HomeMy WebLinkAboutProject Information+ - wrightsoft Project Summary Date., Feb C6, 2020 Entire House By: QUICK CALCS, INC. 317 STLUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax M-46"796 Email: QUICKCALCS@AOLCOM Project• • For. BURNSADDITION 2805 N A1A, FORT PIERCE, FL Notes: Design• • Weather. Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 4414 Btuh Structure 5170 Btuh Ducts 603 Btuh Ducts 938 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh none Blower 0 Btuh Piping 0 Btuh Equipment load 5018 Btuh Use manufacturer's data n Rate/swing multiplier Equipment sensible load 0.95 6803 Btuh Infiltration Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3455 Btuh Ducts 247 Btuh Central vent (0 cfm) 0 Btuh Heatingg Coalingg (none) latent load 3701 Btuh Area (ft� 204 204 Equipment Volume (fts) 2040 2040 Air changes/hour 0.61 0.32 Equipment Total Load (Sen+Lat) 9504 Btuh Equiv. AVF (cfm) 21 11 Req. total capacity at 0.70 SHR 0.7 ton Heating Equipment Summary Cooling Equipment Summary Make Mitsubishi Electric Make Mitsubishi Electric Trade Mitsubishi Electric Trade Mitsubishi Electric Model MUZ-HM09NA2" Cond MUZ-HM09NA2* AHRI ref 201754644 Coil MSZ-HM09NA'" AHRI ref 201754644 Efficiency 8.5 HSPF Efficiency 12.0 EER, 18 SEER Heating input Sensible cooling 6300 Btuh Heating output 10900 Btuh @ 47OF Latent cooling 2700 Btuh Temperature rise 33 OF Total cooling 9000 Btuh Actual air flow 300 cfm Actual air flow 300 cfm Air flow factor 0.060 cfm/Btuh Air flow factor 0.049 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.62 Capacity balance point = 22 OF Backup: Input = 1 kW, Output = 4601 Btuh, 100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ -FW wrlg�hisofY 2020-Feb0616:42:13 •�^�� RightSuheB Lhniwmat 20l9l9.0.Oa RSLID8101 Page 1 �EADocurmetsMigMsoR WACIBURNS ADDITIONrup Cale=M.3 From Door races: E .+'F& WrightsoftRight-J® Worksheet Job: Entire House Date: Feb 08, zozo By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-0799 Fax T72466-6796 Ernst: OLnCKCALCSQAOL.COM 1 Room name Entire House BATH 2 Exposed wall 43.0 it 5.0 ft 3 Room height 10.0 it 10.0 it heaUccol 4 Room dimensions 8.0 x 5.0 ft 5 Roan area 204.0 W 40.0 ft- TY Construction U-\Glue Or HTM Area (ftj toad Ana (ftj lead number (BtLdVft;°F) (BtUWft2) or perimeter (it) (Btuh) or perimeter (ft) (Btuh) Heat Cod Gross N/P/S Heat Cool Gross WP/S Heat Cod 6 VN -12E-0sw '0.068 n. 1.90 1.18 140 122 - 233 -- - 145 - 0 0 0 0 2 glazing„dr lw ... 1.010 n.. __28.28 __15.01 _ . 18 0,-,-- 505 _ _.._ 258 -_--_0 _ _ .0 .._ 0 _ ,. _ , 0 _ W, .. 12E-0sw 0.068 a 1.90 1.18 130 110 209 130 0 0 0 0 2 damp. Gr lox 1.010 e 28 28 20 .. 0 � — 880 —__ 0 ._.__. 0 _ 0 _..�- 0 11 _ W 12E-0sw. .__ __ . _.. _ __ 0.088 _ _ _s_ _ .. _,.go �43.98 ..._T.18 .__ ...160 _ _. __., 160 _.305 . _. __-189 _ _- _?0 _ _ 50 95 .._ . 59 C 16X1g-0md _ 1.59 1.37 _.__323 279 _ 40 .___-40 ...__ - 63 _ _ .,, 55 _ _._ 2A1ph.._ . ..__0.408 ._ .. 1.358 _ ;. _.-.. . _... _ —38.02 .. : _ _ .0.00 _ _ _2D4 ,_ _. 204 __ ----204 ,_ .._ _43 _. . 1635 -0 . _ _ . 40 _ _._ _ 5 _ __.190 _ --.0 6 c)AED excursion 0 0 Envelope loss/gain 3776 1891 349 114 12 a) InFiltralion 638 179 74 21 b) Roan \mtilatim 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 3100 800 Subtotal (lines 6 to 13) 4414 5170 423 935 Less edema) load 0 0 0 0 Less transfer 0 0 0 0 Redstrilwtion 0 0 0 0 14 Subtotal 4414 5170 423 935 15 Duct loads 14% 18% 603 938 140/6 18% 58 170 Total room load 5018 6109 481 1104 Air required (Cfm) I I XG no 29 54 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -i-LF wrig�fCsofC- 2020-Feb-0616:42:13 - Right-Sufte® Unbersal 2019 19.0.08 RSW8101 Page 1 E:1Ducurmets\Wdghtsoft HVACWURNS ADDITION.mp Cale = MJB Front Door faces: E wr'ghtsofi Right-J@ Worksheet Date: Feb 06, 2020 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-066-6799 Fac 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC BEDROOM 2 Exposed wall 3.0 It 35.0 R 3 Roan height 10.0 ft hnallcod 10.0 It heal/coot 4 RONn dimenSiaus 5.0 x 6.0 It 'I.O x 139.0 It 5 Room an?a 25.0 ft2 139.0 ft2 Ty construction 11-value Or HTM Area (ft2) Load Area (ft2) Load number (Btulnfftz°F) (BtWft2) or perimeter (ft) (Btuh) or perimeter (ft) (8tuh) Heat I Cod Gross N/PIS Heat Cad Gross WPIS Heat Cod 8 12C--0sw 0.088 n � 1.90 1.18 30 30 ' 57 0 35 110 - —^92 0 -- -175 109 '_._258 . I�r V)I 2 glazing, dr lave 12E-0sw ___._. 1.010, 0.068 n___28.28 a 1.90 _ 15.01 1.18 _ 0_ 0 _v0_ 0 . 0 _0 0 .18.. 130 --- . i 110 -.505 209 130 —__ loge 1.010 a 28 28 43.98 0 0 a 20 0 566 880 ' _ _ 2 glazinn. cir _ _. __190 .....1.,18. . 0. _ 0 . __�.__ 0. _ _.0 _ _. 0-._ _ .._. __110__ _ ___._ 110 _ _.__209 -- _.... _130 C_ 16X19-0mtl 0.,408 1358 1.59 1.00 75 _ _ 25 _ _ _- 40 __ 34 _ __ _139 , _ 130 _ 220 _ _ 190 ;F _ , _ 2M4ph__. ....... _ _..... ..s. _ _ ,. , 38.02 _ O.Og _ _ ..25 _ . 3 . ji4 . ___.0 __ 139 .._,... ,_35 _. _ 1331 _ _._ 0 6 c)AED excursion 1 0 Envelope loss/gain 1 211 70 3218 1707 12 a) Infiltration 45 13 519 146 b) Room venfilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 1 Applianceslother 8W ISM Subtotal pines 6 to 13) `255 B82 3736 3353 Less e)dwd load 0 0 0 0 Less lmrefer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 255 882 3736 3353 15 Dud loads 14% 18% 35 160 14% 18% 511 809 Tom roorn load 290 1042 4247 3962 Air required (elm) 17 51 254 195 Calculations approved byACCA to meet all requirements of Manual J lath Ed. _ -FFF w_rlghfsoYe' 2020-Feb-0616:42:13 RightSufte® Unhemal 2019 19.0.08 RSU08101 Page 2 E:1DocunnetslWdghtsoRWAC%BURNSADDITIOUmp Calc=MJB Front Doorfaces: E 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: BURNS ADDITION Builder Name: Street: 2805 N A1A Permit Office: ST LUCIE COUNTY City, Stale, Zip: FORT PIERCE, FL, Permit Number: Y w Owner: Jurisdiction: ST LUCIE COUNTY = Design Location: FL, Fort Pierce v COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air-perneable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. requirements Breaks orjoints in the air barrier shall be sealed. The air barrier in any dropped ceiling/soffit shall be aligned with the The insulation in any dropped ceiling/soffit Ceilinglattic insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls Walls The junction of the top plate and the top of exterior walls shall be sealed. shall be insulated by completely filling the cavity with a Knee walls shall be sealed. material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between windowldoor jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air border shall be installed at any exposed edge of insulation. Floor framing cavity insulation shall be installed to (including maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation shall and cantilevered floors) be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottorr to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvenled crawl spaces shall be covered with a Where provided instead of floor insulation, insulation Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation Narrow cavities readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall Recessed tight fixtures installed in the building be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring ar plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind plying and whin . Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall be on exterior wall tubs shall separate them from the showers and tubs. insulated. Electricalfphone box on The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be sealed sprinklers in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover laces and walls or coilin s. a. In addition, inspection of log walls shall be in accordance with the provisions of IL; 00. 4/812020 9:35 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 2017 EPL DISPLAY CARD ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 81 The lower the Energy Performance Index, the more efficient the home. 1. New home or, addition 1. Addition 12. Ducts, location & insulation level a) Supply ducts R 2. Single-family or multiple -family 2. Single-family b) Return ducts R c) AHU location 3. No. of units (if multiple -family) 3. 1 4. Number of bedrooms 4. 1 13. Cooling system: Capacity 9.0 a) Split system SEER 18.0 5. Is this a worst case? (yes/no) 5. No b) Single package SEER c) Ground/water source SEER/COP 6. Conditioned floor area (sq. ft.) 6. 204 d) Room unit/PTAC EER e) Other 7. Windows, type and area a) U-factor:(weighted average) 7a. 0.911 b) Solar Heat Gain Coefficient (SHGC) 7b. 0.488 c) Area 7c. 37.8 8. Skylights a) U-factor:(weighted average) 8a. NA b) Solar Heat Gain Coefficient (SHGC) 8b. NA 9. Floor type, insulation level: a) Slab -on -grade (R-value) b) Wood, raised (R-value) c) Concrete, raised (R-value) 10. Wall type and insulation: A. Exterior: 1. Wood frame (Insulation R-value) 2. Masonry (Insulation R-value) B. Adjacent: 1. Wood frame (Insulation R-value) 2. Masonry (Insulation R-value) 11. Ceiling type and insulation level a) Under attic b) Single assembly c) Knee walls/skylight walls d) Radiant barrier installed 9a. 0.0 9b. 9c. 10A1. 19.0 10A2. 10B1. 10B2. 11a. 0.0 11b. 11 c. 11d. No 14. Heating system: Capacity 17.0 a) Split system heat pump HSPF 8.5 b) Single package heat pump HSPF c) Electric resistance COP d) Gas furnace, natural gas AFUE e) Gas furnace, LPG AFUE f) Other 15. Water heating system a) Electric resistance EF 0.99 b) Gas fired, natural gas EF c) Gas fired, LPG EF d) Solar system with tank EF e) Dedicated heat pump with tank EF_ 0 Heat recovery unit HeatRec% g) Other 16. HVAC credits claimed (Performance Method) a) Ceiling fans b) Cross ventilation No c) Whole house fan No d) Multizone cooling credit e) Multizone heating credit 0 Programmable thermostat No 'Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL display card will be completed based on installed code compliant features. Builder Address of New Home: 2805 N A1A City/FL Zip: FORT PIERCE. FL 4/6/2020 9:34:48 AM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1