THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH CONDOMINIUMS—BLDG.D CONCRETE REPAIRS
5163 N.HWY.AIA,FT.PIERCE,FL 34949
SLC BUILDING PERMIT NUMBER:2002-0526
PROJECT NAME: Ocean Harbor N.Condos—Bldg.D DATE: April 9,2020
Concrete Repairs
CLIENT: Elliott Merrill Community Management LOCATION: Ft.Pierce,FL
CONTRACT-OR:----Structure-Con _ _- - PROJECT MGR: Mr.Khris McConnell
INSPECTED BY: Todd Rhoten WEATHER: Sunny
WORK INSPECTED:
Units 216/316,416/516,,516,616 and 616/716—Continued demo of edge spalls.
OBSERVATIONS:
Unif 216/31.6 ::
•;: Chipping of 5palled concrete is complete and all corrosion in existing reinforcing bars has been exposed.
• °A total of 2'-6'-linear feet of edge&4 square feet of full depth to be repaired.
Uriit 416/516(North enol)
• 6ipping along the•balcony edge is in progress.
• Contractor'is chasing the corrosion in the bars and has stopped due to the location of a post tension anchor.
Unit 516/616
• Repaired areas have been poured and the form boards have been removed.
• Cable ends have been cut and grease caps placed.(Typ x3)
• Contractor is to grout pockets with a non-shrink,high strength grout.
Unit 616/716
• Chipping of spalled concrete is complete and all corrosion in existing reinforcing has been bars exposed.
• A total of 2'-6"linear feet of edge to be repaired.
All work to date complies with the design and permit documents.
RECOMMENDATIONS:
Unit 416/516 Contractor to lock-off(1)PT cable prior to any further chipping.
Unit 616-716 Two existing#4 bursting bars to be replaced.Cut corroded bars&dowel in new 94 bars w/6"epoxy
embed.
P
MTodd Rhoten
Page 1 of 3
M L Engineering Inc. Project No. 20-104 Report No. 7
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmnt.
Threshold Inspector Building Official: St.Lucie County Bldg.Dept.
2030 371 Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure-Con
Phone: (772)569-1257 File
Fax: (772)569-4041
www.mlenginceringinc.com
Pic 1
216-716 stack
North facing balconies.
i
a
Pic 2
Unit 216/316
Existing PT cable locked off.
` Edge spall demo around cable.
Reinforcing bars to be power tool cleaned&coated.
r
1M1 � r
Pic 3
Unit 416/516
Corrosion in reinforcing continues to adjacent PT
cable.
Work stopped until cable is locked off.
Page 2 of 3
M L Engineering Inc. Project No.20-104 Report No.7
Consulting Engineers Project Manager: Mr.Gene Ross—Elliott Merrill Community Mgmnt.
Threshold Inspector Building Official: St.Lucie County Bldg.Dept.
2030.37'Avenue Contractor: Mr.Robert Stark—Structure-Con
Vero Beach,Florida 32960 Mr.Khris McConnell—Structure-Con
Phone: (772)569-1257 File
Fax: (772)569-4041
www.mlengineeringinc.com
;Ta Pic 4
V�* Unit 5.16/616
Cable ends have been cut back and grease caps placed.
Pic 5
Unit 616/716
Bursting bars to be replaced.
r