HomeMy WebLinkAboutRevision ppwk (2)ELECTRICAL NOTES THESE NOTES APPLY TO ENTIRE PROJECT: A. CODES. ALL ELECTRICAL WORK SHALL COMPLY WITH THE DRAWINGS AND SPECIFICATIONS, THE NATIONAL ELECTRICAL CODE AND APPLICABLE LOCAL CODES, WHICHEVER IS MORE STRINGENT. B. CONDUCTORS. ALL CONDUCTORS ARE TO BE COPPER THWN UNLESS OTHERWISE SHOWN OR REQUIRED BY CODES. ALL POWER CONDUITS ARE TO CONTAIN A GROUND WIRE. MC CABLE IS ALLOWED WITH COPPER GROUND WIRES. C. POWER COMPANY. THE ELECTRICAL CONTRACTOR IS TO COORDINATE ALL SERVICE REQUIREMENTS WITH THE POWER COMPANY BEFORE BIDDING TO BE CERTAIN ALL WORK NECESSARY TO MEET POWER COMPANY SPECIFICATIONS IS IN THE BID. ALL ELECTRICAL GEAR SHALL BE APPROVED BY THE POWER COMPANY. THE ELECTRICAL CONTRACTOR SHALL MEET WITH THE POWER COMPANY PRIOR TO BIDDING TO DETERMINE ALL FEATURES, FUNCTIONS AND LOCATIONS OF SERVICE. FURTHERMORE, THE ELECTRICAL CONTRACTOR IS TO MAINTAIN CONTINUOUS CONTACT WITH THE POWER COMPANY DURING THE PROJECT, AND IS TO NOTIFY THE ENGINEER IMMEDIATELY OF ANY CHANGE PROPOSED. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE SERVICE THOROUGHLY AND DOCUMENT THE COORDINATION. D. SCALES. DO NOT SCALE OR TAKE DIMENSIONS FROM ELECTRICAL DRAWINGS. E. MAIN DISCONNECTS. MAIN DISCONNECTS MAY BE HEAVY DUTY FUSED SWITCHES OR CIRCUIT BREAKERS PROPERLY COORDINATED. FUSES ARE TO BE BUSSMAN TYPE LPN -R, LPS-R, OR KRP-C. CIRCUIT BREAKERS ARE TO BE RATED FOR THE AIC SHORT CIRCUITS INDICATED. F. UNDERGROUND WORK. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXACT ROUTES OF ALL UNDERGROUND WORK. ROUTES SHOWN ARE APPROXIMATE. POWER, TELEPHONE, CABLE COMPANIES, AND ALL OTHER UTILITY COMPANIES SHALL BE CONSULTED, AND LINES SHALL BE STAKED. DIGGING BY HAND IS REQUIRED AROUND EXISTING UTILITIES. PLANT J PLANT CONTROL OFFICE SITE PLAN NO SCALE " TEMP POWER STAND MINIMUM CONDUCTOR SIZING MINIMUM CONDUCTOR SIZING FOR FOR 277V/10 MINIMUM CONDUCTOR SIZING FOR MINIMUM CONDUCTOR SIZING 13-413.BC.1.2 COMPLIANCE) FOR 120V/10 BRANCH CIRCUITS 208V/10 BRANCH CIRCUITS 208V/30 BRANCH CIRCUITS MOBILE (FROM PANELBOARD SCHEDULE) UP TO: FOR 48OV/30 BRANCH CIRCUITS (FOR FBC 13-413.BC.1.2 COMPLIANCE) (FOR FBC 13-413.BC.1.2 COMPLIANCE) (FOR FBC 13-413.BC.1.2 COMPLIANCE) o� 100' 12 12 12 (FOR FBC 13-413.BC.1.2 COMPLIANCE) DESIGN LOAD ON CIRCUIT IN VA 150' DESIGN LOAD ON CIRCUIT IN VA DESIGN LOAD ON CIRCUIT IN VA F- 200' DESIGN LOAD ON CIRCUIT IN VA (FROM PANELBOARD SCHEDULE) UP TO: W (FROM PANELBOARD SCHEDULE) UP TO: (FROM PANELBOARD SCHEDULE) UP TO: 8 J 300' 1 (FROM PANELBOARD SCHEDULE) UP TO: 500 11000 1500 2000 2500 3000 B) 0 a o = iE 1500 1 2000 2500 3000 1 3500 4000 4500 5000 B 50' 12 1 12 1 12 10 10 10 50' 12 12 12 12 12 12 12 12 o o 100' 12 12 10 8 8 6 100%' 12 12 12 12 12 12 12 12 a o 150' 12 10 8 6 6 4 150' 12 12 12 12 12 10 10 10 F- 200' 1 10 8 6 4 4 4 200' 12 12 12 10 10 10 10 8 z250' 10 6 6 1 4 4 1 3 250-1 12 12 10 10 10 8 8 8 J 300'1 8 6 4 1 4 1 3 12 1 30011 12 10 10 10 1 8 8 8 8 PLANT CONTROL OFFICE SITE PLAN NO SCALE " TEMP POWER STAND MINIMUM MINIMUM CONDUCTOR SIZING FOR FOR 277V/10 BRANCH CIRCUITS NL MINIMUM CONDUCTOR SIZING 13-413.BC.1.2 COMPLIANCE) 208V/10 BRANCH CIRCUITS ON CIRCUIT IN VA MOBILE (FROM PANELBOARD SCHEDULE) UP TO: FOR 48OV/30 BRANCH CIRCUITS 2000 3000 4000 , 5000 (FOR FBC 13-413.BC.1.2 COMPLIANCE) 12 12 12 10 o� 100' 12 12 12 (FOR FBC 13-413.BC.1.2 COMPLIANCE) ao 150' DESIGN LOAD ON CIRCUIT IN VA 10 F- 200' DESIGN LOAD ON CIRCUIT IN VA 8 W (FROM PANELBOARD SCHEDULE) UP TO: 12 10 8 8 J 300' 1 (FROM PANELBOARD SCHEDULE) UP TO: 11 1000 1500 2000 2500 3000 3500 4000 4500 5000 10,000 15,000 20,000 25,000 30,000 50' 12 1 12 12 1 12 12 10 1 10 10 8 6 ~o -F z 100' 12 10 200' 12 10 300' 12 10 o 0 100' 12 12 12 12 10 10 10 10 8 8 8 8 ~0 150' 12 12 12 10 10 8 8 8 8 8 8 8 F- 200' 12 12 10 10 8 8 8 6 6 z 250' 12 10 10 8 8 6 6 6 6 8 8 6 B300" 12 10 8 8 6 6 6 4 4 PLANT CONTROL OFFICE SITE PLAN NO SCALE " TEMP POWER STAND I� II II II '.� EXISTING UTILITY POLE APPLICABLE BUILDING CODES FLORIDA BUILDING CODE, 6TH EDITION (2017) NFPA 70, NATIONAL ELECTRICAL CODE (2014) FLORIDA FIRE PREVENTION CODE, 6TH EDITION (2017) FLORIDA ENERGY CONSERVATION CODE, 6TH EDITION (2017) MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES IN THEIR LATEST REVISIONS. CONTRACTOR TO COORDINATE SPECIFIC REQUIREMENTS OF EQUIPMENT WITH MANUFACTURERS' SHOP DRAWINGS. ALL EQUIPMENT SHALL BE INSTALLED STRICTLY IN ACCORDANCE WITH THE MANUFACTURERS WRITTEN INSTALLATION INSTRUCTIONS. OM1 K7 400A 480V 3PH250A MINIMUM CONDUCTOR SIZING FOR 277V/10 BRANCH CIRCUITS NL (FOR FBC 13-413.BC.1.2 COMPLIANCE) DESIGN LOAD ON CIRCUIT IN VA MOBILE (FROM PANELBOARD SCHEDULE) UP TO: 2000 3000 4000 , 5000 50' 12 12 12 10 o� 100' 12 12 12 10 ao 150' 12 12 10 10 F- 200' 12 10 10 8 W 250' 12 10 8 8 J 300' 1 10 1 8 1 8 1 8 I� II II II '.� EXISTING UTILITY POLE APPLICABLE BUILDING CODES FLORIDA BUILDING CODE, 6TH EDITION (2017) NFPA 70, NATIONAL ELECTRICAL CODE (2014) FLORIDA FIRE PREVENTION CODE, 6TH EDITION (2017) FLORIDA ENERGY CONSERVATION CODE, 6TH EDITION (2017) MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES IN THEIR LATEST REVISIONS. CONTRACTOR TO COORDINATE SPECIFIC REQUIREMENTS OF EQUIPMENT WITH MANUFACTURERS' SHOP DRAWINGS. ALL EQUIPMENT SHALL BE INSTALLED STRICTLY IN ACCORDANCE WITH THE MANUFACTURERS WRITTEN INSTALLATION INSTRUCTIONS. OM1 K7 400A 480V 3PH250A DJL 02/21/20 M2 OF 100A 2PH FUSED 70A r— OF 2 400A 3PH FUSED #1/0 SCOPE OF WORK THIS PROJECT INVOLVES A NEW SERVICE TO AN OFFICE TRAILER AND TEMPORARY CONCRETE PLANT. RISER DIAGRAM SOURCE: 480Y/277V, 3�, 4W EXISTING WORK SHOWN DASHED NEW WORK SHOWN BOLD Know what's below. 0 Call before you dig. RISER KEYED NOTES X 1O METER RISER 3"C - (3)500MCM+350MCM(N) O2 METER TO GUTTER 3"C-(3)500MCM+35OMCM(M), (1)1 /0 GND O3 WIREWAY SERVICE DISCONNECTS 3"C-3#250MCM+2G TO M1 (TAP A,B,C PHASE +G) 2"C -2#4+#6G TO M2 (TAP A,B PHASE +G) O MAIN 2 TO XFMR 2"C - (2)#4, 1-#6 GND O XFMR TO OFFICE DISC 1 1/2-'C-(3)#1,(1)#4 GND O MAIN 1 TO EQUIPMENT DISC 3"C- (3) 250MCM, 1 #2 GND (�7 OFFICE DISC TO OFFICE 1 1/2"C-(3)#1,(1)#4 GND O EQUIP DISC TO EQUIP 3"C - (3)250MCM, (1) #2 GND 400A 3PH FUSED 250A 480V EQUIP. DISC. MODULAR CONCRETE PROCESSOR PROVIDED BY CUSTOMER #2 Pa EnGInEERInG FiS50CIFiTES InC. 575 NW MERCANTILE PL SUITE 106 PORT ST. LUCIE FL 34986 T.561.746.6343 F.561.746.3602 info@CEAengineers.com CA LIC. 31555 TEMPORARY POWER CONCRETE PLANT 7695 OKEECHOBEE RD. FT. PIERCE, FL JOSEPH L. LAMMERS ,PE PE # 78477 L SEAL © 2020 CARDINAL ENGINEERING ASSOCIATES, INC. THIS DOCUMENT, SHEET NO. HAS BEEN PREPARED SPECIFICALLY FOR THIS PROJECT. THIS DOCUMENT IS NOT SUITABLE FOR USE ON OTHER PROJECTS OR IN OTHER LOCATIONS WITHOUT THE APPROVAL AND PARTICIPATION OF CARDINAL ENGINEERING ASSOCIATES. UNAUTHORIZED REPRODUCTION AND/OR REUSE IS PROHIBITED. SHEET TITLE: GENERAL NOTES, RISER & SITE PLAN REVISIONS: DESIGN BY: DATE: DJL 02/21/20 CUSTOMER CHECKED: NL JL PROVIDED MOBILE OFFICE 100A FUSED 100A 240V 25kVA XFMR 480-240V 1PH #6 I I RISER DIAGRAM SOURCE: 480Y/277V, 3�, 4W EXISTING WORK SHOWN DASHED NEW WORK SHOWN BOLD Know what's below. 0 Call before you dig. RISER KEYED NOTES X 1O METER RISER 3"C - (3)500MCM+350MCM(N) O2 METER TO GUTTER 3"C-(3)500MCM+35OMCM(M), (1)1 /0 GND O3 WIREWAY SERVICE DISCONNECTS 3"C-3#250MCM+2G TO M1 (TAP A,B,C PHASE +G) 2"C -2#4+#6G TO M2 (TAP A,B PHASE +G) O MAIN 2 TO XFMR 2"C - (2)#4, 1-#6 GND O XFMR TO OFFICE DISC 1 1/2-'C-(3)#1,(1)#4 GND O MAIN 1 TO EQUIPMENT DISC 3"C- (3) 250MCM, 1 #2 GND (�7 OFFICE DISC TO OFFICE 1 1/2"C-(3)#1,(1)#4 GND O EQUIP DISC TO EQUIP 3"C - (3)250MCM, (1) #2 GND 400A 3PH FUSED 250A 480V EQUIP. DISC. MODULAR CONCRETE PROCESSOR PROVIDED BY CUSTOMER #2 Pa EnGInEERInG FiS50CIFiTES InC. 575 NW MERCANTILE PL SUITE 106 PORT ST. LUCIE FL 34986 T.561.746.6343 F.561.746.3602 info@CEAengineers.com CA LIC. 31555 TEMPORARY POWER CONCRETE PLANT 7695 OKEECHOBEE RD. FT. PIERCE, FL JOSEPH L. LAMMERS ,PE PE # 78477 L SEAL © 2020 CARDINAL ENGINEERING ASSOCIATES, INC. THIS DOCUMENT, SHEET NO. HAS BEEN PREPARED SPECIFICALLY FOR THIS PROJECT. THIS DOCUMENT IS NOT SUITABLE FOR USE ON OTHER PROJECTS OR IN OTHER LOCATIONS WITHOUT THE APPROVAL AND PARTICIPATION OF CARDINAL ENGINEERING ASSOCIATES. UNAUTHORIZED REPRODUCTION AND/OR REUSE IS PROHIBITED. SHEET TITLE: GENERAL NOTES, RISER & SITE PLAN REVISIONS: DESIGN BY: DATE: DJL 02/21/20 DRAWN BY: CHECKED: NL JL E-1 OF 1 ELECT SHEETS