Loading...
HomeMy WebLinkAboutProject Information+ Project Summary JJoab: Lot 22 Block 77.9 Indian ... ,1�DEL: AIR I�Ara1a•�,�D1DmDIOID Entire House By: KDAVIS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax 407-333.3853 Web: WW W.DELAIR.COM Prowect Information For: ADAMS HOMES 5611 Spruce Drive, Fort Pierce, FL 34982 44 m CR. Fo Notes: L. S. 1-31-20 VWK e m 9 3"0 Design Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/lb Heating Summary Structure 16950 Btuh Ducts 6429 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 23380 Btuh Infiltration Method Simplified Construction qu lily Average Fireplaces 1 0 Heatingg Coolingg Area (ft2) 2010 2010 Volume (ft3) 17400 17400 Air changes/hour 0.32 0.16 Equiv. AVF (cfm) 93 46 Heating Equipment Summary Make Carrier Trade CARRIER Model 25HBC537AO030 AHRI ref 10487322 8.5 HSPF 34600 Btuh @ 47OF 27 OF 1167 cfm 0.050 cfm/Btuh 0.30 in H2O point = 32 OF Sensible Cooling Equipment Load Sizing Structure 17023 Btuh Ducts 8204 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Equipment sensible load 25227 Btuh Latent Coolin Equipment Load Sizing Structure 2593 Btuh Ducts 2222 Btuh Central vent (0 cfm) 0 Btuh (ponEquipment latent load i 4815 Btuh Equipment Total Load (Seri+Lat) 30042 Btuh Req. total capacity at 0.75 SHR 2.8 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond 25HBC537AO030 Coil FX4DNB037L AHRI ref 10487322 Efficiency 12.5 EER, 15.5 SEER Sensible cooling 26250 Btuh Latent cooling 8750 Btuh Total cooling 35000 Btuh Actual air flow 1167 cfm Air flow factor 0.046 cfm/Btuh Static pressure 0.30 in H2O Load sensible heat ratio 0.84 Backup: Input = 7 kW, Output = 24018 Btuh, 100 AFUE CC ���' Calculations approved by ACCA to meet all requirements of MaFII wr4ghtsoR' 2020Jan31 08:49:43 °""" ••• +°^-m Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1 ...OIOAGR\Lot228lk77-9lndianRiverEstate2010AGR.rup Calc=10J8 Front Doorlaces: E ' QEL-AIR Right-M Worksheet °"°°'" Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot 22 Block 77.9 Indian Riv... Dale: By: M.DAVIS 1 2 3 4 5 Roam name Exposed wall Room height Room dimensions Room area Entire House 163.4 it 8.6 ft d 2016.0 IF M. BATH 13.5 ft 8.0 ft heat/cool LO x 146.3 ft 146.3 ft2 Ty Constmction number U-value (Btufditz°F) Or HTM (Btuhlft9 Area (fR) or perimeter (ft) Load (Btuh) Area (fill or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W , LG ;Blk wall, stucco ext`-, ;2A-20v " 4.143 ,_;_0.330 n _n_ 415 � 9 57 2'.59 :,8.52 ­286 16 272 0 .. 1127 .`156 —703 ___._._139 A 0 0 v0 ''0 __0 0 —0 11 WIC �C Elk wall, stucco ext 2A-2ov 2A-2ov 11,10 Blk wall„'stucco ext PA-2ov Blk wall, stucco ext 10Gv 2A-20v 2A 2ov 12C Osw0.091. 16B 30ad 0.143 0.330 0,330 0.600 U;143 __-0.330 0.143 0.550 0.330 0.330 0_032 a a a a s _s_ w w w w '_.__ - 4.15 9.57 9.57 1740 "-415 _--_957- 4.15 15.95 9.57 9.57 :2 64 0.93 =28 68 2.59 21.17 9.21 1758 259"286"'283 ___8:52 259 16.20 22.70 8.52 _� Ul 1.69 `_­0:00 284 33 47 20 5 448 18 49 33 � 164 2137 _2016 184 2 87 20 765 313 448 350 -''�1775 45 477 692 431 353 '-'733--"�36-'—"31 40 0 0 0 0 - 5 0 0 0 0 0 0 0 0 130 45 0 0 0 0 —81 ; 40 186 0 0 0 __0 247 _+ __ _0 �p W ^- VV�}}111 __9 348 36 3 65 =64 2137 =63 1445 285 469 _ 313 _.—._433 1983 '- 4687 _ 902 289 1113 279 ----_,215 3611 ='=____0 72 0 0 0 0 146 =46 ___5 72 0 0 0 __0 146 =J4 _, 299 0 0 0 `-_ __0 136 __= 387 _•' P C 6 c) AED excursion 1439 -27 Envelope loss/gain 13993 11417 996 527 12 a) Infiltration b) Room ventilation 2958 0 785 01 244 0 65 0 13 Intemal gains: Occupants @ 230 Appliances/other 4 920 3900 0 0 0 Subtotal (lines 6 to 13) 16950 17023 1240 592 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 1 38% 48% 0 0 0 16950 6429 0 0 0 17023 8204 38% 48%1 0 0 0 1240 470 0 0 0 592 285 Total room load Air required (cfm) 23380 1167 25227 1167 1711 85 878 41 Calculations approved by ACCA to meet all requirements of Manual J Sth Ed 2020Jan31 08:49:43 Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1 ...OtOAGR\Lot22B1k77.9lndianRiverEstate2010AGR.rup Calc=MJ8 Front Door faces: E 5�DEL-AIR Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot 22 Block 77-9 Indian Riv... Date: By: M.DAVIS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area M. BDRM 30.5 It 8.0 ft heat/coal 12.5 x 18.0 it 225.0 ftx M. WC 10.0 ft 8.0 It heaVcoal 3.5 x 6.5 ft 22.8 fP Ty Construction number U-value (BtulAth-F) Or HTM (BtutVIV) Area (ftq or perimeter (ft) Load (Bluh) Area M9 or perimeter (It) Load (Btuh) Heat Coal Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Bllatucco ext 2A.2ov Blk wall, stucco ext 2A-20v 2A-2ov 11J0 0:143 ,„.0.330 , n . S: =:,.415 -9.57, -2.59 -8.52 00 _ 0 _0 _,„_, 0 __ _,;0 ­0 ,a„--„,,_0 --- 0 0 0 --„-__0 0 �,_,_-_-_0 I 0.143 0.330 0.330 0143 0.143 a a a a 's ,s_ w w w w - - 4.15 9.57 9.57 1740 4.15 _,.e9.57, 259 21.17 9.21 17.58 �2.58 100 33 0 0 144 0 67 1 0 0 -'- 144 279 313 0 0 ` 597 0 174 692 0 0 -`-373 0 0 0 0 --52 0 0 0 0 "-52 0 0 0 0 0 'P16 0 0 0 0 " 135 0 4y_ Blkwall; stucco ez[-" W-W2 ,-_- Blk wall, stucco ext 10Gv 2A-2ov 2A-2ov ,12C-05ww��,,� 16B-30ad 22A-tpl,`_,' WWW '0.600 0.143 0.550 0.330 0.330 u 0.091 0.032 =0.989 4.15 15.95 9.57 9.57 =264 _ 0.93 28.68 ,�&52 2-59 16.20 2270 8.52 =1;37.0 1.69 „-;0.00 __,a _ 0 0 0 0 225 . ��225 __0 0 0 0 0 „_._.00 225 _ �_�:31. 0 0 0 0 209 �875 _.__0 0 0 0 0 380 ._,�0 ___0 28 0 0 0 23 �23'_70 28 0 0 0 _._.0 116 0 0 0 . =_ 0 21 �,�-287, 72 0 0 0 Pf 38 =_0 P, C _ Fw_._.. �,-,.,_.-0 23 6 c) AED excursion 89 -13 Envelope loss/gain 2273 1708 640 233 12 a) Infiltration b) Roam ventilation 552 0 146 0 181 0 48 0 13 Internal gains: Occupants @ 230 Appliances/other 1 230 60D 0 0 0 Subtotal (lines 6 to 13) 2824 2684 821 281 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 38'/ 48% 0 0 0 2824 '1071 0 0 0 26841 1294 38% '480/0 0 0 0 821 311 0 0 0 281 135 Total room load Air required (cfm) 3896 194 3978 184 1132 56 416 19 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed wr o9�+lsof!- 2020Jan-Jan08:49:43 Right-Suite®Universal .rup 9 1 = MJ Front D Page 2 ...OtOAGR\Lot22BIk77-9lndianRiverEstale2010AGR.rup CaIc=MJB Front Door faces: E i�DEL-AIR Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407333-2665 Fax 407333-3853 Web: WWW.DELAIR.COM Job: Lot 22 Block 77.9 Indian Riv... Date: By: M.DAVIS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area M. OWIC 7.0 It 8.0 It heaticocl 4.0 x 7.0 It 28.0 W M. IWIC 0 It 8.0 fl heat/cool 4.0 x 7.0 It 28.0 ft2 Ty Construction number U-value (BtuWft'-"F) Or HTM (Btutvftg Area (ftj or perimeter (ft) Load (Btuh) Area (10 or perimeter (ft) Load (Btuh Heat I Cool Gross WP/S Heat Cool Gross N/P/S Heat Cool 6 11 BIk`wall,-stucco ext.. 2620V Blk wall, stucco ext 2A-2ov 2A-20v 11J0 Blk wafl, stucco exf- 24_20v Blk wall, stucco ext 10Gv 2A-2ov 2A-20v �12C{lsW��=�. 16B-30ad .22A:ipl .�-" -0:1b 0.330 0.143 0.330 0.330 0.600 `0:143 �0.330 -nn _n_ a a a a 'S 4J5 -9.57. 4.15 9.57 9.57 17.40 435 ' 259 8.52 Z59 21.17 9.21 17.58 -2:59 -0 ---0 0 0 0 0 -56 - , 0 _-0 0 0 0 0 --66 "0 - d _0 0 0 0 0 -232 ' 0 0 0 0 0 0 -145 0 0 0 0 0 0 0 _0 0 0 0 0 -" 0 0 -'-- -o 0 0 0 0 0 0 ,0 0 0 0 0 _ WW LAG - 8.52 - 0 = 0 v'0 "0 VWWIL 0.143 0.550 0.330 0.330 =-0:091 0.032 "0:989. ._sue w W w w _9.57 4.15 15.95 9.57 9.57 ,.2 0.93 _`„28:68 Z59 16.20 22.70 8.52 _y1.64 31 1.69 _ 0: „_0 0 0 0 0 _---___0 28 0 0 0 0_ _�TO 28 '00-28 „17.20.1 _.e._._.!0 0 0 0 0 ------0 26 0 0 0 0 _~-.,70 47 =._0 0 0 0 0 0 0 0 0 ==- o 28 � _0 - _0 0 0 0 0 -_0. 26 _ _.- 0 0 0 0 0 -o 47 P`� C ;F._:__ -- =;0 28 !--28 6 c)AED excursion -10 2 Envelope loss/gain 459 182 26 45 12 a) Infiltration b) Room ventilation 127 0 34 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 586 216 26 45 14 15 Less external load Less transfer RedslAbution Subtotal Duct loads 381/6 48% 0 0 0 586 '222 0 0 0 216 104 38% 48% 0 0 0 26 10 0 0 0 45 22 Total room load Air required (cfm) 808 40 320 15 36 2 67 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed 2020Jan31 08:49:43 ftie,Estaite2 Universal mp C 1 =MJ FrontDU23828 Page3 ...010AGR\Lot22B1k77-9lntlianftiverEslate2010AGR.rup CaIc=MJB Front Door laces: E 'DEL: AIR mmwa•�m co�mmolmio Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Far: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot 22 Block 77-9 Indian Riv... Date: By: M.DAVIS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area STUDY 10.0 It 8.0 ft heat/cool 10.0 x 12.0 if 120.0 W FOYER/DINING 13.0 It 8.0 It heat/coal 14.0 x 12.0 It 168.0 W Ty Construction number U-value (Btuhiftz*F) Or HTM (Btut✓ft°) Area (ft') or perimeter (it) Load (Btuh) Area (W) or perimeter (fit) Load (Btuh) Heat C0o1 Gross N/P/S Heat cool Grass N/P/S Heat Cool 6 11 ,W �-.^- 2.59 '8.52 Bll wall, stupco exlexl� 2A 20v-a_____ ;,67W n -4-19 -'9 57 4.15 9.57 9.57 17.40 `� 415 ;-9.57 -70 - 0 :. 0 .. 0 0 0 - ,0 _ 0 -0 0 , 0 0 __-___0 157 0 216 `0 353 -70 " ­0 0 0 0 0 284 -,--0 Elk wall, stucco ext 2A-20v 2A-20v 11.10 Blk wall„stucco ext- 2AZv' -0.330 0.143 0.330 0.330 0.600 "`-0.-143 -,0.330 _n_ a a a a 2.59 21.17 9.21 17.58 '' '-259 80 0 23 0 ""� ; 0 -0 57 0 22 _ 0 - -0 235 0 224 0 146 0 216 0 -0 104 0 23 20 -0 60 0 22 20 -0 251 0 224 35 -, 's' ._s., w w w w =; - -;'_ 0 0 0 ""--"O -"0 w--"�6 0 WWW Blk wall, stucco ext 10Gv 2A-20v 2A-20v 12C Osw,ry� 168-30ad 32A.ipl,_ 0.143 0.550 0.330 0.330 ��0,091 0.032 _ :0:989 4.15 15.95 9.57 9.57 �,2 64 0.93 : ,28.68 -_8.52 2.59 16.20 2P.70 . 8.52 ��7.31 1.69 ._.D,00 -, 0 0 0 0 0 _ 120 .,,^=120 -0 0 0 0 0 --0 120 "'�10 0 0 0 0 '-0 111 =267'_.-`-'-�0 -d_-0 0 0 0 0 �--0 ..,_._0 0 0 0 0 __0 0 0 0 0 0 0 0 0 156 � '._373 P C _ Fes" e" 203 168 "�f68 __ 168 �' 13 I 6 c)AED excursion .40 -57 Envelope loss/gain 857 525 1374 963 12 a) Infiltration b) Room ventilation 181 0 48 0 235 0 62 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 300 1 230 0 Subtotal (lines 6to 13) 1038 873 1610 1255 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 38% - 48% 0 0 0 1038 394 0 0 0 873 421 389/6 48% 0 0 0 1610 611 0 0 0 1255 605 Total room load Air required(cfm) 1431 71 1294 60 2220 tit 1860 86 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed -r.► wrlghtvoR= 2020-Jan-31 08:49:43 RierEst ite2OiOAGrsal .rup 919.0.12 Front U23828 Page4 ...010AGR\Lot22D1k77-9lndianRiverEstate2010AGR.rup Calc = MJB Front Door faces: E iRDEL-AIR Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2865 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot 22 Block 77-9 lndlan Rlv... Date: By: M.DAVIS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area LIVING 17.0 If 9.6 It heat/cool 1.0 x 484.5 If 484.5 f1' KITCHEN/NOOK 13.0 It 9.9 It heat/cool 1.0 x 258.0 It 258.0 fR TY Construction number U-value (BtuIVfR°F) Or HTM (BtUMV) Area Inn or perimeter (It) Load (Btuh) Area (ftq or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W"'. I—C Blkwall;slucco exf 2A-2ov v 0.143 „_0.330 n' _n_. : 415 _957 '2:59 _8.52 "'0', 0 = 0 ._.,,�_O - 0—ro '.0 „�._0 0 ___0 0— _01.,.__ 0—' 0 11 Blk wall, stucco a# 2A-20v 2A-20v 11J0 B wall, stucco ext; '2A 2ov _ _ Elk wall, stucco ext 10C-v 2A-2ov 2A 20v 12C-05w__......�....: 168-30ad 0.143 0.330 0.330 0.600 —0.143 __,-,-_0.330 0.143 0.550 0.330 0.330 ..._.___0.091 0.032 __0.989 a a a a s _s_ w w w wJ - 4.15 9.57 9.57 1740 . A 15 ,�.9 57- 4.15 15.95 9.57 `_ _9 57 .264 0.93 259 21.17 9.21 17.58 • 259 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 , 0 0 0 0 0 0 0 0 0 0 0 0 0 --0 0 0 0 0 0 `-0 0 —,0 ;.__0 0 '0 , O . 0 .0 0 —0 ,_,-e8.52 259 16.20 22.70 8.52 ._:. 1:31 1.69 p:00 135 0 0 33 103 0 0 ,____ 33 _,.._� ^�0 559 428 0 0 313 — _ 0 _ 519 ,� "_ 488 __ 267 0 0 279 ..0 944 104 18 33 ,___0 _.=._._0 305 =258 53 18 1 0 W.__. .0.Z�_..�.0 305 3 „_,__ 222 285 313 ,_, �0 283 `=373 _e_o 138 289 742 _0 =— 0 515 : 0 P.,_..._ ..� C _._� _ 0 559 1._485..17 :`.''__28:68 ___0 6 c) AED excursion 488 971 Envelope loss/galn 1747 1978 1475 2656 12 a) Infiltration b) Room ventilation 308 0 82 0 235 0 62 0 13 Internal gains: Occupants @ 230 Appliances/other 2 460 600 0 0 1200 Subtotal (lines 6 to 13) 2055 3120 1710 3918 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 38% 48% 0 0 0 2055 779 0 0 0 3120 1504 38% 48% 0 0 0 1710 649 0 0 0 3918 1888 Total roam load Air required(cfm) 1 '2834 141 4624 214 2359 118 5806 269 Calculations approved by ACCA to meet all requirements of Manual J Sth Ed -rI&'-",w�o9�'��,�- 2020-Jan-31 08:49:43 - Right -Suite® Universal 9 19.0.12 Front D Page 5 ...010AGR\LOt226Ik77-9lntlianRiverFsfate2010AGR.rup Cale=M11J8 Front Door faces: E g�.DEL.AIR Right-J® Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot 22 Block 77-9 Indian Riv... Date: By: M.DAVIS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area UTIL 0 it 8.0 it heat/cool 6.0 x 12.0 it 72.0 IP BDRM 3 14.9 it 8.0 it he@Ycool 1.0 x 198.0 It 198.0 it - Ty Construction number U-value (BtutrItz*F) Or HTM (BtU✓ft2) Area (ft� or perimeter (it) Load (Btuh) Area (ft2) of perimeter (It) Load (BWh) Heat I Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 - Blk w I, stuccoext 0.143 --0.330 `n _.n_ , , 9.57, — 259 ;_8.52 .,._..».0 -�_�,0'--_, — 0 10 " 0 ._,=,_. 0 "-0 0 120 --16 104 —0 430 56 288 �139 11 V Blk wall, stucco ext 2A-20v 2A-2ov 11,10 Blk wall; stucco exl 2A 2ovv� w Blk wall, stucco ext 10c-v 2A-2ov 2A-2ov ,12C 30ad ._-_„„,,.,_..�..:0.032 16B-30ad '22A Ipl_�_-_, 0.143 0.330 0.330 0.600 "' D 143's: a a a a _a_, w w w w .. - __ 4.15 9.57 9.57 1740 415 5,Z 2.59 21.17 9.21 17.58 —'Z59 8.52 ' 0 0 0 0 0 0 0_ 0 0 --0 0 �-0 0 0 0 0 --0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D "-70 • ' 0 ,0 —0 1��M11 _0.330 0.143 0.550 0.330 0.330 0,032 i0.989 ,.-_,-9 4.15 15.95 9.57 9.57 �.,�2 64 0.93 �28'68 , 2.59 16.20 22.70 8.52 „,. `1.69 i.fi9 `0.00 0 ' .�72 72 72 0 0 0 0 0 0 0_ _�;�,_,.72 72 ____.o 0 0 0 -.-. 0 _„�_ 127 _67 ___0 --0 0 0 0 0 --o 0 0 0 0 „..„198 198 ___198 0 0 0 0 --_„__198 198 �"""=15 —0 0 0 0 0 184 184 �428 —0 0 0 0 0 _.335 3'0 ^�0 P.�._,. C F;� 122 122 D 6 c)AED excursion -34 -55 Envelope loss/gain 193 ISO 1483 829 12 a) Infiltration b) Room ventilation 0 0 0 0 271 0 72 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 600 0 0 300 Subtotal (lines 6 to 13) 193 750 1754 1201 14 15 Less external load Less transfer - Redistribution Subtotal Duct loads 389/6 480/6 0 0 0 193 73 0 0 0 750 362 38% 489/6 0 0 0 1754 665 0 0 0 1201 579 Total room load Air required(cfm) 1 267 13 1112 51 2420 121 1760 82 Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed ,C -pj� wr YBhisoTe� 2020-Jan31 08:49:43 Right -Suite® Universal 2019 19.0.12 RSU23828 Page 6 ...010AGRtLot22BIk77-9lndianRiverEstate2010AGR.rup Calc=MJ8 Front Doorfaces: E '1 DEL:AIR Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC �531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIFI.COM Job: Lot 22 Block 77-9 Indian Riv... Date: By: M.DAVIS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BATH 6.0 It 8.0 it heat/cool 10.5 x 6.0 It 63.0 ft- BDRM 2 28.5 It 8.0 It heat/cool 13.5 x 15.0 ft 202.5 IF Ty Construction number U-value (Btuh/ftL'F) Or HTM (Btuh/ftq Area (ft-) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Grass N/P/S Heat Coal Grass N/P/S Heat Cool 6 W""" L--G "Blk wall; stucco ext 2A.2ov' -�-0:143 0.330 �0.143 n - _,ri_ ' 4.0 ,_-_;9.57, "-`2.59 pff52 `-" 48 -0 - 48 �_0 -199 -0 "-124 -0 - 120 ,.�.-�0 - 120 0 498 D -311' -0 11 W,�G I-C BIk wall, stucco ext 2A-20v 2A-20v 11,10 k wa t' -BIll, sfuccoex 2A 204._ BIk wall, stucco ext 10C-v 2A-2ov 2A-2ov 120,0i -__. 16B30ad ?9A t�l ,.""-`_"'.� 0,330 0.330 0,600 -0.143 _0.330 0.143 0.550 0.330 0.330 ......=:.0.091..' 0032 .` :0.989 e a e a sF : _s_ w w w w ,;,_, = 4.15 9.57 9.67 1740 - 415 __957- 4.15 15.95 9.57 9.57 .=2.64 �, 093 ----.28 68 2.59 21.17 9.21 17.58 -'-`2.59 _, 8,52 2.59 16.20 22.70 8.52 =.31 -�1.69 b:00. 0 0 0 0 --o -__._p 0 0 0 0 =-=0 63 -1-63 0 0 0 0 0 0 0 _0 -, 0 -'.0'�„0 0 0 0 0 0 58 _.� 172 0 0 0 0 --o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �p VA'� L-C _o --0 0 0 0 0 ==0 _ 63 ;=-_._ 0 , • 0 0 0 0 0 1��M11 0 0 0 0 ;,._=0 106 =_0 108 0 16 0 .=0 92 0 1 0 ____0 203 :, -�;,,29 -`__0 380 0 156 0 =1=0 _,__,0 237 0 371 0 =0 342 _.� 0 ^ P C _ ,F,;. 203 -203 188 ��817. 6 c)AED excursion _11 141 Envelope loss/gain 430 219 2039 1402 12 a) Infiltration b) Room ventilation 109 0 29 01 1 516 0 137 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 300 Subtotal (lines 6to 13) 538 248 2555 1839 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 1 38°/ 48%1 0 0 0 538 204 0 0 0 248 120 38% 48% 0 0 0 2555 969 0 0 0 1839 886 Total room load Air required (cfm) 742 37 368 17 3524 176 2725 126 Calculations approved by ACCA to meet all requirements of Manual J Sth Ed -rid wrLgtitno�tt_ 2020Jan.31 08.49:43 RightSuiteO Universal 2019 19.0.12 RSU23828 Page 7 ... Calc - M.18 Front Door faces: E QDEL--AIR Duct System Summary Job: Lot 22 Block 77-9 Indian ... RFMG • IVB 001IDIII0aQ10 Date: Entire House By: M.DAVIS DEL AIR HTG, A/C & REFRIG. INC 531 CODI BCD WAY, SANFOR D, FL 32771 Phone: 407-333-2665 Fax: 407J333853 Web: WWW.D ELAI R.COM Project Information For: ADAMS HOMES 5611 Spruce Drive, Fort Pierce, FL 34982 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.165 in/100ft 1167 cfm Cooling 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.165 in/100ft 1167 cfm 146 it Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mail Actual Ln (ft) Ftg.Egv Ln (it) Trunk BATH h 742 37 17 0.300 4.0 Ox0 VIFx 9.9 70.0 BDRM 2 h 3524 176 126 0.276 7.0 Ox0 VIFx 16.8 70.0 BDRM3 h 2420 121 82 0.315 6.0 Ox0 VIFx 6.1 70.0 FOYERIDINING h 2220 111 86 0.223 6.0 Ox0 VIFx 22.7 85.0 st1 KITCHEN/NOOK C 5806 118 269 0.221 9.0 Ox0 VIFx 23.5 85.0 st1 LIVING c 4624 141 214 0.217 8.0 Ox0 VIFx 25.6 85.0 st1 M. BATH h 1711 85 41 0.174 6.0 0x0 VIFx 38.1 100.0 st2 M. BDRM h 3896 194 184 0.173 8.0 Ox0 VIFx 38.6 100.0 st2 M.IWIC c 67 2 3 0.178 4.0 0x0 VIFx 34.7 100.0 st2 M.owlc h 80 40 15 0.170 4.0 OxO VIFx 4.1 100.0 st2 M. VIC h 113 56 19 0.165 4.0 Ox0 VIFx 4 .8 100.0 st2 STUDY h 1431 71 60 0.211 6.0 Ox0 VIFx 28.6 85.0 sit UTIL C 1112 13 51 0.315 1 5.0 Ox0 VIFx 6.1 70.0 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) MITI FR (fpm) (in) (in) Material Trunk st1 Peak AVF 820 890 0.165 638 16.0 0 x 0 VinlFlx st2 Peak AVF 378 262 0.165 482 12.0 0 x 0 VinlFlx St1 i Wrightsoft• 2020Jan31 08:49:44 •W+•� • w•--.d.... Right -Suite® Universal 2019 l9.0.12 RSU23828 Page 1 XA...010AGR1IA122Blk77-9lndianRiverEstate2010AGR.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rbt Ox0 1167 1167 0 0 0 0 Ox 0 VIFx 'r wrightsaft- 2020Jana108:49:44 •---r-�••--..-+, Right -Suite® Universal 2019 19.0.12 RSU23828 Page 2 ACCK ...010AGR\Lot22Blk77-9lndiwRiverEstate2010AGR.rup Cale -Md8 Front Door faces: E 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 22 Block 77-9 lndianRiverEstate 2010 AGR Builder Name: ADAMS HOMES Street: 5611 Spruce Drive Permit Office: City, State, Zip: Fort Pierce , FL , 34982 Permit Number: Y Owner: Jurisdiction: 661000 U = Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be seated. Ceilinglattic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space ,II I walls Exposed earth in unvented crawl spaces shall be covered with) Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to I exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities) cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spa s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and Wring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind ninina an wirino Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication extedorwalls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be I sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire snrinkler cover nigtes and walls or callinos. a. In aodnion, Inspection of log walls shall be In accordance with the provisions of ICC-400. 1/31/2020 9:13 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 FORM R405-2017 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the residential Simulated Performance Method shall include: ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst -case orientation, name and version of the compliance software tool, name of individual completing the compliance report (one page) and an input summary checklist that can be used for field verification (usually four pages/may be greater). ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO for the Performance Method: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) i I ❑ A completed Envelope Leakage Test Report (usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed Form R405 Duct Leakage Test Report (usually one page) 1/31/2020 9:12:39 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2017 Florida Building Code, Energy Conservation, 6th Edition Jurisdiction: 661000 Permit #: -Job Information Builder: ADAMS HOMES Community: Lot: NA Address: 5611 Spruce Drive City: Fort Pierce State: FL Zip: 34982 Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method ,0 PRESCRIPTIVE METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes.per.hounat a pressure of 0.2 inch w.g. (56 Pascals) in Climate Zones Land 2. O ,'PERFORMANCE or ERI METHOD -The building or dwelling unit shalllbe tested and verified as having an air leakage rate of not exceeding the selected ACH(50) value, as shown on Form R405 2017(Performance) or R406-2017 (ERI), sectionlabeled as: infiltration, sub -section ACH50. ACH(50) specified on Form R405-2017-Energy Calc, (Performance) or R406--2017 (ERI): Z000 x 60 _ 17286 — Method for calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans ❑ PASS • Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNETACC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or inr(dividuals licensed as set forth in Section 489.105(3)(f), (g), or (1) or ann�pproved third party. A written report of the results of the test shall be signed bj the party conducting the test and provided to thecode official. sting shall be performed at any time after creation of all penetrations of the b ilding thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 1 II 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 1/31/2020 9:13:55 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 6th Edition (2017) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods JiDDRESS: 5611 Spruce Drive Permit Number: Fort Pierce , FL , 34982 MANDATORY REQUIREMENTS See individual code sections for full details. J SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section 653.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. R402.4.1 Building thermal envelditim building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. R402.4.1.1 InstallationThe components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exceptiion: Testing is not required for additions, alterations, renovations, or repail - of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal Envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdreft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using Qght-fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. R402.4.3 Fenestration air IeakagcWindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 rim per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 1/31/2020 9:13 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such roams shall be sealed and insulated in accordance with the envelope requirements • of Table R402.1.2, where the walls, Doors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heal pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this wide and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNETlICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postmnstmction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturers air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Se4ldon 405 of this code. A written report of the results of the test shall be signed by the pal conducting the test and provided to the code official. ❑R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. �R403.4 Mechanical system piping insulation (Mandatary). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. El R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory)Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat tram temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when healed water is used in the occupancy. 1/3112020 9:13 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 61h Edition (2017) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. ` R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 1407 (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that dose when the ventilation system is not operating. ❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by an electronically commutated motor. ❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3• If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. 11 R403.7 Heating and cooling equipment (Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions forfuture expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested In accordance with HVI Standard 916 1/31/2020 9:13 AM EnergyGaugeO USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) n R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less L-� than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordancewith Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the IECC—Commerciat P�, visions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shuttinIq off the system when the pavement temperature is above 50"F (10'C), and not precipitation is falling and an automatic or manual fontrol that will allow shutoff when the outdoor temperature is above 407 (4.8)C). I I ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired healers shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. ❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. 1/31/2020 9:13 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5 0 R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A lest report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. ,f1 R403.11 Portable spas (MandatoryAe energy consumption of electric -powered portable spas shall be controlled by the LJ requirements of APSP-14. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps. Exception: Low -voltage lighting. R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights. 1/31/2020 9:13 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 6