5380-F85FB-v20.0 - Sheet - E4 - CONDUIT PLAN
(RE: NOTE 8)ASSOCIATE VESTIBULE OFFICE (SEE NOTE 12) BAS PANEL(SEE NOTE 14)2"C INTERCOM. 2"C DATA. 1"C POWER. 1"C POWER. 2"C DATA. 1"C POWER. 1"C TELE. (SEE NOTE 13) 1"C TELE. 2"C DATA. 2"C INTERCOM. 1"C POWER. 1"C TO OTHER SIDE FOR INTERCOM 0" 20' - 8" 23' - 1" 31' - 2" 31' - 6" 31' - 11" 32' - 4" 32' - 9" 33' - 11" 34' - 6" INTERSECTION OF CENTERLINES OF BUILDING 2"C.SEE ELEVATION NOTES SHEET E6 (1) 1" C. GRC FROM OFFICE TO EACH PYLON /MONUMENT SIGN. FOR DATA SEE NOTE 5.(SEE NOTE 15)1"C LOOP FOR INTERCOM 1"C E-STOP (SEE NOTE 2) 1"C POWER (SEE NOTE 2) 1"C E-STOP. (SEE NOTE 2) 3/4" C. LOTTERY DATA 1"C DATA 3/4"C POWER (SEE NOTE 2)(SEE NOTE 16)0"12' - 7"13' - 0"20' - 1"20' - 7"20' - 7"21' - 0"21' - 0"29' - 3"29' - 8"36' - 8"37' - 6"37' - 10"0" 1' - 8" 2' - 5" 4' - 10" 21' - 7" WATER SERVICE ROOM STAGING WOMEN'S RESTROOM (SEE NOTE 17)(SEE NOTE 17) 1"C DATA. (SEE NOTE 6) (SEE NOTE 12)(SEE NOTE 5)(SEE NOTE 18)(SEE NOTE 4)SEE NOTE #19 SEE NOTE #19 (SEE NOTE 3)0"44' - 0"0"2' - 2"7' - 8"8' - 6"12' - 6"15' - 9"22' - 0"26' - 10"30' - 3"30' - 10"32' - 0"42' - 1"42' - 5"45' - 9"3/4"C POWER (SEE NOTE 2) 3/4"C POWER (SEE NOTE 2) 1"C POWER (SEE NOTE 2) 3/4"C POWER (SEE NOTE 2) 1"C POWER (SEE NOTE 2) 1"C DATA (SEE NOTE 2)1-1/4"C POWER (SEE NOTE 2) 1"C DATA (SEE NOTE 2) 1"C POWER (SEE NOTE 2) 1"C POWER (SEE NOTE 2) 1"C DATA (SEE NOTE 2) 1"C DATA (SEE NOTE 2)1"C POWER (SEE NOTE 2) 1"C POWER (SEE NOTE 2) 0" 2' - 6" 3' - 2" 7' - 11" 17' - 9" 21' - 7" 0" 28' - 9" WALK-IN FREEZER WALK-IN REFRIG. FOOD SERVICE WASH ROOM ELECTRICAL ROOM FOOD SERVICE RETAIL AREA RETAIL AREA SELF SERVICE WALK-IN REFRIG. DELIVERY VESTIBULE RETAIL WALK-IN REFRIG. MEN'S RESTROOM REAR VESTIBULE COFFEE FOOD SERVICE (SEE NOTE 3) (1) 1" C. GRC FROM OFFICE TO EACH PYLON /MONUMENT SIGN. SEE NOTE 5. GENERAL NOTES: ELECTRICAL PLAN NOTES: 1. REFER TO DRAWING E3 FOR ROOF PLAN AND ADDITIONAL ELECTRICAL REQUIREMENTS AND EQUIPMENT CONNECTIONS. 2. REFER TO DRAWING E6 FOR ADDITIONAL ELECTRICAL ROOM INFO 3. COORDINATE CONDUIT REQUIREMENTS AND LOCATIONS WITH THE SITE AND PETROLEUM CONTRACTORS. 4. INSTALL CONDUCTORS AND CONDUITS IN ACCORDANCE WITH NEC REQUIREMENTS FOR VOLTAGE DROP AND DERATING. 5. THIS PROJECT HAS A LARGE QUANTITY OF UNDERGROUND CONDUITS. COORDINATE WITH PLUMBING AND STRUCTURAL PLANS TO AVOID UNDERGROUND SPACE CONFLICTS. PROVIDE REQUIRED BURIAL DEPTHS FOR UNDERGROUND CONDUITS TO AVOID SPACE CONFLICTS WITH OTHER DISCIPLINES. 6. THE ELECTRICAL CONTRACTOR SHALL EXTEND ALL ELECTRICAL CONDUITS FROM THE STORE TO THE EDGE OF THE CONCRETE CANOPY PAD AND AND TANK PAD. PETROLEUM CONTRACTOR TO RUN ALL CONDUITS UNDER CANOPY PAD TO CANOPY COLUMNS AND COORDINATE THE HEIGHT OF THE SEAL OFF FITTINGS WITH THE OPENINGS PROVIDED IN THE STEEL COLUMNS. GENERAL CONTRACTOR TO CONNECT AT SEAL OFF FITTINGS IN COLUMNS FOR CONDUIT RUNS FOR LIGHTING AND INTERCOM. 1. NOT USED. 2. CONDUIT TO BE RUN FROM FLOOR LOCATION TO ELECTRICAL ROOM OR CLOSEST WALL. FIELD COORDINATE LOCATION IN ELECTRICAL ROOM. REFER TO DRAWING E6 FOR ADDITIONAL INFORMATION. 3. THE ELECTRICAL CONTRACTOR SHALL EXTEND ALL ELECTRICAL CONDUITS FROM THE STORE TO THE EDGE OF THE CONCRETE CANOPY PAD AND TANK PAD. PETROLEUM CONTRACTOR TO RUN ALL CONDUITS UNDER CANOPY PAD TO CANOPY COLUMNS AND COORDINATE THE HEIGHT OF THE SEAL OFF FITTINGS WITH THE OPENINGS PROVIDED IN THE STEEL COLUMNS. GENERAL CONTRACTOR TO CONNECT AT SEAL OFF FITTINGS IN COLUMNS FOR CONDUIT RUNS FOR LIGHTING AND INTERCOM. 4. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUITS TO THE AIR PUMP (1-1" POWER CONDUIT TO BE RUN FROM SITE LIGHT CONDUIT), INCLUDING BUT NOT LIMITED TO, TRENCHING AND/OR EXCAVATION. COORDINATE LOCATION OF CONDUITS WITH PETROLEUM CONTRACTOR. 5. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL THREE DEDICATED CONDUITS TO EACH PYLON/MONUMENT SIGN: FROM MANAGER'S OFFICE: (1) -1" FOR DATA FOR PRICE SIGN DIGITS FROM ELECTRICAL ROOM: (1) -1" POWER FOR TO PYLON/MONUMENT SIGN. (1) -1" POWER FOR THE SIGN LIGHTING,PRICE DIGITS AND GENERAL DUTY RECEPTACLE. ALSO, PROVIDE (2) 3/4"C BETWEEN THE SIGNS WHEN THERE ARE (2) OR MORE SIGNS. 6. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A DEDICATED SIMPLEX OUTLET TO PRICE CHANGE CONTROLLER. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A 20 AMP WEATHERPROOF GFCI RECEPTACLE POWERED FROM A SEPARATE GENERAL PURPOSE CIRCUIT AT THE BASE OF EACH PYLON/MONUMENT SIGN. 7. NOT USED 8. SITE CONDUITS TO BE COORDINATED WITH SITE SPECIFIC REQUIREMENTS: (2) 1" PVC FOR SITE LIGHTING (2) 1" PVC TO EACH ID SIGN (1) 3/4" PVC TO EACH DIRECTIONAL SIGN (1) 1" PVC TO EACH AIR MACHINE (1) 2" GRC FOR FUTURE MONITORING AT TRANSFORMER (1) 1" PVC SPARE CONDUIT (1) 1" PVC FOR OIL WATER SEPARATOR (1) 1" PVC TO TAMPER SWITCHES AT BACKFLOW PREVENTER IF REQUIRED BY AHJ. SEE FIRE ALARM PLAN. (6) 3" PVC TO TRANSFORMER FOR SECONDARY SERVICE CONDUCTORS AND SPARES. SEE SHEET E7. (1) 2-1/2" PVC TO TRASH COMPOUND AREA. 9. NOT USED 10. NOT USED 11. NOT USED. 12. 1" CONDUIT CONCEALED IN OVERHANGING CANOPY FROM CAMERA LOCATION TO ABOVE CEILING SPACE INSIDE BUILDING. SEE SHEET E9 FOR CAMERA LOCATIONS. 13. 4" PVC FOR IRRIGATION. COORDINATE LOCATION OF SITE END OF CONDUIT RUN WITH WAWA PROJECT MANAGER. IF IRRIGATION SYSTEM IS FED FROM A WELL, PROVIDE 1" CONDUIT FROM WATER SERVICE ROOM TO IRRIGATION WELL. VERIFY LOCATION OF WELL WITH CIVIL DRAWINGS AND WAWA PROJECT MANAGER. 14. (3) 4" PVC FOR PHONE SERVICE. TERMINATE CONDUIT AT PHONE UTILITY SITE ACCESS BOX/PEDISTAL OR UTILITY POLE. 15. IN ADDITION TO THOSE SHOWN ON SHEET E1 ADD (1) GASOLINE EMERGENCY SHUTOFF AT THE STREET SIDE OF THE GAS CANOPY. POSITION JUST OFF THE CURB IN THE GRASS, CENTERED ON THE GAS CANOPY. MOUNT AT 48" AFG ON 6"X6" CONCRETE POST. 16. PROVIDE 1" CONDUIT TO SITE IRRIGATION METER AS REQUIRED. COORDINATE WITH IRRIGATION PLAN. 17. IF REQUIRED FOR THIS PROJECT PROVIDE THE FOLLOWING: (1) 1"C FROM PANEL RPC TO THE SITE LIFT STATION, (1) 1" CONDUIT FROM LIFT STATION TO OFFICE FOR ALARM. COORDINATE WITH CIVIL. 18. FOR FUEL CONDUITS SEE SHEET E6 FOR MORE INFORMATION. 19. CONDUITS IN THIS AREA CAN BE BUNDLE UP TOGETHER AND DON'T NEED TO BE IN A ROW TO AVOID CONDUITS CONFLICTS WHEN INSTALLING CABINETS, VERIFY LOCATION OF KNOCKOUTS IN BASE CABINET WITH CABINET VENDOR SHEET TITLECLIENT NAMEPROJECT NAMECHECKEDDRAWNDATEPROJECT NO.COPYRIGHT © -All reports, plans, specifications, computer files, field data, notes and other documents are instruments of service preparedby: Cuhaci & Peterson, (C & P) as instruments of service remain the property of C & P. C & P shall retain all common law, statutory and other reserved rights, including the copyright thereto. Any use or reproduction of this document without written permission from C & P is a violation of Federal copyright laws.4/16/2020 10:56:11 AME4218071904-17-2020MLBJPMCONDUIT PLANORANGE AVE. & KINGS HWY, FT. PIERCE, FLWAWA260 WEST BALTIMORE PIKEWAWA, PENNSYLVANIA 19063WAWA F85FB 2020.00 STORE #5380-ORN04/17/2020 1/4" = 1'-0"E4 1 CONDUIT PLAN Revision ScheduleNo.DescriptionDatePERMIT SET04/17/2020