HomeMy WebLinkAboutSpec Transfer SwitchAutomatic
Transfer Switches
Description
Service and non -Service rated
Automatic Smart Transfer Switches
100 - 400 Amps, Single Phase
C @ us
LISTED �MMa
*CUL only applies to non -service rated switches
Generac Automatic Transfer Switches are designed for use with single phase generators that utilize an Evolution TM or Nexus TM
Controller. The 100, 200, and 400 amp open transition switches are available in single phase in both service equipment rated and
non -service equipment rated configurations. The 150 and 300 amp open transition switches are only available in a service rated
equipment configuration.
Standard Features
Service rated (RXSW) Generac Automatic Transfer Switches are housed in an aluminum NEMA/UL Type 3R enclosure*, with
electrostatically applied and baked powder paint. The Heavy Duty Generac Contactor is a UL recognized device, designed for
years of service. The controller at the generator handles all the timing, sensing, exercising functions, and transfer commands. All
switches are covered by a 5 year limited warranty.
* Non -service rated (RXSC) switches are housed in a steel enclosure.
DPM Technology
Through the use of digital power technology (DPM), these switches have the capability to manage up to 4 individual HVAC (24 VAC
controlled) loads with no additional hardware. When used in tandem with Smart Management Modules, up to 8 more loads can be
managed as well, providing the most installation efficient power management options available.
ISO
100 1:
2008
GENERAC®
100-400 Amps, Single Phase
I
All timing and sensing functions originate in the generator controller
Automatic Smart Transfer Switches
Utilityvoltage drop -out ................ ......... ......................................... .......................
.......... ............................................... .................... ........... .............. ....................... <65%
Timer to generator start..................................................................................................10
second factory set, adjustable between 2-1500 seconds by a qualified dealer*
Enginewarm up delay.................................................................................................................................................................................................................5
seconds
Standbyvoltage sensor .................. ....................................... .............................................
....... :...................... ... ............. ............... .................... ...........65% for 5 seconds
Utilityvoltage pickup... ............. _ .............. _ ................................................................................................................
................................. .................................. > 80%
Re -transfer time delay.. .............. ......................................... ...............
_ .......... ...................................... .............. ........ .............. ....... _ ............................... 15 seconds
Enginecool -down timer............................................................................................................................................................................................................60
seconds
Exerciser..............................................................................................................................................................5
or 12 minutes adjustable weekly/Bi-weekly/Monthly.
The transfer switch can be operated manually without power applied.
*When used in conjunction with units utilizing Evolution'" controls
—Adjustable via the controller
Model
RXSC100A3
RXSW100A3
RXSW150A3
RXSC200A3
RXSW200A3
RXSW300A3
RXSC400A3
RXSW400A3
Amps
100
100
150
200
200
300
400
400
Voltage
120/240,10
120/240,10
120/240,10
120/240,10
120/240,10
120/240,10
120/240,10
120/240,10
Load Transition Type
(Automatic)
Open Transition
Open Transition
Service Rated
Open Transition
Service Rated
Open Transition
Open Transition
Service Rated
Open Transition
Service Rated
Open Transition
Open Transition
Service Rated
Enclosure Type
NEMA/UL 313
NEMA/UL 313
NEMA/UL 313
NEMA/UL 313
NEMA/UL 3R
NEMA/UL 311
NEMA/UL 311
NEMA/UL 3R
UL Rating
UUCUL
UL
UL
UUCUL
UL
UL
UL/CUL
UL
Withstand Rating
(Amps)
10,000
10,000
22,000
10,000
22,000
22,000
22,000
22,000
Lug Range
1/0 - #14
250 MCM - #6
600 MCM
- #4 or 1/0 - 250 MCM
Dimensions
Model
RXSC100A3
RXSW100A3
RXSW150A3
RXSC200A3
RXSW200A3
RXSW300A3
RXSC400A3
RXSW400A3
Height
Hit
17.24/437.9
17.24/437.9
26.75/679.4
17.24/437.9
26.75/679.4
42.91/1089.9
31.25/793.8
42.91/1089.9
(in./mm)
H2
20/508
20/508
30/762
20/508
30/762
48/1219.2
36/914.4
48/1219.2
Width
W1
12.5/317.5
12.5/317.5
10.5/266.7
12.5/317.5
10.5/266.7
16.69/423.9
19.18/487.2
16.69/423.9
(in./mm)
W2
14.6/370.8
14.6/370.8
13.5/342.9
14.6/370.8
13.5/342.9
21.82/554.2
24/609.6
21.82/554.2
Depth (in./mm)
7.09/180.1
7.09/180.1
6.3/160.1
7,09/180.1
6.3/160.1
10.06/255.5
10.06/255.5
10.06/255.5
Weight (Ibs./kilos)
20/9.07
22.5/10.21
39/17.69
20/9.07
39/17.69
140/63.5
133/60.33
140/63.5
b
H2 H'
I�DEPTH-1 L-- 112 --1
DEPTH
GENERAC® General; Power Systems, Inc. - S45 W29290 HWY.. 59, Waukesha, WI 53189 - generac.com
02017 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 1000001 3459-A 04/24/17