SHOP DRAWING REVIEW COMMENTS _RE CEIVrD
Reference: St. Lucie County Airport Forensic Analysis 2020
Salas O'Brien Florida #15072
Subject: Final Test and Balance Report Submittal
MAY 01 2020
Reviewed By: Kyle J. P.E.
Y Cartier,Y ST. Lucie County, Permitting
Engineer's review is for general conformance with the design concept and contract documents.Markings or comments
shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor
departures therefrom. The Contractor remains responsible for details and accuracy, compliance with the Contract
Documents and intent,for confirming and correcting all quantities and dimensions,for selecting appropriate fabrication
processes,for techniques of assembly,and for performance of work in a safe manner.
OVERALL DISPOSITION: Revise and Resubmit
1. Verify the recorded values for AHU-1. The summation of the outside air (1,852 CFM) and
return air (4,665 CFM) exceed the supply air from the unit (total of outside and return is
6,517 CFM, recorded supply is S,341 CFM). The summation of the return air from the AHU-
1 table is 2,808 CFM, which is not consistent with the value recorded in the AHU-1 data
sheet (4,665 CFM).
2. It is noted that the final total supply air for RTU-1 is considerably lower than design (73%).
3. There is a difference of 356 CFM between the recorded RTU-2 supply air (1,986 CFM) and
return air(1,630 CFM). This implies that the outside air damper on RTU-2 is not completely
closed. Ensure the outside air damper on RTU-2 is completely closed and sealed and re-
measure to ensure the supply and return airflow values are the essentially the same.
4. It appears exhaust fans EF-1, EF-2 and EF-3 have not been rebalanced to their respective
new airflows as required by sheet M1.1, Plan Reference Notes 14, 13 and 15
respectively. Rebalance exhaust fans to values indicated, record and re-submit for review.
S. The Outside Air Unit test data is missing the entering and leaving dry bulb and wet bulb
air temperatures across the unit heat pipe coils. Measure and record these values and
include in the test report for evaluation. Refer to sheet M4.1, Grade Mounted Package
100% Outside Air Unit Schedule for indicated values across the pre-cooling and reheat
coils.
6. Confirm the 52 degree off-coil temperature indicated in the Outside Air Unit report form
is the temperature leaving the DX cooling coil prior to entering the heat pipe reheat coil.
7. Measure and record the total unit amp draw and voltage at design conditions. It appears
the recorded values for amps and voltage are for the evaporator fan only. Refer to sheet
M4.1,Grade Mounted Package 100%Outside Air Unit Schedule for unit design MCA value.
Shop Drawing Review Comments
Page 2 of 2
8. Rebalance total airflow from the Outside Air Unit to within 10% of the total design (1,540
CFM maximum) as opposed to the 1,852 CFM recorded.
END OF DOCUMENT
OMEGA AIR SERVICES LLC
DBA OMEGA TEST AND BALANCE
NNNA CERTIFIED INDEPENDENT TES TAND BALANCE COMPANY---
126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982
CELL (772)216-7632
TABB CERTIFICATION NO. BB032001C
www.omegaairserviceslic.com
omegamaniac532002@vahoo.com
TESTING, ADJUSTING, AND BALANCING REPORT
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
FORT PIERCE, FLORIDA
MECHANICAL ENGINEER:
SIMS WILKERSON CARTIER ENGINEERING INC.
12124 HIGH TECH AVENUE, SUITE 200
ORLANDO, FL 32817
MECHANICAL CONTRACTOR:
GRIMES HEATING & AIR CONDITIONING
3054 NORTH US HWY. ONE
FORT PIERCE FLORIDA 34946E
ELECTRONIC SHOP DRAWING REVIEW
/ By:Salas O'Brien
REVISE AND RESUBMIT j
rs re w is!or geneml conformance.,in the design concept and
d menu Markings o menb shall no,be constrved a
[heu Cantactor wi,h the proct plans and
tioru,nor departuIt rofrnm.
4-9-20 tractor remains responsible fr details and accuracy,compliznce Contact Documents and intent.for confi,ming ad cometting aes a,d ciimenoons.ro wl,cting appmprute fabrication p,xesses,
niques ofassembly,and for pedom .of work In a safe manna,Kyle J.Cartlair,P.E. Ayr Y1,=020
--TILL WORK PERFORMED IN ACCORDANCE WITH TABB STANDARDS AND PROCEDURES--
c�-r
HUGH GRIMES
TABB TECHNICIAN
BAt0A7t510T SFPTFMRFR t0.7(yl
TESTING,ADJUSTING AND BALANCING BUREAU
HVAC EMPERTISt "THE PROFESSIONAL'S CHOICE
OMEGA AIR SERVICES LLC
DBA OMEGA TEST AND BALANCE
NNNA CERTIFIED INDEPENDENT TESTA ND SA LA NCE COMPA N YNNN
126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982
CELL (772)216-7632
TABB CERTIFICATION NO. BB032001C/BB032002S/BB1032610T
www.omeciaairserviceslic.com
omecjamaniac5320020vahoo.com
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
TEST AND BALANCE INSTRUMENTS
SHORTRIDGE SERIES 8400 FLOWHOOD W/ADM860 AIR DATA MULTIMETER
RANGE: 0 TO 61 IN H.G
ACCURACY: 0.05% FS
CALIBRATION DATE: SEPTEMBER 8, 2019
CHECK-IT DIGITAL PSYCHROMETER—MODEL #622
RANGE: 35° TO 205° F, 5% TO 100% RH
ACCURACY: ±20 ±1 DIGIT t30/o
CALIBRATION DATE: AUGUST 8, 2018
SHORTRIDGE ADT446 TEMPROBE
RANGE: -200 TO 1800 F
ACCURACY: t 0.50 FROM 320 TO 1580 F
CALIBRATION DATE: AUGUST 8, 2018
FLUKE 322 CLAMP METER
HUGH A. GRIMES,
CERTIFIED T.A.B.B. CONTRACTOR/SUPERVISOR/TECHNICIAN
--ALL WORK PERFORMED IN ACCORDANCE WITH TABB STANDARDS AND PROCEDURES--
HUGH GRIMES
TABB TECHNICIAN
B61032610T SEPTEMBER 30.2021
TESTING,ADJUSTING AND BALANCING BUREAU
0" EXPERTISE "THE PROFESSIONAL'S CHOICE""
HUGH GRIMES
TABB TECHNICIAN
810326101 SEPTEMBER 30.2021
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
AIR HANDLING UNIT
MAKE CARRIER
MODEL 40RUAA16
SERIAL 1112UO9486
SHEAVE 7 X 1
BELTS 1/A46
FILTERS i"
MAKE I FR GE 56
HP RPM 3.7 1750
V PH HZ 208-230 3 60
FLA SF 10.6 1.15
SHEAVE 3 3/4 X 1
CL 17
HEAT 2.76 KW ELECTRIC
i
SA CFM 5750 5341
OA CFM 1400 1852**
RA CFM 5225 4665
EXT.SP NA 1.84
DISC. SP NA 1.67
SUCT. SP NA -.17
OAT DB WB NA 88.1 80.1
RAT DB/WB NA 72.3/61.8
LAT DB WB NA 54.1 53.6
FAN RPM NA NA
VOLTS 208 210 AVG.
AMPS 10.6 8.6 AVG.
MODEL
SERIAL
V PH HZ
RLA
LO PRESSURE
HI PRESSURE
REFRIGERANT
FAN HP RPM
V PH HZ
REMARKS:MTR. PULLEY FULLYCLOSED. ** SEE NOTES ON OUTSIDE AIR UNIT.
ALL WORK PERFORMED IN ACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
HUGH GRIMES
TABB TECHNICIAN
BII 7fiinT SFPTFMRFR in-zon
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
AHU-1
SUPPLY
ADDRESS OUTLET TYPE DESIGN PRE. FINAL
NUMBER CFM CFM CFM
101 1 SW 900 822
106 2 SW 900 702 7
121 3 SW 900 808 7
117 4 SW 900 803 8
NA 5 CD 100 82
ill 6 CD 150 130 9
110 7 CD 100 72
106 8 CD 150 66 13
103 9 CD 125 100 12
107 10 CD 175 143 47
107 11 CD 175 146 9
108 12 CD 175 140 0
112 13 CD 75 54
115 14 CD 175 144 1
116 15 CD 275 218 1
116 16 CD 275 232 2
109 17 CD 75 78 1
102 18 CD 125 123 31
5750 4863
REMARKS: NOTE REVISED FUTURE OUTSIDE AIR SETPOINTS COULD
EFFECT THE FINAL NUMBERS
ALL WORKPERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
HUGH GRIMES
TABS TECHNICIAN
B10i7610T CFVTFMRFR tR 7071
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
AHU-1
RETURN
ADDRESS OUTLET TYPE DESIGN PRE. FINAL
NUMBER CFM CFM CFM
116 1 RG -600 -549
116 2 RG -600 -536 348
115 3 RG -175 -155 1 99
108 4 RG -175 -159 ;104
107 5 RG -350 -313 '203
101 6 RG -750 -659 428
101 7 RG -750 -655 425
101 8 RG -750 -680 442
104 9 RG -750 -686 445
106 10 RG -325 -273 fi177
-5225 -4665
REMARKS:NOTE LOWER RETURN VALUES ARE MEASURED WITH
OUTSIDE AIR UNIT PRODUCING WHAT IS REPORTED
ALL WORKPERFORMED MACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
�k Di
HUGH GTABB TECB1n2�A1nT SFPi
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
RTU-1
SUPPLY
ADDRESS OUTLET TYPE DESIGN PRE. FINAL
NUMBER CFM CFM CFM
117A 1 CD 250 145
117A 2 CD 250 151 90*
117A 3 CD 250 149 69*
117A 4 CD 250 156 89*
117A 5 CD 250 138 82*
117A 6 CD 250 137 i77*
p
1500 876 4
REMARKS: ---RTU-1 NOT ACCESSIBLE FOR TESTING.
---EAT @ 74.3
---LAT @ 57.5
NOTE;EXISTING EQUIPMENT UNIT HAS VARIABLE MOTOR DRIVE
Test and Balance has no access to these systems. SEE PRELIMINARY
REPORT
ALL WORKPERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
HUGH GRIMES
TABB TECHNICIAN
81(l37f;jQT SFPTFMRFR In 7071
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
RTU-1
RETURN
ADDRESS OUTLET TYPE DESIGN PRE. FINAL
NUMBER CFM CFM CFM
117A 1 RG -725 -561
117A 2 RG -725 -516
-1450 1 -1077
REMARKS:
ALL WORKPERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
HUGH GRIMES
TABB TECHNICIAN
61Rv610T SFVTFMRFR i0.2n71
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
RTU-2
SUPPLY
ADDRESS OUTLET TYPE DESIGN PRE. FINAL
NUMBER CFM CFM CFM
124 1 CD 175 87
124 2 CD 175 70 133
ATOS 3 CD 150 50 97
126 4 CD 175 51 131
124 5 CD 175 66 1113
99
124 6 CD 175 108139
102 7 CD 175 168171
102 8 CD 125 78114
119 9 CD 125 71109
120 10 CD 125 68
123 11 SW 225 239 217
123 12 SW 225 256 "216
123 13 SW 225 269 211
126 14 CD 125 38 96
Lu-
2000 1619 6
REMARKS: ---RTU-2 NOT ACESSIBLE FOR TESTING.
---EAT @ 73.7
---LAT @ 55.1
ALL WORKPERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
HUGH GRIMES
TABB TECHNICIAN
810126101 SEGTEMBER 30.M21
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
RTU-2
RETURN
ADDRESS OUTLET TYPE DESIGN PRE. FINAL
NUMBER CFM CFM CFM
124 1 RG -575 -265
124 2 RG -575 -208 548 1
102 3 RG -550 -406 S23
-1700 -879
REMARKS:
ALL WORK PERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
HUGH GRIMES
TABB TECHNICIAN
B1Ri761I1T SFFTFMRFR iR.M21
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
EF-1
EXHAUST
ADDRESS OUTLET TYPE DESIGN PRE. FINAL
NUMBER CFM CFM CFM
105 1 EG -200 -137
103 2 EG -75 -61
-275 -198
REMARKS:
ALL WORKPERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
HUGH GRIMES
TABB TECHNICIAN
einamu SFPTFMRFR 4tl_M71
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
EF-2
EXHAUST
ADDRESS OUTLET TYPE DESIGN PRE. FINAL
NUMBER CFM CFM CFM
102 1 EG -75 -74
NA 2 EG -100 -113 113
NA 3 EG -100 -67 67
r
E
-275 -254
REMARKS:
ALL WORKPERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES
1
HUGH GRIMES
TABB TECHNICIAN
BinminT 9FPTFMRFR 7R.M7I
ST. LUCIE COUNTY INTERNATIONAL AIRPORT TERMINAL
PRELIMINARY READINGS
AIR OUTLETS
EF-3
EXHAUST
ADDRESS OUTLET TYPE DESIGN PRE.i
NAL
NUMBER CFM CFMFM118 1 EG -75 * 41
119 2 EG -100 -7570
120 3 EG -125 -13023
119 4 EG -100 -14431
120 5 EG -125 -8980
i
-525 -438 1144S
REMARKS: ---*NO ACCESS
ALL WORK PERFORMED IN ACCORDANCE WITH TABS STANDARDS AND PROCEDURES
a\C�rtMc_.
HUGH GRIMES
TABB TECHNICIAN
B1032610T SEPTEMBER 30,2021
OUTSIDE AIR UNIT
REMARKS: ST.LUCIE AIRPORT
MAKE AAON
MODEL RNA 011
SERIAL 201909
SHEAVE DD
BELTS DD
FILTERS NA
MAKE I FR NA
HP RPM 1 NA
V PH HZ 230\3\60
FLA SF 4.2
SHEAVE DD
CL DD
HEAT NA
SA CFM 1400 1852
OA CFM 1400I1852
RA CFM INA
EXT.SP INA
DISC.SP INA
SUCT. SP INA
OAT DB WB 95 85 84.6 77.8
EAT DB/WB 95\85 84.6\77.8
LAT DB WB 52.3 52.2 52@COIL*
FAN RPM NA NA NA NA NA NA
VOLTS 230 210 AVG.
AMPS NA 2.1 AVG,
MAKE
MODEL PLEASE NOTE WE DO NOT
SERIAL TEST THE REFRIGERANT
V PH HZ SIDE
RLA
LO PRESSURE
HI PRESSURE
REFRIGERANT
FAN HP RPM
V PH HZ
CC HEAT AMPS
NOTE.•LAT @ DISCGARGE=68 160.1 DURING TESTING SETPOINTS BY OTHERS
Unit a/arm/shut down if drive setting below 35 Hertz
Building pressure+.019
ALL WORKPERFORMED INACCORDANCE WITH TABS STANDARDSAND PROCEDURES