HomeMy WebLinkAboutDale Bass Engineering Sealed1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND CLADDING, AND
BASE RAIL ANCHORAGE- OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY
SET -BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON -HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD
LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING
DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED
BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS
ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE
APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET -BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER.
6. ROOF AND WALL SHEATHING SECURED WITH #12-14x1" SELF -DRILLING SCREWS WITH SEAL WASHERS ® 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-143/4" SELF -DRILLING SCREWS.
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP.
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,500LB TENSILE STRENGTH.
10, 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
5(1 KIRe ROLL—UP
------i"eeR------------------- DOOR- ------
-TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION
R318 AND 1816 OF THE 2017 FLORIDA BUILDING CODE, 6TH EDITION
CONCRETE:
-MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
-ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE
DESIGNED TO SLOPE AWAY FROM THE STRUCTURE
REINFORCING STEEL (REBAR) REQUIREMENTS:
-MINIMUM GRADE 40 STEEL
-REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED:
-THE REBAR IS BENT COLD
-THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6 -BAR DIAMETERS: AND
-REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL
CELL, THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1"
HORIZONTALLY TO 6" VERTICALLY.
-COVER:
-2" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CONTACT WITH SOIL OR WEATHER, AND 14" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF J" FOR FINE
GROUT, AND 4" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH OR WEATHER, AND 14" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
WEATHER.
GALVANIZATION:
-METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY
EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153,
CLASS B-2, METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
2.600 PSI 4' CONCRETE SUB WRH W.W.F. (OR nBER
MESH) AND 12'x12' REINFORCED FOOTER PERIMETER
______________________________________________ROLLIIP______-__________-______BOLL-UP_-___________________
DOOR DOOR
J%5j" EXPANSION ANCHOR WITHIN 6"
OF EACH POST/TRUSS ALONG SIDES
AND EVERY OTHER END -WALL POST
2" MIN. -I4 /-BASE RAIL
�_12"—
MINIMUM SOIL BEARING
CAPACITY 2,000 PSF(TYP.)
/ N 1
2,500 PSI 4"
CONCRETE SLAB
W.W.F. OR FIBER
(2) #5 REBAR ® 6" O.C.
CONTINUOUS WITH MINIMUM
12" OVERLAP SPLICE
CONCRETE FOUNDATION/BASE RAIL
ANCHOR DETAIL
2 5" PLAN VIEW DOOR FRAMING
" RECESS
4" --DOOR WIDTI1
CARPORTS ANYWHERE
ELEVATION VIEW
DOOR FRAMING
" RECESS
UTILITY STRUCTURE
.75"1
4" OOR WIDT
OPTIONAL ROLL -UP DOOR
CONCRETE SPLASH -GUARD RECESS
RISK CATEGORY
CODE VERSION
FBC 2017 6th Editior
ASCE-7-10
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II -B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
ENCLOSURE
ENCLOSED OPEN
INTERNAL PRESSURE COEFF.
+/- 0.18/0.0
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
3,360 SQ. FT.
DESCRIPTION
MTB
3/27/20
8310 AndreWs Ave., Ft. Pierce
I--- 84'L X 40'W X 12'H 11
;;i111itt1l;�„
m
0
Zi" r
Lj_j�3 �` ,2'b
z Matthew T. BOIdWin P.E.
Florida License #64608
m Sheet: CA -1 OF 6
t1• 3�
6 3'-O' 3'-O•
,,a
o
»
I
N
CARPORTSANYWHERE
CODE INFORMATION
CODE VERSION FBC 2017 6th Edition,
ASCE-7-10
MANUFACTURER CARPORTS ANYWHERE
BUILDING TYPE UTILITY STRUCTURE
CONSTRUCTION TYPE II -B
RISK CATEGORY I
FIRE PROTECTION NONE
FIRE SUPPRESSION SYSTEM NONE
OCCUPANCY UTILITY, U
WIND SPEED Vult-150mph
EXPOSURE B
ENCLOSURE ENCLOSED OPEN
INTERNAL PRESSURE COEFF. +/- 0.18/0.0
IMPORTANCE FACTOR 1.0
ROOF DEAD LOAD IOPSF
ROOF LIVE LOAD OPSF OR 3001b P.L.
FLOOR DEAD LOAD 1OPSF
FLOOR LIVE LOAD 50PSF
"R"RATING OF WALLS, FLOOR, ROOF N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SQUARE FOOTAGE 3,360 SQ. FT.
REVISIONS
REV DESCRIPTON DATE BY
FRONT END WALL
12
a
t1"
6`
_o
DRAWN BY: MTB
3/27/20
LOC nON: 8310 Andrews Ave., Ft. Pierce
SIZE:
84'L X 40'W X 12'H
!kill
r -D
0
0
sµtNciNc•I
DOOR
-
- --
-- ---
— —
--
�+
3-B�`
MID END WALL
3-9�• 3-9�' 3'-B�• '-9�'
3'-11 3-11�'` 3'-11 3'-11 3-11 3'-11 3'-11�` 3'-11
REAR END WALL
-11 S -11j`
✓'L li $
W
0
LL-
1;-i Z
L1J
_ r
i
-:
.� -
Matthew T. Baldwin P, E,
Florida License #64608
Sheet: CA -2 CI 6
CARPORTSANYWHEM
CODE INFORMATION
CODE VERSION FBC 2017 6th Edition,
ASCE-7-10
MANUFACTURER CARPORTS ANYWHERE
BUILDING TYPE UTILITY STRUCTURE
CONSTRUCTION TYPE II—B
RISK CATEGORY I
FIRE PROTECTION NONE
FIRE SUPPRESSION SYSTEM NONE
OCCUPANCY UTILITY, U
WIND SPEED Vult-150mph
EXPOSURE B
ENCLOSURE ENCLOSED OPEN
INTERNAL PRESSURE COEFF. +/— 0.18/0.0
IMPORTANCE FACTOR 1.0
ROOF DEAD LOAD 1OPSF
20PSF OR 30O1b P.L.
10PSF
FLOOR DEAD LOAD
FLOOR LIVE LOAD 50PSF
c!
-D '-D`
• O.C. mm
ROLL -UP _ _ ROLL -UP
DOOR DOOR
0•
-0•
-- —
"R"RATING OF WALLS,FLOOR,ROOF N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SOU RE FOOTAGE 3,360 SQ_ FT.
REVISIONS
REV DESCRIPTON DATE BY
3'-11 3'-11 3'-11 3'-11 1'-10�• 10,�• 11
3'-9}' '-0• •-0•
84._0.
LEFT SIDE WALL
'-0 '-0•'-0•
'-01 '-0` '-0• '-0• '-0` '-0•
DRAWN BY: MTB
DATE: 3/27/20
�acAnoN: 8310 Andrews Ave., Ft. Pierce
SIZE: 84'L X 4O'W X 12'H
3'-11�•
3'-11�•
5-11�` '-11�•
3'-11�`
......................................................................................................................................
--------------------------0
ROLL-UP
DOOR
'I
1V
`�` � -`�` �•.:.: � � LI'• i � f� .moi.
0
I
S NGN c.�
EDODO
..................................................................................................................................
............. .. ... ..
'-0` '-0• '-D• '-0` '-0• '-0• '-0• '-0• '-0•
-0•
'-0• '-0• 3'-&�•
RIGHT SIDE WALL
11j•10,
_D.
cf)
W
W
w �
cn
1 r r 4
\ J y J
-
\
MattheW T. BOIdWin P.E.
Florida License #64608
Sheet: CA -3 CC
r 6
CARPORTS
CODE INFORMATION
CODE VERSION FBC 2017 6th Edition,
ASCE-7-10
MANUFACTURER CARPORTS ANYWHERE
BUILDING TYPE UTILITY STRUCTURE
CONSTRUCTION TYPE II—B
RISK CATEGORY I
FIRE PROTECTION NONE
FIRE SUPPRESSION SYSTEM NONE
OCCUPANCY UTILITY, U
WIND SPEED ult-150mph
EXPOSURE B
ENCLOSURE ENCLOSED OPEN
INTERNAL PRESSURE COEFF. +/— 0.18/0.0
IMPORTANCE FACTOR 1.0
ROOF DEAD LOAD 10PSF
ROOF LIVE LOAD 20PSF OR 3001b P.L.
FLOOR DEAD LOAD IOPSF
FLOOR LIVE LOAD 50PSF
"R"RATING OF WALLS,FLOOR,ROOF N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SQUARE FOOTAGE 3,360 SQ. FT.
REVISIONS
REV DESCRIPTON DATE BY
FRONT END WALL
4
iV
SWiNONO
DOOR
_O
401-01
-
4
iv
DRAWN BY: MTB
DATE: 3/27/20
LOCAnoN: 8310 Andrews Ave., Ft. Pierce
SIZE: 84'L X 40'W X 12'H
I'
MID
MID
END
WALL
REAR
END
WALL
(1
L J
>
F W
-
I i ?.
3,/30f/26
Matthew T. BaldWin P.E.
Florida License #664608
Sheet: CA -4 OF 6
b
__._.......... _—__ _. _
H 11111 11111H 11 IT 1111111H HHHHHHHHHH11
- BWRP
DOOR WOR
—.._....._.._..___.___. _ _.....____�
CARPORTSANYIIIIHERE
CODE INFORMATION
CODE VERSION FBC 2017 6th Edition,
SCE-7-10
MANUFACTURER CARPORTS ANYWHERE
BUILDING TYPE UTILITY STRUCTURE
CONSTRUCTION TYPE II-B
RISK CATEGORY I
FIRE PROTECTION NONE
FIRE SUPPRESSION SYSTEM NONE
OCCUPANCY UTILITY, U
WIND SPEED Vult-150mph
EXPOSURE B
ENCLOSURE ENCLOSED OPEN
INTERNAL PRESSURE COEFF. +/- 0.18/0.0
IMPORTANCE FACTOR 1.0
ROOF DEAD LOAD 1OPSF
ROOF LIVE LOAD 20PSF OR 3001b P.L.
FLOOR DEAD LOAD 1OPSF
FLOOR LIVE LOAD 5OPSF
R"RATING OF WALLS,FLOOR,ROOF N A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
SHELTER USAGE NO
SQUARE FOOTAGE 3,360 SQ. FT.
REVISIONS
REV DESCRIPTION DATE BY
'-0' ENCLOSED C-0' OPEN
D LEFT SIDE WALL
i
SWINGING DOO
DOOR
i
DRAWN BY: MTB
DATE: 3/27/20
LOCAnoN: 8310 AndreWs Ave., Ft. Pierce
SIZE, 84'L X 40'W X 12'H
—... -.... ....... - ......- ----- ------- ......... _
ROLL-UP
-0' OPEN I ♦D -O' ENCLOSED
-0'
RIGHT SIDE WALL
w
W
Lij
U,
....fir ,.
ems..
Matthew T. BaldWin P.E.
Florida License #64608
Sheet: CA-5 OF 6
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)SCREWS #12-14>j" SELF—DRILLING
NIPPLE TO
BASE RAIL NIPPLE
BASE f
POST TO BASE RAIL
CONNECTION
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SC)REWS 14x4" SELF—DRILLING
2"x2%2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x4"
SELF—DRILLING SCREWS
END POST TO BASE RAIL
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x4"
SELF—DRILLING SCREWS
NON—STRUCTURAL HEADER OR
WINDOW RAIL TO POST DETAIL
I INTERIOR
#12-14x4" SELF—DRILLING
SCREWS ® 10" O.C. MAX.,
3" MAX. FROM CORNERS
HORIZONTALLY/ 4" MAX.
FROM CORNERS VERTICALL`
EXTERIOR
DOOR FRAME TO POST
CONNECTION
1j"
CONNECTION
Ir
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x4"
SELF—DRILLING SCREWS
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x4"
SELF—DRILLING SCREWS
SINGLE OR DOUBLETS
HEADER
INTERMEDIATE POST TO
HEADER/BASE RAIL/OR HEADER CONNECTION
WINDOW RAIL DETAIL DETAIL OPTION 1
2"x2"x2" 16 GA. ANGLE CLIP SECURED
J. MAX. tiF AUINU
—VARIES
SIDE WALL ROLL—UP
DOOR/FRAME OUT
HEADER DETAIL
INSTALL PER MANUFACTURERS INSTRUCTIONS
#140" SELF—DRILLING
SCREWS ® 6" O.C. MAX. TYP
& 6" MAX. FROM CORNERS
ROLL—UP DOOR TO
POST CONNECTION
DESIGN PRESSURES
— 150 Mph
ROOF
+23.3/-51.6
CONSTRUCTION TYPE
WALLS
+25.4/-28.6
FIRE SUPPRESSION
DOORS
+25.4/-28.6
WIND SPEED
WINDOWS
+25.4/-28.6
REVISION`.
REV DESCRIPTON
1
2
3
407 STEEL DOOR
4
5
ZONE
+12.0
1-26.81-40.7
+14.9
+23.3
—51.6
+24.2
—25.91-28.6
+25.4
iA
26 GAUGE ROOF SHEATHING SECURED WITH
(1)#12-14xi" SELF—DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
1 —_4B•
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-14x1" SELF—DRILLING
SCREWS TO EACH RAFTER.
ROOF PANEL CONNECTIO
VERTICAL SHEATHING OPTION
15" TRUSS CONE SECURED TO
WALL POST WITH (4)#12-14)4-
SELF—DRILLING SCREWS
MINIMUM 6" TS NIPPLE. NIPPLE
SCSECURED TO WALL POST WITH CM�E�
REWS 14x4" SELF—DRILLING
SINGLE OR DOUBLETS
OPLE T HEADER
SE RAIL^ �"
HEADER CONNECTION DETAIL
CODE VERSION
MANUFACTURER
BUILDING TYPE
CONSTRUCTION TYPE
RISK CATEGORY
FIRE PROTECTION
FIRE SUPPRESSION
OCCUPANCY
OPTION 2
WIND SPEED
„
NIPPL
TO TRUSS
MINIMUM 6" TS NIPPLE.
NIPPLE SECURED TO WALL
POST WITH (4)#12-14x4"
SELF—DRILLING SCREWS
POST TO TRUSS
CONNECTION
ENCLOSURE
INTERNAL PRESSURE COEFF.
IMPORTANCE FACTOR
ROOF DEAD LOAD
ROOF LIVE LOAD
FLOOR DEAD LOAD
FLOOR LIVE LOAD
"R"RATING OF WALLS,FLOOR,RO(
MODULES PER BUILDING
HURRICANE PROTECTION USAGE
HURRICANE SHELTER USAGE
SQUARE FOOTAGE
REVISION`.
REV DESCRIPTON
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
40' BOX SAVE RAFTER TO RAFTER CONNECTION
POST CONNECTION DETAIL DETAIL
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1 —R1
Hampton Rib Roof Panel
WALL SHEATHING
Carports Anywhere
FL27403.1
t�- _ - r
Hampton Rib Wall Panel
SWINGING DOOR
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
ROLL—UP DOOR
JANUS INTERNATIONAL CORPORATION
FL12765.3—R5
Florida License #64608
SERIES 3100
4SCE-7-10
CARPORTS ANYWHERE
JTILITY STRUCTURE
I—B
I
NONE
NONE
UTILITY, U
Vult-150mph
B
ENCLOSED/OPEN
+/— 0.18/0.0
1.0
10PSF
20PSF OR 3001b P.L.
10PSF
50PSF
N/A
1
No
No
3,360 SQ. FT.
MTB
3/27/20
8310 Andrews Ave., Ft. Pierce
84'L X 40'W X 12'H 11
t�- _ - r
Matthew T. BaldWih'P.E:
Q
Florida License #64608
ww
o
F-
Sheet: CA— 6 0 F 6