HomeMy WebLinkAboutPursuit Boats - FINAL FIRE ALARM PERMIT DRAWINGS 12-21-19,,,
SHEET ROCK CEILING-� � / 3'-0"MIN.
L// N F.PA 72
24"MIN. HANDICAP (CURRENT EDITION)
BEDROOM STROBE
CEILING MOUNTED '
SMOKE/HEAT DETECTOR
SYNCHRONIZE AUDIO/VISUAL AND
MORE THAN � VIBUAL ONLY DEVICES
TWO APPLIANCES IN
ANY FIELD OF VIEW.
N.F.P.A 72
(CURRENT EDITION)
ANNUNCIATOR
ANNUNCIATOR
ENTIRE LENS BO"A.F.F, INSTALL AT 60"MAX TO TOP 5'-0"MAX
OR 6"BELOW CEILING
(WHICHEVER IS LOWER)
N.f.P.A 72 (CURRENT EDITION)
INSTALL AT 48" TO LEVER
MANUAL PULL STATION
qe"FORWARD REACH
54"ONSIDE APPROACH (ADA)
42" MIN. 54" MAX (NFPA 72
CURRENT EDITION)
TO THE HANDLE AF.F.
SECTION 5.73.4.
FINISH FLOOR
� CEILING FAN SHUTDOWN
M48 M47 M46 M45 M44 M43 M42 M41 M40 M39
g � � �
I-1 t-1 T-( r� r-1 r-1
I-%P LJP L� �I P P P 1
M29 M30 M31 M32 M33 M34 M35 M36 M37 M38
� � b � g � g �
T1 T-1 1--'1 T-1
L J I_I L"J uP I_I P
M28 M27 M26 M25 M24 M23 M22 M/p�21 M20 M19
DOS V '.
a WP M M M
P P `� p P P P P
M1D M11 M12 M13 M14 M15 M16 M17 M18
7�i
M09r
M08r M07
OM 6 MOSP
M04P OM 3
M02P '. MO1
75cd 75cd
75cd
75cd
18�[5'77cd
75cd
75cd
75cd
185cd
110cd 185cd 110cd
E.O.L.
CKT#2 n�r,��
� �
`r,
�
F.�I
�
�
�
� �i
2.027 AMPS VVVV
0-2-12 0-2-11
0-2-10
0-2-9
0-2-8
0-2-7
0-2.6
0-2-5
0-2-4
0-2-3 0-2-2 0-2-1
185cd
185cd
75cd
75cd
185cd
75cd
75cd
75cd
110cd 110cd 75cd
E.O.L.
A � it
�
�
�i
�i
J� 1i
�i
�
�
�i
� �i
1.984 AMPS VVVV
0-1-11
0-1-10
0-1-9
0-1-6
0-1-7
0-1-6
0-1-5
0-1.4
0-1-3 0-1-2 0-1-1
CELLULAR RADIO
TELGUARD - TG-7
'D^JO1�
Vp
FIRE ALARM
CONTROL PANEL
NOTIFIER
NFW-t 00X
SP 1ST FLOOR
ELEC ROOM 03
12ov �
TO DEDICATED 120V
20AMPS CIRCUIT BY
OTHERS
CEILING MOUNTED
A/C SUPPLY DIFFUSER SMOKE/HEAT DETECTOR
TOP OF WALL MOUNTED
SMOKE/HEAT DETECTOR
ACCAPTABLE HERE
REMOTE
ANNUNCIATOR
NOTIFIER N-ANN-80
GROUND #12
AWG THHN CU.
CONDUCTOR
DOOR WIDTH FINISH
LESS THAN 3" _
REMOTE POWER
SUPPLY
HONEYWELL
HPFF12
SP 1ST FLOOR
ELEC ROOM 03
12ov �
TO DEDICATED 120V
20AMPS CIRCUIT BY
OTHERS
RISER DIAGRAM
E: MEASUREMENTS
WN ARE TO THE
SEST EDGE OFTHE
ECTOR.
?A. 72 (CURRENT EDITION)
SH:I�1[7:ITT7.H7117y,
:HT.T�nll�
-DUCT DETECTOR
REMOTE TEST S WRCH
/INDICATOR
INSTALL AT 60" MAX TO TOP
FIRE ALARM NOTES
1. ALL NEW EQUIPMENT AND DEVICES SHALL BE NRTL LISTED FOR FIRE SERVICE AND SHALL BE
COMPATIBLE WITH THE EXISTING SYSTEM IN USE
2. ALL WIRING AND CONDUIT TO CONFORM TO N.F.PA. 72 AND N.E.C. ARTICLE 760. WIRING SHALL BE
SOLID COPPER OR STRANDED COPPER WITH A MAX. OF 7 STRANDS FOR t6 GA AND 18 GA, STRANDED
COPPER WITH A MAX.OF 19 STRANDS FOR S12ES 14 AND LARGER PER N.E.C. 760 AND N.F.P.A. 70.
3. ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED (NEC) METALLIC CONDUIT AND SHALL
BE SEALED WITH A U.L. APPROVED FIRE STOP MATERIAL. (SEE FIRE STOP DETAIL)
4. COLOR CODING MAY NOT APPLY TO EXISTING SYSTEMS. LABEL EXISTING WIRING ACCORDINGLY.
5. ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC ONLY, VERIFY EXACT LOCATIONS
PRIOR TO STARTING WORK:
6. ALL FIRE ALARM SIGNAL STROBES SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM.
7. ALL FIRE ALARM VISUAL SIGNALS IN OPEN AREA SHALL HAVE A THREE PLUS TEMPORAL PATTERN.
8. ALL FIRE ALARM AUDIBLE SIGNALS SHALL HAVE A SOUND LEVEL OF AT LEAST 15 dba ABOVE THE
AVERAGE ABMBIENT SOUND LEVEL.
9. MANUAL STATIONS TO BE INSTALLED AT 48" INCHES A.F.F.
10. MOUNT FIRE ALARM SYSTEM HORNISTROBES AT 30" A.F.F. OR 6" BELOW CEILING, WHICH EVER
iS LOWER.
11. MOUNT FIRE ALARM SYSTEM STROBES AT 60" A.F.F. OR 6" BELOW CEILING
WHICH EVER IS LOWER.
12. SMOKE DETECTORS TO BE INSTALLED AS REQUIRED BY N.F.P.A. 72.
13. THE FIRE ALARM PANEL MUST HAVE AN EARTH GROUND CONNECTION AS REQUIRED 8Y THE SYSTEM
MANUFACTURER, AND N.E.C. ARTICLE 760.
14. A GENERAL ALARM SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY PULL STATION, FLOW SWITCH
OR DETECTION DEVICE.
15. A TROUBLE SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF ANY DETECTION OR
MANUAL DEVICE.
16. A SUPERVISORY SIGNAL SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY FIRE SPRINKLER
SYSTEM TAMPER SWITCH.
17. HVAC DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM CONTROL PANEL AND
SHALL INITIATE A GENERAL FIRE ALARM.
18. FIRE ALARM SYSTEM SHALL BE U.L. CERTIFIED.
19. FIRE ALARM CIRCUITS AND DEVICES SHALL BE CLASS "B", STYLE "C".
20. SECURITY LOCK SYSTEM (BY OTHERS) SHALL BE TIED INTO FIRE ALARM SYSTEM. EMERGENCY EXITS
SHALL UNLOCK UPON RECEIPT OF ANY FIRE SIGNAL OR LOSS OF PRIMARY POWER.
21. PROVIDE CERTIFICATE OF COMPLETION AT THE FINAL INSPECTION OF THE FIRE ALARM SYSTEM.
22. FIRE ALARM CONTRACTOR SHALL PROVIDE A DETAILED SEf OF SHOP DRAWINGS (INCLUDING DEVICE
CUT SHEETS), A COMPLETE POINT TO POINT WIRING DIAGRAM, FLOOR PLAN DRAWINGS INDICATING
ALL DEVICE LOCATIONS AND NUMBERS, COMPLETE BATTERY CALCULATIONS AND COMPLETE
NOTIFICATION APPLIANCE CIRCUIT CALCULATIONS (FOR THE SYSTEM TO BE INSTALLED) TO THE
BUILDING DEPARTMENT (AUTHORITY HAVING JURISDICTION) AT THE TIME OF APPLICATION FOR
BUILDING PERMIT.
23. PROVIDE THE OWNER WITH A COMPLETE FIRE ALARM SYSTEM AND INSTALLATION MANUAL COVERING
MANUAL COVERING ALL SYSTEM EQUIPMENT INSTALLED FOR THIS PROJECT. KEEP AT THE MAIN FIRE
ALARM CONTROL PANEL.
24. ALL DOCUMENTATION WILL BE LEFT ON SITE INSIDE THE DOCUMENT ENCLOSURE LOCATED NEXT
TO THE FRCP.
135cd 185cd 135cd 185cd 135cd 135cd' 185cd 185cd 185cd 185cd
��i �i r�,..H- r�i �i � � � � n���� E.O.L.
1-4-1 1-4-2 1-4-3 1-4-4 1�-5 1-4-6 1.4-7 1-4-8 1-4-9 1.4-10 VYVV� p,4 6AMPS
13p5cd 185cd 135cd 185cd 135cd 185cd 185cd 185cd 165cd 13c57cd
SrYI1�_- fkf 1� R� 1� �i rt-Ir � �A n it � � it E.O.L.
1-3�-1 1-3�-2 1-3-3 1-3-4 1-3-5 �1-3-6 1-3-7 1-3-6 1-3-9 1-3-10 VYVV4� p,416AMPS
18p5cd 185cd 185cd 115cd 115cd 115cd 185cd 75cd 185cd
J5�1�i T� ,fin ,fin. �h Ili �i Ili n � � A � E.O.L.
1-2-1 1-2-2 1-2-3 1-2-4 1-2-5 1-2-6 1-2-7 1-2-8 1-2-9
VVVVV" 2,055 AMPS
185cd 185cd 135cd 135cd 135ed 135cd 115cd 115cd 115cd 115cd 115cd 115cd 75cd
�R4r� �i � �, r�, � A� �h ,�. � nli�il� CKT#1
1-1-1 1-1-2 1-1-3 1-1-4 1-1-5 1-1-6 1-1-7 1-1-8 1-1-9 1-1-10 1-1-ti 1-1-12 1-1-13 VYVVV 2.719AMPS
WIRE SCHEDULE
1O 2#14THHN
0 2#12THHN
O3 16/2 FPLR
GROUND #12
AWG THHN CU.
CONDUCTOR
FIRE STOP PENETRATION DETAILS
1. WALL ASSEMBLY
THE i, 2, 30R 4 HOUR.FIRE RATED GYPSUM WALL BOARDS/STUD WALL ASSEMBLY
SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE
INDIVIDUAL U300 OR U400 SERIES WAIL OR PARTITION DESIGN IN THE Ul FIRE
RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION
FEATURES.
A sTuos
- WALL FRAMING MAV CONSIST OF EITHER WOOD STUDB (MAXIMUM 2 HOUR FlRE
RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST ON NOM
2X41n. LUMBER SPACED IN 78In. OC (On Center) WIT (Welghq NOM (Nominel) 2X4In.
LUMBER, PLATES AND CROSS BRACES. STEEL STUDS TO BE 3-38fn. WIDE BY t-3/B IN.
DEEP CHANNELS SPACED A MAXIMUM 24In. OC.
B. WALLBOARD GYPSUM
- NOM t/pOR 3/6 in. THICK, 40. WIDE WRH SQUARE OR TAPERED EDGE. THE GYPSUM
WALL BOARD RYPS, THICKNESS, NUMBER OF LAYERS, FASTENER TYP AND SHEET
ORIENTATION SHALL BE SPECIFIED IN THE INDIVIDUAL U3000R U400 SERIES DESIGN
IN THE UL FIRE RESISTANCE DIRECTORY. MAX. DIAMETER OF AN OPENING IS 73-t/21N.
2. PIPE OR CONDUIT
-NOM 72in. DIAMETER (OR SMALLER) SCHEDULE 70 (OR HEAVIER) STEEL PIPE NOM
eln. DIAMETER (OR SMALLER) STEEL CONDUIT, NOM 41n. DIAMETER (OR SMALLER)
STEEL (OR SMALLER) FlE%IBLE STEEL CONDUIT. WHEN COPPER PIPE OR FLEXIBLE
STEEL CONDUIT IS USED, MAX. "F" RATING OR FIRE STOP SYSTEM (ITEM STRUTTED
USING STEEL CHANNEL STUDS). A MAX. OF ONE PIPE OD CONDUIT IS PERMITTED IN
THE FLRST STOP SYSTEM, PIPE OR CONDUIT TO BE INSTALLED NEAR CENTER OF
STUD CAVITY AND WIDTH TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL
ASSEMBLY.
3. FILL, VOID OR CAVITY MATERIAL
-CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BEI WEEN
PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MINIMUM i/41N. DIAMETER
BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUR AT ITS EGRESS FROM
THE WALL CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF THE WAIL
ASSEMBLY. RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN
THE FOLLOWING TABLE. THE HOURLY RATING OF TNE'T RATING OF THE FIRE STOP
SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE
HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS
TABULATED BELOW:
-WHEN COPPER PIPE IS USED, T' RATING IS 0 NOM MINNESOTA MINING & MFG. CO.
TYPES CP•25N/S, CP-25WB, CP-25W0+(NOTE: "L° RATINGS APPLY WHEN TYPE
CP-25W5+CAULK IS USED). ,
MAXIMUM PIPE ANGULAR °F" 'T'
OR CONDUIT SPACENN RATING RATING
INCH DIAMETER INCHES HOUR HOUR
i OT03/76 tOR2 D+tOR2
1 tl4 TO 1/2 30R4 30R4
4 OTO t/4. 70R2 0
8 t/4 T01/2 30R4 0
72 3/78 T03/B tOR2 0
SYSTEM N0. UL 1001 (FORMERLY SYSTEM NO. 147)
"F"RATINGS - i, 2, 3, AND 4 HR (SEE ITEMS 2 & 3)
"7" RATINGS • 0, t, 2, 3, AND 4 HR (SEE ITEM 3)
"L` RATINGS AT AMBIEM- LESS TNAN i CFM/ SQ. FT (SEE ITEM 3)
"L" RATING AT 400 FT "F"-LESS THAN t CFM /SQ. FT (SEE ITEM 3)
CONCRETE WALL
1/31NCH MAXIMUM
ANGULAR SPACING
6INCH DIAMETER
METAL PIPE /
3M FIRE BARRIER V ;
CP-25WP CAULK
i IN MINERAL WOOL
PACKING
WHEREVER APPLICABLE
CONC. WAIL
UL SYSTEM NO. CAJ7027
4 HOUR RATING
Ul SYSTEM CAJI0044
PENETRATION THROUGH CONCRETE WAILS
t HOUR FIRE RATED t/41NCH BEAD 3M
GYPSUM BOARD FIRE BARRIER CP 25
CAULK
6INCH DIAMETER
METAL PIPE
3M FIRE BARRIER
WHEREVER APPLICABLE P3-795 WRAP/STRIP
GYP. BOARD FRAMED WALL
UL SYSTEM N0. W11007
1 HOUR RATING
UI SYSTEM
PENETRATION THROUGH GYPSUM WALL BOARD
BO"AF.F. OR TO THE BOTTOM OF F L1
6"BELOW CEILING STROBE OR i -ll
(WHICHEVER IS LOWER) HORN/STROBE R �-
E '-�)
II
��
�I
��
�I
I
PULL STATION L�
46"A.F.F.
��J
ADA HEIGHT REQUIREMENTS
N.T.S.
ST. LUCIE COi1NTY FIRE DISTIBICT
��WEA FqR COMPL CF
w I1I3JECT TO FIELD ITVSP
SEE ATTAC�I? ��'ISI S� L� T
P.�i�y�OY: C �L C
Ira ��,: oT
CODES THAT APPLY TO THIS PROJECT:
2017 FBC
2014 NFPA-70
2015 NFPA-101
2013 NFPA-72
FLORIDA FIRE PREVENTION CODE 6TH ED.
13812
tng
\/ Tel (56
\\ email:
Registered
P.E. # 411
�e 91ne. ...� - .; '//
No 'I�IP,
i amo'rP,E. 'U==
al ngln' e�_/Of- ' 4f
�• ':L;.�
//nniu�((��
REVISION RECORD
REV DATE ISSUE DESCRIPTION
FIRE ALARM MANUAL PULL STATION
�P NOTIFIER-NOT-BG12LX
WP --':-MANUAL PULL STATION, WEATHERPROOF
P �IOTIFIER-NOT-BGI2LX W/STOPPER II COVER
\gHOTOELECTRIC SMOKE DETECTOR
Op � NOTIFIER-FSP-951
DUCT SMOKE DETECTOR
ODD �- NOTIFIER ONR W/FSP-951R
FACP FIRE ALARM CONTROL PANEL
NOTIFIER - NFW-100X
Rps REMOTE POWER SUPPLY
HONEYWELL-HPFF12
FSA FIRE ALARM SYSTEM ANNUNCIATOR
NOTIFIER - N-ANN-80
R FIRE ALARM HORN /STROBE COMBINATION
�( SYSTEM SENSOR-P2RL
FIRE ALARM HORN /STROBE, CEILING MOUNT
SYSTEM SENSOR-PC2RL
`O' FIRE ALARM STROBE
SYSTEM SENSOR-SRL
p FIRE ALARM FLOW SWITCH
o -, (FURNISHED BY SPRINKLER CONTRACTOR)
1 FIRE ALARM TAMPER SWITCH
Ol (FURNISHED BY SPRINKLER CONTRACTOR)
RT `-REMOTE TEST
NOTIFIER - RTSt 51 KEY
CR CONTROL RELAY MODULE
NOTIFIER - NC-1 OOR
MONITOR MODULE
NOTIFIER - NMM-t00P
SP SURGE PROTECTION DEVICE
KB KNOX BOX
FIRE AND SECURITY
SOLUTI�I�IS, INC.
3000 HIGH RIDGE RD. SUITE 9
BOYNTON BEACH, FL 33426
TEL (561) 588-9542
EF-20000304
L]J
FIRE AND SECURITY SOLUTIONS, INC
MANUFACTURING
BUILDING FOR
PURSUIT BOATS
3901 ST. LUCIE BLVD.,
FORT PIERCE, FLORIDA
FIRE ALARM PLANS
P.E.
FA-1
(°J NOTIFIER° . . -
e �
by Honeywell
NFW-100X Fire Alarm Control Panel
Protected Premises: PURSUIT BOATS Dad: 11/6/2019
Address: 3901 ST. LUCIE BLVD
City: FORT PIERCE State: FLORIDA Zip:
Prepared By: E&C ENGINEERS, INC. Phone:
Address: 13812 GERANIUM PLACE Email:
City: WELLINGTON State: FLORIDA Zip: 33414
Clear Project Information
AC Branch Current Requirements 3.20 AMPS @ 120 VAC check
Current required by source to power the fire
alarm system.
Primary Standby Load 0.04 Amps check
Current load on the primary power supply during
nonalarm conditions.
Primary Alarm Load 4.45 Amps check
Current load on the primary power supply during
alarm conditions.
Secondary Load Requirements 5.78 Amp Hours check
Total Secondary Load from the calculation table below.
- � • .
Secondary Standby Load Required Standby Time
0.184A x 24hours 4.42
Secondary Alarm Load
Re uired Alarm Time hours
4.716 A
x
0.084 hours 0.40
Total Seconds Load 4.82
r. usA c Canada Derating factor x 1.2
Secondary Load Requirements 5.78
AH
Battery Selection � Amp HOurs Check
' Select batteries from the list below.
7 AH BAT-1270 Batte 12 volt
C Two C' Four (two 12VDC sets in parallel)
�J NOTIFIERa
by Honeywell
�
.
� _
NFW-100X Fire Alarm Control
Panel
Quantity x [device
Cunent draw] =total
current
draw per device
(n amps)
°t
Main Circuit Board
x
0.00000
= 0.00000
x O.00o00
= O.DOD00
x 0.14100
= 0.141 DO
PWRMOD24
1
x
O.00D00
= D.o0D00
x
0.00000
= 0.00000
x O.Oo700
= 0.00700
P2RL75
10
x
O.D0000
= 0.00000
x
[0.13900
=1.39o0D
x 0.00000
= D.DOD00
P2RL110
4
x
0.00000
= D.00000
x
0.1820D
= 0.72800
x 0.00000
= O.DDDOD
P2RL7 85
6
x
D.00000
= D.DODOD
x
0.26200
=1.5720D
x O.ODODD
= 0.00000
SRL75
3
x
0.00000
= 0.00000
x
0.10700
= D.32100
x D.ODOOD
= D.D0000
N-ANN-80
1
x
D.D1500
= D.D150D
x
O.D400D
= 0.04000
x D.Dt 5DD
= 0.01500
FSP-951
2
x
0.00020
= O.00D4D
x
O.D000g
= D.000DO
x 0.00g20
= D.DOD40
NOT-BG12LX
22
x
D.D003B
= D.00825
x
O.000OD
= D.00000
x O.DD038
= 0.00625
NC-i OOR
12
x
0.00026
= 0.00306
x
O.00DOD
= O.000OD
x 0.00026
= 0.00306
DNR
3
x [0.00000]
= 0.00000
x [0.00000]
= 0.00000
x [0.00000]
= 0.00000
FSP-951R
3
x [0.00020]
= 0.00060
x (O.000OOJ
= 0.00000
x (0.00020J
= 0.00060
NMM-100P
15
x [0.00060J
= 0.00900
x [0.00000]
= 0.00000
x [0.00060J
= 0.00900
RTS151KEY
3
x [0.00000]
= 0.00000
x [0.00000]
= 0.00000
x [0.00000]
= 0.00000
Max Alarm Draw All Addressable Devt
1
x [0 OOOOOJ
0
00000
x [0 40000J
0 40000
x (0 OOOOOJ
0 00000
4 � �.I �
�J
,�
{
_
Total
(Amperes):
0,0363 A
4.4510 A
0.1843 A
Total Primary Alarm Load - C2
1
x [4.45100J
= 4.45100
Main Cimuit Board
1
x [0.25700J
= 0.25700
PWRMOD24
1
x [O.00BOOJ
= 0.00800
P , _ s
_.. �
�ar
... ,.,
Total
(Amperes).
4 7180 A
� �' Secondary Power Requirements
�' ' �; � ; � HPFF�2;Power Supply �?; Print Pege
Protected Premises: PURSUIT BOATS Date: 11(7/2019
Address: 3901 ST. LUCIE BLVD.
City. FORT PIERCE State: FL Zip:
Prepared By: EBLC ENGINEERS, INC. Phone:
Address: 13812 GERANIUM PLACE Email:
City: WELLINGTON State: FL ZIp: 33414
Clear Projectlnformation
Secondary Load Requirements 3.15 Amp Hours check
Total Secondary Load from the calculation table below.
� .
Secondary Standby Load Required Standby Time
0,075 A x 24 hours 1.80
Secondary Alarm Load
Required Alarm Time (hours)
9.812 A
x 0.084 hours
0.82
Total Secondary Load
2.62
<•' USA n Canada Derating factor
x 1.2
Secondary Load Requirements
3.15
AH
Battery Selection 0 Amp Hours check
Select batteries from the list below.
7.0 AH BAT-1270 Battery (12 voft)
r Two � Four (iwo 12VDC sets in parallel)
�" System Current Draw - HPFF12
Select devices using the !'Qty"column.
° I Use yellow cells to enterpuahtitie3 and cunentvalues i Pnnt Page ;
Standby 0.075 A Use the drop downs to select parts for NACcircuits L ._
Alarm 9.812A Toclearselectedtlevices,select "Clear3elections". � GearSelechons
1. S stem Modules
HPFF12MainCircuit8oard
1
x
0.07500
0.0750D
1
x
0.206D0
0.2D600
2. NAC #1
P2RL735
•
4
x
0.00000
0.00000
4
x
0.21100
0.8440D
P2RLt85
2
x
o.00000
0.00000
2
x
0,26200
0.52400
P2RL75
•
1
x
0.00000
O.000DO
1
x
0,13900
0.7390D
PC2RU15
•
6
x
D.00000
0.00000
6
x
0.20200
1.21200
o
x
o.00goo
o
x
D.D000D
•
0
x
0.00000
0
x
O.D000D
•'
0
x
O.D0000
0
x
O.000DO
•'
0
x
O.00D00
0
x
O.DODoO
NAC#1Totais ax3Am s):
D.000DD
2.7190D
3. NAC #2
P2Rg5
•'
1
x
O.000OD
0.00000
1
x
0.13900
0.1390D
P2RL785
•'.
5
x
0.00000
0.00000
5
x
0.262D0
1.310DD
PC2RL115
•'
3
x
O.DODOD
0.00000
3
x
D.20200
0.6D60D
o
x
D.00000
D
x
o.D0000
•'
0
x
O.DD000
0
x
D.000DO
•
0
x
O.000OD
D
x
O.DOODO
0
x
O.DDODD
0
x
O.D0000
•'
0
x
D.00000
D
x
O.000DO
NAC #2 Totals Max 3 Am s ;
0.00000
2.05500
4. NAC #3
PZRu35
•'
4
x
0.00000
O.D0000
4
x
D.211D0
0.84400
PZRLt85
•'
6
x
O.oDDDD
0.00000
6
x
0.26200
1.5720D
•'
D
x
D.DDDDo
D
x
D.D0000
o
x
o.0000D
o
x
o.D0000
•'
0
x
O.D0000
0
x
D.000DO
0
x
0.00000
0
x
D.DOD00
•
0
x
O.ODOOD
0
x
D.00o00
� !
0
x
0.00000
0
x
D.D0000
NAC #3 Totals {Mex 3 Amps):
O.D000D
2.41600
5. NAC #4
P2RL135
q
x
O.00DDD
O.000OD
4
x
0.21100
0.64400
P2RL785
6
X
O.00D00
O.D000D
6
X
0.26200
1.5720D
o
x
o.00000
o
x
o.00000
•''
o
x
o.a0000
o
x
o.00000
•'
- 0
x
O.00D00
0
x
O.DOD00
0
x
0.00000
0
x
O.D0000
I-'
o
x
D.00goo
o
x
o.00000
o
x
o.0000D
D
x
D.00000
NAC#4Totals Max3Am s):
O.DD000
2.4160D
6. Auxiliar Power
Auxiliary Device
0
x
O.00D00
0
x
D,D0000
Auxilia Device
0
x
O.D0000
0
x
0.00000
Auxili Device
0
x
O.ODOOD
0
x
O.D0000
Auxin Devica
o
x
D.00goD
o
x
o.00000
Auxiliary Device
0
x
OAOOOD
0
x
D.00000
TB4 Totals (Max 2 Amps):
0.00000
0.00000
7. Com atible Devices not listed
Othercom atible devices
0
x
O.D0000
0
x
oA0000
Othercom atibtedevices
0
x
0.00000
0
x
D.D0000
Othercom atible devices
D
x
0.00000
0
x
O.D000D
Total Non -Alarm Load:
0.075
Total Alarm Load:
9.812
THIS IS BASED ON A 24 VOLT SYSTEM ONLY
! j
! _
_
Point to Point Method
Project Name
PURSUIT BOATS
Calculations and allowable
wltage drop are based on
UL srandards 1971 & 464
CIRCUIT IS WITHIN LIMITS
Date
5/11/2019
_
___
Circuit Number
FACP NAC CKT #1
_
Totals
Voltage
__ _
may 2004 revisions
Area Covered
1st Floor
_
Current
Distance
Drop
_ _
Nominal System Voltage
20.4
I
j
1.964
532
2.90
___
_ _',
--
Minimum Device Voltage
16
_
j
End of Line Voltage
17.50
_ _ ___ __ _
I -
___ __ _ __I______
_
Total Circuit Cunent
1.984
Wire
Ohm's
',
Pement Drop
14.20
%
__
'
i
i
Gauge
Per 1000
End of Line method uses only the wire guage for the first device
to source for calculation
Distance from soume to 1st device
12
14
3.07
Standard Wire Resistance in Ohms per 1000 feet @ 75 C.
3.07
18 777' !16=489' ! 14=307 1.98E_10 124', I
Enter Device Type
Distance
j
I
_', __72
- ---- _
118-14 Awg =Solid Conductors 12-10 Awg =Stranded Conductors I
�
__
WHS cd, H, CHS cd Etc
from
Veltage
This circuit is soumed from: !, i i !
I !
At j Drop from I, Percent
Device
Enter
Device
previous
Number
Device Type
Current
device
Device ; soume ! Drop
Device 1
WHS 75
0.139
12
20.25
0.146
0.72%
Notes: ! i ' i ' I l i i
Device 2
WHS 110
0.182
30
20.25
0.148
0.73 %
_ __ __
Wire eisrstance is doubled in the calculations for two Positiw and Ne atiw
___' _
Device 3
WHS 110
0.182
70
19.54
0.863
4.23%
_wires
_ --(--------g----� -I
The wltage calculated to the last device in any method not be lower then 16 VDC
_must
Device 4
WHS 75
0.139
30
19.26
1.136
5.57 %
I
� !
Device 5
WHS 75
0.139
60
18.77
1.630
7.99%
_ _ i_�__ _ I ____ �I-_ __
No Current entered =device not offeretl at that candela
------
_
;
Device 6
WHS 75
0.139
25
18.59
1.815
8.90%
(, WHS i I WS ; CHS
CS j I WSS ! CSS
_
j
Devtce 7
WHS 185
0.262
45
18.29
2.109
1D.34%
i Wali I I Wall I Ceiling
� Hom �l Strobe ; Hom
,Strobe ( Only � Strobe
I i Ceiing I I __ Wall I I Celltng
;_j Strobe I Speaker ! S Baker
l I ; Strobe ; -Strobe -
Device 8
WHS 75
0.139
70
17.95
2.454
12.03%
- ---
i_
Device 9
WHS 75
0.139
30
17.82
2.576
12.63 %
Device 10
WHS 185
0.262
40
17.70
2.704
13.26 %
_
Candela
_I
% Cunent Rating
__ _Only ;_ _ _ _ _
for DC per data sheet
Device 11
WHS 185
0.262
120
17.50
2.897
14.20%
15
END
0.000
0
17.50
2.897
14.20%
15/75
END
0.000
0
17.50
2.897
14.20%
30
__ __
j
END
0.000
17.50
2.897
14.20%
75
0.139
0.107
__ _ _ __
�'
END
0.000
17.50
2.897
14.20%
95
_�__
END
0.000
17.50
2.897
14.20%
110
0.182
___ _ _
j
END
0.000
17.5D
2.897
14.20%
115
�
END
0.000
17.50
2.897
14.20%
135
0.211
-------------
j
END
0.000
17.50
2.897
14.20%
150
__
i
END
0.000
17.50
2.897
14.20%
177
j _
END
0.000
17.50
2.897
14.20%
185
0.262
_ _
END
0.000
17.50
2.897
14.20%
Hom Only
I
j
!
'
I
j_
j
I
___� __
j ;
_
END
0.000
17.50
2.897
14.20%
H1
_
II
_ _ _ _
i j
END
0.000
17.50
2.897
14.20%
H2
_
j
Totals
1.984
532
End of Line Voltage
17.50
H3
_
!
i
;
I
THIS IS BASED ON A 24 VOLT SYSTEM ONLY
I j
Point to Point Method
Project
Name
PURSUn BOATS
Calculations and allowable
wltage drop are based on
UL srandards 1971 & 464
ma 2004 revnslons
CIRCUIT IS WITHIN LIMITS
____ __
_
Date
5/11/2019
Circuit Number
FACP NAC CKT#2
_
Totals
Voltage
-(
Area Covered
1st Floor
-
Cunent
Distance
Dro
(- -
_
Nominal System Voltage
20.4
_ I �
_ _
2.027
385
2.84
_
j
L
Minimum Device Voltage
16
_ _
I-
End of Line Voltage
17.56
__
j
,
_
Total Circuit Cunent
2.027
Wire
Ohm's
Percent Drop
13.92%
_
j
j
Gauge
Per 1000
_ _End of Lin_ e_method uses only the wire_ guage for the first device
to source for calculati_o_n_
Distance from source to 1st device
100
14
3.07
__
Standard Wire Resistance in Ohms per 1000 fee__t @ 75 C.
3.07
__ __
j___ 114=3,07� � 12= I 10=1.24I, I
_ _j_(18=7.771.16=4.89 _9
_____ Enter Device Type _ __
.Distance_
I
18-14
Aw =Solid
Conductors 12-10
Aw =Stranded Conductors
WHS cd, H, CHS cd Etc.
Voltage_
This circuit
is sourced from: ! I
I ! i i I I I I
Device
Enter
Device
_from
previous
__
At
�Dropfrom:
__
Percent
Number
Device Type
Current
device
Device
I, source
; Drop
Device 1
WHS 110
0.182
100
19.16
1.245
6.10%
Notes_ I, ', ! ; � !_.-_ I ;
I
Device 2
WHS 185
0.262
5
19.15
1.248
6.12 %
_!,.i __
Wire resistance is doubled in the calculations for two wires (Positive and Negative)
j
Device 3
WHS 110
0.182
60
18.57
1.831
8.97%
The wltage calculated to the last deuce m any method must not be lower then 16 VDC
j__
Device 4
WHS 185
0.262
20
18.40
2.003
9.82 %
',_',_ � ; I I___ !___
_
_ _ _ ____I_i
,_
Device 5
WS 75
0.107
40
18.12
2.283
11.19 %
__ _ _
No Current entered =device not offered at that candela.
i'
_
j
Device6
WHS75
0.139
20
17.99
2.409
11.81%
( WHS j I WS j { CHS
i I CS I j__WSS LI CSS
Device 7
WS 75
0.107
20
17.88
2.519
12.35%
Wall ! WaII � ! CeilmO
� Ceiling I Wail I I Celhng
-
---
j -- --
Device 8
WHS 185
0.262
25
17.76
2.640
12.94%
Horn ; j Strobe I Hom
I Strobe � ! ; 'Strobe
Strobe S aker � I_ Speaker
I_ �__ Only f �__ Strobe
( _
!____-_-
Device 9
WHS 75
0.139
25
17.68
2.720
13.33 %
Device 10
WS 75
0.107
25
1 Z62
2.779
13.62 %
Candela
- .Only
Cunent Rating
_Strobe
for DC per data sheet
___
j
Device 11
WHS 75
0.139
25
17.58
2.822
13.83 %
15
_
Device 12
WHS 75
0.139
20
17.56
2.839
13.92%
15/75
__ -�--
I_
END
0.000
0
17.56
2.839
13.92%
30
j
END
0.000
17.56
2.839
13.92%
75
0.139
0.107
(
END
0.000
17.56
2.839
13.92%
95
j
END
0.000
17.56
2.839
13.92 %
110
0.182
____ ^
j
END
0.000
17.56
2.839
13.92%
115
_
I
END
0.000
17.56
2.839
13.92%
135
0.211
(
END
0.000
17.56
2.839
13.92%
150
;
END
0.000
17.56
2.839
13.92%
177
_
(__
END
0.000
17.56
2.839
13.92 %
185
0.262
______
____
END
O.00D
17.56
2.839
13.92%
Hom Only
i
I
I
I
;_;__
�
!
---
_.
END
0.000
17.56
2.839
13.92 /°
H1
,
i
I
_
_
END
O.00D
17.56
2.839
13.92%
H2
i
!
�
(!
!
_ _ _
-- -
Totals
2.027
385
End of Line Volta a
9
17.56
H3
I
l
i
I
I
I
i
I --
_
�.�.�i17.!�,Q���QLIQ
REVISION RECORD
REV DATE ISSUE DESCRIPTION
FIRE AND SECURITY
SOLUTIONS, INC.
3000 HIGH RIDGE RD. SUITE 9
BOYNTON BEACH, FL 33426
TEL (561) 588-9542
EF-20000304
FIRE AND SECURITY SOLUTIONS, INC
� , � �
� e ••-
■ � � • l
Cert. of t # 656a sneLocanoN
13812 er nl m Place
Wellin o , F 33414� ,'�.t�l� I � I `/� � 3901 ST. LUCIE BLVD.,
emeu: enytn ,rs,co` _ = '' t j��' FORT PIERCE, FLOR/DA
_ C.'= /i
� �~,. , nTIE
/ hlo �' �"'� �', * �= FIRE ALARM PLANS
r ' , tr '; E. SAMOUR, P.E. 11.05.19_j AS NOTED � 19
} i:. .rVC�\ NICET LEVEL SHEET NO.
- - :. ,.� °��e, FA-2
'id;`.�- JRH
Iliii el\�� CPDFlLE
THIS IS BASED ON A 24 VOLT SYSTEM ONLY
j
i
Point to Point Method
Project Name
PURSUIT BOATS
Calculations and allowable
wltage drop are based on
UL srendards 1971 & 464
may 2004 revisions
_
_
CIRCUIT IS WITHIN LIMITS
___
Date
5/11/2019
_
_---..__.____...___------i____..--_-..-
Circuit Number
RPS NAC CKT#1
Totals
Voltage
Area Covered
1st Floor
Distance
Drop
I
-- -
Nominal
System Voltage
20.4
-
I
�[
- -
_Current
-
2.719
810
3.47
_ -- --- --
Minimum Device Voltage
16
i
�_; _
_
End of Line Voltage
16.93
Total Grouit Cunent
2.719
Wire
Ohm's
!
� �
Percent
Drop
17.02%
_ __ _ _
Gauge
Per 1000
End of Line method uses only the wire
guage
for the first device
to source
for calculation
Distance from source to 1st device
40
12
1.98
--
Standard Wire Resis_ tance in Ohm__s_per 1000 feet @ 75 C.
3.07
_
i18 777 116 489� ' 14=3.07�_I 12=1.98 10 124i I
-Solid
Detice T e
Yp___
D_ista_nce
I
___ _
118-14 Awg Conductors 12-10 Awg =Stranded Conductors I
_ _Enter
___,. _ __ _
WHS cd, H, CHS cd Etc.
from
Voltage_
This circuit is sourced from: ' I I ! ! '
i '
Device Enter DeHce
--
prevnous
_ _ .. ---- __
At , Drop from l Percent
Number Device Type Current
device
Device ; source Drop
Device 1
WHS 185
0.262
40
19.97
0.431
2.11%
Notes:__I
i_I i ; I i I_' L__ i
Detice 2
WHS 165
0.262
80
19.97
0.433
2.12 %
_ __ _
Wire resistance is doubled m the calculations for two wires
(Positiw and Negative)
Device 3
WHS 135
0.211
30
19.71
0.694
3:40%
The wltage calculated to the last deuce in any method, must not be then_16 VDC
-- _
Device 4
WHS 135
0.211
70
19.16
1.244
6.10%
i
_
�_ ( , I
__
j
_lower
I I �
-- ----
',
i
DeHce 5
WHS 135
0.211
70
18.66
1.735
8.51 %
__
No Current entered = deuce not offered at that candela.
I
Device 6
WHS 135
0.211
70
18.23
2.168
10.63%
WHS
j__
WS ; CHS
' CS
I WSS j ; CSS
Device 7
CHS 115
0.202
70
17.86
2.543
12.47%
Wail
Hom
Strobe
!_�
'
j
Wall I ; Ceding
Strobe Hom
�,_ Oniy L Strobe
i I Ce16ng
I_',' Strobe
_ i Oniy
;
I__ Wali ! �- Ceding
.Speaker , 'Speaker
-- - --
i
�
Device 8
CHS 115
0.202
60
17.56
2.816
13.80%
Device 9
CHS 115
0.202
60
17.36
3.041
14.91 %
i_Strobe ; j Strobe
_ _____
'
_ _ _
,�
Device 10
CHS 115
0.202
60
17.18
3.218
15.77%
Candela
I Current Rating
_ _
for DC per data sheet
_ _ _----
Device 11
CHS 115
0.202
60
17.05
3.347
16.41 %
15
_ __ _ _ _ _
� _
Detice 12
CHS 115
0.202
60
16.97
3.428
16.80%
15/75
__
Detice 13
WHS 75
0.139
80
16.93
3.472
17.02%
30
_ _ ____
!_
END
0.000
16.93
3.472
17.02%
75
0.139
0.107
END
0.000
16.93
3.472
17.02%
95
___
END
0.000
16.93
3.472
17.02%
110
0.182
_ _ _ __
END
0.000
16.93
3.472
17.02%
115
0.202
_ _.. _
END
0.000
16.93
3.472
17.02%
135
0.211
'
END
0.000
16.93
3.472
17.02%
150
-- -._---
END
0.000
16.93
3.472
17.02%
177
_. _ _ _'-
i
END
0.000
16.93
3.472
17.02%
185
0.262
__ _
END
0.000
16.93
3.472
17.02%
Hom Only ;_
I
� '
�
'
I
i
END
0.000
16.93
3.472
17.02%
H1
_
i
' i
1
END
0.000
16.93
3.472
17.02%
H2>
_
,
;__ i
I
_
�
_
� �
i
_
_.
'-
Totals
2.719
810
End of Line Voltage
16.93
H3
I I
� I
�
_-
I
__
-
_
;
THIS IS BASED ON A 24 VOLT SYSTEM ONLY
___f
I
I_
_
Point to Point Method
Project Name
PURSUIT BOATS
Calculations and allowable
wltage drop are based on
UL smndards 1971 & 464
CIRCUIT IS WITHIN LIMITS
Date
5/11/2019
_
___ ____
Circuit Number
RPS NAC CKT #2
Totals
Voltage
Area Covered
1st Fiocr
may 2004_retisions
Distance
Drop
i
_ _
_Cunent
Nominal System Voltage
20.4
_)
�
_
_
2.055
840
3.62
- _ _- ---
Minimum DeHce Voltage
16
j
�
of Line Voltage
16.78
_ _ _
__�__
__
_End
Total Circuit Current
2.055
Wire
Ohm's
!
�
Percent Drop
17.75%
__ __ ___
'
I
I
Gauge
Per 1000
End of Line method uses only the wire guage for the first device to source for calculation
-- .__ _____-_ _____ ___.____.._ ._
Standard Wire Resistance in Ohms per 1000 feet @ 75 C.
Distance from source to 1s t device
240
12
1.98
3.07
- - - -- -- ----
j18 777 j16 4891 14=3A7 � 12=1.98 ( 10 1.24', I
____ __ Enter DeHce_Type __
Distance_
18-14 Awg =Solid
Conductors 12-10
Awg =Stranded Conductors
WHS cd, H, CHS cd Etc.
from
Voltage
This circuit is sourced from: ! I i ' I I ! !. '
Device Enter Device
prewous_
__
At i _
__ _ _Drop from Percent
Number Detice T e Cunent
yp
device
_
Device ! source Dro
Device 1
WHS 185
0.262
240
18.45
1.953
9.57%
Notes: I (_' i ', I i j
1_ _',
Wire resistance Is doubled m the calculations far two wires (Positiw and Negative)
DeHce 2
WHS 185
0.262
80
18.45
1.955
9.58 %
Device 3
WHS 185
0.262
80
17.96
2.440
11.96 %
_ _
The wltage calculated to the last deuce in any method must not be lower then 16 VDC i
Detice 4
CHS 115
0.202
65
17.63
2.767
13.56%
1 i i ; ' !
� - i
Device 5
CHS 115
0.202
55
17.40
2.999
14.70 %
_ _ _
No Cunent entered =device not offered at chat candela.
i '
i---'__._..._..
Device 6
CHS 115
0.202
55
17.21
3.187
15.62%
__LWHS
i j WS
I i_CHS
CS ; L CSS
i,
Detice?
WHS 185
0.262
70
17.03
3.371
16.53%
WaII
I j Wall
Hom _ Strobe
� Strobe
; Ceiling
I ; Hom
!J_Strobe
_WSS _
I Celhng � I Wall i ' Ceiling
�-� Strobe I ;Speaker i Speaker
I ; Only � I _Strobe '_;_Strobe_
for DC per data sheet
_
i -- --
_ ___
Device 8
WHS 75
0.139
85
16.89
3.506
17.19%
Device 9
WHS 185
0.262
110
16.78
3.620
17.75%
____I
__ __
' ___
END
0.000
0
16.78
3.620
17.75%
Candela
_Only
Cunent Rating
END
0.000
0
16.78
3.620
17.75%
15
_ _ __ _ ___
END
0.000
0
16.78
3.620
17.75%
15/75
__ _'_ _
END
0.000
0
16.78
3.620
17.75%
30
_
END
D.000
16.78
3.620
17.75%
75
0.139
0.107
END
O.ODD
16.78
3.620
17.75%
95
__ __I_ __ _
j
END
O.00D
16.78
3.620
17.75%
110
0.182
_
I
END
O.ODO
16.78
3.620
17.75%
115
0.202
__
i
END
0.000
16.78
3.620
17.75%
135
0.211
__
END
OA00
16.78
3.620
17.75%
150
r
END
0.000
16.78
3.620
17.75%
177
-----------------._.._
END
O.ODO
16.78
3.620
17.75%
185
0.262
�
END
0.000
16.78
3.620
17.75%
Horn Only
!
I
__
i
'
END
0.000
16.78
3.620
17.75%
Ht
!
--
...._-_
L___
END
0.000
16.78
3.620
17.75%
H2
i
i
1 ':_
_-__
I
.__
.. �--- ----
Totals
2.055
840
End of Line Voltage
16.78
H3
!
I
I
_
! �,
__
______
j
THIS IS BASED ON A 24 VOLT SYSTEM ONLY
; j
Point to Point Method
Project Name PURSUIT BOATS
Calculations and allowable
wltage drop are based on
UL srandards 1971 & 464
may 2004 revisions
_
CIRCUIT IS WITHIN LIMI_T_S_
Date
5/11/2019
Circuit
Number
RPS NAC
CKT
#3
Totals
Voltage
Area Covered
1st Floor
-
Cunent
Distance
Drop
--- -
I ;
Nominal System Voltage
20.4
I
2.416
870
4.07
I
Minimum Device Voltage
16
� ) i
End of Line Voltage
16.33
j �__
_ _ _ _
Total Circuit Cunent
2.416
Wire
Ohm's
Percent Drop
19.95%
_ __ _
, ____
I
i
i
Gauge
Per 1000
End of Line method uses only the wire guage for the first deN_ce to source for calculation
Distance from source to 1st device
140
12
1.98
Standard Wire Resistance m Ohms_per 1000 feet @ 75 C.
3.07
__
I j 18 777;_�16 4.89; !_14-3.07 I 12=1.98',1 10=1.24i- �--
_
___ Enter Device Type _ _^
- ----
Distance
-
I
118-14 Awg - Solid Conductors 12-10 Awg -Stranded
Conductors
I
WHS cd, H, CHS cd Etc.
from
Voltage
circuit
is sourced from: I ' ; I I
_ _
__ _ _ _ _ _
_Device _
Enter
Device
_previous
At
i Drop from
_This
Percent
Number
Device Type
Current
device
Device
� source
I Drop
Device 1
WHS 135
0.211
140
19.06
1.339
6.57%
Notes: i i
Device 2
WHS 185
0.262
70
19.06
1.342
6.58 %
_j _ _
Wire resistance is doubled in the calculations for two wires Positiw and Ne alive I
� A- �
DeNce 3
WHS 135
0.211
85
18.40
1.996
9.78 %
- --- - -- -
Th_e_w_It_age_ caicu__lated to the I_as_t device in__a_ny method must not be lo_w_ er then 16 VDC I
Detice 4
WHS 185
0.262
70
17.92
2.476
12.14%
i ! I -----�
i
--
'_
DeHce 5
WHS 135
0.211
75
17.49
2.912
14.28%
_ _ __I
No Cunent entered -device not offered at that candela.
Dev�ce6
WHS185
0.262
80
17.09
3.311
16.23%
I WHS ! ! WS i CHS I CS WSS CSS
''
_
i
_!--
DeHce 7
WHS 185
0.262
70
16.81
3.588
17.59%
� Wall i WaII � Ceiling i Celkng i ; Wall i I Ceding
i Hom i Strobe � j Hom I Strobe _Speaker ! __Speaker_
Stro_b_e ! Only Strobe i j Only Strobe I ;_ Strobe____
__
_ j __ ___ _
DeHce 8
WHS 185
0.262
80
16.58
3.820
18.73 %
_
DeHce 9
WHS 185
0.262
80
16.43
3.970
19.46%
__
__
_; _
;
Detice 10
WHS 135
0.211
120
16.33
4.071
19.95 %
Candela
; Cunent Rating for DC per data sheet
_____
END
0.000
0
16.33
4.071
19.95%
15
__ _ _ _
END
0.000
0
16.33
4.071
19.95%
15/75
I
END
0.000
0
16.33
4.071
19.95%
30
END
O.ODO
16.33
4.071
19.95%
75
0.139
0.107
END
0.000
16.33
4.071
19.95%
95
___� __ __ ___
I
END
0.000
16.33
4.071
19.95%
110
0.182
_
I
END
0.000
16.33
4.071
19.95%
115
END
0.000
16.33
4.071
19.95%
135
0.211
j _
END
O.00D
16.33
4.071
19.95%
150
END
0.000
16.33
4.071
19.95%
177
END
O.00D
16.33
4.071
19.95%
185
0.262
__
END
0.000
16.33
4.071
19.95%
Hom Only
I
,
�
I !
!_
�
i
_i
_
END
0.000
16.33
4.071
19.95%
H1
i
�
I
_
_
END
0.000
16.33
4.071
19.95%
H2
i
; ;
i �
_
__ __
', i
Totals
2.416
870
End of line Voltage
16.33
H3
i
j
i
i
j
THIS IS BASED ON A 24 VOLT SYSTEM ONLY
i !
Point to Point Method
_ _
_
Project Name
PURSUIT BOATS
Calculations and allowable
wltage drop are based on
UL srandards 1971 & 464
_
CIRCUIT IS WITHIN LIMITS
__ _ -------w -
Date
5/11/2019
Circuit Number
RPS
NAC CKT#4
_
Totals
Voltage
_ _
_ -� -
Area Covered
1st Floor
2004 revislo_ns__
Distance
Drop
_':
_may
_Cunent
Nominal
S stem Voltage
y
20.4
ii
2.416
677
2.73
_. - - ---
_._
_
_
Minimum DeHce Voltage
16
_
I j _
End of Une Voltage
17.67
-__ _
j
Total Grouit Cunent
2.416
Wire
Ohm's
I i
Percent Drop
13.37 %
'i
Gauge
Per 1000
End of Line method uses only the wire guage for the first device
to source for calculation
Distance from souroe to 1st device
70 12 1.98
Standard Wire Resistance m Ohms per 10D0 feet @ 75 C.
3.07
-- - __ _ _..
r18 7 77; i16 4 89, , 14 3 07 I 12 1 981 10 1 24,
I
Deuce Type_
Distance_
i !
_
� 18-14 Awg -Solid Conductors' 12-10 Aw Stranded Conductors I
g
__ _Enter __
WHS cd, H, CHS cd Etc.
from
Volta e
9
This circuit is sourced from: i I I � ' I � '
Device Enter Device
_previous
- --
At i Drop from I Percent
Number
Device Type
Current
device
Device
I source
Drop
Device 1
WHS 135
0.211
70
19.73
0.670
3.28/
Notes: I i I I j
Device 2
WHS 185
0.262
65
19.73
0.672
3.29 %
_
Wire resistance is doubled m the calculations_fo_r tw_o_wires (Positiw and Negative)
i
Device 3
WHS 135
0.211
55
19.30
1.095
5.37%
The wltage calculated to the last device in any method must not be lower then 16 VDC
____
I,
Device 4
WHS 185
0.262
30
19.10
1.301
6.38 %
� j !_j j j
_
Device 5
WHS 135
0.211
12
19.03
1.371
6.72%
_ _
No Cunent entered =device not offered at that candela.
i
Device 6
WHS 135
0.211
90
18.58
1.820
8.92%
_ __ _
! WHS
i_i WS j_i CHS ; _CS j WSS
i j CSS
__
�
Device 7
WHS 185
0.262
65
18.31
2.089
10.24 %
� Wall
I Hom
Strobe
j ! Wall , ;Ceding Ceiling _ Wall
. � Strobe I ; Horn Strobe ; I, Speaker __.._
� j Only i i Strobe Only � Stmbe
_
� _I Ceiling
_
_
j
Device 8
WHS 185
0.262
120
17.94
2.463
12.07%
j � Speaker
_
j_f Strobe
_
_
.„-.__._
!
Device 9
WHS 185
0.262
85
17.76
2.639
12.94 %
_;
_i
Device 10
WHS 785
0.262
85
17.67
2.727
13.37 %
Candela
j Cunent Rating for DC per data sheet
_
____
'
END
0.000
0
17.67
2.727
13.37%
15
END
0.000
0
17.67
2.727
13.37%
15/75
END
0.000
0
17.67
2.727
13.37%
30
END
0.000
17.67
2.727
13.37%
75
0.139
0.107
_____�
END
OA00
17.67
2.727
13.37%
95
END
0.000
17.67
2.727
13.37%
110
0.182
-- - -- --
END
0.000
17.67
2.727
13.37%
115
�
END
0.000
17.67
2.727
13.37%
135
0.211
--__--
_ __ -
END
0.000
17.67
2.727
13.37%
150
END
0.000
17.67
2.727
13.37%
177
j
END
0.000
17.67
2.727
13.37%
185
0.262
!
END
0.000
17.67
2.727
13.37%
HomOniy
I
I
j;
i
I
i
I
_
_
END
0.000
17.67
2.727
13.37%
H1
I
I
�
.-._
(I
END
0.000
17.67
2.727
13.37%
H2
_�
I
,_
'
�
'I,
(�_
�
I
i
!
j
_
�
i,
_
j
Totals
2.416
677
End of Line
Voltage
17.67
H3
;
E &CEng' ers,i I
Cert. of Auth � 5
13812 Geranl ce
Wellington, F 4 I I I j I
Tel (561) 71 ,�\1� � ,
Registered
P.E. � 411
No
REVISION RECORD
REV DATE ISSUE DESCRIPTION
FIRE AND SECURITY
SOLUTIONS, INC.
3000 HIGH RIDGE RD. SUITE 9
BOYNTON BEACH, FL 33426
TEL (561) 588-9542
EF-20000304
LT,•
FIRE AND SECURITY SOLUTIONS, INC
MANUFACTURING
BUILDING FOR
PURSUIT BOATS
3901 ST. LUCIE BLVD.,
FORT PIERCE, FLORIDA
%.
TITLE
FIRE ALARM PLANS
r>«glne TATC OF ,'u(,0 ESIONFR Dnr �E .,
(j�� 'TrGSC E. SAMOUR, P.E. 11.05.19 AS NOTED 19
Q`J / �, NICET LEVEL EHEETNO.
/ �V ^.FF�oR,arc�,,,� DN��E� FA-3
//// / � 1 11 1 1 t\\ CRD FlLE
REVISION R
REV DATE ISSUED
M13
0
185cd
0-1-11
E.O.L.
185cd
1-2-9
( AMA
M49
STOCK
ROOM
as
115cd
1-1-9
11 p M10 p
75cd 75cd
0-1-9
DOO6 p
ELEC.
o�
GLASS
ROOM
os
x x x 185cd
185cd
0-1-10
75cd
1A1 13
E.O.L.
CD
115cd 115cd 'I
1-1-10 IA-11
115cd
1-2-6
115cd 115cd
1-1-8 1-14
115cd
1-2-5
_ i—M]ZNLB
MI5 p pAM M M M jM19
WP M16 q
OFF. ®M09
72 75cd
0-1-6
M
x
0
1
1
135cd
1-1-6
1
PARTIAL FIRE ALARM PLAN
SCALE 1116 F = 1'-0"
FIELD COORDINATE LOCATION,
REMOTE ANNUNCIATOR SHALL
BE LOCATED ON INTERIOR
WALL NEAR KNOX BOX.
n
p
FT] D03
M06ODo 01-4
BREAK II PANTRY
ROOM II
7 RT D04 e
CR ODD
M07
185cd
0-2-8
18
12-3
M20
135cd
1-1-5
x
UPHOLSTERY
18
185cd
0-2-4
1
1
110cd
0-2-3
FA
II x
M21 UUUU M24
a � a
110cd
0-1-2
RT D02
CR ODD
M03
ELECTRICAL
10
I
LAMINATION
as
135cd
1 Al 3
Q
185ad
142
E & C EngNe¢rs, I*,
FIRE ALARM
FIRE ALARM MANUi
op NOTIFIER- NOT-BG
WP MANUAL PULL STAI
p NOTIFIER-NOT-BG
OPHOTOELECTRIC E
p NOTIFIER -FSP-95'
DUCT SMOKE DEfI
2 DD NOTIFIER DNR W/ I
FACP FIRE ALARM CONT
NOTIFIER - NF WA C
Rps REMOTE POWER S
HONEYWELL-HPF
FSA FIRE ALARM SYSTt
NOTIFIER - N-ANW
FIRE ALARM HORN
SYSTEM SENSOR -
FIRE ALARM HORN
SYSTEM SENSOR-
FIRE ALARM STROI
SYSTEM SENSOR-
Y FIRE ALARM FLOW
o (FURNISHED BY SF
j FIRE ALARM TAMPI
�l (FURNISHED BY SF
RT REMOTE TEST
NOTIFIER - RTS151
CR CONTROL RELAY h
NOTIFIER - NC-1001
MONITOR MODULE
NOTIFIER - NMM-1 C
SP SURGE PROTECTK
KB KNOXBOX
FIRE AND SE
SOLUTION
3000 HIGH RIDGE
BOYNTON BEACI
TEL (561) 58
EF-20000
FIRE AND SECURITY
Cart. of Auth # 6 8 sttE �oDAnoN
13812 Garen Pla e
Wellington, 341 3901 ST. LUCIE BLVD.,
Tel(561) 7 9
email: ad@ n \�s�v m p < /// FORT PIERCE, FLORIDA
40 41186 I. ;.FIRE ALARM PLANS
Eduardo ( )` ou ,P.E,;
Registered Ele Ica n I ➢ESIGNER onre
P.E. Y. 41166� C '�{� STATE OF ! �. SAMOUR, P.E. 11.05,19
fJ ' : ��ET IEVEI 6HEETNO.
Date:
A
`Cry. COR\�. ,JG' ypnwri or
REVISION RECORD
REV
DATE
ISSUE DESCRIPTION
BY
1-3-1
0
e
--
---------------------------------------
MATCHLINE "B'~
—
— ——CHLINE"6„—
—
--
M38
M3 P
E] F
M3
185cd
/�
185cd
a
1-3-2
1-4-8
LL
185cd
135cd
=
ASSEMBLY
M
--t7j M34
1-4.6
,P
of
(
M
o—Q M33
M309
a
EEC.
(
M
—ta M32
FIRE ALARM SYMBOLS
1�
M
M31
CR M45
OR M44
CR M 3FIRE
ALAM STATION
P NOTIFIERR NOT BGA2LX
185cd
°
1 1 1
WEATHERPROOF
x
1
0
p NOTIFIER NOT BG12LX W/STOPPER 11 COVER
PHOTOELECTRIC SMOKE DETECTOR
OP
❑
NOTIFIER-FSP-951
135cd
1-3-3
DUCT SMOKE DETECTOR
ODD
NOTIFIER DNR W/FSP-951R
I
FACP FIRE ALARM CONTROL PANEL
-
Q
NOTIFIER - NFW-t00X
LU
aas REMOTE POWER SUPPLY
Z
HONEYWELL-HPFF12
J
H
185cd
_
185cd
-4 9
F—Fs"A�j FIRE ALARM SYSTEM ANNUNCIATOR
Q
1-3.4
135cd
1 4-5
ASSEMBLY
I
NOTIFIER - N-ANN-80
tr
pt
FIRE ALARM HORN / STROBE COMBINATION
185cd
SYSTEM SENSOR -P2RL
El
1-4 4
FIRE ALARM HORN /STROBE, CEILING MOUNT
MILL
SYSTEM SENSOR -PC2RL
SHOP
pp
`O' FIRE ALARM STROBE
_
SYSTEM SENSOR -SRL
g
185cd
135cd
(FURNISHED BY SPRINKLER CONTRACTOR)
2
~
1-3
1 FIRE ALARM TAMPER SWITCH
-
I M30
_
I
�l (FURNISHED BY SPRINKLER CONTRACTOR)
RT REMOTE TEST
—
= IL
NOTIFIER - RTSI M KEY
CONTROL RELAY MODULE
li-
o
M3
CR
NOTIFIER - NC-100R
135cd
1-3-10
tr
F MONITOR MODULE
135cd
E.O.L.
NOTIFIER - NMM-t OOP
1-1-3
SP SURGE PROTECTION DEVICE
—
I
CR M41
CR M 2 010
KB KNOX BOX
185c
o
ASSEMBLY
DT
185cd
CR M47
CR M46
135W
0
1-4-2
P
_
CF
MATCHLINE "B"
CHLINE "B" ts
Q
185cd
1-3-7
W
Z
�
"
�
PARTIAL
FIRE ALARM
PLAN
N
Q
SCALE
1/16" = 1'-0"
8e
185cd
1-3-9
,-36
FIRE AND SECURITY
M25
SOLUTIONS, INC.
3000 HIGH RIDGE RD. SUITE 9
BOYNTON BEACH, FL 33426
MI M26
M27 01
M28
TEL (561) 588-9542
P.I.V.
BACKFLOW
EF=20000304
FIELD LOCATE
FIELD LOCATE
FIRE AND SECURITY SOLUTIONS, INC
CUSTOMER
N
PARTIAL FIRE ALARM PLAN
SCALE 1l16" =1'-0"
MANUFACTURING
BUILDING FOR
PURSUIT BOATS
E & C Eng' a
rs, n
Cart. Of Auth # fi 8
SDELOL VON
13812 Geranl Is
Wellington, F 1
Tel
0111
` �i
3901 ST. LUCIE BLVD.,
(561) 71
email: ed@e In
��\
J,.) �//
FORT PIERCE, FLORIDA
JM
�J
'
'fJJTLE
No 186 '�,
/
_FIRE ALARM PLANS
Eduardo (E
ur E. '.1
Registered Elect i@C sneer TATE OF
4
DESIGNER DAE
� E. SAMOUR, P.E. 11,05,19 AS NOTED 19� 1156
P.E. # 41186
/,/
-
Date: r
,FLORIOP,.'_\�:
NICETLEVEL
SHEETNO.
REV.
,'
F/
oRnJRH
��//
CND FILE
l m\\
n. ® N®'I-I �•, I E R®
V �P
by Honeywell
PROGRAMMING AND SOFTWARE
vised output for local energy munlUpal bon transmitter alarm and
trouble. Includes a disable switch and disable bauble LED.
NH-20gR: Low -profile 135°F fined lhertnal sensor B3g0-8 base
included, FlashSpn only.
zone of wnventional two -vase detectors. Requires resettable 24
VDC Refer to the Device Campefibility Document for listed
SPECIFICATIONS
Autoprogmmming (Isom mode) reduces insbgafion time
power.
System Capacity
Addressable Device Accessories
• Custom En8lish labels (per point) may be manually entered or
selected from an infamal library file
PWRMOD24 Power Expander Module: Optional power module.
Inrseesea alarm power output to 6amps.
NH-200R4V: Low•profile 135'F fined Nermel sensor. Ivory. 8300.6-
IV base included, FleshSean sad CLIP mods.
compafible devices and quantity limitation.
NZM-100: Similar to NMM-700. Addressable Monitor Module forone
Intelligent Signaling Une Cirouits................................................1
Entl-ot•Llne Resistor Assembly (R-07K and R-0.eK): The
NFW-100X I i d
A dressable FACP Communicator
• Twn proeremmable Form-C relay outputs
COMPATIBLEANNUNCIATORS
FST-851H: Low-profle intelligent 190°F/88°C fixed thermal sensor.
zone of conventional two -wire detectors. Requires resettable 24
• Addressable device copadty..................................................188
47k ohm assembly supervises the NMM-700-10, NOM-I00, NMM-
t00P, end NC-100 module circuits. The 3.9k ohm assembly auper-
ntell ent
with
piashgca„ °„, Y'
VDC power, Refer to the Device Compe86ility Document for listed
• Progmmmahie software zones.................................................99
99 software zones
N-ANN•80; Remofa LCD annuncator mimics the information ells-
Compatible devices and quantity Ilmimgon.
• Annunciabars
vises the NZM-100-e module circuit These resistors ere included
• Continuous fire protec0on during online programming
played on the FACP LCD display. Recommended wire type is un-
FST-961 H4V: Low -profile intalli8ent 190°F/88°C fixed thermal son-
.............................................................................16
with each module.
General
Program Check automatically vetches common ertors not linked
shielded. (Basic model is black; order-W for white; sea DN-7114.)
sor. Ivory. FlashSwn and CLIP mode.
FCM•1: Addressable Control Module for one Style Y/Z (Class a/A)
Power Supervision Relay; Supervises Ne power to 4-wire smoke
to say zone orinput point
N-ANN-t00R: Remote LCD ennuneiamrmlmies the information ells-
NH•200H: Lawprofile lnte111gent 190'F/88°C fined thermal sensor.
zone of supervlsatl polarized Notification Appliances. Mounts
EleCtrlCal Spr3CItICat10t1S
detectors and no6fica0on appliances.
The FlreWarden-100X NFWt00X isthelatest intelli entaddress-
OFFLINE PROGRAMMING: Create the entre ro rem in ur
played on the FACP LCD display. Recommended wire type is un-
8300.E base included, FlashScan only.
directly to a 4.0" (10.t6 cmJ elecMwl box. NAC op5on requires
AC Power: Operetes in either 120 pr 240 VAC, 60/80 Hz, 3,25 A
able Fire Alarm Control(Panel FACP within the FlreWarden Series
( )
P g Yo
shlalded. For use in FM applicagons only. (Basic model is black
NH-200H-IV: Low Intelligent I90°F788°C fixed thermal
eztemal 24 VDC tc powerno5fid5on appliances.
Wirin Re uirements
g q
and is a direct replacemamfor The FlreWaNen-100 (NFW-10g). The
office using FS•Tools, a Wndows�based sofware pacimge, end
order R far redJ
-profile sea-
NC-100: Addressable Control Module for one Style Yl2 (Class 8/A)
auto -sensing- no snitch required. YMre size: m nimum t4 AWG
i
While is
upload/download system programming locally. OfOins program-
sor. No 83D0-8-IV base induded, FlashScan and CLIP made.
n''
(2�00 mm2) with 600 V Insulation. Nonpower-limited, supervised.
shielded wire Satre
not re d, it Is rewmmended that ell SLC
NFW-100X comes with a tailed communlcafor and su arts
pre -ins pp
mmg regwres an elhemet connec5on. FS-Tools Is avagahle on
N•ANN4/0: LED Driver Module provides connections to a user sup-
Legacy De Noes
zone of u rvisad poleaxed N°tificahon A Ilences. Mounts
spa PP
wiring be twisted -pair 4 minimize the egects of elecm'cei interfer-
upto198eddressebledevicos(99 detectorsantl 99 modules).WN
�'
www.nofifier.eom,
plied gmphicannunciat°r. (See DN-7105.)
directly toe4.0°(10.18 cmJ electrical box. NAC opSon requires
BaHery: Two 12V 18 AH lead -acid batteries. Rairory Charger
once. Rsferrothepanslmanual for widng details.
n extensive list of powerful feaWres, the NFVtat00X progremsJust
N-ANN•LED: Annundator Module provides Nres LEDs far each
FSI-651: Addressable low -profile ionizatlon smoke detector.
exmma124 VDC to power notification appliances. �
Capadty: 7.18 AH (FlreWarden-100X cabinet holds maximum of
Ilke FlreWarden-t00 products, yet fib into appllcagons previously
User interface
zone: Alarm, Trouble, and Supervisory. Ships with red enoloeare.
NI.100: Addressable low -profile Ionization smoke demctnr.
FRM-1: Addressable relay module containing two isolated sets of
two 18 AH battenas. )
NFPA Standards
served only by wnvendonal panels,
-
( See ON-60242.)
FSP4151: Addressable low- rofile homelectnc smoke dotecmr.
p p
Farm-C contacts, which aperete as a DPDT swich. Mounts directly
Communleadon Loo Su d and
p: pervise power -limited.
The pre -Installed (POTS-COM is a dual technolo gy (POTS and IP)
-
�76
LED INDICATORS
N-ANN•RLED: Provides alarm (red) indicators for up to 30 Input
NP-100: Addressahleiow-profile photoelectric smoke detector.
toe 4.0' 10.1E cm. box, surface mount usin the SM8500.
( ) g
NoUgcadon Appliance Circuits: Terminal Block canner•
The Fire Warden-t00X complies with Ne fallowing NFPA 72 fire
Alarm Systems
communicator. The POTS transmits system status (alarms, troubles,
_; �=urr;+=°
Fire Alarm (red) CO Alarm (red)
zones or addressable points. (See ON-60242.)
FSP4151T: Addressable low -profile smoke detector
NC-100R: Addressable relay module containing two tutored sets of
provides
bons for tour NACs,.STyle Y (Class 0) or Style Z (Class A). Spacial
requirements:
AC loss, etc.) to a Central Station via the public swiched telephone
,_ �uu�,=�
...?�+,.._,�
AC Power (green) Supervisory (yellow)
N•ANN-RLY: Rela Module rovitles 10 ro remmable Forth-C
y p p g
photoelectric
with thermal sensor.
Form-0 contacts, which aperete es a DPDT switch. Mounts direcgy
Application power. PowaHimitea, supervised drcuitry. Maximum
-LOCAL (Automatc, Manual, Waterflow and Spnnklar SupervF
network. Tha IP communicators intemet monitoring capahilitysends
• Trouble (yellow) Ground fault (yellow)
relays. Can be mounted Inside the cabinet (See DN-7107J
fa a 4.0° (10,16 cm.) bon, surface mount using the SMB500.
signaling curtant par cimuit 2.5 amps spadal application, 250mA
ury).
alarm signals over the Ntemet saving the monthly cost of two dedl-
N-ANNS/PG;
NP-100T: Addressable law -profile photr,electric smoke detector with
NBG-12LX: Addressable manual pull station with interface module
regulated. End•of-Line Resistor. 4.7k 'h 71252 UL
_AUXILIARY (Automatic, Manual end Watemow) (requires
eared business thle hone lines. Althou h not re fired, the second-
P g qu
Battery fault (yellow) Disabled (yellow)
Serial/Pamllel Printer Gateway module provides e
thermal sensor.
mounted inside.
ohm, watt (PIN
4XTM).
ary blephane line may be retained providing backup communlcatian
Maintenance (yellow) Communication (yellow)
connection for a anal or parelld printer. (See ON•7103.)
FSP-851 R: Remote test capable addressable photoelectric smoke
listed) far Style Y (Class B) NAC; system capable of 1.9 kS1- 22 k51
NOT-BG72L%: Addressable manual pull station with Interface mod-
ELR rengo. Refer b the N07/FIER Device Compatibility Document
-REMOTE STATION (Automata Manual end Watedlow)
over the public switched telephone line. Optional cellular reporting is
Alarm Silenced (yellow) F7-F4 Progremmable Function
ADDRESSABLE DEVICES
detectorfor use with DNR(1xOduct detector housing.
ale maunmdinside.
for listed compatlble devices.
(VvnereaDACT is note¢epted,Nealartn,baubleandsupervi-
available usin8 the CELL -MOD orCELL-CAB-N.
Keys (yellow)
FSP•951: Addressable low -profile photoelectric smoke detector.
NP-t00R: Remote test capable addressable photoelectric smoke
190-X; Fault Isolates Module.
sory relays maybe connected to UL B841istsd transmitters. For
Remote and local progamming ofthe control panel is ble usin
POD g
FlashScan onl .
y
detector for use with DNR dud detector housin .
(� g
Two Programmable Relays and One Fined Trouble Relay: Con-
tact mtin 2.OA 30 VDC IsOva O.SA@30 VAC
reverse polarity signalin8 of alarm and trouble, 4XTM is
the FS•Tools U load/Download atilt .Pro mmmin databases
p ty g g can
KEYPAD
FSP-9514V: Addressable low -profile phooelectric smoke datedoc
FST-861:Fest-response, lowprofile heat detector.
N1004S0: Faultlulatnr Module.
B� @ free ), resistive).
Fora-C relays, non -power -limited, non -supervised.
re aired.
q )
be uplaaded/downloeded via the panel's US8 port (and USB cable)
76 key alpha-numonc pad Acknowledge
Ivory. FlashScon and CLIP mode.
NH-1D0: Fast-respanu, low-pmfila heat detector.
I30$: Six -fault Isolator module. Mount one ortwomodules in a BB-
-PROPRIETARY (Aummaga Manual and Watorfiow).
or via an ethernet connection using the (POTS-COM communicamr.
Alarm Silence Drill (Manual Evacuate)
NP-290: Addressable low-pmfila photoelectric smoke detector.
FST-851 R: Fast -response, low•profile heat detector with retecf-rise
XP cabinet (optlone)). Mount up to slz modules on a CHSE chassis
Cabinet $peClfiCati0I1S
-CENTRAL STATION (Aufnmagc, Manual and VJaterliow, end
The USB port also allows for the download or upload of the entire
• Four(4)progremmable function keys• Reset (lamp test)
B3006 base included, FlashScananly.
option
in a CABS/CAB-0 series cabinet
Sprinkler Supervised).
proBrem, history file, walk -test data, curtent s1aWsand system volt•
SMBfi00; Used N mount all modules except the FMM-I01/NMM-
Door. 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72°
ages by means of a US8 Sash drive.
NP-200-IV: Addressable low -profile photoelectric smoke detector.
NH•t00R: Fast -response, low-pmfila heat detector with reteof-rise
lggp
1 g2 cm. doe
(. ) p. Backboz: 19.00" (48.26 an.) high x I6.65" (4229
-OT, PSDN (Other Technologies, Packet-svritehed Data Net-
• Maintenanco alert warns when smoke tlatedor dust ecoumula-
PRODUCT LINE MFORMA710N
Ivory, 8300.E-IV base indudad. FlashScan end CLIP mode.
°pg0n'
rk
� )
Tha power supply and all electronics ors contained on a drwit
Lion Is excessive
NFW-100X: Addressable Flre Alertn Contrd Panel SLC
NMM-100.10: Ten4npd monitor module. Mount one or two modules
cmJ wide x 5.25" (13.34 cmJ deep. Trim rang (TR•CE/B): 22.00'
board supported an a new quick Install chassis end housed in a
One -person audible or silent walk test with walk -test log and
with one
FSP-861T: Addressable low -profile photoelectric smoke deector
fST-857 H: Fast -response, l°w-profile heat defector thatactivates at
In a BB-2F cabinet (optional). Mount up to sin modules on a CHS-8
(55,88 cm,) high x 19.65" (49.91 an.)w1da.
-IBC 2012, IBC 2008, IBC 2008, IBC RODS, IBC ROOD (Seismic).
metal cabinet Available accessories Include local
loop. Includes main circuit boaN with display chassis with trans-
with thermal sensor FlashScan only.
190°f/88°C.
chassis in a BB -BF cabinet
-CBC 20W (Seismic)
end remote
upload/download u0tvure, remote annundators, end reverse polar-
printout
System alarm verification selection perdetedorpolnt
former, hackbox with door, plastc bag containing screws, cables,
key, etc.
FSP•961T4V: Addressable low -profile photoelectric smoke detector
NH-100H: Fast -response, low -profile heat detedor that ac5vates at
N2M•100.6: SIx-zone interface module. Mount one or two modules
Shipping Specifications
ity/city bon transmitter (4XTM).
PAS (Posigve Alarm Sequence) and Pre -signal par paint (NFPA
with thermal sensor. Ivory. Fiash9ean and CLIP mode.
190°F/88°C,
n a 8B-XP cabinet (optional). Mount up to six motlulos on a CHS-6
Agency Listings and Approvals
Features
72 compliant)
FS-Tools; Pmgremming software for Wndows't9-haled PC cam-
pater. Available for download et w+m.notifer.com.
NP•290T: Addressable low -profile photoelectric smoke tletectorwlN
FAPT-851: Addressable low-pmfila mul0-sensor detector.
chassis ins CAB-3/CABd series abinet
WelghU 26.916s. (12.2g kg.) Dlmenslons: 20.00' (50.80 cm.) high
x22.5' 57.15 cm. widex 8.5'(21.59 cm. dee
( ) )
The listin below I
• Up to 16 ANN-BUS annunciators-B psreaeh ANN-Bus
thermal sensor. B300-6bese included. FlashScan only.
NP-At00: Addressable low-mfile mul8-seams detecor,
p
SW/fT�e/ass Oev/cos
p
s and a ravels a to the bask FireWaMen-
g Pp Ppy
• Listed to UL Standard 864, loth edition
• Remote Acknowledge, Alarm Silence, Resat and Onll via
CELL•CAB-NICELL-MOD: Optonal GSM communicators.
NP-200T4V: Addressable low -profile smoke datecbr
t00X control panel. In some cases, certain motlulos may not be
• Pre -Installed (POTS-COM ENemet IP and POTS (Plain Old Tele-
IPOTS-COM: Dual tachnoloeY (POTS and IP) communicator.
photoelactrie
82005: Programmable, addressable sounder base.
FWSG; Wreless Gatewa y
Temperature and Humidity Ranges
listed by certain approval agencies, or listing may be in process.
phonsService)Central Station CommuniwloraverAlartnNet
addressable modules orremom annunciator
Upload/Download ofprogrem end data via USB with optional FS-
(replacement board)
wiN thermal sensor. Ivory, 8300-8-IV base included. FladaScen and
CLIP
82005R: Addressable sounder base.
FWD-200P:intelligent, wireless photo datedar.
Consult factory forletest listing status.
• Optional CELL•MOD or CELL-CAB-N GSM Cenlml Station Com•
Tools Programming Utility
OP•ES-R: Optional dress panelfirthe NFW-100X (red).
made.
DNR: InnovelrFlez low -Dow non -relay duct-deiactorhousing�(Order
FWH•200ROR7J5: UteS eel intalll8ant wireless cote of dee 135°
Pa i )
Thls system meets NFPA requirements for opemtlon at 0- 49°C)32
-120°F and eta relative humidity 93%t2%RH(noncondensing)at
•UL: S635
muniwtoroverAlartnNelaD
OP-ES43: Optlanal dress panel for NFW-100X (black).
FSP•e51 R: Remote testa ble addressable hotoelactris smoke
Pa P
dalsdor for use with DNR(WJ dud detector housing. FleshScan
FSP-851R, FSP-95I R, or NP-t00R separately.)
heat detector.
32°C t 2°C (90°F t 3°F). However, the useful life of the systsm's
• CSFM: 7165-0028:0505
• Automated activation of the NFC-50/100 Emergency Command
SLC COMMUNICA7)ON LDOP
TR-CE-B: Optional trim nag far -flush mounting. Far
only.
DNRW; InnovairFlex low -Pow non -relay dud -detector housing, with
FWD•200ACCLIMATE: NArelessAcdimate Detedor
standby bailedes and the electronic mmpanants may he adversely
. FONY: COA #6268
Center
• NFC-FFT Firefighter Telephone option
• Supports FlashScan®and CLIP protocols
semi (Black.
red, erderTR4:EJ
FSP•961 R4V: Remain test capable addressable horoelectrie
NEMA-0 reting. Watertight (Order FSP-t)51R, FSP-951 R, or
FWH•200FIX1J5: Intelligent wireless fixed -temperature (135°) heat
afieeted by extreme temperature renBas and humidity. Therefore, It
• Compatible wiN SWIFT® wireless devices
SLC opBmtes up m 10,000 R (3,000 m) in FlashScan made with
BB-XP: Optional cabinet for one or two modules.
P
smoke tletedor for use wiN DNR(Vv) dud detedor housing. Ivory.
NP-t00R separately.)
detector.
is recommended Nat this system and Its ponpherels tie installed In
• Aute-progremmin8 (team made) reduces Installation time.
twisted, unshielded wire
88.26: O tional cabinet for u fin six modules mounted an CHS�6
P P
FleshScan and CLIP mode.
Addressable Modu/es
FW-MM: Intelligent wireless monRarmodule.
an environment with a normal mom temperature of 15 - 27°C/60-
Repoils nvo devices set to Ne same address
• Single addressable SLC loop which mee6 NFPA Class B and
chassis.
NP-200R: Remote test capable addressable photoelectric smoke
FMM•1: Addressable Monitor Module far one zone of normailyopen
FW-RM: Intelligent wireless relay module.
80°F.
• Four built-in, Independently progremmabie Style Z Class A or
( )
ClassA requirements
BB•26: Battery backbox, holds up to two 25 AH batteries and CHG-
detector for use with ONR(V'f) dud detector housing. FlashScan
dry -canted initiating devices. Mounts in sandard 4.0" (10.16 cm.)
NBG-12LW: tnteiligent wireless pull sta0on.
Style Y (Class B) NAC drouits
• 198 addressable device capacity (99 addressable detectors end
75.
only.
bon. InUutles plastic cover plate and endrof-line resisor. Module
WgV•RL, WAV-WL,WAVLRL,WAV-CWL:IntelligantAV bases.
• Selectable strobe s nchroniza6on for S stem Senun Vvnaelock
y
89 modules)
NFS-L88: Battery box, houses two 55 AH battenee
NP-2gOR4V: Remote fast copabla addressable photoelectric smoke
ma be confi used (or eiNar a S le 8 Class 8 r S la D Class A
g ty ( ) o ty ( )
W-USB: Wireless US8 radio/antenna dangle Nat plugs into Ne
and Gentex devices
• NoSfidtion Appliance Circuit End of Une resistor matching
Compatible wiN NOTIFIER FireNYarden and ONYX Senas
addressable devices (refer N the FireWeNen SLC widng Men-
CHS-8: Chassis, moumsu t six multi -modules In a BB-25 phNet
p °
detedor for use with ONR(Vtg dud detector housln8• Ivory, FlashS-
IOC.
USB port of a PC running SWIFT Tools.
• Fourprogremmable function keys for ease of maintenance
uep
CHG-75; Battery char er farlead-acid batteneswitha retie of25 to
g B
can and CLIP mode.
NMM-700: Addressable Monitor Module for one zone of nertnali •
Y
gram
SWIFT Tools: Pro ming and tliagnostic utility for the Wleless
• Two ro remmabie seta send one (nod treu6le seta
p g y Y
75 AH.
FST-851: Low-pmfila 135°F fixed Nertnal sensor. FlashScan only.
open dryconfad initiatng devices. Mounts in stantlahl 4.0' (70.78
Gatevray and devices. Available for downleatl fromfrelite.com.
ISO 900�
• Built-in Proeremmer
NO7)FlCATIONAPPLIANCECIRCUITS /NAGS)
CHG-120: Remote battery charging system for lead -acid batteries
F5T•961•IV: Lowprofile 135°F fined Normal sensor Ivory. FlashS-
cm.) box. Indudes plastic cover plain and end -of -line resister. Motl-
NOTE: For more Inrorna5pn on Compaflbie Addressable DeNcres hr
• Iota 100thareder LCD die la wiN hackll htrn
9re P Y 8 g
Faurindependently progremma6le output drouils. Circuits can ba
with a retln f 55 to 120 AH. Ra
g o quires eddigonal NFS•LBB for
cam and CLIP mode.
ale may be configured for eithare Style B(Cless e)or Style D(Class
use wish the F/reWarden-100X, see the Ipllpwln date sheets document
g (
apirni tteiaee
• Reai-time UocWcalendar vrith aummatic da II ht savin trot
Y9 95 roe
ton( uredfor the following au uts:
B IP
mountin8•
NH•Z00: Low -profile 135°F fixed Normal sensor. B300.6 base
A)IDC.
numbers); NP-20g Seliea (DN-60979), NH-200 Sedes (ON-60980),
• History file with 1,000 event ppadty
- Style Y (Class B)
NOTE: CHG•f20 or CHG75 mqulmd firbattedeslargerfhan 18AH.
included, FlashSwn only
FDM-1: Dual Monitor Module. Same as NMM-f00 except it provides
FSP-B51 Sedes (DN-8935), FSP-95f Sedes (DN-B0977), FST-g51
msm-„°nhnao-maai°e°uwbhmem,Pi,ve<•.
- Addressable sounder base compatibility
-Style2(ClassA)
two Style B (Class 8) only IDCs.
Sodas (DN-6936), FST-95] Sodas (ON-60975), FAPT-B51 (ONL937),
w•buuowrvxaiemea,m..v+ezx••^a.�i°i>.
• Control module delay timer
BAT Serlas: Batteries, sae data sheet DN-6933.
NH-2004V: Law file 135°F fixed Normal sensor. Iva 8300-8-IV
ry
NDM•100: Dual Monitor Module. Same as NMM-100 except it pro•
N100-ISO ON•6994 NP-]OO sodas (DN6995), NH-100MH•f00R (ON-
( )�
w°a„�m�a,v,mend�,u<,upwn,•tl,..,,,u.
• Avlamatie detedor sensitivityfesting (NFPA 72 compliant)
Sllonce InhibR and Autosllenco tlmoro lions
P
PRN Series: UL listed compatible event punter. Uses tractor -fed
base included, F ashSnn and CLIP mods.
vides two Style 8 (Class B) only IDCs.
6997), DNRAnnovalrFiex (DN-6g424, DN-60429), NP-Af00 (ON-6998),
u�em,°,.wkntea,"a.anon.wm.
• Automatic device typetotle venfic4tlon
• Continuous, Meroh Time, Temporal, or California code for main
paper.
FST•951 R: Low- rofile, intelli nt rated -nee thermal sensor.
P ga
FMM-101: Miniature version of NMM-700. Exelutlas LED and S le
ty
NMMfOOMMM•]OOPMOM-}OOMZM-f00 (ON6998), NC-100 (ON-
,°Nx%uanneao, mi.ro,e•�°. snrc, Ha sy°m sM°.a
• Point trouble Identification
eiroult board NACs with two -stage eapahlliry
OPTIONAL MODULES
FlashScan and y'
Doptian. Connect with wire pigtails. May mouMin device backbox.
7000), NG100R (ON-60383), NMM-1g0.f0 (DN-6980), MM-fiFOM-]/
FZM-1rFMM-70f NN-6720), FCM-1rFRM4 (DN-6724), NOLBG72LX
NOTIFIER v°,.ya„rva,am,m, otxe,m.mmm„m,xx,.um..et°me
• Watertlow selection per module point
Selectable strobe synchronization per NAC
2.5 Aspedal 250mA total for NACs
4XTM Reverse Polarity Transmitter Module: Provides a caper-
FST•951 R4V: Low-pmfila, Intelligenq ratebf-rise Normal sensor.
NMM•100P: MinlaWre version of NMM-100. Excludes LED and Style
(DN-7001), NBG-]2LX (ON-6726), and flraWamen SLC Manuel
12 CIIntanvlile Road its,w.,n,n,tµm.eu.xnn.,ewua•.•m.vm<,.
rw� ®®
INIOTI
• Alarm verification selection per detector point
application, regulated, power
Ivory. Flashscon and CLIP mode.
D option, Canneds wiN wire pigtails. Mey mount in device backbox.
(52304).
Nonhford, CT 06472 ctai9ayxmrmm�imaaw akuromi.w••nurwww J FI E:IR
NOTE: Ma imam orfara124VOCsystempmversheredbehvean aBNAC
eimulfs end the ANN-BUS Is 2.7 A
FZM-1: Similar to NMM•100. Addressable Monitor Module for one
203.464.7161 �INwt�mx`�pxa� by Honeywell
Pogo 2 of 4- DNSDB59:C • ]/larzeta
DN-60968C • ]/1a2019-Page 3 of 4
wwwnonfioc°om r<unW mariyn: use
ON-W959:C•7/182m8-PeBo t of 4
�(
�
U
ar
® t�
®If6CJfdd@'0
• Su ervised AC In u6 belle volts e, auxllla out uL char-
P P ry 9 ry P
Cebinat Dimeneiona:
�`
� �'
TQ.I9uaird � � -
Y 1 withfitilda4n
a ® a
t
t'ruiy
'
t
gar, and earth ground faults,
HPFFt2 Cebinat 18,65• W x 79.0' H x 5.2° D 42.29 W x
(
d � � TE LULAR
°
�, � ° v
' •
ue ��,
1 � 4�
+n '�
• Trouble Indication forsupervislon of the following:
46.2E H 73.23 D cm)
� - • a
HPFFi 2 HPFFI2CM�
-NADdmalta.
Large a ul meat enclosure EOBB-D4 24° W z 45.9' H
q p ( ):
CORPORATION
�
Tel uard Online Account � °
g
> -
HPFFi 2E HPFFI2CME
=-rr^ _�
-Auxiliary output.
x5.15 D(60.96 Wx11652 Hz t3.lD cm)
"'"-
Maria ement5 stem iG o u
g v
a o
np�a{
�°�,�p§"�
3
-AC Input
- .... °,._.._ .. °_.
-;�',
NAC Expander/Power Supply
�f�
�'�-'�� `,?
'c�F_ )
-eatterychargervdtage.
-EerN ground faults.
Product line Information
HPFFt2: 120A tra-rated ponies supply Unit (ncluAes redi
_
•••*�=�r
Teiuiar makes adopting ••
e nF u S
1`
y.:+,
y
� `;'
�'-
Description
j�I �
a�r�
O tionaltwo-hourdala t rACloss,
P Y °
encldsure,b���e sable andlnsiallationlnstmc0ons;]20VAC/:
ry
,BOHz,i
>I
f� -
cellular easy with a secure � �rt �n�
� -
° °
'��') 4
k'� -: t r 1 q
;
��il
.4,$�
.,
�;�:
- ^•� •� ..•.
• Separate Trouble and AC Fell Form-C relay contacts.
d =:
Internet portal. The :_- -
k
h
The Honeywell HPFF72(E)and HPFF72CM(E)are Noglica-
The Trouble Form-C ref conmctsselactable torlmmedlele
HPFF12E: 240VAC/SOHz version of HPFFt2.
C,
® T(�q
-
);, q:
� �
�,7, �I„
goo Appliance Circuit (NAC) Expander Power Supplies
ora2hour delay wiNAC failure.
NPFF72CM:t2.0A Ore mtedpowersupply (chassis mounted),
® e ® ® ® e
e ® ® aY�ir
straightforward web __= _
s�f{'•'�
dasi nod to e e d
g xt n Ne power capeblliilas o1 exisgng NACs
for devices.
26 AH battery charger capehllity:
Unit Includes mounting hardware, battery cable and Instmc-
�
�
� � 5 ir; �'j
Interface allows SeCUrlty __ --
,±�8 v.
� -%
-�'�s
end provide power auxlllary The HPFPo2 and
HPFFt2CM connects to any 12 or 24V Flre Alarm Control
g
§
- HPFFt2(E) supports two 12V 76AH batteries
lions for InsWllallon In large equipment endosure. t20VAC/
• - • . °
2�
• ,:
� {� t
dealers and Central Stations t0 - : _ =-
'�
t �4
Panel (FACP)oropemtes smndalone.
bauetles
60Hz.
-
-"'•�. �� t�,1 �`
vaww.TelguardOnlme.eom
�,
.�
HPFFt2 �
-HPFF72CME su rts two 12V 12AH er unit.
O PPo P
HPFPo2CME: 240VAC/50Hz HPFF12CM.
., r�tG n+ r _:
Ultkl and effidentl access
Q Y Y
`+ - �
as
They provide regulated and filtered 24VOC power to tour
• NAC Overload protecgon and indicatlon.
version of
'-f
I'{h
r � '�� `,�„t ; {, ;,
Telguard Digital based services
j
ti'� ° '.g. ,'i..
'� `
(a.
.. ' i
'IgS�i
'°
'
NAC's and an auxlllary output. The NAC outputs are rated at
Provision for mounting single or a cimuit atltlressable con-
HPP31W6: Class A (Style Z) NAC Ada pros. Increase Class A
droults from
- `
'_` - - • � �
�
24/7. This t001 has
�
x`
. ;,
+,
3.0 am s each and the auxllla out ut Is rated at 2.0 am s
P ry P P
(This output is conWuously supplied, In there-
trot or relay modules Inside the enclosure. (Use mounWg
210 4.
•Delivers full data reporting
� �
• Supports multiple alarm formats
advanced
�.
' t
�
v i'�'
even alarm, end
kitPN 90475.)
Lerga Equipment Enclosure: EO series cabinet for mounting
multi -level user authorization
tore must he taken Into account for power supply loedng end
HPFF72CM power supplies consists of a backbox (Fogg-D4)
and provides total aCCOUnt
r
�
„
battery size calculations). The combinedautput cannot exceed
Specifications
andalocking door (EODR-D4 orfCl-VDR-D48. Ordersa a-
) P
,-
t2.°amps•
mrety.
•Provides security supervision with
+Utilizes advanced encryption
management of uL usted
�` ��.x
� --�
�
The HPFF72 and HPFF72CM provide Independent output clr-
Primary Input Power: 120VAC, 60Hz, 6.4A standard;
240VAC, 60Hz, 3.2A on units wIN E suffix.
CMF�oas: Six-cimuit supervised addressable control mod
automatlC Self -test and S Stem
y
teCI1nOI0 for secure
gy
T61gUard Digital cellular alarm
'1
{fir
cult supervision so In the event of aNAC /ault Ne can notify
Y
.; ,;y,""�
ale activated through FACP progmmming on a select basis m
communicators.
1�' i
`
Ne attached FACP. In addition they have atrouble memory
feature that displays NAC) for
Secondary Power. 24 volt oparetionawo 7.2E AH ballades.
control powersupply activatlon or output
trOUble OUtpUtS
COmmURICatIOnS
?
past troubles (by rapid dlagnos-
Battery Charg(ng Capadty: Up to 28 AH ballades.
CMF-3Dg: Supervised addressable control module activated
� • zr
tics. Synchronlzaticn is built In forfive appliance brands.
HPFFt2 Cabinet: Holds up to two )BAH batteries.
p g gio acgvate owes su I.
through FACP ro mmmin p ppy
y'
„� �k
+:
�'
The HPFFt2 and HPFF72CM have two fully Independent
supervlsatl Initlating circuits that can be used br synchronized
a„.
HPFFI2CM: Holds up to two 12AH batteries.
BAT-12t20: Battery, 12 volt, 120 AH (hvo required).
BaCICUp Tran6mi55i0n Paths
'•;t
strobes and coded hams. Their NAC outputs may be config-
Total Output CumenL•120A max.
BAT-127g: 0auery 12 volt, 7.0 AH (two required).
Telg Uard Dlgltal CeII UIar SeCUCIty
p
IOr COm merCla 1, Retail,
�#-
used as any of the /allowing:
Standby Current: 0.075 A.
80474: Mounting kit; required to attach en addressable mod-
Financial and Fire System
Markets
Telguard Digital TG-7 & TG-8 are designed t0 function d6 backup
e: � .
�:i;
foarDlaa6B(BtyleY)
Auxuiary power output: 2.oA underall cOndiuons.
nlenntaNaconiro,airoaltboardQndadedwithaappty).
alarm communiptars. When communication is not available over
`y, -•
a
• two classA (style 2)
NAC Output RoUnga: fully
the telephone line, Telguard Digital the host
�`
• two Class 8 and one Class A
24VOC regulated, 3.oA max per
Listings and Approvals
switches alarm
��
• tourClassAwiththeoptionalHPP31W6ClassAadapter
cimuit (12.OA total).
+h
uanngaandapprovalabdawapplyman. maomepaaaa,ear-
The Telguard Dlgitai models TG-7 and TG-8 can
serve as primary or backup burglary alarm
systemscommumcauontothedlgital celiularnetwork. An alarms
'r1 f �
-
��fi
These power supplies contain an internal Bette char er
ry g
End-of-IJne Resistor Range: 7.9K to 25k ohm, watt. Prod-
sin modules may not be listed by cattalo approval agencies,
are then t2nsmitted via secure digital ceiluiar exactly as If the
`�
k• ' .
capable of charging up to 26.0 amp -hour (AH)bmterles.
act ships with 4 separate progmmming resistors. They are
orllsting may be In process. Ustetl under UL 8649th EdlUon.
COmmUnlCatOrS for retell) and flnanC161 markets.
In addltlOn, the TG-7 and TG-8 are designed
t, -•- -
�J
3.9K (5 each -only need one for progmmming), 2.2K (1 each),
signal had bean Conveyed over the telephone line.
Ni3
-
The HPFFt2 Is mounted In a lockable wall cabinet Nat can
HPFFI2CM:
4.7K (1 each) and IOK t each
( )
UL Listed: 524562
to be the secondary transmission path for commercial fire systems. Alarm signals are
accommodate up to two 18AH ballades. The HPFF72CM Is
Three modules In EQBB•D4
Common Trouble: 2.OA at 30VDC.
FM Approved
I '
'
designed to mount In Hone ell's tar a e ul meat enclosure
vw g q p
trensmitted over the digital cellular network when the telephone line or data network has
� j-,.
�� `�
,
(EOB&D4; oMer separately). Up to three HPFF72CM sup-
Reiey fall Relay: 2.OA et 30VDC.
Teiuiar CeIlUiar SBrVICe
�`-k"
'
� �
ii
pnaa can be maadedmaD•alzea ED cabmean pasigaha z, 3,
-Two cia66e&aria claaa A.
Inpat control cirowta: anmpaghle wiN lz and za vOc cam
been disrupted or compromised. This ensures critical data will reach the designated
''
.
� 5
and 4. Each HPFF7 RCM can accommodate two 12AH batter-
_Two gees A (Style Z).
trot panel NACs.
o
A
lea
-four Class A (requires Ne HPP31076 Class A adapter).
Input Control Current (elmm): 5.fi6 mA ®72 VDC, 12.28
mOnitOring Station.
Teiuiar Cellular Service provides natldnwide digital cellular network
� 1 '� '
'
-
One of the most challenging aspects of a retrolu epplkellon Is
locatin the exlslln Endoi-We EOL resistor 1 I-
g ( ) n these app I
Four tleld•programmable operational modes:
mA ®24 VDC.
- • t
coverage for all Telguard Dlgltal units. TelUlar's Communication
1' ,y-
g
rations that have EOL values other Nan Ne 3.9k nortnaily
-Pass-thmugh.
Tem erelura Ragn 3
p g: 2°F to t20°F (0°C to 49°C>.
UL.Listed, TE!Iguard Dlgltal CeilUlar SBCIJYiI�/
S
',i
Center is UL Listed and provides seamless connectivity between the
�er ! "
-•
�
used wiN Iha HPFFt2, a single resistor matching the exlstlng
-T mporal generator.
Relegve Humidity; 70% to 93% non•contlensing.
SOIUtiOnS t2nsmit fUli data from VirtUdily ail
� )� 1pt'�
alarm papal, the Telguard TG-7 or TG-8 and the cent2l station.
� �-
`
EOL can be used as a reference for ell Ne outputs. This Tea-
care speeds Instella8on and sydem checkout because Ne
_Sync generator.
.q °"� �i
`,
Teiuiar Technical Support provides a single point ofcontact for both
�
` - ;. y
�
� • • � �
r���
,�
actual EOL does hat need to be located and rhea eel in Ne
g
-Pass-through Filtered,
security and fire SyStemStO tentrel stations
,,1"'
Teiuiar Cellular Service and Telguard Dlgitai for a. complete cellular
+ ..
�,
�
cimuit. Therelerence resistor mustbe wlNin the range of l.ek
•Temporal Coding end sync protocols compatible with Ne fol-
Tnh e«umemenet lmentlaatobausoatarinsielbnonpwposee. wo tryto koep ourpmtlua mmrmatmnuptoema antlawimte. we caanol coverall spacnic
usingthe naNOrlWide digital cBIIUIdr network.
AlmmPatel _ Deuuwxotaork
�
security
,,, a,
`�*•_ ;.
to 25k.
lowing nogficagon appliance brands:
applmallans°ranndpate ag mBxxomoms al spe=ntanons ero aunledmcnen9a wnhom nog°e,
Symem&eroaiWSemgLslamtlimtlammk Honeywell
_ .wltnTtsa ,
�.
solution.
ktmn _
'�'
-
� '
NOTE:45epemle progrsmming msisfors for The HPFFf2ere pro-
-System Sensor,
of lnlpmallonN ins
ozmaby HoneywalllnlamollonW inc Nl,lghis raservotl UnaNhogmdusa of ihla tlaumanikshldy pmlilaned.
-
n` •:.. ...
� ;,
.. ....
• -
-
vlded In The hnrthvsre kit shipped with each HPFF72(E) and
HPFFf2CM(E). iheyare 3.8K (5oflheu are provided, need only
- Faraday
Telguard Digital uses advanced encryption
����-
-1
� ,�q �
:,
_gmseco.
'(
f 1prprogmmming),22K (1 each), 4.7K(f eech)and 10K(} eadl)
-Cooper-Wheelock
technolo for secure communications..
9y
Ta alas
Ph0°'u°B(� I' tammunlpatlpn
�a'af
�4 /
Features
Automation and Control Solutions
®i�6I' ��'
Superior• buiidin9penetration is achieved
Center
�,
�
� A �
j� e
,y -
..�
• Ustetl to UL Stenderd 864, 9N edition.
protocol pass-Nroughforsynchronizing large systems.
Honeywell
� � � TEt-ULAR
e.4
}i�.';,
• Four (4) power limited supervised nogOcellon eppllcagon
Two iullylndapentlant supervised lnputloulpulcomroldrcuitg,
12 Clintonville Road 1(877)HPP-POWR
through maXimUm aii0wabie trdnsmltting
peg p
t �*y�v's
cicuits (NAC's) capable of supplying +24VDC at 3.0 amp
Redundant activation opemgon for survivability.
Northford, CT 06472-1610 hpp techserv@honeywell.com
pOWeG
,,; ®
Telular Co oration 1-800-229-2326 $IiiriaLlris
rp
- § g.`i . 4 ❑•
ba 9 a
maximum each.
Supports FACP's Selectable Silence ability.
v/ww.honeywetlpoweccom
Emeroarmp Sarticae " �
2727 Paces Ferry Road, SE TelguardSales@Telularwm
• NAC eutpul drouils may be configured es any of the tallow•
i"9:
2.0 amp auxlllary continuously supplied °input
off s9safm
a: awrmio
,
'x' K � s�i°aw a
SUlte 1-800 I www.TelUlarcom �L
-
-Four Classe(sryle Y).
Eight status LEDs.
eusao�mi afra4m,mx
zownonmwaoim•malw,.um.
'S®
centreiSWon UL
AUanta, GA 30339 USA www.Telguard.com
PaBaBMt
e:.ti;e�'ra„`"-tee
LISTED
usrm
upMghtoTewtweomorowm, an Hghts,curvea. svednuuoas svelect
'
mchang�. Drawings may vary ]rom naval eguipment wppiied.
E & C Engi rs, n
Cart. of Auth # 5
13812 Geraniu lac
Wellingtan, FL 414 \\\ it i l i
Tei (561) 712 \\
email: eel@e ee Co •) U _ A
��' i'":•eras
���yQ -'-
�/ .' No •has
Eduardo (E Sa Sr, .�.
Registered Elects � Ineer STAl�E OF
P.E, #' 4118ry,. a jr�n `n0 a n
REVISION RECORD
REV DATE ISSUE DESCRIPTION
FIRE AND SECURITY
SOLUTIONS, INC.
3000 HIGH RIDGE RD. SUITE 9
BOYNTON BEACH, FL 3342E
TEL (561) 588-9542
EF-20000304
FIRE AND SECURITY SOLUTIONS, INC
MANUFACTURING
BUILDING FOR
PURSUIT BOATS
3901 ST. LUCIE BLVD.,
FORT PIERCE, FLORIDA
FIRE ALARM PLANS
�!1 ID�JRH
11.05.19 I AS NOTED 119
6HEETND.
FA-6
do-7114m • A1,65
REVISION RECORD
REV ( DATE ISSUE DESCRIPTION DY
N-ANN-80
NOTIFIER
80•Character LCD
O
Serial Annunciator by Honemell
General
The N-ANN-80 annunciator is a compact, bacIf it. 80.character
LCD fire annunciator that mimics the Fire Alarm Control Panel
1
(FACP) display. It provides system status indicators for AC
Power, Alarm, Trouble, Supervisory, and Not Silenced aondl
lions The N-ANN-80 and the FACP communicate war atwo.
wire aerial Interface employing the ANN-BUS commun'catian
format. Connected devices are powered, vie two additional
pores, theAN host FACP of a remote UL-listed, ened
supply. 604v.
pawersupply N-ANN-80 is black; for white order N-ANN-BD-W.
ply. N
The N-ANNSD displays English -language text of system pomi
^w6
��
information including device type, zone, independent poin
®
alarm, trouble or supervisory status, as well as any custom'm'Gfri
alpha labels programmed Into the control panel. It includes Can
•"°,"1, <. 1-:'-°"P ".°7S+'
trial switches for remote control of critical system functions. (A
$
keyswitch prevents unauthorized operation of the contrml
switches.)
-
Up to eight N-ANN-80s may be connected to the ANN-BUS of
each FACP. Minimal programming is required, which saves time
during
system commissioning. The N-ANN-80 is compatible
with NOTIFIER FACPs with an ANN-BUS, such as the NFW-50.
Features
• Trouble
• Supervisory
• Listed to UL Standard 864, Sit Edition.
sAlarm Silenced
• Backlit 80chamcter LCD display(20 characters x 4 lines).
• Mimics all display information from the host panel.
Specifications
• Control switches for System Acknowledge, Signal Silence,
Operating voltage range; 18 VDC to 28 VDC.
Drill, and Resat.
• Control switches can be independently enabled or disabled
• Current consumption a 24 VDC nominal (filtered and non.
et the FACP.
ewHable): 40 mA maximum.
• Keyswitch enables/disables control switches and mechani-
Ambient temperature; 32OF to 120°F (0'C to 490C).
catty locks annunciator enclosure
Relativeumitli g) 93%x 2% RH {noncondensin at 32°C
h
• Keysvilch can he enabled or disabled at the FACP.
k 2•Cs3°F).
• Enclosure supervised for tamper.
. 5.375" (13.65 cm.) high x SUIT (17A6 cm.) wide x 1,375"
(3.49 cm.) deep,
• System status LEDs for AC Power, Alarm, Trouble, SupeM-
• For use indoors In a dry location.
wry, and Alarm Silence.
• L
Local sounder can be enabled or disabled at me FACP.
• All connections are powerdimited and supervised.
• N-ANN-80 connects to the ANN-BUS terminal on the FACP
Agency Listings and Approvals
and requires minimal panel programming.
• Displays device type Identifiers, Individual point alarm, trou-
The ][stings and approvals below apply to the N-ANN-80. in
ble, supervisory, zone, and custom alpha labels.
some eases, certain modules may not be listed by Certain
• Time -and date display field,
approval agencies, or listing may be in process. Consult factory
• Surface mount directly to wall or to single, double, or 4'
for latest listing status.
square electrical box.
• UL: S635
• Semi-fivah mount to single, double, or 4' square electrical
• FM approved
box. Use ANN-SSSOKff for angled view mounting.
• CSFM: 712D.0028:240
• Can be remotely located up to 6,000 feel (1,800 m) from the
• MEA: 442-06-E Vol. 2
panel.
• Backlight turns off during AC loss to conserve battery power
The ANN•DUS
but will turn back on if an alarm condition occurs.
• May be powered by 24 VOC from the host FACP or by remote
POWERING THE DEVICES ON THE ANN-BUS FROM
power supply (requires 24 VDC).
AUXILIARY POWER SUPPLY
• Up to eight N.ANN-80s can be connected on the ANN-BUS.
The ANN-BUS can be powered by an auxiliary power supply
when the maximum number of ANN-BUS
devices exceeds the
Controls and Indicators
ANN-BUS power requirements. See the FACP manual for more
• AC Poser
information.
• Alarm
MENEENES
dn-7114:o • 5221a9-Page I art
Ill OOR(A)
Relay Module for
FireWarden Series Panels
The NC40OR(A) Addressable Relay Module provides NOTI-
FIER's FireWarden Series Intelligent Control panels with two
Isolated sets of Forme C dry -contact outputs for activating a
variety of auxiliary devices, such as fans, dampers, door hold,
ere, Control equipment, etc. Addressability allows the dry con-
tact to be activated, either manually or through panel
programming, on a select basis.
Features
• Built-in type identification automatically Identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two -wire
SLC loop.
• Integral LED 'blinks" green each time a communication is
received from the Control panel and turns on in steady when
activated.
• High noise immunity (EMF/RFI).
• Wide viewing angle of LED,
• GEMS sans with clamping plates for wiring ease,
• Direct Decade entry of address: Ot - 99 with the RmWar-
den-100-2(C) and 01 -50 with the FireWarden-50(C).
Applications
The NC-1 OOR(A) may be programmed to operate dry contacts
for door holders, Air Handling Unit shutdown, etc., and to reset
four -wire smoke detector power.
Construction
• The face plate is made of off-white heat -resistant plastc.
• Controls include two rotary switches for direct -dint entry of
address setting.
• The NC-100R(A) provides two Form-C dry Contacts that
switch together.
Operation
Each NC-10OR(A) uses one of me addresses on a SLC loop. it
responds to regular polls from the Control panel and reports Its
type and status, The LED blinks with each poll received. On
command, ft activates Its Internal relay.
Rotary switches set a unique address for each module. The
address may be set before or after mountng. The built-in
TYPE CODE (not seeable) will Identity the module to the con-
trol panel.
v
NC-10OR(A)
Specifications
Normal operating voltage: 15 to 32 VDC.
Maximum SLC current draw: 6.5 mA (LED).
Average operating current; 230 pA direct poll (CLIP mode),
255 pA group poll with LED flashing.
EOL resistance: not used.
Temperature range: 32°F to 120°F (0°C to 499C).
Humidityrange: 10%to 93%non.condensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4' (10,16 cm) square x
2.125" (5.398 mm) deep box.
Relay Contact Ratings
Load Description
Application
Maximum
Voltage
Current
Rating
Resistive
Non -Coded
30VOC
3.DA
Resisive
Coded
30VOC
20A
Resistive
Non -Coded
110VDC
DSA
Resistive
Non -Coded
125 VAC
D9A
Inductive (UR=Sms)
Coded
30VOC
DSA
Inductive(UR=2ms)
Coded
30VOC
t.OA
Inductive (PF=0.35)
I Nan -Coded
I 125 VAC
USA
dn-60383:A2. 06/17110-Page I of 2
ANN-BUS DEVICE ADDRESSING
Each ANN-BUS davits requires a unique address (ID Number)
In order to communicate with the FACP. A maximum of 8 devices
can be connected to the FACP ANN-BUS communication circuit.
See the FACP manual for more information.
WIRE REQUIREMENTS: COMMUNICATIONS CIRCUIT
The N-ANN-80 connects to the FACP ANN-BUS commu m.
tions circuit. To delermine the type of wire and the maximum wir.
ing distance that Can be used with FACP ANN-BUS accessory
modules, it is necessary to calculate the total worst case current
draw for all modules on a single 4-conductor bus. The total worst
was current draw is calculated by adding the individual worst
was currents for each module.
NOTE: For total worst trio current draw on a single ANN-BUS
rotor to appropriate FACP manual.
After calculating the total worst was current draw, the following
table specifies the maximum distance the modules can be
located from the FACP on a single wire run. The table ensures
6.0 volts of line drop maximum. In general, the wire length is I]m-
tled by resistance, but for heavier wire gauges, capacitance is
the limiting factor.
These cases are marked in the chart with an asterisk ('). Mask
mum length can never be more than 6.000 feet (1,800 m),
regardless of gauge used. See table below.
WIRE REQUIREMENTS: POWER CIRCUIT
• 14 to 18 AWG (0.75 - 2.08 truing) wire for 24 VDC power cir.
cult Is acoaptabla.
• NI connections are paver -limited and supervised.
• A maximum of eight WANN-80 modules may be connected
to this circuit.
Communication Pair Wiring Distance: FACP to Last ANN-BUS Module
Total Worst Case
Current Draw (amps)
22 Gauge
18 Gauge
1s Gauge
UGauge
0.100
1,852It
4,688 it,
' 6,000 it,
065000 ft.
0.200
926 A.
2,3014 ft
3,731 ft.
Sees ft.
0.300
617 f.
1,563 ft.
21488 ft.
3,937 ft.
0.400
483 ft.
1,172 ft.
1,666 ft.
21953 ft.
0.500
370 ft.
938 ft.
11493 ft.
2,362 ft.
0.600
309 ft.
781 ft.
1,244IL
1,969It
0.700
2658.
670It
1,066 ft.
15687 ft.
0.800
231 It
586 ft.
933 ft.
1,476 ft.
0.900
206 ft.
521 IL
829 ft.
1,312 ft.
1.000 (max.)
185 ft.
469 ft.
746 ft.
11181 a
WIRING CONFIGURATION ORDERING OPTIONS:
The fallowing figure illustrates the wiring between the FACP and N•ANN-80: Black 80 character LCD Annunciator.
ANN-BUS devices, N-ANN,80.W: White, 60 character LCD Annunciator.
ANN-BUS and power ANNS880KR-B: Black surface mount backbox with angled
wiring are supervised wedge,
and power-Ilmited. ANNSBBOKIT•W: White surface mount backbox with angled
® wedge.
ANN-BUS Devlca
NFW-50
FACP Wiring to ANN-BUS Device
' 1 "
Page 2 of 2-dn-7114:0 • 622A9
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may as in process. Consult fac-
tory for latest listing status,
• UWLC Listed: S635.
• CSFM approved: fil17300-0028:230.
• FM approved.
• MEA approved: file 72.01-E, Vol. 2.
Product Line Information
NCA00RA: Intelligent addressable relay module, ULC listed
model.
SMB500: Optional sudaca-mount backbox.
NOTE: For installation instructions, sea document 156-2593.001
and regal to the SLC WHng Manual, document 52304,
@009 by Honeywell intonational Inc. All rights reserved. Unauthorized use
of Ihb document Is slrk4y prohibited.
NOTIRER0Is a registered ftmema,kd Honeywelludomalional Inc
02010 by Honeywell International Inc, Ali tights tommod. Unauthorized use
of this dominant is slikUy prohibited.
ISO 9001 This document 15 not intended to be used for lnelallmon purposes.
We try to keep our product Information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
BdH0115611M11@tN@IC All speclficafions are subject to change without notice.
QUALITY SYSTEMS Madsiniheu.s.A.
Far more Information, Contact Nolirior. Phone: (203) 484-71619 FAX: (203) 484-7118.
wwwnoufiar.cam
Page 2 of 2-dn6WM A2. 06/17/m
FSP-951 Series
Intelligent Plug•ln Photoelectric
Smoke Detectors
The NOTIFIER FSP-951 Series intelligent plug -In smoke detectors
are designed for both performance and aesthetics. A new modem
9
sleek, contemporary design and enhanced awidel sensing chamber
Is engineered to sense smoke produced by a wide range of combus-
tion sources In accordance with more stringent code standards. The
FSP-951 Series detector sensitivity can be programmed In the con.
trol panel software. Sensitivity is continuously monitored and
reported to the panel. Point ID capability allows each detectors
address to be set with rotary, decimal address switches, providing
exact detector location for selective maintenance when chamber
contamination reaches an unacceptable level. Duel electronic
thembstors add 135°F (57°C) fixed temperature thermal sensing on
the FSP-951T. The FSP-951 R Is a remote test Capable detector for
use with DNR Series duct detector housings. FSP-951 series deter
tars are available for both Ramscan® and CLIP applications as
designated.
Features
• New modern profile for Improved aesthetics.
• Designed to most UL2687th Edition.
• Stable communication technique with noise immunity.
• Low standby current.
• Two -wire SLC Connection,
• Compatible with FlashScan® and CLIP protouol systems.
• Rotary, decimal addressing 11-99 on CLIP systems, 1-159 on
FlashScan systems).
• Optional remote, single -gang LED accessory.
• Dual LED design provides 3600viewing angle.
• Visible hl-color LEDs blink green every time the detector is
addressed, and illuminate steady red on alarm (FlashSoon Sys*
tams only).
• Remote test feature tram the panel.
• Walk test with address display (an address an 121 will blink the
detector LED: 12-(Pause]-1(FlastiScan systems only).
• Built-in functional test switch activated by external magnet.
• Built -In tamper•rmistant feature.
• Basted against back pressure.
Expanded Color options,
• SEMS screws for wiring of the separate base.
• Optional relay, Isolator, and sounder bases,
Specifications
Sensitivity:
• ULApplirations:0.5%to 4.0% per toot obscuration.
at ULC Applications: 0.5% to 3.5% per toot obscuratlon.
Size: 2.0' (5.3 cm) high; base determines diameter.
-8300.8: S N (15.6 cm) diameter.
- B501: 4" (10.2 cm) diameter.
For a complete list of detector bases see DN-60981.
Shipping weights 3.4oz (95.4g)
Operating Temperature range:
• FSP-951, 0'C to 50°C (32'F to 122°F).
• FSP-951T, 0°C to 38°C (32°F to 100°M
NOT BG12LX
Addressable Manual Pull Station
For FireWarden Series Panels
•
FSP-951 In B300-6 Base
• FSP-g51R Installed in a DNR/DNRW, -20°C to 700C (-4°F to
158°F).
ULNLC Listed Velocity Range: 0-400D Nmin. (1219.2 m1min.),
suitable for installation in ducts.
Relative Humidity: 10%-93%nommndensing,
Thermal Ratings: Faced -temperature setpoint 135°F(57°C).
DETECTOR SPACING AND APPDCAr/ON9
NOTIFIER recommends spacing detectors in compliance with NFPA
72. In low alillow applications with smooth ceiling, apace detectors
30 feet 19.1 m). For specific Information regarding detector spacing,
placement, and special applications refer to NFPA 72. System
Smoke Detector Application Guide, document A05.1003, is available
at systemseneoccom
ELECTRICAL SPECIRCA77ON5
Voltage Range: 16.32 volts DC peak
Standby Current (max. avg,): 200pA c 24VDC (one communim,
tion every five seconds with LED enabled).
LED Current (max.): 4,SmA O 24 VDC ("ON').
Installation
FSP-951 series plug -In detectors use a separate base to simplify
Installation, service, and maintenance.
Mount base (all base types) on an electrical backbox which is at
least 1.5" (3.81 an) deep. Fora chart of compatible )unction boxes,
see DN-60981.
NOTE: 1) Because of inherent supervision provided by the SLC loop,
end-ot-line resistors are fact required. Wiring T--taps" or branches era
permitted tar Slide 4 (Class B") wiring. 2) When using relay or wonder
bases, consult the ISO-X(A) Installation sheet 156.1380 tordevice limits -
dons between Isalatormodulas and ealatorbases.
of
•
DN-609R.A • 4/17//8-Page / of 3
DN-7001:8 • Al-380
General
The Noi fier NOT-BG12LX Is a state-of-theart, dual-acllon
requires two motions to salivate the slogan) pull station
,
that Includes an addressable interface for FireWarden series
Intelligent control panels. Because the NOTBGI2LX Is
addressable, the control panel can display the exact location of
the activated manual stollen. This leads Ore personnel quickly
to the location of the alarm.
Features
• Maintenance personnel can open station for lnspemon and
address setting without causing an alarm condition.
• Built-in bicolor LED, which Is visible through the handle of
the station, flashes in normal operation and latches steady
red when in alarm.
• Handle latches In down position and the word •ACTIVATED•
appears to clearly Indicate the station has been operated.
$
• Captive screw terminals wire -ready for easy connection to
SLC loop (accepts up to 12 AWG/3.26 man wire).
i
• Can be surface mounted (with SB-10 or SB-1/0) or semi -
flush mounted. Semi -flush mount to a standard single -
gang, double -gang, or 4' (10.16 cm) square electrical box.
• Smooth dual -action design.
The NOT-BG12U(
• Meets ADAAG controls and operating mechanisms guide-
Addressable Manual Pall Station
lines (Semlon 4.1.3[131); meets ADA requirement for 5 lb.
maximum activation force.
Operation
• Highly visible.
• Attractive shape and textured finish.
Pushing In, then pulling down on the handle causes it to latch
In the down/activated position. Once latched, the word •ACTI-
• Ke reset.
Y
VATED' (in bright yellow) appears at the top of the handle,
• Includes Braille text on station handle.
while a portion of the handle protrudes from the bottom of the
• Optional trim ding (BG12TR).
station. To reset the station, simply unlock the station with the
• Meets UL 38, Standard for Manually Actuated Signaling
key and pull the dooropen. This action resets the handle; clos-
Boxes,
ing the door automat of ly resets the switch.
Each manual station, on Command from the control panel,
Construction
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow address settings
Shell, door, and handle are molded of durable LEXAN® (or
If - 99 on FlreWarden-100.2,1 -50 for FireWarden-50),
po[i atbonate equivalent) with a textured finish.
Architectural/Engineering
Specifications
Specifications
• Normal operating voltage: 24 VDC.
Manual Fire Alarm Stations shall be non -coded, with a key-
• Maximum SLC loop voltage: 28.0 VDC.
operated most lock in order that they may be tested, and so
• Maximum SLC loop current: pA.
designed that after actual Emergency Operation, they cannot
• Ambient Tempemture: 32°F to l2OoF (O'C to 4g'C)
be restored to normal except by use of a key. An operated sta-
• Relative Humidity: 93%s 2% PH (noncondensing) at 32°C
tion shall automatically
condition itself so as to be visually
detected as activated.
Manual stations shall be constructed of
x 2°C (90°F x 3°F)
red -colored LEXAN (or polyearbonate equivalent) with clearly
• For use Indeorm in a drylocation
visible opemgng Instructions provided on the cover. The word
FIRE shall appear on the front of the stations In white letters,
Installation
1,00 Inches (2.54 am) or larger. Stations shall be suitable for
surface mounting on matching backbox SB-10 or SB-VO; or
The N T-B 12 mountse
The NOT-BGi2LX will mount semi -Gush into asingle-gang,
a sinicalouilet
semi -gush mounting on a standard single -gang, double -gang,
standard 4" cm) square
cloubox,
( era) square electrical box, and shall be Installed
or will surface mount to the model SB-10 or SB-1/0 sur-
within the the limits defined by the Americans with Disabilities Act
face backbox. If me NOT-BG12LX is being semi -flush
(ADA) or per nationaVfocai requirements. Manual Stations
mounted, then me o tional trim ring (BG72TR) may be used,
P
shall be Underwriters Laboratories listed.
The BG12TR Is usually needed for sent) Aush mounting with 0
(10A 6 cm) or double -gang boxes (not with single -gang boxes).
DN-70ai:8.1Ur2asKIN-Page 1 of 2
Agency Listings and Approvals 822481•111H: White, Isolator detector base.
These listings and approvals apply to the detectors specified In this 8224514V: Ivory Isolator detector base.
document. In some cases, certain detectors or applications may not B224SIA-WH:While, isolator detector base, ULC fisfng.
be listed by certain approval agencies, or listing may be in process. B224131A•IV: Ivory Isolator detector base, ULC listing.
Consult factory for latest listing status.
• UL/ULCUsted:S971 B200S-WH:White, Intelligent addressable sounder base capable of
producing sound output in high or low volume with ANSI Temporal 3,
• FM Approved ANSI Temporal 4, continuous tone, marching tone, and custom tone.
• CSFM: 7272-0028:0503 Uses FlashScan protocol.
Product Line Information B200S IV: Ivory, Intelligent addressable sounder base Capable of
producing sound output In high or low volume with ANSI Temporal 3,
NOTE: ANSI Temporal 4, Continuous tone, marching tone, and custom tone.
• Detectors must be mounted to one of the Intelligent Bases listed Uses FlashScan protocol.
below. B200SA•WH: Same as B20OS-WH, ULC listing.
• A" suIrm Indicates ULC UmadmodeL B200SA4V: Same as B20GS-IV, ULC listing.
• •IV"std6xIndies tea FiashScarl® and CLIP de vice. B200SCOA-WH: White, Intelligent, programmable sounder base in
._ _ _ - English/French (required in Canada for ULC applications with SO
FSP-951;Whlte low-prgfilq_infailigent photoelectric sansdf,;PashS;) Series detector applications,
can only.:
8200SCOA•N: Ivory Intelligent, programmable sounder base in
FSP•951A: Same as FSP-951 but with ULC listing. English/French (required in Canada for ULC applications with SO
FSP•951•IV: Ivory, low -profile intelligent photoelectric sensor. Series detector applications, ULC listing.
FSP-951A-IV: Same as FSP-951-IV but with ULC listing. 82005•LF•WH: White, low Frequency Intelligent, programmable
sounder base. Produces a fundamental frequency of 520 Hz +A
FSP-g51T: White, same as FSP-951 but Includes a built-in 135°F 10% with a square wave or its equivalent; designed to meet the
(576C) fixed -temperature thermal devise. FlashScan only. NFPA 72 sleeping space requirement.
FSP-951TA: Same cs FSP-951T but with ULC listing. B200S•LF-IV: Ivory, Low Frequency Intelligent, programmable
FSP•951T-IV:Ivory, same as FSP-951T but lnclutlesebuilt-in 135°F sounder base. Produces a fundamental frequency of 520 Hz+F
FSP"S ITAVemory, same
ture marmot device. 10% with a square wave or its equivalent; designed to meet tha
NFPA 72 sleeping space requirement.
FSP-951TA4N: Same as FSP-951T-IV but with ULC listing. B200SR-WH: White, Intelligent sounder base copabla of producing
FSP951H:1 While,t tow-pra0le IntelllgenC� phoi electric'-] sensor;; sound output with ANSI Temporal 3 or Continuous tone. Intended for
remolelem cap able. For use with ONFWNRW.FlashScanonly.i retrofit applications.
FSP-951RA: Same as FSP-951R but with ULC listing. For use with 82005R4V: Ivory, Intelligent sounder base capable of producing
DNRA. sound output with ANSI Temporal 3 or Continuous tone. Intended for
retrofit applications.
FSP•g51R•IV: Ivory, low -profile intelligent photoelectric sensor, remote test capable. For use with DNPA)NRW. 8200SRA•WH: Same as B200.SR-WH with, ULC listing.
FSP-951 RA -IV: Same as FSP-951 R-IV but with ULC listing. For use 8200SRA-IV: Same as 8200SR4V in Ivory color, ULC listing.
with DNRA. B200SH-LF•WH: White, Low Frequency Intelligent, programmable
INTELQGENT BASES sounder base. Produces a fundamental frequency of 520 Hz +A
10% with square wave or its equivalent; designed to most me
NOTE: Fordeteils an intelligentbases, see DN-609B1 NFPA 72 sleeping space requirement. Intended for retrofit applies -
bons.
8300.6:White, 6" base, standard flanged low -profile mounting base, 8200SR-LF4N: Ivory, Law Frequency Intelligent, programmable
8300.84V: Ivory,6" base, standard flanged low -profile mounting sounder base. Produces a fundamental frequency of 520 Hz +A
base, 10% with a square wave or Its equivalent; designed to meet the
8300A G: Same as B300.6, ULC listed. NFPA 72 sleeping space requirement. Intended for retrofit applies-
8300A•64V: Ivory, 6" standard flanged tow -profile mounting base, lions.
ULC listed. MOUNTING KIT$ AND ACCESSORIES
8300-6.813: Bulk pack of B300.6, package contains 10 TR300: While, replacement bongo for B21OLP(A) base.
8501•WHfTE: White, 4" standard European tiangeless mounting TR300-IV:Ivory, replacement flange for B21OLP(A)Low.
base. UWLC listed. RA10OZ(A): Remote LED annundator. 3 - 32 VOC. Mounts to a
B501-BL: Black, a standard European bungalow mounting base. U.S. single•gang electrical box. For use with 8501(A) and B300(A)-
ULNLC listed, 6.
B501-IV: Ivory color, 4" standard European flangeless mounting M02,0440: Test magnet.
base. ULNLC listed. M02.09.00: Test magnet with telescoping handle.
8501•W HITESP: Bulk pack of ELSOI-WHITE contains 10.
B224RO-WH: While, relay base.
B224RB-IV:.Ivory, relay base.
B224RBA-WH: White, relay base, ULC listing.
B224RBA4V: Ivory, relay base, ULC listing.
Page 2 of 3-DN-E09" A • 4117/I8
Manual stations shall connect with two wires to one of the con -
Lot panel SLC loops. The manual station shall, on command
from the control panel, send data to the panel representing the
state of the manual switch. Manual stations shall provide
address setting by use of rotary decimal switches.
Product Line Information
NOTBG12LX: Dual-acllon addressable pull station. Includes
key locking feature.
SB-10: Sudace backbox; metal.
SB-VO: Surface backbox; plastic
of station without door
Terminal Connections:
1 SLC (-); 2 SLC (+)
rig Haul
hived lduq
T
Cover open to show easy access to miniature
monitor module, rotary switch, and UL label.
Patented:
U.S. Patent No, D428,351; 6,380,B46; 6,314,772; 6,632,108.
SG72TR: Optional trim ring.
17021, Keys, set of two.
Agency Listings and Approvals
In some cases, certain modules or applications may not be
listed by certain approval agencies, or listing may be in pm-
Cass. Consult factory for latest listing status.
• ULLlsted:S692
• MEA: 67-02-E VaL IV
• CSFM:7150.0028:199
• FM Approved
�7
'Do not remove tab.
NotHIa106aregietamtllmdamark of Honeywell Inlamatlonallnc LEXANO
Is a registered trademark at GE Plastics, a subsidiary of General Electric
coan
Wines by Honeywell International Inc. All rights reserved. Unauthorized use
of th s document Is sltklty pmhblled.
ISO 9001 This document is notlnbanded to be used for installation purposes.
We try to keep our product Informinon up-to-date and accurate.
We cannot coverall specl0c applicaflons or anticleate all requirements.
DMNBr4&MASENM016 All spedfiptlons are subject no change without notice.
Im
t OALITY SYSTEMS Modolnlheu.S.A
For morn Information, contain Noliflar. Phone: (203) 4647161, FAX: (203) 484-7118.
wwwriotifler,com
Page 2 of 2-DN-7Wl:8 • to2020M
E & C Engi
Cart. of Auth # 2E
13812 Geranium
Wellington, FL
Tel (561) 712I
tauarao
Registered Eli
P.E. # 41186
Date:
pr S 1/7
r ,SF •
o 411 u
k 5' F
QNAI� r
FIRE AND SECURITY
SOLUTIONS, INC.
3000 HIGH RIDGE RD. SUITE 9
BOYNTON BEACH, FL 33426
TEL (561) 588=9542
EFn20000304
FIRE AND SECURITY SOLUTIONS, INC
MANUFACTURING
BUILDING FOR
PURSUIT BOATS
3901 ST. LUCIE BLVD.,
FORT PIERCE, FLORIDA
FIRE ALARM PLANS
F4
FAJ
REVISION RECORD
Monitor Modules
DN-6999:C
NMM•100(A),NMM•100P(A),
C ® ®
N i�'
NMM•100P(A) Mini Monitor Module
Dimensions: 1.3' (3.302 cm) high x 2,75" (6.865 cm) wide x
0.65•(1,651=Ideep.
NDM•100(A) Dual Monitor Module
MEA: 72-01-E Vol. 2 (NMM-100, NMM-IODP, N2M-100);
227.03-E
®T E
O
BuiltntypeIdentificationautomaticall Identifies this device
Y
Vol. 3(NOM-100)
N2M•100A and NDM•100A
( )r O
as monitor to the anal.
P
were length: 6'(15.24 cm)minimum.
for use in
The NDM-t00(A) Ova Monitor Module is o Independent
Intelligent iwawire system, It two independent two-
y
1 )
I
I I
for FireWarden Series Panels
by Honeywell
• Poweredirectiybywo-wireSLC loop. Noadditional power
provides
wire circurits two consecutive
Product Line Information
II
required.
uired.
N2M•100(A)Interface Module
esheft.gdevico
normaparofe,
bleofmIDCs)g
tfire
addresses lttscvisoryofrtes. godule
NOTE::4"sufru indices tea ULGlisledmodel.
-- •..,•._+r`v`IraaO'
�(TEK
- • .. - .. • -
High
High noise (EMFrAFi) immunity.
Supports compatible two -wire smoke detectors.
alarm end supervisory devices. The module has a single panel•
Thehas a single panel,
LED.
NMM 100(A) Monitor module.
Surge Protection
r9
General
Tinned, stripped leads for ewe of wiring.
Supervises IDC wiring and connection of external power
controlled
NOTE: The NDM-100(A) provides two Style B (Class B) IDC air-
NMM t00P(A) Monitor module mint atuje i
Four different monitor modules are available for Nolifier's Fire-
:»
• Direct Decade entry of address; 01 - 99 on RreWarden-
700.2, O7 -50 on FireWardeo-50.
source.
cults ONLY Style D(Class A) IDC circuits are NOT supported in
NZM100(A): Monitor module, two -wire detectors,
-'--
DITEK's DMIriW Series of Surge protective devices are
Warden Series intelligent control panels for a variety of appll-
- �- - �••, "' '-
High noise (EMFIRFI) immunity
SEMS
anyapplicalion.
NOMAOO(A): Monitor module, dual, two independent Class 8
designed and manufactured to meet the standards of the life safety
cations. Monitor modules supervise a circuit of dry -contact
R
screws with clamping plates for ease of wiring.
NDM-100(A) SPECIFICATIONS
circuits.
industry, These Compact, SPD's
Input devices, such as conventional heat detectors and pull
stations, or and paver a circuit of two -wire smoke
4
y 141 0 1 00 E 0 i
13 2 2
• Direct Decade entry of address:, 01 - 99 on RreWarden-
LED 01
normal
Normal operating voltage range: 15 to 32 VDC.
SM6500: Optional surface -mount baddaox.
120V, 240V and 120/240V
parallekinourt are available for
systems; and are widely used to protect
M-100onitor
detectors (NZM-100(A)).
1 1 3
es don
LED Hashes during
fleshes operation,
Maximum current draw: 6.4 mA (LED an).
NOTE: See installation Instructions and rater to the SLC Wiring
f12
NMM•100(A)isasfentlerd-sized module (typically mounts toe
.�
r '"""
LOOPS
11 4 4
�3
10 5
to In irate alarm
LED latches steady to Indicate alarm on commend tram
Average operating current: 750 pA (LED flashing).
Manuel, PN 52304.
'
♦
a)aRrt panels and
small footprint enables
Other dedicated branch CI[CUIi )Gads. Their
installation in
4' 110.16 cm) square box) that supervises either a Style 0
u 6
6 B 7 8 e 8 7 6
control panel.
Msximum IDC wiring resistance: ISOO ohms,
a vane of locations.
tY
(Class A) or Style B (Class 8) circuit of dry -contact input
TENS ONES
The NZM-100(A) Interface Module Is intended for use in intelli•
Maximum IDC Voltage: 11 Volts.
devices.
M
gent, addressable systems, where the individual address of
Ammodit4 is a miniaturemonitor module- a mere 1.32;
each motlule is selected using hu'lt-in rotary witches. This
Maximum IOC Current: 240 ILA-
(3.302 rim) H x 2.75' (6:965 cm) W x 0:5' (1.270 cm) Dncat;.
°
l�j
module allows intelligent panels to interface and monitor two-
EOL resistance: 47K ohm.
Part Number:,
_
DTK-120HW DTK-24DHW
supervises a Slyle,8 i(Claw e) circuit: of dry•coruact'input;
TIM
3
wire conventional smoke detectors. It transmits the status (nor-
DTK4201240HW
devices. Its compact design allows the NMM-IODP(A) to bet
.. 43
tu-�
O V
mat, open, or alarm) of one full zone of conventional detectors
Maximum SLC Whine resistance: 40 Ohms.
--
Single Single rp
`manted in a singteignng,boxbehind the device t monitors.!.
-
rl ,f 4 - ,)r • 4
d
- p S
beck to the control panel. All two -wire detectors being moat-
Temperature range: 32° to 120°F (0° to 49°C).
Product Features
Service Velta e:
9
g Split
)
(120VAC (2W+G,
qt
bred must be UL compatible with the module.
G
(3W+G),
NZM-YOo(A) Is a standard -sized motlule that monitors antl
_'• . �
>•
Humidity range: l0%to 93%(norrcondensin9).
120VAC 240VAC 1201240VAC
supervises compatible two -wire, 24 volt, smoke detectors one
- ,
NZM-100(A) APPLICATIONS
Dimensions: 4.5' 11.43 cm high x 4' 10.16 cm wide x
( ) ( )
• Approved for 20A circuit breakers
MCDV:
Style D (Class A) or Style B (Class 8) circuit
Use the monitor a zone of re smoke
9
2.125' (5.386 cm) deep.
Weatherproof
•NEMA 4X Weathe roof enc105Ure alioWs
15N, 32N, t5L.
is a duel monitor module that
NDMtors rtwo
NMM•100(A) fNPa H)
detectors. The monit re
The monitored ed as
may be wired as an NFPA
for in
Protection Modes:
L-G, L-N, N-G L-G, L-N, N-G L-G, L-L, L-N, N-G
L-N.
an) rvises Intl
monitors and supervises two Independent two -wire Style a
StyleB(Class
Style a (Class B) or Style D (Class A) Initiating Device Circuit
NOM•f00(A) AUTOMATICADDRESSING
use harsh environments
(Class B) dry -contact Initiating device circuits (IDCs) at two
The NMM400P(A) Mini Monitor Module can be installed in a
A 3.9 K ohm End-o1•Line Resistor (provided) terminates the
The NDM-100(A) automatically assigns itself to two address-
• Diagnostic LED indicates round presence,
g p
Voltage Protection
700V L-G 11200V L-G, 700V L-G. L-N
separate, consecutive addresses in intelligent two -wire systems.
NMM-100(A) OPERATION
single -gang junction directly behind the monitored unit. Its
and of the Style a or 0 (class B or A) circuit (maximum IDC
able points, starting with the original address. For example, i1
system power and SPD function
Rating;
700V L-N 11200V L-N 11500V L-L,
small size and light weight allow it to be Installed without rigid
loop resistance Is 25 ohms). Install ELR across terminals 8
the NDM-100(A) is set to address "26", then It will aulomati•
1,500V N.G ZOOOV N-G 11500V N-G
NMM•100(A) Monitor Module
Each NMM-100(A) uses one of the aveliable module
addresses on an SLC loop. It responds to regular from
mounting. The NMM-100P(A) Is Intended for use in intelligent,
and 9 for Style D application.
tally assign itself to addresses "26" and "Zr.
• Complies with ANSLAEEE C62.41 and
Surge Current
• Built-in ntifies this device
tnitormnfitioetiote
polls
the control panel and reports its type and the status (op rwhor-
two -wire systems where the Individual address of each module
is selected using
gt fro wire tallier-
NZM-100(A)OPERATION
NOTE: 'Ones" addresses on the NDM-Y00 A e d, 2, a, e, ore
Od
C62.46 Category
eg ry8standards
Rating
g;
SO,000A 50,000A t0O,0E0A
comaticanel.
es a monitor module to the control panel.g
reel/short) of its Initiating Device Circuit (IDC). A flashing LED
In for
device circuit for normally -open -contact lire alarm end
Each NZM•100 A uses one the
)
only. 6 and 7 use the (ref address, end terminals Bend
-- - - - �- - - - - -
SCCR:
---
Indicates that the module is In communication with the control
t
security devices. NMM-100P(A)
( of eva0eble module
the second
9 use the secondeddmss.
- � - - - � � �- - � �� - - - - �
tOkA
• Powered directly by two -wire SLC Imp. No additional power
panel. The LED latches steady on alarm (subject to current
addresses on an SLC 1po It responds
p. ponds to regular polls from
Applications
Nominal Discharge
required.
limitations on the loop).NMMd00PA
() APPLICATIONS
the control penal and reports its type and the status (open/nor-
its Initietin
CAUTION:
Q
.Current Rating �_
1OkA
• High noise (EMFARFO Immunity.
NMM•100(A) SPECIFICATIONS
Use to monitor a single device or a zone of four -wire smoke
reel/shod of
) g Device Circuit (IOC). A flashingLED
Indicates that the module is in communication with the ntrol
Avoid duplicating addresses on the system.
•Fire Alarm Control Panels
• SEMS screws with clamping plates for ease n wiring.
Nominal operating voltage: 15 to 32 VDC.
detectors, manual fire alarm pull stations, waterllow devices, or
panel. The LED latches steady on alarm (subject to current
• Equipment Panels
Mechanical Characteristics
• Direct Decade en of address: Ot - BB on Fire Warden•
entry
other normally -open dry -contact devices. May also be used to
Y
limitations on the loop).
100.21 Of -50 on RreWartlen•50.
Maximum current draw: 5.0 mA (LED on).
monitor normallyopen supervisory devices with special super-
Installation
• Dedicated Blanch Circuits
Connecgon Method:
'/.' NPT Parallel Wired
• LED flashes duringnormal operation and latches an stead
P Yp
Average o operating
g current: 350 pA (LED flashing), i core-
visory indication at the control panel. Monitored circutt/device
NZM-100(Aj SPECIFICATIONS
-----EMA------.-.-_
'
to Indicate elertn.
munication every5 seconds, 47k EOL.
Is wired as an NFPA Style a (Class B) Initiating Device Circuit.
Nominal a
operating voltage: 15 to 32 VDC.
NMM-100(A), NZM-100(A), and NDM-100(A) modules mount
• Pumps,
ps, Motors and Lift Pump Stations
.Housing:
NEMA 4X
The NMM-100(A) Monitor Module is Intended for use In intelli-
Maximum IDC
A ohm End -of -Line Resistor (provided) terminates the cir-
Maximum current draw: 5.1 mA (LED on),
am) square,
directly lect real ardbox 4• They
deep, electrical box. They he to
to cm)the
Temperature Range:
J7°F-176°F -3
( 5°C-80°C)
wiring resistance: 40 ohms.
cuiL
it.
they also mounted
moue ed the
- . _ ... - _ .....
address of each
gent )coo -wire systems, where the tin rot
Is
EOL resistance: 47K ohms.
Maximum IDC wiring resistance: 25 ohms.
SMSSOOsurface -mount box. Mounting hardware and
_.... - _ ...... _ -
Maximum Humidity:
95% non•condensing
module rotary
selected using the built-in rotary witches. it pro-
NMM-100P(A) OPERATION
Instructions
Ron Instructions are provided with each module. All wiring
l wiring
Accessories
vides either a two -wire or four -wire fault -tolerant Initiatin 9
Temperature range; 32°F to 120°F(DECto 49°C
P 9 ( )
Each uses one or the available module
Average operating current: 30D pA, 1 communication and 1
must conform to applicable local codes, ordinances, and rise,
Dimensions:
3,5'L x 1.89'W x 3.4'H
Device Circuit (IDC. for ontact fire alarm and
Humidity range; 1o%to 83%noncondensing.
see an n SLC
addresses on an SLC loop. It responds to regular polls kom
LED flash every 5 seconds, 3.Bk so[.
leaons. These modules are Intended for power -limited wiring
•DIN Rail MountingKt-DTK-DRK
(88.9mm x 48 3mm 864mm)
module
supervisory devices. The motlule has a panel•coniroiled LED
a
Indicator.
Dimensions:
the control panel and reports its type and the status (o en/nor-
p
SOL resistance: 3SK ohms.
only.
- - - - -
Weight
x
wide x
4.5° deep.
high x 4' 0,16
1.25' (3.175 an) deep. Mounts to a 4'
Mounts
reel/short) of its Initiating Device CimuH (IDC).
External supply voltage (between Terminals T3 and T4):
The NMM-t OOP(A) module is Intended to be wired and
- - -- - - --- - - _ _ - ....... _
0.551b. (0.25 kg)
NMM-100(A) APPLICATIONS
c ) s
(10.16 cm) square x
2.12T (5,398 cm) deep box.
NMM•100P(A) SPECIFICATIONS
DC voltage: 24 volts power limited, Ripple voltage: 0.1 Vrms
mounted without rigid connections inside a standard electrical
Dimensions
-
Use to monitor a zone four -wire smoke detectors, manual
maximum. Current: BO mA err module maximum.
P
box. All wiring must conform to applicable local codes, ordi-
0.r8 (-'
Quality, Standards &
Approval
PP
fire therm pull stations, w devices, or other normally-
Nominal operating voltage: 15 to 32 VDC.
Temperature range: 32°F to 120°F (0°C to 49°C).
nences, and regulations.
w4•-tauPr
Agen
Agency Approvals:
UL 14494m Edition,
activation
open dry -contact alarm activation devices. May also be used
Average operating current: communication every
cUL
to monitor normally -open supervisory devices with special
A Max.1
5 seconds, 47k EOL; 600 pA ez(Communicating, IDC
Humidity range: IO%to 93%noncondensing.
Agency Listings and App1'OV81S
SPD Type:
Type SPD
supervisory Indication at the control panel. Monitored circuit
Shorted).
Dimensions: 4.5' (11.43 cm) high x 4• (10.16 cm) wide x
In some cases, certain modules may not be listed by certain
Warranty:
Ten Year Limited
may be wired as an NFPA Style B (Class B) or Style D (Class
Maximum IDC wiring resistance: 40 ohms.
1.25' (3.175 cm) deep. Mounts to a e (10.16 cm) square x
approval agencies, or Rsting may be in process. Consult fao
190
z0e
A) Initialing Device Circuit. A 47K ohm End -of -Line Resistor
Mazlmum IDC Voltage: it Vohs.
ge'
2,125• (5.398 cm) deep box.
tory for latest listing status.
y for
(provided) terminates the Style B circuit. No resistor Is
required for supervision of the Style D circuit.
Maximum IDC Current: 400 IA.
• Sties
resistance: ohms.
SOLperature
°
• ULC: S635
0.35 z06 oma (--1.ea
FM Approved
Tem35
ge:
range:
Temperature range: 320Flo 120°F (0°C to 480C).
• CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM-
w.,n.,w
e•rw•+ma�re,., coma,rmm..ym,y,,,r,.�Plm.grecu,n„x,,,,,...,m
Humltllty range: 70% to 93%noncondensing.
100); 7300.0028:0237 (NOM-100)
mw>•<rarewaran.urasrrsm-amoeme.wmn.rmmn„•bm.•mco.
OneDREKCala 17205tarkey ftoatl•targo, FL33771 Dec Number.$PS-ID0O57.00i Revl4O511A MADE IN
tAlq-7512345Dtrat 727411250W 020180fla Carp. I IgnlgO-H1a �L 6s
Peat f41A84726100
Page
1 ort
C:.G.=�
ON fi999;C•10N62010-Page� oi4
Page 2 of 4-aN-6999:e•10MMIO
DN�6999:C• IOMEW10-Page 3 oA
l iredlteksurgaprotedlon.com
mm trt=
Product Features
• Sides connection, parallel function adds no
resistance to loop circuits
• Protects up to 2 pairs of SLC wire
Applications
• Alarm Panel SLC Circuits
• 4.20 mA Current Loops
Accessories
• DIN Rail Kit -pad number DTK•DRK
DITEK's DTK-2LVLPF is specifically designed to
protect 24V SLC loops on fire alarm control panels where
a current limiting feature is required. Its low•current fusing
prevents induced surges from damaging sensitive (and
expensive) control boards.
111111111
Service Voltage:
24V
!: MCOV: -
38V
j. Clamping Voltage:
47V
`Protection.Modes:
Line-Ground(All)
:. Surge Current Rating:
2,000 Amps per pair
-Max; Continuous Current:
200 mA
Mechanical Characteristics
Connection Method:
#22-#10 AWG screw terminals
:i Housing:
ABS
Operating Temperature:
-40°F-158°F(40°C-70°C)
<' Maximum Humidity:
95% nomcondensing
ensions:.
3.0"Lx 1.8^Nx 1.6'H
(76mm x 41mm x 41mm)
Weight:
2.65oz (75g)
Wiring Example: Quality, Standards &Approval
EQUIPMENT amecrso Agency Approvals: UL497B
wrwr�iFruaeiu .Warranty: Ten Year Limited Warranty
Duct Smoke
Detector Accessories
Expand the versatility of the InnovairFlex" line of duct
smoke detettors with System Sensornotfficotionend
test accessories.
Available
Accessories
Duct smokedetector accessories add functlonaliry to [he duct
APA751
Piero Mnundato,
smokedetectlon system byallowing quick, mnvenlentinspectbns
MHR
Mini-Hom, Red
at eye level and effective audihle and visible notification options. Ali
System Sensor tied srrroke detectors and accessories are ULlisted.
MHW
Mid-Hom,Whlte
M10oLM1OOZA
Renate Annunclator
The APA751 plezo annunciator, which replaces the APA451 with
anew, Improved look, provides an audible alarm signal,a fed LED
RT5151
Remote TestStatlon
10 Indicate alarm status, and a green LED to indicate powerstatus
RTSi51KEY;
iemoiafearStation vilth Key
It is Intended for use with System Sensor-4 wire conventional duct
RT52
MuIt45ignaling Accessory
smoke detector applications without a system control panel, to
comply with NFPA 90A.
A05
Add -On Strobe
The MHR and MHW SpectrAlere Advance minbhorns feature
RT52-AOS
Mulil-Signaling Accessory
temporal or continuous tones at high and low volume self7ngs.
Their small footprint allows mounting to single -gang back boxes for
applications where a small device Is desired.
The RA100Zand RAt00L1 remote annunciators are designed
for both conventional and Intelligent appllcatlons.Thelrred LED
provides visual Indication of an alarm condition.
The RT5751 and RT5151KEY remote test stations are automatic
fire detectaraccessories designed to test duct smoke detectors
tram a convenient (oration. For 4-wire detectors, the ATS151KEY test
statlonfeatures amulti-colored LED that alternates between steady
green and red. far 2-wire detectors, the LED Illuminates red for alarm.
The RT52 and RT52-AOSreulti-signaling accessories are designed
to work with InnovairFlex 4 wire conventional duct smoke detectors.
These accessories Include a key switch that on be used to select
one of two connected sensors to he tested, reset, or both by a push
Agency Listings buaon They also enable sensitivity measurements using
the SENS.RDR sensitivity reader (sold separately). The AOS (Add -On
Strobe) Is an optional accessory Included with the RT52-AOS model.
�L FM
usTm
Specifications, Duct Smoke Detector Accessories
Vohage
Regulated 24 VDC
Powe Requirements
AWrm LED23Io32vOC, 12 mA mac
OperalingVohage
161o33VOC
Taal Cunene: 105 mAmac
Maximum Alarm Current
30 mA
Test Switch
MVAp32VDC
iempemlure Rarge
WC to 49'C 02T to 120T)
Reset Switch
IOVA032VDC
RelalNe Humltllty
10 to 93%nomcorxknsllg
Alarm Response Time
40semrdsmac
Vole Gauge
12to18AWG
Temperature Range
-106CI06TC(14Tto 140•n
Dlmensbns
4.6-Hx 29-Wx.AS*D
Relative Hamidity
95%noncondensing
wire Gauge
141018AWG
Voltage
Regulated 12 DC or FWR(Full Wave Rectified)
Dimensions
4.8- H x 290-W x 1.4-D
or Regulated 24VDC a FWR
-
OpaalingVohage
8to33VDC
Pawa Requirements
Power lED(Greenk 14 to 35VDC 12 mA max
(91033 VDC with Sync-Orcuh-Module)
AWrm LED (Red: 28 to 32 VDC, 12 mA max
Sourcla Current IXaw
22 mA RMS met at 8 to 175 Wits DC
Tom[ Current 105 mA max
17tM RMS max at 8 to 175 Vohs FWR
Narm ResporeeTlme
40 seconds max
29 mA AMS mac at 161033 Volts DC
Temperature Range
-10TIO QTZ0RF to 1401
25 mA RMS max at 16to33Vdn FWA
Relathe Humidly
9596noncondensing
TempemWreParse
O'Ct04TC D2'F to 120T)
VAre Gauge
14 to ISAWG
Fnmdlry Aansp
10 W9396 non condensing
Dlmensbns
4b-H x 2.7FWx 18-D
Nominal5aurder Frequency
3142
,
Voltage •
20to29VDC
VAm Gauge
12 10 18 AWG
Dlmensbns
4.Cllx Z94W x0.4FD
Power Requiremenn
Smrdby:3.0mAmax
Trouble: 16D led max
Vohage lmrge
Conventional System: 3.11032 VDC
AWrm without strobe: 30 mA max
Intelligent System: 18 to 32 VDC
Alarm with sitcom 55 mA max.
Maximum Alarm Cunene
12 mA
Sounder
85dilAmteri(eel
Dlmensbm
4.6-H x 2B-Wx 13•D
Temperalule Range
-10Tto60'C(14T to I4 R
Relailse Humdlty
95%rronccndensing
wife Gauge
14 to 22 AWG
Dimensions
48-W x 53•Hx 1.6-D
For the very latest product specifications and thong inferm oon, please visit
the system Sensaweb
site at wwwsyeemsereacom.
154
3825 Ohio Avenue, St. Charles, IL60174
7+ <.
E&CEn a rs,I
Cart. of Au[h # 6 58
13812 Geranl a e
WeIlington, F 1 i till i
'' Eduardo
No Ttsn
thou ,P:1=.
u Inee aTATE OF
REV I DATE ISSUE DESCRIPTION BY
FIRE AND SECURITY
SOLUTIONS, INC.
3000 HIGH RIDGE RD• SUITE 9
BOYNTON BEACH, FL 33426
TEL (561) 588m9542
EFw20000304
FIRE AND SECURITY SOLUTIONS, INC
MANUFACTURING
BUILDING FOR'
PURSUIT BOATS
3901 ST. LUCIE BLVD.,
'ice. FORT PIERCE, FLORIDA
FIRE ALARM PLANS
JRH
P.E.
11.05.19
REVISION RECORD
REV DATE ISSUE DESCRIPTION 13Y
Indoor Selectablew
Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.
Features
• Updated Modem Aesthetics
• Small profile devices for Horns and Ham Strobes
• Plug-in design with minimal Informed into the back box
• T per -resistant wnsimction
• Automatic selection of 12-or 24-volt operation at 15 and 30
candela
• Field -selectable candela settings an wall units:
15, 30, 75, 95, 110, tics, and 1 BE
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for hard tone and two volume selections
• Mounting plate for all standard and all compact wall units
• Mounting plate shading spring checks wiring continuity before
device installation
• Electrically Compatible with legacy SpectrAlert and SpectAled
Advance devices
• Compatible with MDL3 sync module
• Listed for wall mounting only
E
Agency Listings
ORlgllO
tad
Ufirm
SW
loce
DNR-InnovairFlex
Intelligent Non•Relay Photoelectric
Duct Smoke Detector
The Noliffer InnovairFlex DNR Intelligent non -relay photoalocida
duct smoke detector and DNRW watertight non -relay photoelec-
tric duct smoke detector feature a pivoting housing that fits both
square and rectangular footprints capable of mounting to a
round or rectangular duct.
DNRW duct smoke detector, with its NEMA-4 rating, is listed as
a watertight, UV resistant enclosure providing protection against
falling dirt, ranand windblown dust, splashing and hose
directed water, allowing operators to use the detector in the
most extreme environments.
These units sense smoke in the most challenging conditions,
operating in afdlow speeds of 10D to 4,00(0 feet per minute, lem-
peratures of -4 degrees F to 158 dogmas F and a humidity
range of 0 to 95 percent (non -condensing.)
An improved cover design isolates the sensor head, which
allows for ease of maintenance. A cover tamper feature Indi-
cates a (rouble signal for a removed or Improperly installed send
so ecover. The Notifler InnovalrFiex housing provides a 3/4-Inch
conduit knockout and ample space to facilitate easy wiring and
mounting of a relay module.
The Notified InnovairFlex duct smoke detector can be comedy.
ized to meet local codes and specifications without additional
wiring. The new InnovairFlex product line la compatible with all
previous henowdr models, including remote test acessodes.
Features
• Photoelectric, integrated low -Bow technology
• Air velocity rating from 100 fttrnin to 4,000 fill (0.5 m/s to
20.32 m/a)
• Versatile mounting options: square or rectangular conggurs-
tied
• Broad ranges for operating temperature (41F to 1SSF) and
humidity (0%to 95% non -condensing)
• Patented sampling tube installs from front or back of the
detector with no Coals required
• Cover tamper signal
• Increased wiring space with a newly added 3/4" conduit
knockout
Available space within housing to accommodate mounting of
a relay module
• Easily accessible code wheels on sensor hand (sold sepa-
rately)
• Clear cover for convenient visual inspection
• Remote testing capability
• Requires win line power only
• Accommodates the installation of an addressable relay mod-
ule, sold separately, (FRM-1 or NC-100R) for applications
requiring a Form-C relay,
The System Sensor Legation; offers the most versatile and
easy -my -use line of horns, globes, and ham strobes in the industry
with lower current crows and modem aesthetics. With white and red
plastic housings, standard and compact devices, and plain, FIRE,
and FUEGO-printed devices, System Sensor L-Serfes can
meet virtually any application requirement.
The L-Series line of wall -mount hems, strobes, and horn strobes
include a variety of features that Increase their application versatility
while simplifying installation. All devices feature plug-in designs
with minimal inbusfon into the back box, making installations fast
and foolproof vAlile virtually eliminating costly and lime -consuming
ground faults,
To further simplify installation and protect devices from consWction
damage, the L-Sores utilizes auniversal mounting plate for all
models with an onboard shorting spring, so Installers can test wiring
wnlinuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range
of application requirements using field -selectable candela settings,
automatic selection of 12-or 24-volt operation, and a rotary switch
for horn tones with two volume selections.
Specifications
Size: (Rectangle) 14.38 in (37 cm) Length; 5 in (12.7 cm)
Width, 2.5 in (6.6 cm) Depth
Size: (Square) 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width;
2.5 in (6.35 cm) Depth
Weight: 1.6 to (0.73 kg)
Operating Temperature Range: -4 degrees F to 158 degrees F
(-20 degrees C to 70 degrees C)
Storage Temperature Range:.22 degrees F to 158 degrees F
(-30 degrees C to 70 degrees C)
Operating Humidity Range: 0%to 95%relative humidity (non-
ondensing)
Air Duct Velocity: 100 to 4,000 fthnin (0.5 to 20.32 m/s)
Accessories
Nether provides system flexibility with a variety of accessories,
including two remote test stations and different means of visible
and audible system annunciation. As with our dud smoke raised
tors, all duct smoke detectors accessories are UL listed.
DNR(W)s with a date code of 0013 or higher do not require
external 24VDC for remote test applications when used with a
remote -test -capable detector.
ACCESSORY CURRENTLOADS AT24 VDC
Device
Standby
Alarm
RA100Z
OmA
12 mA Max
RrS151/
OmA
12mA Max
FTS151KEY
dm60429:1si • W/ta/il -Pape 1 of 2
L--Series Specifications
General
LSenes standard horns strobes and hom strobes shall mount to a standard 2 x 4 x 12 a back box 4 x 4 x 11 -
/ nch /: inch beck box, 94nch
octagon box or double -gang back box. LSenes compact products shall mount Iback go g g p p unl to as and a sng2x4x1%-nch mounting
box. Auniversal
mounting plate shall be used for rtounl rig ceiling and wall products for all standard models and a separate unlvemal mounting plate shall be
used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate Also L-Series
products, when used theS c•CXcur" Module accessory shall be powered from a non -coded notification
m mono appliance circuit outputs ut
P Yn ry P P P P
end shell o orate an a mom dal 12 or 24 volts. Wren used w41h the 5 c•C'rou'1 Module mled nolHoatio a p yn 12-voil n p6.5 an 33 voo
shell operate between 8.5 and 17.5 wails; 24-volt-rated notification appliance cocoa outputs shall operate between 16.5 and 33 volts. Indoor
LSenes products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full -wave rectified unfiltered power supply.
Strobes and hom strobes shall have field -selectable candela settings including 15, 30, 75, 954 110, 135, and 185.
Strobe
The strobe shall be a System Sensor L-Series Model _ listed to UL 1971 and shall be approved for fire Pressure service, The glace
shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements forvisibla
signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model _ listed to UL 1971 and UL 464 and shall be approved for fire protective
service. The horn strobe shall be Weed as a primary -signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the stray entire operating voltage range. The stabs light shall consist
of a xenon flash tube and associated lens/reflector system. The hom shall have two audlbllity options and an option to switch between a
temporal three pattern and a non temporal (continuous) patientThese options are set by a multiple position switch. The hom on hom strobe
=data shall operate on a coded or non -coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circult model MDL3listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize Strobes at 1 Hz and home at temporal Three. Also, while operating the strobes, the module shall silence the hams
on hom strobe =data over a single pair of wires. The module shall mount to a 41"6 x 411/16 x 21R-inch back box. The module shall also
control two Style Y (class S) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining rvo or more
synchronization modules together will synchronize all the zones they control. The module shell not operate on a coded power supply.
Amspsa nnrrmr2 •ba•2
Agency Listings and Approvals
Consult product manual for lists of compatible UL-Listed
devices. In soma cases, certain modules may not be listed by
certain approval agencies, or listing may be in process. Con-
sult factory for latest listing status.
• UL: Sg11, S635
• ULC:S911,S635
• CFSM: 3242-0075:0221
Product Line Information
NOTE: "A or CDW suffix indicates ULC listed model,
DNR(A) Intelligent non -relay plammalechic law flow smoke;
detector housing. Requires photoeledro smoke detector insist
i"Parplely),i
DNRW: Watertight intelligent non -relay photoelectric low flow
duel smoke defector housing. Requires photoelectric smoke
detector (sold separately). NEMA-4.
FS1241811f: flemote lest capable addressable low -profile photo-;
lalectric smoka dstwtodi
FSP-851: Addressable low -profile photoelectric smoke defector.
NP400: Addressable low -profile photoelectric smoke detector
for FreWarden series panels.
NP-100R: Remote test capable addressable low -profile photo-
electric smolm detector for Fire Warden sakes panels.
DCOIL: Remote test wild Required for older DNR(W) duct
detector housing.
DST1(A): Metal sampling tube dual width up to 1 it (0.3m)
DST1.5(A): Metal sampling tube duct widths up to 1 It to 2It (0.3
to 0.6 m)
DST3(A): Main[ sampling tube duct widths up to 2 it to 41t (0.6
to 1.2 m)
DS75(A) :Metal sampling tube duct widths up l0 4 it l0 81t(1 2
to 2.4 my
DSTto(A): Metal sampling tube duct widths up to 8 0 to 12 it
(2.4 to 3.7 m)
DH4000E-1: Weatherproof enclosure
ETX: Metal exhaust tube dud, width 1 it (0.3 m)
M02.04410: Test magnet
P48-21A0: End cap for most sampling tubes
RA10OZ(A): Remote annunciator alarm LED
RTS151(A): Random test station
RTS151KEY(A) Remote last i lionwhinIkeylodu
Important Note
• DNRW duct detector housings with a date code of 0013 or
higher do not require a DCOIL or auxiliary 24 VDC for remote
test applications when used with a remote test capable
detector.
• DNRW duct detector housings with a date code of 0012 or
earlier require a DCOIL and auxiliary 24 VDC power for
remote test applications.
ONYX® and NOTIREB© are registered trademarks and
NOT(• F1RE•NETn^ is a trademark of Preserving Internationalism
Mil by Honeywell international Ina. Al rights reserved. unauthorized use
of the document insulaly prohbilad.
eve
For more Information, contact NotiOer. Phone: (203) 484-716/1 FAX: (203) 404.7116.
waranatiflar.cour
Pager 2of 2-dm60429:1/ •07/13I11
UL Current Draw Data
!R
f3-�} Cqh::i'�tLntt7ia;ig77;i^1if5Til
�K,y`�%+},i%y1
�ti
rl
.:,hryyl
8-175 Volts 16-33 Volts
Candela
DC
DC
FWR
Gondola 15
88
43
60
Range 30
143
63
83
75
N/A
107
136
95
WA
121
155
110
N/A
148
179
135
WA
172
209
185
WA
222
257
Horn Tones and Sound Output Data
8-17.5 16-33
Switch Volts Volts
9' Coded High B5 90 90
10• 3.1 kHz Coded High B4 B9 89
•Savage 9 and lower not unstable on 2-Wm horn sroeos.T peal cooled must
W prm1drdby Me NAC. 11 the NAC volmgo Is hold constant, Um hom oulpulfomalm
consmnlN an.
.xeseaa 1191017•r1rdoa
Dimensions
its
00 i
I Mom
�� II
I
1 (I�
..I 6
Compact Strobe, Horn Strobe Compact Horn
Compact Wall Surface Mount Back Box ro
SBBGRL, SSSGWL
dead aa
I illll
1 �
I�III
Oil
•
Notes:
Att-P models have a plain housing (no'FmE- writing on cover)
NI -SP models have TUFOO-annoying on cover
At-ALERTmetals have'ALERI" marling on never
3625 Ohfo Avenue • St, Charles, IL 60174
��SYSTEM�• Phone: BOO-SENSOR2 •Fax: 630,377.6495 4- pvni nftt.eabruTwr;+aN.an
}y7 www.systemsensor.com
E & C Engi
Cert. of Auto k 26
13812 Geranium
Wellington, FL 3:
Eduard'
Registered
P.E. # 411
r,O:T
STATE OF
•.FCORIQP
.j\
FIRE AND SECURITY
SOLUTIONS, INC:
3000 HIGH RIDGE RD. SUITE 9
BOYNTON BEACH, FL 33426
TEL (561) 588w9542
EF-20000304
FIRE AND SECURITY SOLUTIONS, INC
MANUFACTURING
BUILDING FOR
PURSUIT BOATS
3901 ST, LUCIE BLVD.,
FORT PIERCE, FLORIDA
FIRE ALARM PLANS
11,05,19 1 AS NOTED
FA-9
REVISION RECORD
L-Series Specifications
UL Current Draw Data
L--Series Dimensions
24714.7mm)
®®� �+
.r:' Y. o.- ti;,P^-a., �.- y ;:: �. 'v�it'I: {};9'
8-175 Volts 1G�3 Volts � a-17.5 Volts tGJ3 Volt
�, � L ",-.:= To :'_. �<� fit.. nt:•.. �..n Se J'ti
General
Indoor Selectable-
Output Strobes and
,,
�'«;?.-'
t u
jd„p
�� KF
LSenes ce'Ing-mount slmbes and ham slmbes shell mount toestandard4x4z7h-mch hack box,4 nth act ganb kb rdouble-
gang beck box Two-w re pmducls shell also naunt to asingle-gang 2 x 4 x 17/B-inch beck boz. A universal mounting pl¢le shall be used
for mounting ceiling entl wallproducts. Thenoliiication appliance ciroull wiring shall lenninate at the universal mounting plate. Also, L-Series
products, when used wtlh the Sync•Clrcuil'"Module accessory, shall be poweredfmmenon-coded noldiceUon eppllanca circuit output
and shall operate onanomnal 12 or 24 volts. When used wth the Sync•Circul Module 72-volt aced notdtcation appliance circuit outputs
shallopemla between 8.5 end t75volts 24-volt-rated notficeuon eppl(enceamuit outputs shall oparalebstween t65and33 voles.Indoor
LSedas products shell operate between 32 entl 720 degrees Fahrenheitfromaregulated DC orlull-vreve recldied unfilleretl power supply.
Ceiling slmbes and ham sUohes shell have held -selectable candela settings Including 15, 30, 75, 95, 115, 150, end 177.
Candela
Candola 15
Rango 30
75
95
715
150
OC
67
753
N/A
N/A
N/A
N/A
DC
41
63
777
734
15B
189
FWR
60
86
t42
164
191
228
Sound Paltem
Temporal
Tempoml
Non-Temporel
Non-Tempoml
3.1 KHz Tempoml
3.1 KHz Temporel
d8
High
Low
High
Low
High
Low
DC
39
28
43
�
39
29
DC
44
32
47
32
41
32
RVR
54
54
54
54
54
54
is!'pramm)
a� da"'
(ismm)
estcan
(I>sna°^)
2s -•..I
� (u"""I I
o O o
Horn Strobes for
C'
alling Applications
System Sensorl-Series audible visible notification
pmd1lClS alelletl With teatnfeS gea/anteed tO CUt
installationtimesandmaximizep/olitswithlower
CU((entd(aWandmodemaesthetles.
Features
• Plug�n design with minimalNWsion into the beck box
• Tamper-reslslant consWction
• Automatic 6eleclion of t2-or24-volt operation
at l5 and 30 candela
• Fi¢Id�selecleble centlela settings on ceiling units:
15, 30, 75, 95, 1t5, 750, entl 777
=` ':
�,�
j�rlfi 1.
yAx' 'A '
�
��.
®
�
/�' ,.
The System Sencor 45erles offers the most vers¢tlle afltl
easy -to -use line of horns, strobes, and hom strobes in the industry
w lh lower current draws and modern aesthetics. With white end red
plastic housings wall and ceiling mount ng opl'ons, System Sensor
L-Series can meal virtually any apphcalion requirement.
The entire L-Series pmdum line of ceiling -mount slmbes and horn
- slmbes include evariely of features that increase their application
versatility while 5implllying installation. All devices fealureaplug-in
Strobo
Thestmbe shell beaSystem Sensor L-Banes Model_Ilsted to UL t97t and shall be approved toff re protective service. Thestmbe
shall be wired as ¢ pr mary-s•gnahng not hcel on appl ante and comply with the Pmedcens w Ih Disable lies Acl requirements for via bee
s'gneUngapplances,flashngatt Hz overthe stobe§ant re operet ng vokagemnge Thestmbe light shall cons sl oiaxenonflesh tubeand
essoc aced lanslrefleclor system
Hom Blrobo Combinat on
ThehornslmbeshallbeaSyslemSensorL-SeriesMadel_hstedtoUL197tandUL464antlshallbeapprovedforfreproteclive
service. Thehorn strobe shallbe weed asepr mary-s'gnel ng notfcation eppllanca and comply with Ute Americans with0 seh lilies Act
requirements for visible signaling appliances, flashing ati Hz over the strobe's entire operatingvollage range.Thestrobe light shell consist
ofezerwn Plash tube and essocialed lenslreflector system. Thahom shellheve two audbl'ty options end en option to switch belweene
lemporallhreepaltemandenan-Temporal(coninuous)pettem.Theseoplionearesetbyamulliplepositionswitch.Thehomonhomstrobe
models shallOpereteonecodedornon-c�dedpowersupply.
Synchronint'on P,todulc
Thenodule shallbee System Sensor Sync•Cirail model MDL3lisled to UL464 and shall be approved for fire protective service. The module
shall synchronize L-Series slmbes all Hz andhorns at temporal three.Also, while operating lha strobes, the module shall silence the homs
on hom strobe models werasingle pairof wires. The module shell mount to a47V16 x411/16x2t/a-inch back boz. The module shall also
wntrol two Style Y (class R) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining Ivm or nrore
synchronization modules logetherwll synchronize all the zones th ywnlroLThe module shall not opemte onawded power supplyi
177
WA 226
264 3,1 KHZ Non Tempoml High
3.7 KHZ Non-Temporel l.ow
Coded High
3.1 KHZCodd High
42
29
a3
42
43
29
47
43
54
54
54
54
O
nos+sm
Ceiling-PAounl Horn Saobes
O ®
,oar^�^
® 0
/,
�
1
`©
0 o O o e
nrasm
Ceiling Surface MowtBacic Box
��
®®�p �
� - wR^•"D
� I
'
\
-
( - - � •• C"'4k� ""''r-�`W
a-175Volls t6-a3Volts
DC input 15cd 3ocd tscd 3ocd 75W 95cd t15cd 15ocd 177cd
Temporal High 103 1fi7 71 90 143 165 167 217 254
Temporel Low 96 165 54 71 137 161 165 211 249
Non -Temporal High 1W 173 71 90 747 165 1a7 230 273
Non-lemportalLow 95 t66 54 71 124 161 170 216 258
3.1K Tempoml High 111 164 69 94 147 163 169 229 257
3.1KTemporal Low tD3 163 5a 68 143 755 185 212 252
3.7K Non -Temporal High 111 172 69 94 144 164 202 229 271
3.1K Ntin-Temporal Low to3 169 54 68 137 155 167 217 259
76.Oa Volts
FWRlnput 15cd 3ocd 75cd 95cd 175cd 150cd 1Tlcd
Temporal High 1W 135 179 198 p?3 254 28fi
,, „; - ., „- ;,: � f, , '�. <,-v.s�'. i 7 "
-II,"� „ ; +�;:haz7/,-.�, .ear c,�„�,(..
Standard OporaungTempsraturo 32°F to 120°F (D°C tv 49°C)
TemporalLav 78 101 151 172 799 229 262
Non-Temporel High 107 135 179 798 223 254 266
Humidity Range 10 to 93%nomm�densing
Non-Temponel Low 7a 107 15t 172 199 229 262
Strohe Flash Rare 1 flesh per second
3./K Tempoml High 108 135 179 20D 225 255 289
hlominal Voltage Regulated t2VDC or regulated 240C/FWR�
3.1KTemporel Low
79
101
750
171
196
229
266
Operagng Voltage flangN 810 17.5V(I2VnominaQ or 16 to 33V(24 VnominaQ
• Hom rated at 88+d8A at 16 vvlls
design with minimal inlrusien into the beck box, making installations
3.1K Non-Tempoml High 10a 135 t79 200 225 255 289
Operndng Voltage Range(P.1DL3) 8.510 17.SV(t2 Ynominap or t6.510 33V(24V nominag
InputTerminal Wro Gaugo 12 to 18 AWG
3.7K Non -Temporal Low
79
701
t50
177
196
229
260
• Rotary switch for horn tone entl two volume selectons fast andfoolprool while virtually eliminating costly and time-
nan+a,
nms,.m
Hom Strobe Tones
:-'- ..." .: �y;+,,
g,.,itch
Position Sound Pattern
and
Sound Out ut Data
p
„, ,•-,:::;;.§ 4;z, ^azrPi ti,,,.l .,s,t*��;-:.,,,.d";
s-n5 t6a3
Volts Volta
de Dc OC FWR
• Universal rnounlin late for ceilin units consuming ground faults.
g p g
• Mounting plate short ng spring feature checks wiring continuity To further simpl'ly nstalletion, the L-Ser es ut lrzes auniversal
before device installation mounting plate so installers ran mount them to awide army of back
• Electrically Compatible with legacy SpectrAlert and SpeclrAlert boxes. With en onboard shading spring, installers can lest wiring
Advance devices continuity before the device is installed
2-Vfire Ceiling Mount Hom Strobes
with Ceiling Surfaco hfount Back Box
L--Series Orderin Information
g
4-YAre Ce'i ng Mount Horn Strobes
with Ceiling Surface Mount Back Box
Ceiling-PAounl Dimension^, (including lens) 6.8'diamalerx 2.5'high (173 ram diemeler xfi4 ram high)
Ceilmgd4ounl Surface Mount Back Box Skirl Dimensions 6.9'tllameterx3.4'high (175 ttM diamelerx B6 ram high)
(SBBCRL, SBBCWy
Notes:
1. Full Wave RectMied (FWR)vollage isanon-regulated,lime-varying powersource that is used on some power supply and paneloulpuis,
2.P,S,PC, and SC pmducls volt operate el l2 Vnominal only for l5 end 30 cd.
• Compatible with MDL3 sync module
• Listed forceiling mounting only
Installers can also easily adapt devices toasuitawide range of
application requirements using (teed -selectable candela settings,
aulomalic selection of 12-or 24-voltoperalion, and a rotary switch
Par horn tones with nvo volume selections.
i Temporal
2 Tempoml
3 Non -Temporal
4 Non -Temporal
5 3.1 KHz Temporel
High 84
Low 75
High 85
Low 76
High 83
B9
&T
90
84
88
89
83
90
84
88
'; ..,-;. <. ..E .,:4 .�.,
�
c ting Horn Strobes any.
PC2RL 2-Wire, Horn Strobe, Red
PC2WL 2-Wire, Horn Strobe, White
PC4RL 4-Wire, Horn Strobe, Red
.:} :... ,":`.?:-". :a=� ,.�. ..
-
C fling Strobes "
SCRL Strohe, Red
SCWL Strobe, White
SCWL-CIA-ALEHI' Strobe, White, ALERT
6 3.7 KHz Temporel
Low 76
82
82
PC4WL 4-Wire, Horn Strobe, While
Accessories
7 3.1 KHZ Non -Temporal
High 84
89
69
TRG2
Universal Ceiling Trim Ring Red
B 3.1 KHz Non-Tempoml
Low 77
83
83
TRC-2W
Universal Ceiling Trim fling White
Agency Listings
SBBCPL
SBBCWL
Ceiling Sudace Mount Beck Box, Red
Ceiling Surface Mount Back Box, White
9Awm
�L F� ���
For eceiling-listed homanly tlevice, see AVDS865 °Indoor Selecteble-
Output Homs,Strobes, end Hom Stmhes for Wall Applications'.
�•
118T®
s+ou -yr 3 nx..�_,�
4��'���q,e��•��r� 3a25 Ohlo Avenue • SL Charles, IL 60774
�� m�7�YNYe �3t1' Phone: 600-SENSOR2•Fax: 630.3776495
pO �"•"'�,�.,
"C1O-,nm^v-^.b�� �iry .:ao°.o��u.°".'
STI STOPPER II°
7
srvttoo
I SEf aEVEaSE
PRODUCT OVERVIEW
This protective cover has been helping to stop false fire alarms around the world for
more then 35 years, without restricting legitimate alarms. All models offer excellent
protection against physical damage (both accidental and intentional) and several
against severe environments both inside and out. It is ideal for schools, colleges,
hospitals, nursing homes, stores, hotels and public builtlings of almost every kind
where there is a threat of false alarms.
HOW IT WORKS
Stopper II consists of a clear, tamperproof, tough polycarbonate shield and frame, but
the line includes models wish the option of a piezo hom, spacer, Form "C" dry relay
contact and gaskets. The cover accommodates most manual pull stations. When the
Stopper II with ham is lifted to gain access to the protected alarm, a piercing self-
contained 95 or 10b d8 warning ham (a[ one foot) sounds. Immediate attention is
drawn to the area and a pranksterwlll either run or be caught. The cover is connected
to the frame by a cable. When the cover Is lifted, i[ drops off of the frame end a horn
will sound (models with horn) until the cover Is snapped back onto the frame or far the
life of the battery.
For more Infortraflon, call 248-673.9898 or Nslt wwwsg-usa.com
KEY FEATURES
General Information
Proven effective for more then
35 years In helping stop false fre
alarms w4hwtresldcling legitimate
alarms.
• Can bs used aseguerd against
phyairal damage to a manual pull
station, with or wkhoul the optiond
warning horn.
• Three year guarantee against
breakage o(polycarbonate in
rural use (oneyear on electro
mechanical entl electronic
components),
Oaeign
• Lergar sizes end surface mounted
pull stetlons accommodated with
STI-3100 conduh spacer.
Wsethar models have closed cell
gaskets.
• Tho Stopper II design is a registered
trademark of Safety Technology
Intemetionel, Inc.
Construction
• UL Listed to U.S. end Canetlien
safely atentlerds (also for custom
labeling).
Inataflation
- When rAvedng a pull sation
outside, UL mquires stations to be
fisted for outdoor use.
• Typical working properties of
polycarbonale ere -40° to 250°F
Efactronice
Power source is a BV OC alkaline
battery Included on slantlerd
Stopper II (remote powered unh
w table).
Options
Optional horn has a choice of g5 or
toy dB of one fool.
Stend¢rd red units heve'In Case
of Fire...' label unless specified with
no label° or'custom Iahel" (extra
charge for custom lebeq.
rSTt.. , , , , , : .
STI Stopper II°
Dimensions and Technical Information
MODELS AVAILABLE
Stopperll• Models Indoor Usa
STI-1700•+
With horn for Msh mount
STI-7730'+
With horn entl spacer
STI-1200'+
Without horn flush mount
STI./230••
WthoW horn wAh spacer
WeotherStopper' with gnakota (Indoor/Outdoor rotod)
STI-1150'
Stopper ll with hom flush mount
STI-7755•
Stoppor ll wAh horn antlspacer
STI-125D•
STI-1200 gush mount and gasket
STI-3750't
STI-1200 with spacer and gaskets
Aec sortee
KIT•3/6
Lowers for STl-3100
KIT-Htg015
Two 3/16"Phan wrenches
STI.1102
Replacement horn for cover wllh alarm
STI-1290
eackplale
STI.3002
Weather gasket
STI.3003
Conduit gasket
STI.3004
Rlgld conduit gflsket
STI-3700
2' conWll spacer with ¢frame, 54' or A:' contlWt entry
STI-3104
2"conduit spaCsr wllh'h'or 93'conduit entry
(includes or» g.' candud entry gasket)
• Add-NR for
no labelon horn housing
Add -CR far
custom Zabel on horn housing
Add -FR for
French labeling
Add -ES for
Spenieh 1¢boling
+ Available in a 6•pack (STI-7100 85TI-1730 also in a 12-pack)
,
III,f(�
,-LL
:�
i
i
�( __
J,
(
fir=•
�"4(i
i
APPROVALS &WARRANTY
TESTING
II has been tested and approved or listetl by:
• UL7cUL Usled No. 52466
• Far Are alarm appllcatbns, UL38 requires outdoor Ilsletl stetlons for
outdoor use
• State of California (obtain local fife marshal approval)
MEA 49.00-E (STI-1200)
• flush modals ADA Compliant Surtace rootlets ADA Compliant for
operation (UL Certified No. 52466)
• Weather Stopper• versions designed to meet the requirements
of IP54.
The Indoor/outdoor rated slatlon corers, when mountetl on ¢
month surface, provide a rain tight seal simper to a 3R enclosure
rating.
WARRANTY
Three year guarantee against breakage of polycarbonete In normal
use (one year on electro mechanical nntl elecironlc components).
IMPORTANT NOTICE
Stopper II "FIRE" models era intended to be usetl In areas where
the Incldenee of false fre alarms from manual pull stetlons Is high or
ties proven to be a serious problem. Any dis¢Wantege of this tlevice
Is more than balancetl when one considers the consequences of
false fire alarms, especially If fire seMce personnel end equipment
re respontling to a false fire alarm when they ere needetl for a real
fife somewhere else. Add to Ihls the dlsruptlon to the facility when
!else alarms occur. IP you have, or may have, a problem with /else
the alarms or physlcelAveDlher tlamege fo your fire alarm acllvallon
devices, the Stopper II could prove Invaluable.
' WARNING:QFor RC models: UL Usting does not permit relay
onlacts to connect to the ire alarm or a life sanity function.
The power supply for homs, according to UL Usting, cannot
be connected to a UL Listed fire alarm system. For electrical
speclficatlons see Install book RC rootlets canteen one net of Form
°C' tlry contacts. Contacts reled 30 VACNDC 1 amp.
ETERNAL DIMENSIONS: •Flush 7.2 W x 10.2 H x 3.3 D in. (183x259xe4mm)
• Sudace 7.2 W z 10.2 H x 5.5 D in. (183x25gx140mm)
._._. aln. ........._._._._.._.........._.
t h.
4w�^""'� to tn. (etmN
Oo:mn> Irt-_._._-.....i- t s to pommy
ssm Onmm) stk(w )
n4o,,.,, �" )
aem. w<tanoos
sa m. Doan) rarete Ram*J
Dvsaaval
rittltLSF77tl16�tl:1111A5•i
Rhtatlh USA.,0190i-2a18 Sorely TWwbay trxv,^Ikr,al, Fe. 9uNalto d+anpowtlhcul nolko, tt(19
E & C En i ere,
Cart. of Auth 2 5 8
13812 Gera Iu lace �`�1i �'P
Wellington, F 3 1 \\`
Tel (661) 7 9,4 ' tj0 ' 'G�
email: ed n• I eeys- o - E N � '
��; •
No a' as
Eduardo _Too ,.,�P;r.E.ol
Registered EI ctrir`a t
P.E. � 4118 E �LOR}�
Dare: �- S�: ---""
����i/7�Pl4� �
REV ( DATE � ISSUE DESCRIPTION
FIRE AND SECURITY
SOLUTIONS, INC.
3000 HIGH RIDGE RD. SUITE 9
BOYNTON BEACH, FL 33426
TEL (561) 588-9542
EF-20000304
m
FIRE AND SECURITY SOLUTIONS, INC
MANUFACTURING
BUILDING FOR
PURSUIT BOATS
3901 ST LUCIE BLVD.,
FORT PIERCE, FLORIDA
FIRE ALARM PLANS
E.
P.E. I 11.05.19
FA-10