areas other than Miami Dade County)reserve the right to have this
product or material tested for quality assurance purposes.If this product or material fails to perform in the accepted
manner,the manufacturer will incur the expense of such testing and the AHJ may immediately revoke,modify,or
suspend the use of such product or material within their jurisdiction. RER reserves the.right to revoke this acceptance,
if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein,and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Polyglass Self-Adhered Roof System over Wood Decks
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and following
statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use,and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA# 17-1016.01 and consists of pages 1 through 38.
The submitted documentation was reviewed by Alex Tigera.
NOA No.: 19-0311.04
MIAMI-DAD,COUNTY Expiration Date: 10/11/22
opApproval Date:03/21/19
�ne C
Page 1 of 38
r '
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub-Categorv: Modified Bitumen
Materials SBS/APP/TPO
Deck Type: Wood
Maximum Design Pressure -112.5 psf
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
TABLE 1
Test Product
Product Dimensions Specification Description
Polyanchor 250' x 48" ASTM D 4601, A polymer woven,high performance,synthetic base
Type II sheet.
Polyglass G2 Base 108' x 36" ASTM D 4601, Asphalt-coated fiberglass reinforced base sheet
Type H
Elastoshield HT 65' 8"x 3' 3-3/8" ASTM D 6162 SBS modified asphalt coated fiberglass/polyester
reinforced base sheet.
XtraFlex SBS HT 65' 8"x 3' 3-3/8" ASTM D 6162 SBS modified asphalt coated fiberglass/polyester
Base 650 reinforced base sheet.
Elastobase 65'2"x 3' 3-3/8" ASTM D 6163, SBS modified asphalt coated fiberglass reinforced
Type I base sheet.
+Elastoflex SA V 66' 8"x 3' 3 3/s" ASTM D 6163, Self-adhered,fiberglass reinforced, SBS modified
Type I bitumen membrane with a self-adhering back face and
a smooth top surface.
Elastoflex SA V FR 66' 8"x 3' 3-3/8" ASTM D 6163, Self-adhered,fire-rated,fiberglass reinforced, SBS
Type I modified bitumen membrane with a self-adhering back
face and a smooth top surface.
Elastoflex SA V 66' 8"x 3' 3-3/8" ASTM D 6163, Self-adhered,fiberglass reinforced, SBS modified
PLUS Type I bitumen membrane with a self-adhering back face and
a smooth top surface.
Elastoflex SA V 66' 8"x 3' 3-3/8" ASTM D 6163, Self-adhered,fire-rated,fiberglass reinforced, SBS
PLUS FR Type I modified bitumen membrane with a self-adhering back
face and a smooth top surface.
XtraFlex SBS Base 66' 8"x 3' 33/8" ASTM D 6163, Self-adhered,fiberglass reinforced, SBS modified
SA Type I bitumen membrane with a self-adhering back face and
a smooth top surface.
XtraFlex SBS Glass 65' 8"x 3' 3-3/8" ASTM D 6163, SBS modified asphalt coated fiberglass reinforced
Base Type I base sheet.
Elastobase P 65' 8"x 3' 3-3/8" ASTM D 6164, SBS modified asphalt coated polyester reinforced base
Type I sheet.
Elastoflex SA P 32' 10"x3' 3-3/8" ASTM D 6164, Self-adhered,fiberglass reinforced, SBS modified .
Type I bitumen membrane with a self-adhering back face and
a granule top surface.
NOA No.: 19-0311.04
MAMI-DADE COUNTY Expiration Date: 10/11/22
Approval Date:03/21/19
Page 2 of 38
Membrane Type: SBS/APP
Deck Type 1: Wood,Non-Insulated
Deck Description: 19/32° or greater plywood or wood plank,fastened at 24"spans with 8d common nails at 4"o.c.
or#8 wood screws at 6"o.c.
System Type E(1): Base sheet is mechanically attached to roof deck. Membranes subsequently adhered.
All General and System Limitations apply.
Base Sheet: One ply of Elastobase,Elastobase P,Elastoshield HT,Polyanchor,XtraFlex SBS Glass Base
or XtraFlex SBS HT Base 650 fastened to the deck as described below:
Fastening: Attach base sheet using 11 ga. annular ring shank nails and 1-5/8"diameter tin caps spaced 8"
o.c. in a 4"lap and 8"o.c. in three equally spaced staggered rows in the center of the sheet.
Ply Sheet: One or more plies of Elastoflex SA V,Elastoflex SA V FR,Elastoflex SA V PLUS,Elastoflex
SA V PLUS FR or.XtraFlex SBS Base SA self-adhered.
Membrane: One ply of Elastoflex SA P,Elastoflex SA P FR,Poiyflex SA P,Polyflex SA P FR,Polyfresko
G APP SA,Polyfresko G APP SA FR,Polyfresko G SBS SA,Polyfresko G SBS SA FR,
PolyKool,Polyreflect,XtraFlex APP G SA,XtraFlex Kool APP S SA or XtraFlex SBS G SA
self-adhered.
Surfacing: Install one of the approved surfacing products listed in Table 4 to obtain desired coating or
(Optional) required fire classification.
Maximum Design
Pressure: -52.5 psf; (See General limitation#7.).
NOA No.: 19-0311.04
MIAMI-mane COUNTY Expiration Date: 10/11/22
Approval Date:03/21/19
Page 30 of 38
WOOD DECK SYSTEM LIMITATIONS:
1. A slip sheet is required with Ply 4 and Ply 6 when used as a mechanically fastened base or anchor sheet.
GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. Insulation may be installed in multiple layers. The first layer shall be attached in compliance with Product
Control Approval guidelines. All other layers shall be adhered in a full mopping of approved asphalt applied
within the EVT range and at a rate of 20-40 lbs./sq.,or mechanically attached using the fastening pattern of the
top layer
3. All standard panel sizes are acceptable for mechanical attachment. When applied in approved asphalt,panel size
shall be 4'x 4'maximum.
4. An overlay and/or recovery board insulation panel is required on all applications over closed cell foam
insulations when the base sheet is fully mopped.If no recovery board is used the base sheet shall be applied using
spot mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip mopped 8"ribbons in three rows, one
at each side lap and one down the center of the sheet allowing a continuous area of ventilation. Encircling of the
strips is not acceptable. A 6" break shall be placed every 12' in each ribbon to allow cross ventilation. Asphalt
application of either system shall be at a minimum rate of 12 lbs./sq.
Note: Spot attached systems shall be limited to a maximum design pressure of-45 psE
5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force(F')value of 275 ibf.,as
tested in compliance with Testing Application Standard TAS 105. If the fastener value, as field-tested,are below
275 lbf. insulation attachment shall not be acceptable.
6. Fastener spacing for mechanical attachment of anchor/base sheet or membrane attachment is based on a minimum
fastener resistance value in conjunction with the maximum design value listed within a specific system. Should
the fastener resistance be less than that required,as determined by the Building Official,a revised fastener
spacing,prepared,signed and sealed by a Florida registered Professional Engineer,Registered Architect,or
Registered Roof Consultant may be submitted. Said revised fastener spacing shall utilize the withdrawal
resistance value taken from Testing Application Standards TAS 105 and calculations in compliance with Roofing
Application Standard RAS 117.
7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these areas. Fastener
densities shall be increased for both insulation and base sheet as calculated in compliance with Roofing
Application Standard RAS 117. Calculations prepared, signed and sealed by a Florida registered Professional
Engineer, Registered Architect, or Registered Roof Consultant (When this limitation is specifically referred
within this NOA,General Limitation#9 will not be applicable.)
8. All attachment and sizing of perimeter nailers,metal profile,and/or flashing termination designs shall conform to
Roofing Application Standard RAS 111 and applicable wind load requirements.
9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones(i.e. field,
perimeters, and corners).Neither rational analysis,nor extrapolation shall be permitted for enhanced fastening at
enhanced pressure zones(i.e.perimeters,extended corners and corners). (When this limitation is specifically
referred within this NOA,General Limitation#7 will not be applicable.)
10. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61 G20-3 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No.: 19-0311.04
CMIAMIM-DAMDEa COU=NTYExpiration Date: 10/11/22
Approval Date:03/21/19
Page 38 of 38