MACK RHVAC MANUAL J UPDATED
Burton 12940 Mack Residence HVAC Load Calculations for Mack Residence 7840 Saddlebrook Drive Port Saint Lucie, FL 34986 H)IACHVACFZECSIDZHIIAL LoADs Prepared By: Kristin Kelly Florida Breeze 6928 Vickie Circle Suite B West Melbourne, FI 32904 3219518767 Thursday, April 23, 2020 Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. Rhvac , Residential & Light Commercial H11AC Loads Florida Breeze West Melbourne, FL 32904 Project Report General Protect Information_ Project Title: Burton 12940 Mack Residence Designed By Kristin Kelly Project Date: Monday, March 23, 2020 Client {Name: Mack Residence Client Address: 7840 Saddlebrook Drive Client City: Port Saint Lucie, FL 3498E Company Name: Florida Breeze Company Representative: Kristin Kelly Company Address: 6928 Vickie Circle Suite B Company City: West Melbourne, F1 32904 Company Phone: 3219518767 Design Data Reference City: Building Orientation: Daily Temperature Range: Latitude: Elevation: Altitude Factor: Fort Pierce, Florida Front door faces East Medium 27 Degrees 25 ft- 0.999 Elite Software Development, Inc. Burton 12940 Mack Residence Page 2 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 42 39.4 nla nla 70 n!a Summer. 90 78 59% 5c)% 75 61 Check Figures Total Building Supply CFM: 7,758 CFM Per Square ft-: 0.600 Square ft. of Room Area: 12,940 Square ft. Per Ton: 630 Volume (ft'): 183,799 Building Loads Total Heating Required Including Ventilation Air: 236,835 Btuh 236.835 MBH Total Sensible Gain: 204,525 Btuh 83 % Total Latent Gain: 42,110 Btuh 17 % Total Cooling Required Including Ventilation Air: 246,635 Btuh 20.55 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J, ❑ and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\Users\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Florida Breeze Burton 12940 Mack Residence . West Melbourne, FL 32904 Page 3 Miscellaneous Report System 1 Guest Living Bed 7 And 8 (Blue) Outdoor Outdoor Outdoor Indoor Indoor Grains Input Data Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Differenc e Winter: 42 39.4 806% nla 70 nla Summer: 90 78 59% 50% 75 61.09 System 2 Living Dining Study Parlor (Green} Outdoor Outdoor Outdoor Indoor Indoor Grains Input Data Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Differenc e_ _ Winter: - - - 42 39.4 80% nla --- 70 - nla Summer: 90 78 59% 50% 75 61.09 System 3 Flex Bed 9 Bed 10 (Yellow) Outdoor Outdoor Outdoor Indoor Indoor Grains Input Data Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 42 39.4 80% nla 70 nla Summer: 90 78 59% 50% 75 61.09 System 4 Kitchen Gyre Game Bed 3 4 Theater In Law (Pink) Outdo Outdo Outdo Indoor Indoor Grains I Input Data or ❑r or ReI.H Dry ❑iffere Dry Wet Ref-H um Bulb nee Bulb Bulb um Winter: 42 39.4 80% nla 70 nla Summer: 90 78 59% 50% 75 61.09 . System 5 Second Floor Outdoor Outdoor Outdoor Indoor Indoor Grains . Input Data Dry Bulb Wet Bulb Rel.Hum R_el.Hum Dry Bulb Difference Winter: 42 39.4 80% nla 70 nla Summer: 90 78 59°Ia 50% 75 61.09 [Duct Sizing Inputs -- Main Trunk Trunk Runouts _ -- Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor: 0.01000 0.01000 Pressure Drop: 0,1000 in.wg.1100 ft. 0,1000 in.wg.1100 ft. Minimum Velocity: 550 ft./min 450 ft.1min Maximum Velocity: 600 ft.1min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. Outside Air Data Infiltration Specified: Infiltration Actual: Above Grade Volume: Total Building Infiltration: Total Building Ventilation: Winter 0.250 ACIhr 766 CFM 0.250 ACIhr X 183,799 Cu.ft. 45,950 Cu.ft.lhr X 0.0167 766 CFM 0 CFM Summer 0.130 ACIhr 398 CFM 0.130 ACIh r X 183.799 Cu.ft. 23,894 Cu.ft.lhr X 0.0167 398 CFM 0 CFM ---System I - Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0,250 ACIhr (116 CFM), Construction: Semi -Tight Summer Infiltration Specified: 0.130 ACIhr (60 CFM), Construction: Semi -Tight ---System 2--- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1,10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0.250 ACIhr (263 CFM), Construction: Semi -Tight C:IUsersWulialDropboxlRhvae 9 Projects\BurtonlBurton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Florida Breeze Burton 12940 Mack Residence West Melbourne, FL 32904 Page 4 Miscellaneous Re ort (coned) -- Outside Air ©ata - - - - Summer Infiltration Specified: 0.130 AClhr (137 CFM), Construction: Semi -Tight ---System 3--- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp- Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 26.00 Winter Temp. Difference) Winter Infiltration Specified: 0.250 AClhr (100 CFM), Construction: Semi -Tight Summer Infiltration Specified: 0.130 AClhr (52 CFM), Construction: Semi -Tight ---System 4--- Infiltration & Ventilation Sensible Gain Multiplier: 16-49 = (1-10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0.250 AClhr (147 CFM), Construction- Semi -Tight Summer Infiltration Specified: 0.130 AClhr (77 CFM), Construction: Semi -Tight ---System 5--- Infiltration & Ventilation Sensible Gain Multiplier: 16-49 = (1.10 X 0-999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0-250 AClhr (140 CFM), Construction: Semi -Tight Summer Infiltration Specified: 0.130 AClhr (73 CFM), Construction: Semi -Tight C:\Users\Julia\Drapbox\Rhvac 9 Projects\BurtonlBurton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential S Light Commercial HVAC Loads Florida Breeze West Melbourne, FL 32904 Duct Size Pre vie w Elite Software Development, Inc. Burton 12940 Mack Residence Page 5 Room or 5ourr� Minimum MEDdmLm Hough. Design SP Duct Duct Htg Clg Act Duct D�actName Velocity Velocity Factor Lf100 Loss Velocity LenO Flow Flow Flow Size Systern 1 Supply Runouts Zone 1 1-Guest Living Bed 7A rod 8 (B lu a) Built -In 450 750 0.01 0.1 524.3 523 1,338 1,338 13-6 OtherDucts In system 1 Supply Main Trunk Built -In 550 600 0.01 0.1 506.9 5M 1,336 1,338 22 System 2 Supply Run outs Zone 1 2-Living pining Study Parlor (Green) Built-in 450 7$0 0.01 0.1 556 525 1 fi37 1,637 15-6 Other Ducts In System2 Supply Main Trunk Built -In 550 600 0.01 0.1 521.2 525 1,637 1,637 24 System 3 SuppV Runouts Zone 1 3-Flex Bed 9 Bed 10 (Yellow] Built -In 450 750 0.01 0.1 519 481 '1,223 1,223 124 Other Ducts in System 3 Supply Main Trunk Built-in 550 tD0 0.01 0.1 %0.6 481 1,223 1,223 20 System 4 Supply Runouts Zone 1 4-IGhohen Gym tame Bed 3 4 Theater In Law(Pink)Built-In 450 750 0.01 0.1 555.8 566 1,837 1.637 15-6 Other Ducts In System 4 Supply Main Trunk Built-in 550 600 0.01 0.1 521.1 586 1= 1,037 24 System 5 Supply Runouts Zone 1 5-Second Floor SuWIn 450 750 ().Di 0.1 544 500 1,923 1,923 1" Other Ducts in Systems 5upptyMainTrunk Built-in 650 600 0.01 0.1 521.5 500 1,97,3 19 3 26 Summary System 1 Heating Flow: 523 Coding Flow: 1338 System 2 Heating Flow: 525 Coding Flow: 1637 System 3 Heating Flaw: 481 Cooling Flow: 1223 System 4 Heating Flow: 566 Cooling Flow: 1637 System 5 Heating Flow: 500 Cooling Flow; 1923 CAUsers\Julia\Dropbox\Rhvac 9 Projects\Surton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Florida Breeze Burton 12940 Mack Residence West Melbourne, FL 32904 - Page $ item I Guest Living Bed 7 And 8 (Blue) Summary Loads Component - - Area Sen - - Lat Son Total Description Quan Loss Gain Gain Gain 2B-m-o: Glazing -Double pane low-e (e = 0.60), fixed 84 918 0 1,414 1,414 sash, metal frame no break, U-value 0.39, SHGC 0-27 10C-m: Glazing -French door, double pane low-e glass (e 60 940 0 1,425 1,425 = 0.40), metal frame no break, U-value 0.56, SHGC 0.27 2A-m-o: Glazing -Double pane low-e (e = 0.60), operable 60 656 0 1,300 1,300 window, metal frame no break, U-value 0.39, SHGC 0-27 11J, Door -Metal - Fiberglass Core, U-value 0.6 102 1,713 0 1,591 1,591 13AB-Ofcs: Wall -Block, no blanket or board insulation, 1983.7 10,164 0 6,317 6,317 filled core, siding finish, U-value 0.183 1881-21o: Roof/Ceiling-Roof Joists Between Roof Deck 2496.3 3,285 0 2,464 2,464 and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle; Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-21 open cell 1/2 lb. spray foam, 5-5 inches in 2 x 6 joist cavity, 1 inch on joist, U-value 0.047 22A-pm: Floor -Slab on grade, No edge insulation, no 196 6,476 0 0 0 insulation below floor, any floor cover, passive, heavy dry or light wet soil, U-value 1.18 Subtotals for structure: 24,152 0 14,511 14,511 People: 4 800 920 1,720 Equipment: 660 2,300 2,960 Lighting: 0 0 0 Ductwork: 21,786 4,299 16,822 21,121 Infiltration: Winter CFM: 116, Summer CFM: 60 3,576 2,508 996 3,504 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 AED Excursion: 0 0 1,020 1,020 System 1 Guest Living Bed 7 And 8 (Blue) Load Totals: 49,514 8,267 Check Fi ures -- Supply CFM: 1,338 Square ft. of Room Area: 2,324 Volume (ft3): 27,888 System Loads Total Heating Required Including Ventilation Air: Total Sensible Gain - Total Latent Gain: Total Cooling Required Including Ventilation Air: 36,569 44,836 CFM Per Square ft.: 0.576 - Square ft- Per Ton: 622 49,514 Btuh 49.514 MBH 36,569 Btuh 82 % 8,267 Btuh 18 % 44,836 Btuh 3.74 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J. ❑ and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual ❑. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C.kUsers\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial FIVAC Loads Elite Sofiwar-e Development, Inc. Florida Breeze Burton 12940 Mack Residence West Melbourne, FL 32904 Page 7 System 2 Living Dining Study Parlor (Green) Summary Loads - - - -- 1 Component - - Area Sen Lat Description Quan Loss Gain 2B-m-o: Glazing -Double pane low-e (e = 0.60), fixed 291.6 3,184 0 sash, metal frame no break, U-value 0.39, SHGC 0.27 10C-m: Glazing -French door, double pane low-e glass (e 48 752 0 = 0.40), metal frame no break, U-value 0.56, SHGC 0.27 11J: Door -Metal - Fiberglass Core, U-value 0.6 60 1,008 0 13AB-Ofcs: Wall -Block, no blanket or board insulation, 2115.6 10,840 0 filled core, siding finish, U-value 0-183 18B1-21o: Roof/Ceiling-Roof Joists Between Roof Deck 2496.3 3,285 0 and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle, Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-21 open cell 112 lb. spray foam, 5.5 inches in 2 x 6 joist cavity, 1 inch on joist, U-value 0.047 22A-pm: Floor -Slab on grade, No edge insulation, no 112 3,700 0 insulation below floor, any floor cover, passive, heavy dry or light wet sail, U-value 1.18 Subtotals for structure: 22,769 0 People: 1 200 Equipment: 680 Lighting: 0 Ductwork: 16,619 5,586 Infiltration; Winter CFM: 263, Summer CFM: 137 8,094 5,677 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 AED Excursion: 0 0 System 2 Living Dining Study Parlor (Green) Load Totals: 47,482 12,143 Check Fi ores Son Total _Gain Gain 8,281 8,281 1,164 1,164 936 936 6,735 6,735 2,464 2,464 0 0 19,580 19,580 230 430 2,500 3,180 0 0 17,874 23,460 2,255 7,932 0 0 1,156 1,156 43,595 55,738 Supply CFM: 1,637 CFM Per Square ft.: 0.623 Square ft. of Room Area: 2,630 Square ft. Per Ton: 566 Volume (ft'): 63,130 System Loads Total Heating Required Including Ventilation Air: 47,482 Btuh 47.482 MBH Total Sensible Gain: 43,595 Btuh 78 % Total Latent Gain: 12,143 Btuh 22 % Total Cooling Required Including Ventilation Air: 55,738 Btuh 4.64 Tons (Based On Sensible + Latent) � Nates Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C-\Users\Julia\DropboxlRhvaC 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial HVAC Loads Florida Breeze Elite Software Development, Inc. Burton 12940 Mack Residence West Melbourne, FL 32904 - - - ---- - - Page 8 'System 3 Flex Bed 9 Bed 10 (Yellow) Summary Loads Component Area Sen Lat Sen Total Description Quan Loss _ Gain Gain Gain 2A-m-o: Glazing -Double pane low-e (e = 0.60), operable 45 492 0 519 519 window, metal frame no break, U-value 0.39, SHGC 0.27 2A-m-d: Glazing -Double pane low-e (e = 0.60), sliding 160 2,419 0 2,206 2,206 glass door, metal frame no break, U-value 0.54, SHGC 0.27 2B-m-o: Glazing -Double pane low-e (e = 0.60), fixed 72 786 0 1,220 1,220 sash, metal frame no break, U-value 0.39, SHGC 0-27 1OC-m: Glazing -French door, double pane low-e glass (e 12 188 0 169 169 0-40), metal frame no break, U-value 0-56, SHGG 0.27 11 D: Door -Wood - Solid Core, U-value 0.39 24 262 0 243 243 11J: Door -Metal - Fiberglass Core, U-value 0.6 24 403 0 374 374 13AB-Ofcs: Wall -Block, no blanket or board insulation, 1026.2 5,258 0 3,268 3,268 filled core, siding finish, U-value 0.183 12E-Osw: Wall -Frame, R-19 insulation in 2 x 6 stud 472.8 901 0 560 560 cavity, no board insulation, siding finish, wood studs, U-value O.068 18B1-21o: Roof/Ceiling-Roof Joists Between Roof Deck 2496.3 3.285 0 2,464 2,464 and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle, Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-21 open cell 1/2 Ib. spray foam, 5.5 inches in 2 x 6 joist cavity, 1 inch on joist, U-value 0.047 22A-pm: Floor -Slab on grade, No edge insulation, no 153 5,055 0 0 0 insulation below floor, any floor cover, passive, heavy dry or light wet soil, U-value 1-18 Subtotals for structure: 19,049 0 11,023 11,023 People: 2 400 460 860 Equipment: 560 2,100 2,660 Lighting: 0 0 0 Ductwork: 25,956 5,069 21,654 26,723 Infiltration: Winter CFM: 100, Summer CFM: 52 3,062 2,147 853 3,000 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 System 3 Flex Bed 9 Bed 10 (Yellow) Load Totals: 48,067 8,176 36,090 44,266 Check Figures - Supply CFM: 1,223 CFM Per Square ft.: 0.615 Square ft. of Room Area: 1,p9p9p0 Square ft. Per Ton: 539 Volume (ft') 23,880 [-System Loads Total Heating Required Including Ventilation Air: 48,067 Btuh 48.067 MBH Total Sensible Gain: 36,090 Btuh 82 % Total Latent Gain: 8,176 Stuh 18 % Total Cooling Required Including Ventilation Air. 44,266 Btuh 3.69 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary - Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:1Users\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commereial HVAC Loads Elite Software Development, Inc. Florida Breeze Burton 12940 Mack Residence West Melboume, FL 32904 _ - - - Page 9 item 4 Kitchen Gym Game Bed 3 4 Theater In Layt pi k) Summary Loads Component Area Sen Lat Sen Total Description Quan Loss Gain Gain Gain 2A-m-d: Glazing -Double pane low-e (e = 0.60), sliding 320 4,838 0 6,183 6,183 glass door, metal frame no break, U-value 0-54, SHGC 0.27 1 OC-m: Glazing -French door, double pane low-e glass (e 24 376 0 338 338 = 0-40), metal frame no break, U-value 0.56, SHGC 0.27 2B-m-o: Glazing -Double pane low-e (e = 0.60), fixed 48 526 0 1,040 1,040 sash, metal frame no break, U-value 0.39, SHGC 0.27 2A-m-o: Glazing -Double pane low-e (e = 0.60), operable 60 656 0 1,908 1,908 window, metal frame no break, U-value 0.39, SHGC 0.27 11J: Door -Metal - Fiberglass Core, U-value 0.6 48 806 0 748 748 11 D: Door -Wood - Solid Core, U-value 0.39 48 524 0 486 486 13AB-Ofcs: Wall -Block, no blanket or board insulation, 1532 7,850 0 4,879 4,879 filled core, siding finish, U-value 0.183 12E-Osw: Wall -Frame, R-19 insulation in 2 x 6 stud 999.4 1,903 0 1,182 1,182 cavity, no board insulation, siding finish, wood studs, U-value 0.068 18B1-21o: Roof/Ceiling-Roof Joists Between Roof Deck 2496.3 3,285 0 2,464 2,464 and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle, Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-21 open cell 112 lb. spray foam, 5.5 inches in 2 x 6 joist cavity, 1 inch on joist, U-value 0.047 22A-pm: Floor -Slab on grade, No edge insulation, no 262 6,656 0 0 0 insulation below floor, any floor cover, passive; heavy dry or light wet soil, U-value 1-18 Subtotals for structure: 29,420 0 19,228 19,228 People: 3 600 690 1,290 Equipment: 804 2,850 3,654 Lighting: 0 0 0 Ductwork. 16,723 3,319 16,310 19,629 Infiltration: Winter CFM: 147, Summer CFM: 77 4,533 3,179 1.263 4,442 Ventilatlon: Winter CFM: 0, Summer CFM: 0 0 0 0 0 AED Excursion: 0 0 2,580 2,580 System 4 Kitchen Gym Game Bed 3 4 Theater In Law 50,676 7,902 42,921 50,823 (Pink) Load Totals: Check Figures Supply CFM: 1,637 Square ft. of Room Area: 2,946 Volume (fe): 35,351 System Loads Total Heating Required Including Ventilation Air: Total Sensible Gain: Total Latent Gain: Total Cooling Required Including Ventilation Air: CFM Per Square ft.- 0.556 Square ft. Per Ton: 696 50,676 Btuh 50.676 MBH 42,921 Btuh 84 % 7,902 Btuh 16 % 50,823 Btuh 4.24 Tans (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\Users\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial HVAC Loads Elite software Development, Inc. Florida Breeze Burton 12940 Mack Residence West. Melbourne, FL 32904 Page 10 System 5 Second Floor Summaryoads Component Area Sen Lat Sen Description Quart Loss Gain Gain 10C-m: Glazing -French door, double pane low-e glass (e 12 480 0 551 = 0.40), metal frame no break, U-value 1.43, SHGC 0.43 2B-m-o: Glazing -Double pane low-e (e = 0.60), fixed 97.2 1,062 0 2,402 sash, metal frame no break, U-value 0.39, SHGC 0.27 10C-m: Glazing -French door, double pane low-e glass (e 36 564 0 855 = 0.40), metal frame no break, U-value 0.56, SHGC 0.27 2B-m-o: Glazing -Double pane low-e (e = 0.60), fixed 316.4 5,934 0 19,484 sash, metal frame no break, U-value 0.67, SHGC 0.61 2A-m-o: Glazing -Double pane low-e (e = 0.60), operable 15 353 0 1,069 window, metal frame no break, U-value 0.84, SHGC 0.61 2A-m-o: Glazing -Double pane low-e (e = 0.60), operable 30 328 0 954 window, metal frame no break, U-value 0.39, SHGC 0.27 11 J: Door -Metal - Fiberglass Core, U-value 0.6 96 1,612 0 1,497 12E-Osw: Wall -Frame, R-19 insulation in 2 x 6 stud 2982.8 5,678 0 3,527 cavity, no board insulation, siding finish, wood studs, U-value 0.068 1861-21o: Roof/Ceiling-Roof Joists Between Roof Deck 2496.3 3,285 0 2,464 and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle, Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-21 open cell 112 lb. spray foam, 5.5 inches in 2 x 6 joist cavity, 1 inch on joist, U-value 0.047 22A-pm: Floor -Slab on grade, No edge insulation, no 343 11,333 0 0 insulation below floor, any floor cover, passive, heavy dry or light wet soil, U-value 1.18 Subtotals for structure: 30,629 0 32,803 People: 4 800 920 Equipment: 850 3,120 Lighting: 0 0 Ductwork: 6,164 956 7,256 Infiltration: Winter CFM: 140, Summer CFM: 73 4,302 3,017 1,198 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 AED Excursion: 0 0 52 System 5 Second Floor Load Totals: 41,095 5,623 45,349 F-Check Figures Supply CFM: 1,923 CFM Per Square ft.: Square ft. of Room Area: 3,050 Square ft. Per Ton: Volume (ft'): 33,550 Total Gain 551 2,402 855 19,484 1,069 954 1,497 3,527 2,464 n 32,803 1,720 3,970 0 8,212 4,215 0 52 50,972 0.630 718 System Loads _ Total Heating Required Including Ventilation Air_ 41,095 13tuh 41.095 MBH Total Sensible Gain: 45,349 Btuh 89 % Total Latent Gain: 5,623 Btuh 11 % Total Cooling Required Including Ventilation Air: 50,972 Btuh 4.25 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J, D and S computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D All computed results are estimates as building use and weather may vary. C:1Users\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac . Residential & Light Commercial HVAC Loads Elite Software Development, lnc. Florida Breeze Burton 12940 Mack Residence West Melbourne, FL 32904 T^ Page 11 System 5 Second Floor Summary Loads (cont'd) Lkotes Be sure to select a unit that meets both sensible and latent loads according to the manufactures performance data at your design conditions. C:\Users\Julia\Drcpbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial HVAC Loads Florida Breeze West Melbourne, FL 32904 --- �F ui ment Dada - Sysfem 1 -Guest Cluing Bed 7 Rnd 8 Btue} Cooling System Type: Outdoor Model: Indoor Model: Tradename� Outdoor Manufacturer: Description: AHRI Reference No.: Capacity: Efficiency: Heating System Type: Model: Tradename: Manufacturer: Description: Capacity: Efficiency: Air Source Heat Pump DZ16TC0481 C* CA*F4961 *6D*+MBVC200D" AA*+TX DZ16TC DAI KI N Air Source Heat Pump 202148839 48,000 16 SEER Air Source Heat Pump DZ16TC0481 C" DZ16TC DAIKIN Air Source Heat Pump 47,000 9 HSPF Elite Software Development, Inc. Burton 12940 Mack Residence Page 12 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SORB: 90F, SOWS- 78F, WODB: 42F, SIDE: 75F, SIRH: 50%, VVIDB: 70F, Sen. gain: 36,569 Btuh, Lat. gain: 8,267 Btuh, Sen. loss: 49,514 Btuh, Entering cig. coil DB: 79.9F, Entering clg. coil WB: 64.2F, Entering htg. coil DB: 53.9F, CIg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 1338 CFM, Req. htg. airflow: 523 CFM C:lUsers\Julia\Dropbox\Rhvac 9 Projects\Burton\Burtan 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc - Florida Breeze Burton 12940 Mack Residence j West Meihourne, FL 32904 Page 13 Equipment Data - System 2 - Living Dining Study Parlor (* "Green Cooling System Type: Outdoor Model: Indoor Model. Tradename: Outdoor Manufacturer: Description: AHRI Reference No.: Capacity: Efficiency: Heating System Type: Model: Tradename: Manufacturer: Description: Capacity: Efficiency: Air Source Heat Pump DZ16TC0601 C" CA" F4961 "6 D*+M B VC2 000**-1 A'tTX DZ16TC DAI KI N Air Source Heat Pump 202148727 56,500 17 SEER Air Source Heat Pump DZ16TC0601 C* DZ16TC DAI KIN Air Source Heat Pump 59,500 9.5 HSPF This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODS: 90F, SOWB: 78F, WODB: 42F. SIDE: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 43,595 Btuh, Lat. gain: 12,143 Btuh, Sen. loss: 47,482 Btuh, Entering clg. coil ❑B: 79.2F, Entering clg. coil WB: 63-9F, Entering htg. coil DB: 57.8F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req- clg- airflow: 1637 CFM, Req. htg. airflow: 525 CFM C:IUsers\Julia\Drophox\Rhvac 9 Projects\Burtcn\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & tight Commercial HVAC Loads 'Florida Breeze West Melbourne, FL 32904 11 i Equipment Data - System 3 - Flex Bed 9 Bed 74 (Yellow) Coaling System Type: Outdoor Model: Indoor Model: Tradename: Outdoor Manufacturer: Description: AHRI Reference No.: Capacity. Efficiency: Heating System Type: Model: Tradename: Manufacturer: Description: Capacity: Efficiency: Air Source Heat Pump DZ16TC0481 C* CA*F4961 *6❑*+MBVC2000**-1A*+TX DZ16TC DAWN Air Source Heat Pump 202148839 48,000 16 SEER Air Source Heat Pump DZ16TC0481C* DZ16TC DAIKIN Air Source Heat Pump 47,000 9 HSPF Elite Software Development, Inc. Burton 12940 Mack Residence Page 14 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODS: 90F, SOWS: 78F, WODB: 42F, SIDE: 75F, SIRH: 50%, WIDE: 70F, Sen. gain: 36,090 Btuh, Lat. gain: 8,176 Btuh, Sen. loss: 48,067 Btuh, Entering clg. coil ❑B: 81.9F, Entering clg. coil WB: 64.8F, Entering htg. coil DB: 49.1 F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow 1223 CFM, Req. htg. airflow: 481 C F M C:1UsersWulia0ropboxlRhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM RWac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Florida Breeze Burton 12940 Mack Residence West Melbourne, FL 32904 _ Page 15 �Equipment Data - System 4 - Kitchen Gym Game Bed 3 4 Theater in Law Pink) Cooling System Type: Outdoor Model: Indoor Model: Tradename: Outdoor Manufacturer: Description: AHRI Reference No.: Capacity: Efficiency: Heating System Type: Model: Tradename: Manufacturer: Description: Capacity: Efficiency: Air Source Heat Pump DZ16TC0601 C* CA*F4961 *6D*+MBVC2000**-1A*+TX. DZ16TC DAIKIN Air Source Heat Pump 202148727 56,500 17 SEER Air Source Heat Pump DZ16TC0601C* DZ16TC DAIKIN Air Source Heat Pump 59,500 9.5 HSPF This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SORB: 90F, SOWS: 78F, WODB: 42F, SIDE: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 42,921 Btuh, Lat. gain: 7,902 Btuh, Sen. loss: 50,676 Btuh, Entering clg. coil DB: 78.917, Entering cig. coil WB: 63.8F, Entering htg. coil DB: 58.61F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 1637 CFM, Req. htg. airflow: 566 CFM C:1Users\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM I Rhvac - Residential 8 Light Commercial HVAC Loads Florida Breeze West Melbourne, FL 32904 Equipment Data - System 5 - Second Floor Cooling System Type: Outdoor Model: Indoor Model: Tradename: Outdoor Manufacturer: Description: AHRI Reference No.: Capacity: Efficiency: Heating System Type: Model: Tradename: Manufacturer: Description: Capacity: Efficiency: Air Source Heat Pump DZ16TC0601C* CA*F4961 *6D*+MBVC2000**-1A*+TX DZ16TC DAIKIN Air Source Heat Pump 202148727 56,500 17 SEER Air Source Heat Pump DZ16TC0601 C* DZ16TC DAIKIN Air Source Heat Pump 59,500 9.5 HSPF Elite Software Development, Inc. Burton 12940 Mack Residence Page 16 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SCDB: 90F, SQWB: 78F, WODB: 42F, SIDE: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 45,349 Btuh, Lat. gain: 5,623 Btuh, Sen. loss: 41,095 Btuh, Entering clg. coil DB: 76.5F, Entering clg. coil WB: 63F, Entering htg. coil DB: 65.21F, Clg. coil TD: 2017, Htg. coil TD: 70F, Req. clg. airflow: 1923 CFM, Req. htg. airflow: 500 CFM C:Wsers\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential & Light Commercial WVAC Loads Elite Software Development, Inc. Florida Breeze Burton 12940 Mack Residence West Melbourne, FL 32904 _Rage 17 System 1 Room Load Summary Htg Min Run Run Clg CIg Min Act Room Area Sens Htg Duct Duct Sens Lat Clg Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM --Zone 1--- - 1 Guest Living Bed 2,324 40,247 523 13-6 524 29,414 3,968 1,338 1,338 7 And 8 (Blue) Duct Latent 2,470 Return Duct 9,267 7,155 1,829 System 1 total 2,324 49,514 523 36,559 8,267 1,338 1,338 System 1 Main Trunk Size: 22 in. Velocity: 507 ft.lmin Loss per 100 ft.: 0.029 in.wg Coaling System Summary -- -- l__ Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh! Net Required. 3.74 82% / 18% 36,569 8167 44,836 Actual: 4.00 75% 125% 36,000 12,000 t n -1 48,000 q ipmen_ t Data — -- ---- -- Heati_ng-System Cooling System Type: Air Source Heat Pump Air Source Heat Pump Model: DZ16TC0481 C* DZ16TC0481 C* Indoor Model: CA*F4961*6D*+MBVC2000**-1A*+TX Brand: DZ16TC DZ16TC Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 9 HSPF 16 SEER Sound: 0 0 Capacity: 47,000 Btuh 48,000 Btuh Sensible Capacity: n1a 36,000 Btuh Latent Capacity: nla 12,000 Btuh AHRI Reference No.: n/a 202148839 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 42F, SIDB: 75F, SIRH: 50%, WIDB: 701F, Sen. gain: 36,569 Btuh, Lat. gain: 8,267 Btuh, Sen. loss: 49,514 Btuh, Entering clg. coil ❑B: 79.9F, Entering clg. coil WB: 64,2F, Entering htg. coil DB: 53.9F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. cig. airflow: 1338 CFM, Req. htg. airflow: 523 CFM C.\Users\Julia\Dropbox\Rhvae 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential &Light Commercial HVAC Loads Elite software Development, Inc. Florida Breeze Burton 12940 Mack Residence West Melbourne, FL 32904 _ Page 18 System 2 Roam Load Summary Htg Min Run Run Clg Cig Min Act Room Area Sens Htg Duct Duct Sens Lat Cig Sys No Name 5F Btuh ---Zone 1--- CFM Size Vel Bfuh Btuh CFM CFM 2 Living Dining 2,630 40,413 525 15-6 556 35,992 6,557 1,637 1,637 Study Parlor (Green) Duct Latent 3,210 Return Duct 7,069 7,603 2,376 System 2 total 2,630 47,482 525 43,595 12,143 1,637 1,637 System 2 Main Trunk Size: 24 in. Velocity: 521 ft./min Loss per 100 ft.: 0.027 in.wg Cooling System Summary Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 4.64 78% 122% 43,595 12,143 55.738 Actual: 4.71 75%125% 42,375 14,125 li 66,600 Equipmenf Data _ Heating System Cooling System T - Type: Air Source Heat Pump Air Source Heat Pump Model: DZ16TC0601 C* DZ16TC0601 C* Indoor Model: CA*F4961 *6D**MBVC2000**-1A*+TX Brand: DZ16TC DZ1 6TC Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 9.5 HSPF 17 SEER Sound: 0 0 Capacity: 59,500 Btuh 56,500 Btuh Sensible Capacity: nla 42,375 Btuh Latent Capacity: nla 14,125 Btuh AHRI Reference No.: nla 202148727 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODS: 90F, SOWS: 78F, WODB: 42F, SIDE; 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 43,595 Btuh, Lat. gain: 12,143 Btuh, Sen. loss: 47,482 Btuh, Entering c1g. coil DB: 79.2F, Entering clg. coil WB: 63.91', Entering htg. coil DE: 57.8F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req, clg. airflow: 1637 CFM, Req. htg, airflow: 525 CFM C:\UserslJulia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential 8 Light Commercial HVAC Loads Elite Software Development, Inc. Florida Breeze Burton 12940 Mack Residence West Melbourne, FL 32904 Page 19 [System 3 Room Load Summary _ _ -- j — Htg Min Run Run Cig Clg Min Act Room Area Sens Htg Duct Duct Sens Lat Cig Sys No Name SF — Btuh _ CFM Size Vel --- Btuh — - Btuh CFM__ CFM - -Zone 1--- 3 Flex Bed 9 Bed 1,990 37,026 481 12-6 519 26,879 3,107 1,223 1,223 10 (Yellow) Duct latent 2,913 Return Duct 11,041 9,211 2,156 System 3 total 1,990 48,067 481 36,090 8,176 1,223 1,223 System 3 Main Trunk Size: 20 in. Velocity: 561 ft./min Lass per 100 ft.: 0.040 in.wg Coaling System Summary Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh -- Stuh -- Btuh . - Net Required: 3.69 82% / 18% 36,090 - - 8,176 44,266 Actual: 4.00 75% 125% 36,000 12,000 l Q' 48,000 Equipment Data - -- -- - Heating System Cooling System Type: Air Source Heat Pump Air Source Heat Pump Model: DZ16TC0481 C* DZ16TC0481 C* Indoor Model: CA*F4961*6D*+MBVC2000**-1A*+TX Brand: DZ16TC DZ16TC Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 9 HSPF 16 SEER Sound: 0 0 Capacity: 47,000 Btuh 48,000 Btuh Sensible Capacity n/a 36,000 Btuh Latent Capacity: n/a 12,000 Btuh AHRI Reference No-: n/a 202148839 This system's equipment was selected in accordance with ACCA Manual S. Manuai S equipment sizing data: SODS: 90F, SQWB: 78F, WODB: 42F, SiDB: 75F, SIRH: 50%, WIDB: 70F, Sen- gain: 36,090 Btuh, Lat. gain: 8,176 Btuh, Sen. loss: 48,067 Btuh, Entering clg. coil DB: 81.9F, Entering clg. coil WB: 64.8F, Entering htg. coil DB: 49.1 F, Cig. coil TD: 20F, Htg. coil TD: 70F, Req. cig. airflow: 1223 CFM, Req- htg. airflow: 481 CFM C:IUsers\JulialDropbox\Rhvac 9 Projects\BurtonlBurton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhvac - Residential Light Cornmrcial HVAC Loads Florida Breeze West Melbourne, FL 32904 System 4 Room Load Summary Htg Room Area Sens No Name SF Btuh - -Zone 1--- 4 Kitchen Gym 2,946 43,563 Game Bed 3 4 Theater In Law (Pink) Duct Latent Elite Software Development, Inc. Burton 12940 Mack Residence Page 20 Min Run Run Clg Clg Min Act Htg Duct Duct Sens Lat Cig Sys CFM Size Vel Btuh Btuh CFM CFM -------------- 566 15-6 556 35,983 4,583 1,637 1,637 Return Duct 7,113 System 4 total 2,946 50,676 System 4 Main Trunk Size: 24 in. Velocity: 521 ft./min Loss per 100 ft.: 0.027 in.wg Cooling System Summary 566 Cooling Sensible/Latent Tons Split Net Required: 4-24 84% 1 16% Actual: 4.71 75% 125% Eauir)m®nt Data Sensible Btuh 42,921 42,375 Heating Sy stem Type: Air Source Heat Pump Model: DZ16TC0601 C`` Indoor Model: Brand: DZ16TC Description Air Source Heat Pump Efficiency: 9.5 HSPF Sound: 0 Capacity: 59,500 Btuh Sensible Capacity: n/a Latent Capacity: n/a AHRI Reference No.: n/a 1,907 6,938 1,412 42,921 7,902 1,637 1,637 Latent Total Btuh Btuh 7,902 �, 50,823 14,125 56,500 Cooling System Air Source Heat Pump DZ16TC0601C" CA*F4961 *6D*+MBVC2000`*-1 A*+TX DZ16TC Air Source Heat Pump 17 SEER 0 56,500 Btuh 42,375 Btuh 14,125 Btuh 202148727 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODS: 90F, SOWB: 78F, WODB: 42F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 42,921 Btuh, Lat. gain: 7,902 Btuh, Sen. loss: 50,676 Btuh, Entering clg. coil DB: 78.9F, Entering clg. coil WB: 63.BF, Entering htg. coil DB: 58.6F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req- clg- airflow: 1637 CFM, Req. htg. airflow: 566 CFM C:IUsers\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM Rhuac - Residential & Light Commercial HVAG Loads Elite Software Development, Inc. Florida Breeze 46b Burton 12940 Mack Residence West Melbourne, FL 32904 Page 21 Sysam 5 Room Load Summary - - - - Htg Min Run Run Clg Clg Min Act Room Area Sens Htg Duct Duct Sens Lat CIg Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM ---Zone 1--- 5 Second Floor 3,050 38,473 500 18-6 544 42,263 4,667 1,923 1,923 Duct Latent 549 Return Duct 2,622 3,086 407 System 5 total 3,050 41,095 500 45,349 5,623 1,923 1.923 System 5 Main Trunk Size: 26 in. Velocity: 622 ft./min Loss per 100 ft.: 0.024 in.wg Cooling System Summary Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 4.25 89% l 11% 45,349 5,623 50,972 Actual: 4.71 75% 125% 42,375 14,125 i �, 56,500 F—Equipment Data Type: Model: Indoor Model: Brand: Description: Efficiency: Sound: Capacity: Sensible Capacity: Latent Capacity: AHRI Reference No Heating System Air Source Heat Pump DZ16TC0601C* DZ16TC Air Source Heat Pump 9-5 HSPF 0 59,500 Btuh n/a n/a n/a Cooling System Air Source Heat Pump DZ16TC0601 C* CA*F4961 *6 D*+M BVC2000**-1 A*+TX DZ16TC Air Source Heat Pump 17 SEER 0 56,500 Btuh 42,375 Btuh 14,125 Btuh 202148727 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODS: 90F, SOWS: 78F, WODB: 42F, SIDE: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 45,349 Btuh, Lat. gain: 5,623 Btuh, Sen- loss: 41,095 Btuh, Entering cig. coil ❑B: 76-517, Entering clg. coil WB: 63F, Entering htg. coil ❑B: 65.2F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 1923 CFM, Req. htg. airflow: 500 CFM C:\Users\Julia\Dropbox\Rhvac 9 Projects\Burton\Burton 12940 Mack Residence.rh9 Thursday, April 23, 2020, 2:57 PM ACCK Ar« County, Town, Municipality, Jurisdiction Header Information Contractor Florida Breeze REQUIRED ATTACHMENTS' Manual J1 Form {and supporting worksheets}: Mechanical License # CAC1814113 or MJ1AE Formz land supporting worksheets): OEM performance data (heating, cooling, blower): Building Plan # MACK RESIDENCE Sys. 1 Manual D Friction Rate Worksheet Duct distribution system sketch: Home Address (Street or Lot#, Block, Subdivision) 7840 SADDLEBROOK DRIVE, PSL FL 34986 Design Conditions Winter Design Conditions Outdoor temperature 42 OF Indoor temperature 70 OF Total heat loss 49514 Btulh Summer Design Conditions Outdoor temperature 90 OF Indoor temperature 75 OF Grains difference 61 ❑ Gr @ 56 % Rh Sensible heat gain 36569 Btulh Latent heat gain 8267 Btulh Total heat gain 44836 Btu/h Heating Equipment Data Equipment type Furnace, Heat pump, Boiler, etc. Model Feat pump DZ16TC0481C* Form RPER 1.01 8Mar 10 ATTACHED Yes X❑ No ❑ Yes ❑ No ❑X Yes X No ❑ Yes ❑ No ❑X Yes ❑ No ❑X Building Construction Information Building Orientation (Front door faces) East{ North, East, West, South, Northeast, Northwest, Southeast, Southwest Number of bedrooms 4 Conditioned floor area 2324 Scl Ft Number of occupants 4 Windows Eave overhang depth 4.7 Ft Internal shade Blind$, drapes, etc Number of skylights Cooling Equipment Data Equipment type Heat pump Air Conditioner, Heat pump, etc Model DZ15TC0481 C* Blower Data Roof Eave Depth Window Heating CFM 1998 CFM Cooling CFM 1998 CFM Heating output capacity 47000 Btulh Sensible cooling capacity 36000 Btulh Heat pumps - capacity al winter design outdoor conditions Latent cooling capacity 20 0 ^ Btulh u 12000 Auxiliary heat output capacity Btulh Total cooling capacity 48000 Stulh 'HVAC DUCT DI STRI BUTION■ .1 Design airflow CFM Longest supply duct: Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, External Static Pressure (ESP) IWC Longest return duct: Ft Lined sheet metal, Other {specify} Component Pressure Losses (CPQ Available Static Pressure (ASP) ASP = ESP - CPL IWC Total Effective Length (TEL) IWC Friction Rate: _ Fraien Rate = (ASP • 100) , TEL Contractor's Printed Name Kristin Kelly Contractor's Signature AIRY - Ft Branch Duct: Duct board, Flex, Sheet metal, IWC Lined sheet metal, Other (specify) Date 3/23/2020 ' The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. ' If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edltion Version 2 Elite Software Rhvac program. i ACCA AiCo db" 0mWdoisdMWa Contractor Florida Breeze Mechanical License # CAC1814113 Building Plan # MACK RESIDENCE County, Town, Municipality, Jurisdiction Header Information REQUIRED ATTACHMENTS' Manual J1 Form [and supporting worksheets]: or MJ1AE Forma (and supporting worksheets): OEM performance data (heating, cooling, blower): Sys. 2 Manual ❑ Friction Rate Worksheet: Duct distribution system sketch: Home Address (Street or Lot#, Block, Subdivision) 7840 SADDLEBROOK DRIVE, PSL FL 34986 Form RPIER 1.01 8Mar 10 ATTACHED Yes® No❑ Yes❑ No❑X Yes ❑?C No ❑ Yes ❑ No Yes ❑ No X❑ HVAC LOAD CALCULATION40 Design Conditions Building Construction Information Winter design Conditions Building Outdoor temperature 42 °F Orientation (Front door faces) East Indoor temperature 70 °F North, east, West, South, Northeast, Northwest, Southeast, southwest Total heat Toss 474R7 Btulh Number of bedrooms 4 Summer Design Conditions Conditioned floor area 2630 Sq Ft Outdoor temperature go OF Number of occupants 1 Indoor temperature 75 OF Windows Grains difference 61 ❑ Gr @ 50 % Rh Eave overhang depth 8.5 Ft Roof Sensible heat gain ((77 4357a57 Btulh Internal shade <- Eave Latent heat gain 12143 Btulh Blinds, drapes, etc Depth Window Total heat gain 55738 Btulh Number of skylights 0 SELECTIONHVAC EQUIPMENT 40 Heating Equipment Data Cooling Equipment Data. Blower Data Equipment type Heat pump Equipment type Heat pump Heating CFM 1998 CFM Furnace. Heal pump, Boiler, etc. Air Condftioner, Heat pump, etc Model DZ16TC0601 C" Model DZ16TC0601 C* I' CFM Heating output capacity 59500 Btulh Sensible cooling capacity Heat pumps - capacity at winter design o&door conditions Latent cooling capacity Auxiliary heat output capacity Design airflow External Static Pressure (ESP) Component Pressure Losses (CPL) Available Static Pressure (ASP) ASP = ESP - CPL Contractor's Printed Name Kristin Contractor's Signature Btulh Total cooling capacity CFM Longest supply duct: IWC Longest return duct: IWC Total Effective Length (TEL) IWC Friction Rats: Friction Rate = (ASP x 100) + TEL Coo Ing CFM 1998 42375 Btulh 14125 Btu1h 56500 Btulh Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, Ft Lined sheet metal, Other (specify) - Ft Branch Duct: Duct board, Flex, Sheet metal, IWC Lined sheet metal, Other (specify) Date 3/23/2020 ' The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program. ACCK A rebnd0wg care rwW oFATww County, Town, Municipality, Jurisdiction Header Information Contractor Florida Breeze REQUIRED ATTACHMENTS' Manual X Form (and supporting worksheets): Mechanical License # CAC1814113 or MJ1AE Form' (and supporting worksheets): OEM performance data (heating, cooling, blower): Building Plan # MACK RESIDENCE Sys. 3 Manual D Friction Rate Worksheet: f7uct distribution system sketch: Home Address (Street or Lot#, Block, Subdivision) 7840 SADDLEBROOK DRIVE, PSL FL 34986 Design Conditions Winter Design Conditions Outdoor temperature 42 °F Indoor temperature 70 'F Total heat loss 48067 Btu/h Summer Design Conditions Outdoor temperature 90 OF Indoor temperature 75 OF Grains difference 61 ❑ Gr @ 50 % Rh Sensible heat gain 36090 Btulh Latent heat gain 8176 Btulh Total heat gain 44266 Btulh Heating Equipment Data Equipment type Heat pump Furnace. Heat pump, Wier, etc. Model n71 RTrn4R 1 r.* Form RIPER 1.01 8 Mar 10 ATTACHED Yes © No ❑ Yes ❑ NOR Yes 0 No ❑ Yes ❑ NOR Yes ❑ No ❑?C Bull fing Construction Inf—o —tiio Building Orientation (Front door faces) East North, East, West, South, Northeast, Northwest, Southeast, Southwest Number of bedrooms 4 Conditioned floor area 199❑ Sq Ft Number of occupants Windows Eave overhang depth Internal shade Blinds, drapes, etc Number of skylights Cooling Equipment Data Equipment type Heat pump Air Conditioner, Heat pump, etc Model DZ16TC0481 C* Heating output capacity 47000 Btu/h Sensible cooling capacity Heat pumps - capacity at winter design outdoor conditions Latent cooling rapacity Auxiliary heat output capacity Btulh Total cooling capacity HVAC DUCT DISTRIBUTION rESIGN (IRC M164 Design airflow CFM Longest supply duct: External Static Pressure (ESP) Component Pressure Losses (CPL) Available Static Pressure (ASP) ASP = ESP - CPL Contractor's Printed Name Kristi Contractor's Signature IWC Longest return duct: IWC Total Effective Length (TEL) IWC Friction Rate: Friction Rate = (ASP x 100) - TEL 36000 Btulh 12000 Btu/h 48000 Btu1h 2 7.3 Ft Blower Data Roof Eave Depth Window Heating CFM 1998 CFM Cooling CFM 1998 CFM Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, Ft Lined sheet metal, Other (specify) — Ft Branch Duct: Duct board, Flex, Sheet metal, IWC Lined sheet metal, Other (specify) Date 3/23/2020 ' The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. z If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program. ���+ i---w /`1CCK ArUnJbncaaaausdA = Contractor Florida Breeze Mechanical License # CAG1814113 Building Plan # MACK RESIDENCE County, Town, Municipality, Jurisdiction Header Information REQUIRED ATTACHMENTS' Manual A Form (and supporting worksheets): or MJ1AE Forme (and supporting worksheets): OEM performance data (heating, cooling, blower): Sys, 4 Manual D Friction Rate Worksheet: Duct distribution system sketch: Home Address (Street or Lot#, Block, Subdivision) 7840 SADDLEBROOK DRIVE, PSL FL 34986 Design Conditions Winter Design Conditions Outdoor temperature r� 42 °F Indoor temperature 70 °F Total heat loss 50676 Btulh Summer Design Conditions Outdoor temperature 90 OF Indoor temperature 75 OF Grains difference 61 ❑ Gr @ 50 % Rh Sensible heat gain 42921 Btulh Latent heat gain 7902 Btulh Total heat gain 50823 Btulh Heating Equipment Data Equipment type Furnace, Heat pump, Boiler, etc. Model Heat pump DZ16TC0601 C* Form RIPER 1.01 8 Mar 10 ATTACHED Yes O No❑ Yes ❑ NON Yes No El Yes ❑ No ❑X Yes ❑ NO Building Construction Information Building Orientation (Front door faces) East North, East, West, South, Northeast, Northwest, Southeast, Southwest Number of bedrooms 4 Conditioned floor area 2946 Sq Ft Number of occupants 3 Windows Eave overhang depth 5.8 Ft Internal shade Blinds, drapes, etc Number of skylights Cooling Equipment Data Equipment type Heat pump Air Conditioner, Heat pump, etc Model DZ16TC0601 C* Blower Data Roof Eave Depth Window Heating CFM 199 CFM Cooling CFM 1 C)C CFM Heating output capacity 59500 Btulh Sensible cooling capacity 42375 Btulh Heat pumps - capacity at winter design outdoor conditions Latent cooling capacity _l Btulh 1 41 2 Auxiliary heat output capacity Btulh Total cooling capacity 56500 Btulh HVAC DUCT DISTRIBUTION SYSTIzM ■ 1 Design airflow CFM Longest supply duct: Ft Duct Materials Used (Circle) Trunk Duct: Duct board, Flex, Sheet metal, External Static Pressure (ESP) IWC Longest return duct: Ft Lined sheet metal, Other (specify) Component Pressure Losses (CPQ Available Static Pressure (ASP) ASP = ESP - CPL Contractor's Printed Name Kristin Kel Contractors Signature FW IWC Total Effective Length (TEL) IWC Friction Rate: Friction Rate = (ASP % 100 _ TEL — Ft Branch Duct: Duct board, Flex, Sheet metal, IWC Lined sheet metal, Other (specify) Date 3/23/2020 ' The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions. Y If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructlons. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvec program. �- ACCK AirCmdWnrV oer,�dpxsdpurnica County, Town, Municipality, Jurisdiction Header information Contractor Florida Breeze Mechanical License # GAG1814113 Building Plan # MACK RESIDENCE Home Address (Street or Lot#, Block, Subdivision) {REQUIRED ATTACHMENTS' Manual A Form (and supporting worksheets): or MAAE Forme (and supporting worksheets): OEM performance data (heating, cooling, blower): Sys. 5 Manual D Friction Rate Worksheet: Duct distribution system sketch: 7840 SADDLEBROOK DRIVE, PSL FL 34986 Design Conditions Buildin-q Construction information Winger Design Conditions Building Outdoor temperature 42 OF Orientation (Front door faces) East Indoor temperature 70 OF Total heat loss 41 095 Btulh Summer Design Conditions Form RPER 1.01 8Mar 10 ATTACHED Yes © No ❑ Yes ❑ No X❑ Yes ® No ❑ Yes❑ No© Yes ❑ No ❑X North, East, West, South, Northeast, Northwest, Southeast, southwest Number of bedrooms 4 Conditioned floor area 3050 Sq Ft Outdoor temperature go OF Number of occupants 4 Indcortemperature 75 of Windows Grains difference ❑ Gr % Rh �� lave overhang depth Roof Z.� Ft Sensible heat gain - 45349 Btu/h Internal shade E- Latent heat gain 5623 Btulh Blinds, drapes, etc Eave Depth Window Total heat gain 50972 Btulh Number of skylights 0 FIVAC EQUIPMENTr(IRCM14013) Heating E ui ment Data Cooling Equipment Data Blower Data Equipment type Heat pump Equipment type Heat pump 1998 CFM Heating CFM Furnace, Heat pump, Boiler, etc. Air Conditioner, Heat pump, etc Model DZ16TC0601 C* Model DZ16TC0601 C' Cooling CFM 1998 CI=M Heating output capacity 59500 Btulh Sensible cooling capacity 42375 Btulh Heat pumps - capacity at winter design outdoor conditions Latent cooling capacity 14125 Btulh Auxiliary heat output capacity Btulh Total cooling capacity 56500 Btulh !HVAC DUCT DISTRIBUTION Design airflow CFM Longest supply duct: Ft Duct Materials Used (circle) Trunk Duct: Duct board, Flex, Sheet metal, External Static Pressure (ESP) IWC Longest return duct: Ft Lined sheet metal, Other (specify) Component Pressure Losses (CPL) Available Static Pressure (ASP) IWC Total Effective Length (TEL) IWC Friction Rate: ASP = ESP - CPL Friclion Rate = (ASP K 100) +TEL — Ft Branch Duct: Duct board, Flex, Sheet metal, IWC Lined sheet metal, Other (specify) Contractor's Printed Name Kristin Kelly Date 3/23/2020 Contractor's Signature ' The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions, If abridged version of Manual J is used for toad calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions. Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.