HomeMy WebLinkAboutMechanicalCOMcheck Software Version 4.1.2.1
Mechanical Compliance Certificate
Project Title:
2017 Florida Building Code, Energy Conservation
Project Type:New Construction
Location:Fort Pierce, Florida
Climate Zone:2a
Construction Site:
Orange Ave. & Kings Hwy.
Ft. Pierce, FL 34945
Owner/Agent:
Cuhaci & Peterson Architects
Engineers and Planners
1925 Prospect Ave.
Orlando, FL 32814
407-661-9100
Designer/Contractor:
Cuhaci & Peterson Architects
Engineers and Planners
1925 Prospect Ave.
Orlando, FL 32814
407-661-9100
Project Information
Energy Code:
Wawa - ORN - F85FB - 2180719
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package(s)
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each - Central Furnace, Electric, Capacity = 25 kBtu/h
No minimum efficiency requirement applies
Cooling: 1 each - Single Package DX Unit, Capacity = 102 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception:
Humidity Requirements
Proposed Efficiency = 12.40 EER, Required Efficiency: 11.20 EER + 12.8 IEER
Fan System: FAN SYSTEM 1 | RTU-1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 3375 CFM, 2.0 motor nameplate hp, 0.0 fan efficiency grade
1 HVAC System RTU-1 (Single Zone):
Cooling: 1 each - Single Package DX Unit, Capacity = 120 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception:
Humidity Requirements
Proposed Efficiency = 12.20 EER, Required Efficiency: 11.20 EER + 12.8 IEER
Fan System: FAN SYSTEM 2 | RTU-2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 4800 CFM, 5.0 motor nameplate hp, 0.0 fan efficiency grade
EF 1 Exhaust, Constant Volume, 200 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
EF 3 Exhaust, Constant Volume, 100 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 HVAC System RTU-2 (Single Zone):
Heating: 1 each - Central Furnace, Electric, Capacity = 25 kBtu/h
No minimum efficiency requirement applies
Cooling: 1 each - Single Package DX Unit, Capacity = 92 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception:
Humidity Requirements
Proposed Efficiency = 12.70 EER, Required Efficiency: 11.20 EER + 12.8 IEER
Fan System: FAN SYSTEM 3 | RTU-3 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 3 Supply, Constant Volume, 2700 CFM, 2.0 motor nameplate hp, 0.0 fan efficiency grade
EF 2 Exhaust, Constant Volume, 60 CFM, 0.0 motor nameplate hp, 0.0 fan efficiency grade
1 HVAC System RTU-3 (Single Zone):
Electric Storage Water Heater, Capacity: 50 gallons w/ Circulation Pump
Proposed Efficiency: 0.86 EF, Required Efficiency: 0.86 EF
1 Water Heater 1:
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
131 ofPage
Quantity System Type & Description
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2017 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.1.2.1 and to comply
with any applicable mandatory requirements listed in the Inspection Checklist.
Jose J.Diaz-Velazquez, P.E.
Name - Title Signature Date
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
132 ofPage
04/17/2020
Air System Sizing Summary for RTU-1
Project Name: 2180719-Wawa #ORN (F85-FB) v2020.00 04/06/2020
Prepared by: Cuhaci and Peterson Architects 12:30PM
Air System Information
Air System Name RTU-1
Equipment Class PKG ROOF
Air System Type SZCAV
Number of zones 1
Floor Area 2574.0 ft²
Location Fort Pierce, Florida
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone CFM Sizing Peak zone sensible load
Space CFM Sizing Coincident space loads
Central Cooling Coil Sizing Data
Total coil load 8.5 Tons
Total coil load 102.5 MBH
Sensible coil load 77.1 MBH
Coil CFM at Oct 1400 3360 CFM
Max block CFM 3360 CFM
Sum of peak zone CFM 3360 CFM
Sensible heat ratio 0.752
CFM/Ton 393.4
ft²/Ton 301.3
BTU/(hr·ft²) 39.8
Water flow @ 10.0 °F rise N/A
Load occurs at Oct 1400
OA DB / WB 86.6 / 75.9 °F
Entering DB / WB 76.4 / 64.5 °F
Leaving DB / WB 55.1 / 54.1 °F
Coil ADP 52.8 °F
Bypass Factor 0.100
Resulting RH 50 %
Design supply temp. 55.0 °F
Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data
Max coil load 21.0 MBH
Coil CFM at Des Htg 3360 CFM
Max coil CFM 3360 CFM
Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg
BTU/(hr·ft²) 8.1
Ent. DB / Lvg DB 66.1 / 71.9 °F
Supply Fan Sizing Data
Actual max CFM 3360 CFM
Standard CFM 3358 CFM
Actual max CFM/ft² 1.31 CFM/ft²
Fan motor BHP 0.92 BHP
Fan motor kW 0.73 kW
Fan static 1.00 in wg
Outdoor Ventilation Air Data
Design airflow CFM 490 CFM
CFM/ft² 0.19 CFM/ft²
CFM/person 11.08 CFM/person
Hourly Analysis Program 5.11 Page 1 of 3
Air System Sizing Summary for RTU-2
Project Name: 2180719-Wawa #ORN (F85-FB) v2020.00 04/06/2020
Prepared by: Cuhaci and Peterson Architects 12:30PM
Air System Information
Air System Name RTU-2
Equipment Class PKG ROOF
Air System Type SZCAV
Number of zones 1
Floor Area 930.0 ft²
Location Fort Pierce, Florida
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone CFM Sizing Peak zone sensible load
Space CFM Sizing Coincident space loads
Central Cooling Coil Sizing Data
Total coil load 10.1 Tons
Total coil load 121.6 MBH
Sensible coil load 107.9 MBH
Coil CFM at Jul 1500 4934 CFM
Max block CFM at Jul 1500 4934 CFM
Sum of peak zone CFM 4934 CFM
Sensible heat ratio 0.888
CFM/Ton 487.0
ft²/Ton 91.8
BTU/(hr·ft²) 130.7
Water flow @ 10.0 °F rise N/A
Load occurs at Jul 1500
OA DB / WB 91.0 / 78.0 °F
Entering DB / WB 75.9 / 63.0 °F
Leaving DB / WB 55.7 / 54.5 °F
Coil ADP 53.4 °F
Bypass Factor 0.100
Resulting RH 48 %
Design supply temp. 55.0 °F
Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.3 °F
Supply Fan Sizing Data
Actual max CFM at Jul 1500 4934 CFM
Standard CFM 4930 CFM
Actual max CFM/ft² 5.30 CFM/ft²
Fan motor BHP 1.35 BHP
Fan motor kW 1.07 kW
Fan static 1.00 in wg
Outdoor Ventilation Air Data
Design airflow CFM 183 CFM
CFM/ft² 0.20 CFM/ft²
CFM/person 36.67 CFM/person
Hourly Analysis Program 5.11 Page 2 of 3
Air System Sizing Summary for RTU-3
Project Name: 2180719-Wawa #ORN (F85-FB) v2020.00 04/06/2020
Prepared by: Cuhaci and Peterson Architects 12:30PM
Air System Information
Air System Name RTU-3
Equipment Class PKG ROOF
Air System Type SZCAV
Number of zones 1
Floor Area 1295.0 ft²
Location Fort Pierce, Florida
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone CFM Sizing Peak zone sensible load
Space CFM Sizing Coincident space loads
Central Cooling Coil Sizing Data
Total coil load 6.5 Tons
Total coil load 78.3 MBH
Sensible coil load 57.3 MBH
Coil CFM at Nov 1400 2508 CFM
Max block CFM 2508 CFM
Sum of peak zone CFM 2508 CFM
Sensible heat ratio 0.732
CFM/Ton 384.5
ft²/Ton 198.6
BTU/(hr·ft²) 60.4
Water flow @ 10.0 °F rise N/A
Load occurs at Nov 1400
OA DB / WB 83.6 / 74.9 °F
Entering DB / WB 76.0 / 64.5 °F
Leaving DB / WB 54.8 / 53.8 °F
Coil ADP 52.5 °F
Bypass Factor 0.100
Resulting RH 50 %
Design supply temp. 55.0 °F
Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data
Max coil load 18.7 MBH
Coil CFM at Des Htg 2508 CFM
Max coil CFM 2508 CFM
Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg
BTU/(hr·ft²) 14.4
Ent. DB / Lvg DB 65.8 / 72.7 °F
Supply Fan Sizing Data
Actual max CFM 2508 CFM
Standard CFM 2506 CFM
Actual max CFM/ft² 1.94 CFM/ft²
Fan motor BHP 0.69 BHP
Fan motor kW 0.54 kW
Fan static 1.00 in wg
Outdoor Ventilation Air Data
Design airflow CFM 400 CFM
CFM/ft² 0.31 CFM/ft²
CFM/person 26.67 CFM/person
Hourly Analysis Program 5.11 Page 3 of 3
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.2.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2017 Florida Building Code, Energy Conservation
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
Complies
Does Not
Not Observable
Not Applicable
C405.6
[PR17]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Provisions are
made for metering individual tenant
units. Feeder connectors (for feeder
and branch circuits) sized in
accordance with approved plans with
maximum drop of 5% voltage drop
total.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
133 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C402.2.6
[FO12]3
Radiant heating systems panels
insulated to >=R-3.5 on face opposite
space being heated.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C403.2.4.
5,
C403.2.4.
6
[FO9]3
Snow/ice melting system sensors for
future connection to controls. Freeze
protection systems have automatic
controls installed.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
134 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.6.1,
C404.6.2
[PL3]1
Automatic time switches installed to
automatically switch off the
recirculating hot-water system or heat
trace.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
135 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
136 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.1
[ME60]2
HVAC ducts and plenums insulated
and sealed according to Florida
Section C403.2.9, Table C403.2.9.1.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
2
[ME79]2
All ducts, air handlers, filter boxes,
building cavities, mechanical closets
and enclosed support platforms that
form the primary air containment
passageways for air distribution
systems are constructed and erected
in accordance with Table C403.2.9.2
and with Chapter 6 of the Florida
Building Code, Mechanical. Ducts are
be constructed, braced, reinforced
and installed to provide structural
strength and durability. All transverse
joints, longitudinal seams and fitting
connections are securely fastened in
accordance with the applicable
standards of this section.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.2
[ME80]2
Duct insulation is protected from
damage but not limited to the
following: 1. Insulation exposed to
weather is suitable for outdoor
service. Cellular foam insulation is
protected or painted with a coating
that is water retardant and provides
shielding from solar radiation. 2.
Insulation covering cooling ducts
located outside the conditioned space
is vapor retardant located outside the
insulation, all penetrations and joints
of which shall be sealed.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME81]2
Additional insulation with vapor
barrier is provided where the
minimum duct insulation requirements
of Section C403.2.9.1.1 are
determined to be insufficient to
prevent condensation.
Complies
Does Not
Not Observable
Not Applicable
C403.2.13
[ME71]2
Unenclosed spaces that are heated
use only radiant heat.
Complies
Does Not
Not Observable
Not Applicable
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.9.
3
[ME10]2
Ducts, air handlers, filter boxes,
building cavities, mechanical closets
and enclosed support platforms that
form the primary air containment
passageways for air distribution
systems are sealed in accordance with
the applicable criteria of this section
and Table C403.2.9.2.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
137 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.9.
4
[ME78]2
Cavities in framed spaces are not
used to deliver air from or return air to
the conditioning system unless they
contain an air duct insert which is
insulated in accordance with Section
C403.2.9.1 and constructed and
sealed in accordance with the
requirements of Section C403.2.9.2
appropriate for the duct materials
used.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
5
[ME76]2
Air distribution systems are sized and
designed in accordance with
recognized engineering standards.
Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
6
[ME77]2
Air-handling units not installed in
attics of commercial buildings.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
1
[ME53]3
Air system balancing accomplished in
a manner to first minimize throttling
losses, then for fans with fan system
power greater than 1 hp, fan speeds
shall be adjusted to meet design flow
conditions. Balancing procedures shall
be in accordance with NEBB
Procedural Standards, the AABC,
National Standards, or equivalent
procedures.
Complies
Does Not
Not Observable
Not Applicable
C403.2.6.
1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
C403.2.6.
2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
C403.2.7
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.7(1)
and C403.2.7(2).
Complies
Does Not
Not Observable
Not Applicable
C403.2.8
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
138 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
C403.5,
C403.5.1,
C403.5.2
[ME123]3
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Complies
Does Not
Not Observable
Not Applicable
C403.5.3
[ME124]3
Condensing coils installed in cool air
stream of another air-conditioning
unit. The condensing coil of one air-
conditioning unit shall not be installed
in the cool air stream of another air-
conditioning unit.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
139 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.4
[FI56]3
Minimum one humidity control device
per installed
humidification/dehumidification
system. Controls prevent
simultaneous operation of
humidification and dehumidification
equipment.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.4
[FI56]3
Minimum one humidity control device
per installed
humidification/dehumidification
system. Controls prevent
simultaneous operation of
humidification and dehumidification
equipment.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.4
[FI56]3
Minimum one humidity control device
per installed
humidification/dehumidification
system. Controls prevent
simultaneous operation of
humidification and dehumidification
equipment.
Complies
Does Not
Not Observable
Not Applicable
C403.2.1
[FI50]3
HVAC systems and equipment design
loads calculated in accordance with
ANSI/ASHRAE/ACCA Standard 183 or
ACCA Manual N or by an approved
equivalent computational procedure.
Design loads shall be attached to the
code compliance form submitted to
the building department when the
building is permitted or, in the event
the mechanical permit is obtained at a
later time, the sizing calculation shall
be submitted with the application for
the mechanical permit.
Complies
Does Not
Not Observable
Not Applicable
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
1310 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
1.2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
C404.12.2
[FI53]3
Public lavatory facilities equipped with
outlet devices which limit the flow of
hot water to a maximum of 0.5 gpm or
are equipped with self-closing valves
that limit delivery to a per cycle
maximum of 0.25 gallons of hot water
for recirculating systems and to a
maximum of 0.50 gallons for non-
recirculating systems.
Complies
Does Not
Not Observable
Not Applicable
C404.12.2
[FI57]3
Public lavatory water temperature
<=110°F.
Complies
Does Not
Not Observable
Not Applicable
C404.12.1
[FI52]3
Showers used for non-safety reasons
equipped with flow control devices to
limit the water discharge to a
maximum of 2.5 gpm per shower
head. Flow restricting inserts used as
a component part of a showerhead
are mechanically retained at the point
of manufacture
Complies
Does Not
Not Observable
Not Applicable
C408.2.2
[FI54]3
Construction documents require that a
written balance report be provided to
the building owner or rep for HVAC
systems serving zones with total
condition area > 5,000 sqft. Air
distribution systems shall be tested,
adjusted, and balanced by a licensed
engineer or certified company.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Report date:
1311 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C404.3
[FI11]3
Heat traps installed on supply and
discharge piping of non-circulating
systems.
Complies
Does Not
Not Observable
Not Applicable
C404.4
[FI25]2
All piping insulated in accordance with
section details and Table C403.2.10.
Complies
Does Not
Not Observable
Not Applicable
C404.6.1
[FI12]3
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
Complies
Does Not
Not Observable
Not Applicable
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename: