HomeMy WebLinkAboutSTEFANAKIS- MANUAL JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Project Summary Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
Project Information
STEFANIAKIS RESIDENCEFor:
S. INDIAN RIVER DRIVE, FORT PIERCE, FL
Notes:
Design Information
Fort Pierce, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F42 Outside db °F90
Inside db °F70 Inside db °F75
Design TD °F28 Design TD °F15
Daily range M
Relative humidity %50
Moisture difference gr/lb61
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh22434 Struc ture Btuh15436
Ducts Btuh4946 Ducts Btuh6956
Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0
(none)(none)
Humidification Btuh0 Blower Btuh0
Piping Btuh0
Equipment load Btuh27380 Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load Btuh21272
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average
0Fireplaces Structure Btuh3203
Ducts Btuh1883
Central vent (0 cfm)Btuh0
CoolingHeating (none)
20322032Area (ft²)Equipment latent load Btuh5086
1977919779Volume (ft³)
Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh26358
Equiv. AVF (cfm)53105 Req. total capacity at 0.70 SHR ton2.5
Heating Equipment Summary Cooling Equipment Summary
Make Make Carrier
Trade Trade CARRIER
Model Cond CA16NW03000G0A0
AHRI ref Coil FX4DNF037L
AHRI ref 9201884
Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER
Heating input kW7.7 Sensible cooling Btuh20580
Heating output Btuh26238 Latent cooling Btuh8820
Temperature rise °F24 Total cooling Btuh29400
Actual air flow cfm980 Actual air flow cfm980
Air flow factor cfm/Btuh0.036 Air flow factor cfm/Btuh0.044
Static pressure in H2O1.00 Static pressure in H2O1.00
Space thermostat Load sensible heat ratio 0.81
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name Entire House BEDROOM 2
2 Exposed wall 158.9 ft 25.0 ft
3 Room height 9.7 ft 9.3 heat/coolft
4 Room dimensions ft159.0x1.0
5 Room area 2032.0 ft²159.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 344 314 1255 686 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 30 0 546 450 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 464 304 1218 666 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 45 0 819 1520 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 13 0 244 453 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 80 0 1463 2042 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 20 20 223 211 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 532 475 1900 1038 112 100 399 218
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 6 6 109 90 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 9 9 164 135 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 12 12 218 180 12 12 218 180
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 30 30 546 358 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 223 200 802 438 121 113 453 247
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 8 0 142 263 8 0 142 263
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 15 0 273 507 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2032 2032 3222 2780 159 159 252 218
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2032 159 6043 0 159 25 951 0
6 c) AED excursion 0 32
Envelope loss/gain 19188 11817 2415 1158
12 a) Infiltration 3246 869 483 129
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 2750 400
Subtotal (lines 6 to 13)22434 15436 2898 1687
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 135 54
14 Subtotal 22434 15436 3033 1741
15 Duct loads 22%45%4946 6956 22%45%669 785
Total room load 27380 22392 3702 2526
Air required (cfm)Air required (cfm)980 980 132 111
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name CLST 2 BATH
2 Exposed wall 2.0 ft 5.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft2.0x10.0 ft5.0x5.0
5 Room area 20.0 ft²25.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 19 19 74 41 47 41 162 89
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 6 6 109 90
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 20 20 32 27 25 25 40 34
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 20 2 76 0 25 5 190 0
6 c) AED excursion -2 -6
Envelope loss/gain 182 66 501 207
12 a) Infiltration 39 10 97 26
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)221 76 598 233
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -221 -76 50 17
14 Subtotal 0 0 648 250
15 Duct loads 22%45%0 0 22%45%143 113
Total room load 0 0 791 363
Air required (cfm)Air required (cfm)0 0 28 16
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 3
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name SINKS PANTRY
2 Exposed wall 0 ft 6.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft5.0x5.0 ft6.0x13.0
5 Room area 25.0 ft²78.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 56 56 223 122
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 25 25 40 34 78 78 124 107
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 25 0 0 0 78 6 228 0
6 c) AED excursion -1 -10
Envelope loss/gain 40 33 575 219
12 a) Infiltration 0 0 116 31
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 150
Subtotal (lines 6 to 13)40 33 691 400
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 70 34 36 30
14 Subtotal 110 68 727 430
15 Duct loads 22%45%24 30 22%45%160 194
Total room load 134 98 888 624
Air required (cfm)Air required (cfm)5 4 32 27
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 4
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name BEDROOM 3 CLST 3
2 Exposed wall 10.9 ft 0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft151.0x1.0 ft15.0x1.0
5 Room area 151.0 ft²15.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 102 87 350 191 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 15 0 273 507 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 151 151 239 207 15 15 24 21
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 151 11 415 0 15 0 0 0
6 c) AED excursion 174 -1
Envelope loss/gain 1277 1079 24 20
12 a) Infiltration 213 57 0 0
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 400 0
Subtotal (lines 6 to 13)1490 1535 24 20
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 38 32 -24 -20
14 Subtotal 1528 1568 0 0
15 Duct loads 22%45%337 706 22%45%0 0
Total room load 1865 2274 0 0
Air required (cfm)Air required (cfm)67 100 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 5
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name AHU CLST LINEN
2 Exposed wall 0 ft 0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft2.0x4.0 ft10.0x2.0
5 Room area 8.0 ft²20.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 8 8 13 11 20 20 32 27
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 8 0 0 0 20 0 0 0
6 c) AED excursion 0 -1
Envelope loss/gain 13 11 32 27
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)13 11 32 27
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -13 -11 -32 -27
14 Subtotal 0 0 0 0
15 Duct loads 22%45%0 0 22%45%0 0
Total room load 0 0 0 0
Air required (cfm)Air required (cfm)0 0 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 6
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name LAUNDRY KITCHEN
2 Exposed wall 0 ft 10.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft118.0x1.0 ft10.0x17.0
5 Room area 118.0 ft²170.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 93 84 336 184
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 9 9 164 135
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 118 118 187 161 170 170 270 233
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 118 0 0 0 170 10 380 0
6 c) AED excursion -17 -40
Envelope loss/gain 187 145 1150 511
12 a) Infiltration 0 0 193 52
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 500 1000
Subtotal (lines 6 to 13)187 645 1343 1563
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 69 58 34 29
14 Subtotal 257 703 1377 1592
15 Duct loads 22%45%57 317 22%45%304 717
Total room load 313 1020 1681 2309
Air required (cfm)Air required (cfm)11 45 60 101
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 7
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name GREAT ROOM M HALL
2 Exposed wall 47.0 ft 0 ft
3 Room height 10.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft549.0x1.0 ft68.0x1.0
5 Room area 549.0 ft²68.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 278 164 656 359 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 13 0 244 453 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 80 0 1463 2042 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 20 20 223 211 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 206 176 705 385 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 30 30 546 358 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 549 549 870 751 68 68 108 93
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 549 47 1787 0 68 0 0 0
6 c) AED excursion -16 -2
Envelope loss/gain 6494 4543 108 91
12 a) Infiltration 1006 270 0 0
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)7501 4812 108 91
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 35 29 -108 -91
14 Subtotal 7536 4842 0 0
15 Duct loads 22%45%1661 2182 22%45%0 0
Total room load 9197 7023 0 0
Air required (cfm)Air required (cfm)329 307 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 8
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name HALL M BATH
2 Exposed wall 0 ft 11.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft64.0x1.0 ft155.0x1.0
5 Room area 64.0 ft²155.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 102 92 370 202
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 10 0 182 150
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 64 64 101 88 155 155 246 212
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 64 0 0 0 155 11 418 0
6 c) AED excursion -2 -23
Envelope loss/gain 101 85 1216 541
12 a) Infiltration 0 0 213 57
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 300
Subtotal (lines 6 to 13)101 85 1428 898
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -101 -85 0 0
14 Subtotal 0 0 1428 898
15 Duct loads 22%45%0 0 22%45%315 405
Total room load 0 0 1743 1302
Air required (cfm)Air required (cfm)0 0 62 57
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 9
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name M TOILET M WIC 2
2 Exposed wall 0 ft 0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft3.0x5.0 ft6.0x5.0
5 Room area 15.0 ft²30.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 15 15 24 21 30 30 48 41
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 15 0 0 0 30 0 0 0
6 c) AED excursion -1 -1
Envelope loss/gain 24 20 48 40
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)24 20 48 40
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 8 7 11 9
14 Subtotal 32 27 58 49
15 Duct loads 22%45%7 12 22%45%13 22
Total room load 39 39 71 71
Air required (cfm)Air required (cfm)1 2 3 3
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2020-Feb-07 08:45:32
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 10
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Feb 07, 2020Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name M WIC 1 MASTER BEDROOM
2 Exposed wall 6.0 ft 36.0 ft
3 Room height 9.3 heat/coolft 10.3 heat/coolft
4 Room dimensions ft6.0x5.0 ft332.0x1.0
5 Room area 30.0 ft²332.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 56 56 223 122 185 165 662 362
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 20 0 364 300
.WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 185 140 562 307
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 45 0 819 1520
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 25.4025.40 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 30 30 48 41 332 332 526 454
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 30 6 228 0 332 36 1369 0
6 c) AED excursion -5 -79
Envelope loss/gain 499 158 4303 2864
12 a) Infiltration 116 31 771 206
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)615 189 5073 3070
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 11 9
14 Subtotal 615 189 5084 3080
15 Duct loads 22%45%136 85 22%45%1121 1388
Total room load 751 275 6205 4467
Air required (cfm)Air required (cfm)27 12 222 196
2020-Feb-07 08:45:38
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 1
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Duct System Summary Feb 07, 2020Date:
Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
Project Information
STEFANIAKIS RESIDENCEFor:
S. INDIAN RIVER DRIVE, FORT PIERCE, FL
CoolingHeating
External static pressure in H2O1.00in H2O1.00
Pressure losses in H2O0in H2O0
Available static pressure in H2O1.00in H2O1.00
Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500
Lowest friction rate in/100ft1.000in/100ft1.000
Actual air flow cfm980cfm980
Total effective length (TEL)ft198
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st2115.014.6VlFx0x04.01.0001628791hBATH
st2115.013.4VlFx0x07.01.0001111323702hBEDROOM 2
st2115.011.7VlFx0x07.01.000100672274cBEDROOM 3
st5155.040.9VlFx0x08.01.0001541654599hGREAT ROOM
st5155.042.9VlFx0x08.01.0001541654599hGREAT ROOM-A
st4135.022.3VlFx0x07.01.000101602309cKITCHEN
st4135.020.7VlFx0x06.01.00045111020cLAUNDRY
st1115.030.0VlFx0x06.01.00057621743hM BATH
st1115.025.2VlFx0x04.01.0002139cM TOILET
st1115.027.2VlFx0x04.01.0001227751hM WIC 1
st1115.027.2VlFx0x04.01.0003371cM WIC 2
st3135.037.3VlFx0x07.01.000981113103hMASTER BEDROOM
st3135.035.3VlFx0x07.01.000981113103hMASTER BEDROOM-A
st4135.023.6VlFx0x05.01.0002732888hPANTRY
st2115.09.9VlFx0x04.01.00045134hSINKS
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st3 Peak AVF 222 196 1.000 636 8.0 0x0 VinlFlx st1
st1 Peak AVF 315 269 1.000 714 9.0 0x0 VinlFlx
st5 Peak AVF 329 307 1.000 745 9.0 0x0 VinlFlx st4
st4 Peak AVF 432 480 1.000 728 11.0 0x0 VinlFlx st2
st2 Peak AVF 665 711 1.000 905 12.0 0x0 VinlFlx
2020-Feb-07 08:45:38
Right-Suite® Universal 2019 19.0.08 RSU08101 Page 2
...umnets\Wrightsoft HVAC\STEFANAKIS RESIDENCE.rup Calc = MJ8 Front Door faces: E
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb1 0x 9800 980 0 0 0 0 x0 0 VlFx
���������������������������������������������������������������������������
���������������������������������������������������������������������������������
�����������������������������������������������������